Antunes RHLGP-A Installation Manual

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
Model A Installation Information
IMPORTANT
Please read these instructions carefully to assure correct installation. This equipment must be installed only by a licensed electrician who is experienced with combustion safeguard control systems and understands the functions of inter­locking switches, such as gas pressure switches. Prior to being put into operation in conjunction with the combustion safeguard systems, all switches should be tested for proper range setting and proper wiring. Check piping connections and switch house for leaks with a soap bubble test. All exhaust fans and blowers should be inspected and checked for proper rotation prior to starting up.
Model A Switches
You are installing one of the finest switches of its type on the market. The Model A is adjustable within its range as shown on the range scale located on the front of the unit. The latch position in the reset models and the level indicator position in the recycle models show whether the switch is on or off.
Specifications
Electrical Ratings: 10A, 1/8 HP @ 125 VAC; 5A, 1/4 HP
@ 250 VAC; Pilot Duty, 125 VA @ 125-250 VAC
Max. Surge Pressure: 10 PSI
Max. Ambient Operating Temperature: 140°F (60°C)
Min. Ambient Operating Temperature: -40°F (-40°C)
Shipping Weight: HGP-A, LGP-A, RHGP-A, RLGP-A:
2 lbs. (.9 kg) HLGP-A, RHLGP-A: 4 lbs. (1.8 kg)
Options:
Panel Mount
Dust Proof
Dimensions
FRONT
4 1/16”
(103 mm)
SIDE
High Low Gas Pressure Switch
FRONT
4 1/4”
(108 mm)
SIDE
3/8” NPT
High Pressure
Inlet
Single Gas Pressure Switch
4 1/16”
(103 mm) dia.
4 1/16”
(103 mm) dia.
5 5/8”
(143 mm)
5 3/8”
(136 mm)
Gas Inlet 1/4” NPT
Vent 1/8” NPT
NOTE: Dimensions are for reference only.
Low Pressure
NOTE: Dimensions are for reference only.
1/8” NPT Gas Vent
1/8” NPT
Gas Vent
Range Available
High Gas Pressure Low Gas Pressure
2 - 16” W.C. 50-400 mm 1-6” W.C. 25-150 mm
5 - 28” W.C. 125-700 mm 1-35” W.C. 25-875 mm
10 - 50” W.C. 250-1250 mm 2-14” W.C. 50-350 mm
2-20” W.C. 50-500 mm
6-24” W.C. 150-600 mm
10-50” W.C. 250-1250 mm
1-630-784-1000 Fax: 630-784-1651 Page 1 of 4 P/N 1011087 06/10 1-800-253-2991
A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
Model A Installation Information
Electrical Wiring-Combination Models
Model: HLGP-A
Duty: High Low Gas Reset Switch
Reset HLGP-A
Reset RHLGP-A
Elec. Rating: 10A, 1/8 HP, 125 VAC
Pilot Duty: 125 VA, 125-250 VAC
High Gas
NO
NC
NO
Low Gas
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 10 PSIG
Model: RHLGP-A
Duty: High Low Gas Reset Switch
Elec. Rating: 10A, 1/8 HP, 125 VAC
Pilot Duty: 125 VA, 125-250 VAC
High Gas
NO
NC
NO
Low Gas
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 10 PSIG
5A, 1/4 HP, 250 VAC
C
By Others
Indicator On Indicator Off
C
By Others
5A, 1/4 HP, 250 VAC
C
By Others
Indicator On
Indicator Off
C
By Others
Reset lever will latch when gas pressure is below setting
Reset lever will latch when gas pressure is above setting
Contacts C & NC break when pressure rises above setting
Contacts C & NO make when pressure rises above setting
Electrical Wiring-Single Models
Model: HGP-A
Duty: High Gas Reset Switch
Reset HGP-A
Reset LGP-A
Recycle RHGP-A
Elec. Rating: 10A, 1/8 HP, 125 VAC
Pilot Duty: 125 VA, 125-250 VAC
NC
NO
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 10 PSIG
Model: LGP-A
Duty: Low Gas Reset Switch
Elec. Rating: 10A, 1/8 HP, 125 VAC
Pilot Duty: 125 VA, 125-250 VAC
NC
NO
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 10 PSIG
Model: RHGP-A
Duty: High Gas Recycle Switch
Elec. Rating: 10A, 1/8 HP, 125 VAC
Pilot Duty: 125 VA, 125-250 VAC
NC
NO
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 10 PSIG
5A, 1/4 HP, 250 VAC
C
By Others
Indicator On
5A, 1/4 HP, 250 VAC
C
By Others
Indicator Off
5A, 1/4 HP, 250 VAC
C
By Others
Indicator On
Reset lever will latch when gas pressure is below setting contact C & NC make
Reset lever will latch when gas pressure is above setting contact C & NO make
Contacts C & NC break when pressure rises above setting
Model: RLGP-H
Duty: Low Gas Recycle Switch
Recycle RLGP-A
Elec. Rating: 10A: 1/8 HP, 125 VAC
Pilot Duty: 125 VA, 125-250 VAC
NC
NO
5A, 1/4 HP, 250 VAC
C
By Others
Contacts C & NO make when pressure rises above setting
Indicator Off
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 10 PSIG
1-630-784-1000 Fax: 630-784-1651 Page 2 of 4 P/N 1011087 06/10 1-800-253-2991