Antunes HGP-H Installation Manual

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
Model H Installation Information
IMPORTANT
Please read these instructions carefully to assure correct installation. This equipment must be installed only by a licensed electrician who is experienced with combustion safeguard control systems and understands the functions of inter­locking switches, such as gas pressure switches. Prior to being put into operation in conjunction with the combustion safeguard systems, all switches should be tested for proper range setting and proper wiring. Check piping connections and switch house for leaks with a soap bubble test. All exhaust fans and blowers should be inspected and checked for proper rotation prior to starting up.
Model D Switches
You are installing one of the finest switches of its type on the market. The Model H is adjustable within its range as shown on the range scale located on the front of the unit. The latch position in the reset models and the level indi­cator position in the recycle models shows whether the switch is on or off.
Specifications
Electrical Ratings: 10A, 1/8 HP, 125 VAC; 5A, 1/4 HP,
250 VAC; Pilot Duty 125 VA @ 125-250 VAC
Max. Surge Pressure: 35 PSI
Max Operating Pressure: 8 PSIG
Max. Ambient Operating Temperature: 140°F (60°C)
Min. Ambient Operating Temperature: -40°F (-40°C)
Shipping Weight: 2 lbs. (.9 kg)
Options:
Panel Mount
Dust Proof
Dimensions
FRONT
4 1/16”
(103 mm)
4 1/16”
(103 mm) dia.
SIDE
4 1/16”
(103 mm) dia.
Gas Inlet 1/4” NPT
Vent 1/8” NPT
NOTE: Dimensions are for reference only.
Range Adjustment
To adjust gas pressure set point on either high or low pressure units, remove the electrical junction box cover, and adjust indicator up or down to desired setting, as shown on the range scale on front of the switch. Use the center of the range indicating tab as a guide for accurate setting. Turn adjusting screw clockwise to lower the set point and counterclockwise to raise the setting. To prevent tampering with setting after adjustment, be sure to replace the junction box cover firmly.
Ranges Available
Ranges
Models
HGP-H
RHGP-H
LGP-H
RLGP-H
PSI Bar
1-7
1-7
1-7
1-7
.06 -.48
.41 - 1.03
.06 -.48
.41 - 1.03
.06 -.48
.41 - 1.03
.06 -.48
.41 - 1.03
6-15
6-15
6-15
6-15
1-630-784-1000 Fax: 630-784-1651 Page 1 of 4 P/N 1011089 06/10 1-800-253-2991
Natural
or
L.P. Gas
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Automatic or Manual
Reset
Manual Manual
Automatic Automatic
Manual Manual
Automatic Automatic
Field
Adjustable
Yes Yes
Yes Yes
Yes Yes
Yes Yes
A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188
Model H Installation Information
Mounting
All gas pressure switches must be mounted in a horizontal position, with the inlet stem down. Switches should be reasonably level but do not require accurate leveling.
Single gas switch models have a 1/4” NPT gas inlet.
Electrical Information
Model: HGP-H
Duty: High Gas Reset Switch
Elec. Rating: 10A, 1/8HP, 125 VAC
5A, 1/4HP, 250 VAC
Pilot Duty: 125VA, 125-250 VAC
Double combination Hi-Lo switches have a 3/8” NPT for high pressure inlet and a 1/8” NPT for low pressure inlet.
Gas vent outlets are 1/8” NPT on all models.
Piping can be either standard black pipe or aluminum tubing.
All switches can be supported by the inlet pipe, but optional mounting brackets are available if needed.
All switches have been factory-calibrated and tested for leaks. However, it is recommended that after the installation is completed, switch, gas pipe inlets, and connections be tested for leaks with a soap bubble test.
2 5/8”
(67 mm)
1/2”
(13 mm)
7/8”
(22 mm)
1 1/8”
(28 mm)
Large
Mounting
Holes:
5/16”
(8 mm) dia.
Small
Mounting
Holes:
7/32”
(6 mm) dia.
7/8”
(22 mm)
Operation
Low Gas Pressure: Low gas pressure switches break
the electrical circuit on pressure drop at the point when gas pressure becomes lower than the indicated set pressure.
Before the manual reset latch can be properly latched, gas pressure in the chamber must be higher than the indicated setting. The position of the reset latch on the top cover of the switch shows whether reset latch is in the on or off position. Reset latch must be in “on” position after latching to be properly set.
High Gas Pressure: High gas pressure switches break
Reset HGP-H
Recycle RHGP-H
Reset LGP-H
NC
NO
C
By Others
Reset lever will latch when gas pressure is below setting contact C & NC make
Indicator On
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 35 PSIG
Model: HGP-H
Duty: High Gas Reset Switch
Elec. Rating: 10A, 1/8HP, 125 VAC
Pilot Duty: 125VA, 125-250 VAC
NC
NO
5A, 1/4HP, 250 VAC
C
By Others
Contacts C & NC break when pressure rises above setting
Indicator On
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 35 PSIG
Model: LGP-H
Duty: Low Gas Reset Switch
Elec. Rating: 10A, 1/8HP, 125 VAC
Pilot Duty: 125VA, 125-250 VAC
NC
NO
5A, 1/4HP, 250 VAC
C
By Others
Reset lever will latch when gas pressure is above setting contact C & NO make
Indicator Off
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 35 PSIG
the electrical circuit when pressure rises above the indicated preset pressure. The reset latch should be latched in the “on” position if the gas pressure in the switch chamber is below the indicated high setting.
Recycle Models: High and Low Gas Pressure Recycle models operate automatically and do not need to be reset. Otherwise they are constructed, adjusted, and operate in the same manner as the reset models.
Recycle LGP-H
Combination Models: The combination unit contains one high pressure unit and one low pressure unit, in the ranges you select. They may be either reset or recycle type. Each unit has on/off indicator, and its own range scale indicator.
1-630-784-1000 Fax: 630-784-1651 Page 2 of 4 P/N 1011089 06/10 1-800-253-2991
Model: RLGP-H
Duty: Low Gas Reset Switch
Elec. Rating: 10A, 1/8HP, 125 VAC
Pilot Duty: 125VA, 125-250 VAC
NC
NO
5A, 1/4HP, 250 VAC
C
By Others
Contacts C & NO make when pressure rises above setting
Indicator Off
Field wiring to be rated @75ºC for max 120ºF Ambient Field wiring to be rated @90ºC for max 140ºF Ambient Max Surge Pressure: 35 PSIG