A.O. Smith BTH-120A, BTH-150A, BTH-199A, BTH-250A, BTH-300A User Manual

...
Commercial Gas Water Heaters
CYCLONE® Mxi MODULATING
MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY
The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable service and feature industry leading technology. Models are available from 120,000 to 500,000 Btu/h and all deliver thermal efficiencies of 95% and higher. The unique helical coil heat exchanger limits weld joints for optimal service life while maximizing heat transfer.
Cyclone is the industry leader in high efficiency commercial water heating. The current Mxi modulating models adjust firing rate to the specific demand further increasing efficiency and money savings.
INTELLIGENT CONTROL SYSTEM WITH LCD DISPLAY AND iCOMM CONNECTIVITY
• Exclusive A. O. Smith designed touch display control system
• Provides detailed water heater status information
• Precise temperature control adjustable from 90 to 180 degrees
• Built-in diagnostics
• Run history information
• Cyclone
®
Mxi Modulating water heaters are compatible with the iCOMM monitoring system. Call 1.888.928.3702 for information.
remote
COMING SPRING 2017
• Remote monitoring capability utilizing the iCOMM app. Wi-Fi connectivity kit requited for models 120-250, standard on models 300-500.
SUBMERGED COMBUSTION CHAMBER, WITH HELICAL HEAT EXCHANGER COIL
• Positioned in center of tank, surrounded by water to virtually eliminate radiant heat loss from chamber
• Direct spark ignition
• Spiral heat exchanger keeps hot burner gases swirling, uses centrifugal force to maximize efficiency of heat transfer to water in tank
• Spiral heat exchanger reduces lime scale from forming on water-side surfaces, which maintains energy efficiency over time
POWERED ANODES STANDARD ON ALL MODELS
• Provides long-lasting tank protection in varying water conditions
• Powered anodes are non-sacrificial
• Automatically adjusts output needed to properly protect the tank
PERMAGLAS® ULTRA COAT™ GLASS LINING
• Glass coating is applied using a liquid slush coating technique to ensure uniform coating
• Heat exchanger coil is glassed both externally and internally for optimum protection
MECHANICAL VENTING VERSATILITY
• Conventional power venting or direct venting
• Vents vertically or through a sidewall
• Front located exhaust and condensate connections allow for easy install and access
• Vents with low cost PVC Schedule 40 intake and exhaust pipe. Approved for optional CPVC Schedule 40, Polypropylene and AL29-4C stainless steel vent materials
• Direct-vent intake and exhaust pipe can terminate separately outside building or through single opening, using concentric vent assembly
• Canadian installations require ULC S636 PVC/ CPVC, ULC S636 Polypropylene and AL29-4C stainless steel pipe for intake and exhaust
HIGH EFFICIENCY MODULATING PRE­MIX POWERED BURNER
• Down-fired pre-mix burner provides optimum efficiency and quiet operation
• Top-mounted burner position prevents condensation from affecting burner operation
3-YEAR LIMITED TANK / 1-YEAR LIMITED PARTS WARRANTY
• For complete warranty information, consult written warranty or go to hotwater.com.
BTH-120(A) THROUGH BTH-500(A)
MODEL SHOWN:
BTH-199(A) SERIES 300/301
© April 2017 A. O. Smith Corporation. All Rights Reserved
www.hotwater.com | 800-527-1953 Toll-Free USA | A. O. Smith Corporation | 500 Tennessee Waltz Parkway | Ashland City, TN 37015
Page 1 of 6
AOSCG10210
Commercial Gas Water Heaters
OTHER FEATURES: SPACE-SAVING DESIGN FOR INSTALLATION FLEXIBILITY
• Easy-to-remove top cover for convenient access to serviceable parts
• 0˝ installation clearances on sides and rear, 1-1/2˝ installation clearance on top
• Handhole cleanout allows easy access to tank interior for cleaning
• 0˝ clearance to combustibles, approved for installation on combustible floors
VENT REQUIREMENTS FOR BTH 120(A) - 250(A)
Number of 90°
Elbows Installed
One (1) 45 feet (13.7 meters) 115 feet (35 meters) Two (2) 40 feet (12.2 meters) 110 feet (33.5 meters) Three (3) 35 feet (10.7 meters) 105 feet (32 meters) Four (4) 30 feet (9.1 meters) 100 feet (30.5 meters) Five (5) N/A 95 feet (29 meters) Six (6) N/A 90 feet (27.4 meters)
3 Inch Pipe 4 Inch Pipe
Maximum Feet
(Meters)
Maximum Feet
(Meters)
CODES AND STANDARDS
• CSA certified and ASME rated T&P relief valve
• Maximum hydrostatic working pressure: 160 psi
• All models are design certified by Underwriters Laboratories (UL), Inc., to ANSI Z21.10.3 - CSA 4.3 Standards
• Meets the thermal efficiency and standby loss requirements of the U.S. Department of Energy and current edition ASHRAE/IES 90.1
• Design Certified by Underwriters Laboratories to NSF standard 5 for 180°F (62°C) water
• Complies with SCAQMD Rule 1146.2 and other Air Quality Management Districts with similar requirements for ultra low-NOx emissions
• ASME tank construction optional on 120-500 model sizes
VENT REQUIREMENTS FOR BTH 300(A) - 500(A)
Number of 90°
Elbows Installed
One (1) 65 feet (19.8 meters) 115 feet (35 meters) Two (2) 60 feet (18.2 meters) 110 feet (33.5 meters) Three (3) 55 feet (16.8 meters) 105 feet (32 meters) Four (4) 50 feet (15.2 meters) 100 feet (30.5 meters) Five (5) 45 feet (13.7 meters) 95 feet (29 meters) Six (6) 40 feet (12.2 meters) 90 feet (27.4 meters)
4 Inch Pipe 6 Inch Pipe
Maximum Feet
(Meters)
Maximum Feet
(Meters)
GAS PRESSURE REQUIREMENTS
Model Number
BTH-120(A) 0"W.C. (0 kPa) 0"W.C. (0 kPa) 3.5"W.C. (1.10 kPa) 8.5"W.C. (2.12 kPa) 14"W.C. (3.49 kPa) 14"W.C. (3.49 kPa)
BTH-150(A) 0"W.C. (0 kPa) 0"W.C. (0 kPa) 3.5"W.C. (1.10 kPa) 8.5"W.C. (2.12 kPa) 14"W.C. (3.49 kPa) 14"W.C. (3.49 kPa)
BTH-199(A) 0"W.C. (0 kPa) 0"W.C. (0 kPa) 3.5"W.C. (1.10 kPa) 8.5"W.C. (2.12 kPa) 14"W.C. (3.49 kPa) 14"W.C. (3.49 kPa)
BTH-250(A) 0"W.C. (0 kPa) 0"W.C. (0 kPa) 3.5"W.C. (1.10 kPa) 8.5"W.C. (2.12 kPa) 14"W.C. (3.49 kPa) 14"W.C. (3.49 kPa)
BTH-300(A) 0"W.C. (0 kPa) 0"W.C. (0 kPa) 4.8"W.C. (1.19 kPa) 8.5"W.C. (2.12 kPa) 14"W.C. (3.49 kPa) 14"W.C. (3.49 kPa)
BTH-400(A) 0"W.C. (0 kPa) 0"W.C. (0 kPa) 4.8"W.C. (1.19 kPa) 8.5"W.C. (2.12 kPa) 14"W.C. (3.49 kPa) 14"W.C. (3.49 kPa)
BTH-500(A) 0"W.C. (0 kPa) 0"W.C. (0 kPa) 4.8"W.C. (1.19 kPa) 8.5"W.C. (2.12 kPa) 14"W.C. (3.49 kPa) 14"W.C. (3.49 kPa)
Depending on the installed equivalent length, and/or the number of appliances connected, the supply gas line size may need to be increased beyond the minimum required size.
Manifold Pressure Minimum Supply Pressure Maximum Supply Pressure
Natural Gas Propane Gas Natural Gas Propane Gas Natural Gas Propane Gas