A.O. Smith fps50, FPS40, FPS 75, FPSE50 User Manual

~-
~
~
--
I';:::;::
--- -- ~ ' ,
-r~~
~ K
: --'
~
( ;,,'
-
II
~~~.
~~~
t;;.\i(
tF
n
: ~
r
:::=::;-
~
=~~~
0-'1
~;;;;~~,
n ; q
F'
Models
FPS 40 and 50
Series 226-227
Prepared by the
Technical
Information Dept.
Irving, Texas
Printed in the U.S.A. 596 4575
~
ruc Wc ~~D~w
WATER PRODUCTS
COMPANY
A DIVISION OF A.O. SMITH CORPORATION
00
FPSE 40 and 50
Series 226E
FPD 40 and 50
Series 226-227
F PS 75
Series 230-233
Part No. TC-O34
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
WORKBOOK INTRODUCTION
@1995 A.D. Smith Water Products Co.
1
Technical Information
Irvino. Texas
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
TABLE OF CONTENTS
SUBJECT
Choosing the Best Water Heater
Introduction When to choose the FPS When to choose the FPSE When to choose the FPD
Venting Installation
Interior clearances FPS, FPSE, FPD
Exterior clearances FPS, FPSE
Exterior clearances FPD
Condensation
Sealing the vent Horizontal Length Calc. FPS, FPSE
Vertical Length Calc. FPS, FPSE
Horizontal Length Calc. FPD
PAGE
3
3 4
5
6 7
8 9
10 11 12
13
SUBJECT
Service and Operation FPS 40 & 50
Sequence of Operation Wiring Diagram
Troubleshooting Index 23
Parts List 40
FPSE & FPD 40 -50
Sequence of Operation 42 Wiring Diagram
Troubleshooting Index 44
Parts List 66
FPS 75
Sequence of Operation
Wiring Diagram
PAGE
21
22
43
68
69
Vertical Length Calc. FPD
Down Length Calc. FPD
Air for Combustion
Checking the draft
Additional Problems
Negative Pressure Make-up Air
14
15
16
17
19
20
Troubleshooting
70
Parts List 94
Part Infom1ation 96
Service Checklist 97 General Q & A
99
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
CHOOSING THE BEST WATER HEATER
@1995
A.D. Smith
Water Products Co.
3
Technical Information
Irving, Texas
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
CHOOSING THE BEST WATER HEATER cant.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
CHOOSING THE BEST WATER HEATER cant.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTALLATION
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTALLATION cant.
Exterior Clearances:
FPS FPSE
Exterior installation clearance requirements are crucial and must be met to ensure compliance with all safety and code requirements. If all clearances cannot be met, do not unpack the heater.
All exterior clearance requirements for the FPS and FPSE are measured from the vent termination.
Min. clearances for side wall venting: Min. clearances for vertical:
Inside corner - 3' l' above or 4' to the side of any Side of door or window - 4' gable, dormer, or roof structure Above door or window - l' with building interior access. Below a window - 4' l' above snow level. Above public walkway - 7'
Above ground or snow level -1' Air intake to a living space - 3' above if air intake is within 10'
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTALLATION cant.
Exterior Clearances: FPD
@1995 A.D. Smith
Water Products Co.
Exterior installation clearance requirements are crucial and must be met to ensure compliance with all safety and code requirements. If all clearances cannot be met, do not unpack the heater.
All exterior clearance requirements for the FPO are measured from the vent termination.
Min. clearances for side wall venting: Min. clearances for vertical:
Inside corner - 3' l' above or 4' to the side of any
Side of door or window - 9" gable, dormer, roof structure Above door of window - 9" with building interior access. Above public walkway - 7' l' above snow level.
Above ground or snow level -1' Air intake to a living space - 3' above if air intake is within 10'
8
Technical Information
IrvinQ. Texas
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTAllATION cant.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTAllATION cant.
VENTING INSTAllATION cant.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTAllATION cant.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTAllATION cant.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTALLATION cant.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
VENTING INSTAllATION cant
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
AIR FOR COMBUSTION
Checking for Draft
On initial start up, check for the correct draft on the Power Shot. To check the draft, place a smoke stick directly in front of the inlet air damper while the heater is firing. A properly operating system will draw the smoke into the inlet air damper as shown in the right illustration. The illustration on the left shows a negative
To check for a negative condition close all windows, outside doors, and fireplace dampers. Turn on all exhausting appliances, including kitchen draft hoods, clothes dryers, furnaces, bathroom vents, etc. Open all inner doors between these appliances and the Power Shot.
Once all appliances are on and inner doors open, open the inlet air damper on the Power Shot when the heater is not firing. Using your hand, check for air movement. If air is being blown back into the room, a negative pressure condition exists.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
AIR FOR COMBUSTION cant.
CONDITION
Burnt gas odor when heater is operatinq
CAUSE
Leaking vent joints
Blocked vent
SOLUTION
Seal vent joints
Clear vent blockaQe
The majority of the complaints associated with the operation of the will likely be a direct result of improper venting. If the customer complains of smelling burnt gas around the water heater, first check for vent gases that may be leaking from the PVC joints or around the area between the blower assembly and water heater. Seal all leaks with the high temperature silicone sealant provided.
Check for restrictions in the venting that may cause some spillage of burnt gas into the room and check your draft, visually inspecting the vent termination for blockage, clearing blockage as
necessary.
Improper venting is also a major cause of sooting in water heaters. If you experience sooting with the POWER SHO~, check that the inlet air damper swings freely and opens 1 1/4" when the blower is running.
If water is dripping from the blower, condensate is the culprit
To correct the problem, install a
condensate tee, and pipe to drain.
If the customer complains of nuisance pilot outage or pilot gas odor on standby, this may be due to a lack of combustion air, or other appliance (exhaust fans, clothes dryers, etc.) creating a backdratt in the FPS venting. In either case, install additional make-up air ducts.
@1995 A.D. Smith
Water Products Co.
17
Technical Information
Irving, Texas
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
AIR FOR COMBUSTION cont.
CONDITION CAUSE SOLUTION
Inlet air damper not
build-up in PVC venting
Intermittent fan cycling without burner
operation (Propane Only)
A malfunctioning vent damper may also cause excessive heat buildup in the PVC vent piping
unable to free the damper, replace the entire combustion control tee.
If blower does not run when the main burner fires, replace the control box. Also check burner orifice for correct size.
opening completely Blower does not run when
main burner fires
Wrong main burner
orifice size
Build up of pressure in the
main burner tube between thermostat gas valve and solenoid qas valve
Free air damperExcessive heat
Replace entire blower assembly
Install correct orifice
If cycling occurs more than twice per hour, see troubleshooting
procedures.
If
Intermittent cycling of the fan, without main burner operation, indicates a build-up of pressure in the
main burner tube between the thermostatic gas valve and solenoid gas valve.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
AIR FOR COMBUSTION cont.
Negative Pressure
Diagnosing pilot outage complaints requires an examination of the environment in which the heater is installed. Mechanical vent fans are the chief cause of negative pressure. If the house is too tight, more air will be exhausted from the structure than is being brought in from the outside, resulting in a negative pressure condition. Fireplaces, furnaces, wind, and thermal stacking within the house can also playa role in creating negative pressure conditions.
Negative pressure can result from air being backdrafted through the water heater vent down into the combustion chamber, blowing out the pilot. This may happen randomly because it may be a particular combination of appliances which cause
the condition.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
AIR FOR COMBUSTION cont.
A.D. Smith
Water Products Co
20
Technical Information
Irving, Texas
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION cant.
-A~I
DISCONNECT FROM ELECTHICAL SUPPLY BEFORE SERVICING UNIT. REPLACE ALL DOORS AND PANELS BEFORE OPERATING HEATER.
115~LT
POWER SOURCE
""
w
ON
SWITCH
OFF
; rc
CONNECTOR,
I O/Y.. G/Y I
w ,
r<
c
R
r---rr
~~~
PRESSUREI COIL
SWITCH I ~~
I I HEATER (A~ QAS MANIFOLD) - J
""
Gim
W
~~:=: ~~~-~
~.WlAECABLE
SUPPUED WIn! UNIT
'\ I . ===- CONNECroR
,J~"-- I I LEGEND
~
AIR
PRESSURE
~,
B=BLACK W=WHITE R=RED G=GREEN G/Y=GREEN/
YELLOW
U=BLUE
@1995 A.D. Smith
Water Products Co
~
~
22
Technical Information
IrvinQ. Texas
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION cant.
@1995 A.D. Smith Water Products Co.
23
Technical Information
Irving, Texas
Trouble­shooting cont
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION cant
PRELIMINARY CHECKS
1. Gas valve knob is in ON position
2. Pilot is burning
3. 120 VAG is supplied to heater.
4. Thermostat is calling for heat
(See page 25)
5. Blower ON/OFF switch is in the ON position
6. Connection between blower motor and blower control box is secure
7. Heater is installed per manual
@1995
A.D. Smith
Water Products Co.
24
Technical Information
Irving, Texas
Trouble-
shooting cont.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION cant.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION cant.
@1995 A.D. Smith
Water Products Co.
26
Technical Information
Irving, Texas
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION cont.
Trouble-
shooting cont.
BLOWER DOES NOT RUN cant.
RESULTS
If: then: the fan does not run, the fan does run,
@1995 A.D. Smith Water Products Co.
27
replace the fan assembly.
go to Step 2.
Technical Information
Irving, Texas
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION cant.
Trouble­shooting cont.
BLOWER DOES NOT RUN cont.
RESULTS
If: the fan does not run, the fan does run
then' replace the cable go to Step 3.
FPS/FPSE/FPD TECHNICAL TRAINING AND SERVICE WORKBOOK
FPS 40 and 50 SERVICE AND OPERATION cant.
Trouble-
shooting cont
BLOWER DOES NOT RUN cant.
RESULTS If:
the fan does not run, the fan does run,
then replace the harness replace the gas pressure switch
Loading...
+ 73 hidden pages