Copyright 1995, 1996
Andover Controls Corporation
300 Brickstone Square
Andover, Massachusetts 01810
All Rights Reserved.
Published by the Engineering Department at Andover Controls Corporation.
IMPORTANT NOTICE
Examples in this book are for illustrative purposes only and have never been tested in an
actual building.
This product is subject to change without notice. This document does not constitute any
warranty, express or implied. Andover Controls Corporation reserves the right to alter capabilities, performance, and presentation of this product at any time.
The following trademarks are used in this manual:
CROSSTALK is a registered trademark of Digital Communica tions Associates, Inc.
IBM is a registered trademark of Internati onal Busi ness Machines, Inc.
VT is a trademark of Digital Equipment Corporation.
iiInfinity Smoke Control Guide
Chapter 1
The Fundamentals of Smoke
Control
One of the most hazardous situations that you can face in a building is
smoke. While fires themselves are often damaging, it is smoke that can
cause the most injuries. For example, at the World Trade Towers in
February 1993, over 1,000 were injured by the smoke that resulted from
the fire.
TOC
To protect your building’s occupants, as well as furnishings and
equipment that may be damaged by smoke, you need a smoke control
system. A smoke control system, as its name implies, controls the flow
of smoke in your building in the event of fire. It keeps smoke from
spreading throughout the building, giving the building’s occupants a
clear evacuation route, as well as preventing further damage to the
building’s interior.
This chapter gives you an overview of smoke control theory.
The Fundementals of Smoke Con trol
Understanding Types of Smoke
Control Systems
Two types of smoke control systems exist—dedicated and
nondedicated. The dedicated smoke control system is installed in a
building for the sole purpose of controlling smoke. A nondedicated smoke cont ro l syst em uses parts of the building’s HVAC system to
control smoke.
In most instances, a building has both nondedicated and dedicated
systems. Nondedicated systems are used throughout the building for
normal areas (offices, manufacturing). Dedicated systems are used for
special areas, such as elevator shafts, stairtowers, and other areas that
need special smoke control techniques.
The operation of the nondedicated smoke control equipment is verified
by the “comfort level” in the areas that are served by the equipment. In
other words, if the HVAC equipment is not functioning properly, the
building’s occupants will be aware of this and the problem will get
fixed.
TOC
The operation of the dedicated smoke control equipment is verified by
an automatic self-test that is performed on a weekly basis.
1-2Infinity Smoke Control Guide
The Fundementals of Smoke Control
Using Pressure to Control Smoke
The basic concept behind controlling smoke, r egardless of whether it is
with a dedicated or nondedicated system, is to use air pressure to confine
and (if possible) vent smoke from the building.
You cannot confine smoke by simply closing all access ways (such as
doors and vents) to the room that has the fire in it. Even with these
passages closed off, smoke can disperse throughout a building via
cracks, holes made for pipes and electrical wires, and spaces around
doors and windows. Smoke is driven through these small openings by
the expanding gases from the fire. Smoke can also be driven onto other
floors by the stack effect, which causes air to r ise in buildings. The stack
effect is caused by the difference in the interior and exterior temperature
of the building. The following diagram shows how smoke can disperse
throughout a building.
TOC
Figure 1-1. Smoke Infiltrating Areas Adjacent to the Fire
Adjacent
Area
Adjacent Area
Area on Fire
Adjacent Area
Since smoke is carried by the movement of air, you can stop the spread
of smoke throughout the building by lowering the air pressure in the area
containing the fire and by raising the air pressure in the surrounding
areas and floors. The difference in pressure (also called the pressure differential) between the smoke-filled area and the surrounding areas
acts as a barrier to the smoke, pushing i t back into the smoke-filled area.
The next illustration shows how this works.
Andover Controls Corporation1-3
The Fundementals of Smoke Con trol
Figure 1-2. Air Pressure Containing Smoke
TOC
Positive
Air Pressure
Positive
Air Pressure
Positive
Air Pressure
Positive
Air Pressure
NegativePressure
Positive
Air Pressure
Positive
Air Pressure
Positive
Air Pressure
Positive
Air Pressure
You lower the air pre ssure in the smoke-f illed area by shutting off all air
flow into it and turning on the exhaust fans from the area to full capacity.
This technique pulls the smoke out of the area and vents it outside of the
building.
You pressurize the areas and floors surrounding the fire by turning off
all exhaust systems (including closing any exhaust dampers) and forcing
supply air to those areas at f ull capacity. The air in the pressurized areas
tends to leak into the smoke zone, using the same cracks and holes that
the smoke would use to get out. This airflow into the burning room
keeps the smoke from spreading.
Areas that are neither being pressurized nor depressurized (i.e. areas far
away from the fire) have both their air inlets and air return systems
turned off. Turning off the air return prevents the smoke that is being
vented into the return air system from coming into the area.
In cases where there are large openings (such as an open doorway)
between the area on fire and an adjacent area, smoke can be confined by
a large volume of air. Pumping large amounts of air through the adjacent
space creates a constant draft through the opening into the smoke zone
(as shown in the next illustration). The draft through the open space
keeps back the smoke, confining it to the smoke zone. The amount of air
required to keep the smoke from penetrating the open space is quite
large, so you should avoid this sort of situation when possible.
1-4Infinity Smoke Control Guide
The Fundementals of Smoke Control
Figure 1-3. Keeping Smoke Away from a Large Opening
TOC
Andover Controls Corporation1-5
The Fundementals of Smoke Con trol
Creating Smoke Zones
In order to contain the smoke by using pressure, you must divide the
building into smoke control zones. A floor or several floors of the
building can be a single zone, or one floor can be br oken into a number
of zones. A zone must be separated from other zones by smoke dampers,
airtight doors, and smoke-proof barriers.
When a fire breaks out, the smoke control system can then pressurize all
of the zones around the one where the fire broke out (called the fire zone), isolating the smoke to that single zone.
If the smoke control system is nondedicated, the layout of the smoke
control zones should take into consideration the layout of the HVAC
system. You should place multiple areas served by the same VAV boxes
in the same smoke control zone. Also, the smoke control zones must
conform to any fire control zones that have been established, because
the smoke detectors are tied into the fire detection system. Also, keeping
the smoke control zones and the fire control zones the same makes
coordinating the two systems simpler.
TOC
Smoke Control vs. Fire Control Systems
The smoke control system is usually separate from the fire control
system, since they have different goals. The fire control system’s goal is
to contain and extinguish the fire as fast as possible. These systems,
which halt the fire but not the smoke, are often triggered automatically,
relying on the heat of the fire to activate the system. Although smoke
control systems are also automatic, you must have manual overrides for
the automatic controls. Another difference between smoke control and
fire control systems is that where fire control systems, such as
sprinklers, often rely on only a water supply, smoke control systems
usually rely on electricity to run fans and dampers. So, some smoke
control systems have a standby power supply. Standby power provides
the smoke control system with electricity in case the main power fails.
The smoke control system should be designed to work with the fire
control system and not interfere with its operation. For instance, if the
building has a sprinkler system, then the smoke control system does not
need to control a large quantity of smoke, since the size of any fire
should be smaller.
1-6Infinity Smoke Control Guide
The Fundementals of Smoke Control
A smoke control system may also have to be designed to work with
gas-based fire extinguishers, such as the halon gas systems installed in
many computer rooms. If the smoke contr ol system tried to vent a r oom
with such a system, it would probably vent the fire suppressing gas as
well. Removing the gas lets the fire continue burning. Also, pressurizing
the areas surrounding an extinguisher equipped room reduces the
effectiveness of the system as well. Air forced into the room from the
outside by pressure can provide the fire with the oxygen it needs to
continue burning. So, gas-based fire extinguishers and smoke control
systems should not be active at the same time in the same area.
The smoke control system receives the location of the fire from the fire
panel. The fire panel uses a combination of smoke and heat sensors to
determine where the fire is located.
In the event that signals are received from more than one smoke zone,
the smoke control system should continue automatic operation in the
mode determined by the first signal received.
TOC
Smoke control systems should never be triggered by manual pull boxes.
The risk of someone pulling a box someplace other than the fire zone is
too high for you to trust your smoke control system to this form of
activation.
All smoke control systems installed in buildings must meet the
standards established by the National Fire Protection Association in
their publication NFPA 92A, Smoke Control Systems, 1988 edition. You
can find additional information regarding fire alarm control units in the
Underwriters Laboratories Inc. Standard UL 864.
Andover Controls Corporation1-7
The Fundementals of Smoke Con trol
Designing a Smoke Control System
What is the basic goal of the smoke control system? To maintain a
tenable environment. A tenable environment allows:
•The building’s occupants to evacuate safely
•The fire fighters to get to the fire zone
The first step you take in designing your smoke control system is to lay
out the smoke control zones, as previously explained. After the smoke
zones are established, you have to address the following design factors:
•The zone-by-zone smoke control strategies to use
•The amount of pressure needed to contain smoke
•Proper separation between zones
•The fans and ductwork used in the smoke control system
TOC
•Dampers required for smoke control
•The air inlets and outlets used in the smoke control system
•Duct smoke detectors
Devising a Smoke Control Strategy
For each zone in your building, you have to establish a smoke control
strategy. The smoke control strategy is a series of steps the smoke
control system must take to contain the smoke. For each zone, you must
decide:
•Whether you should depressurize the zone if a fire occurs.
•If the zone is to be depressurized, by how much you should
depressurize it.
•Which adjacent zones should be pressurized and how much pressure
is required.
Some zones in your building may need special consideration. As
mentioned earlier, zones that have gas fire extinguisher systems should
not be vented (depressurized) and the zones surrounding the fire zone
with such a system should not be pressurized. You may not be able to
pressurize other areas, such as hospital or animal labs, due to the risk of
contaminating surrounding areas.
Consider the number of zones surrounding the fire zone that should be
pressurized. While in theory, all you need to do is to pressurize all of the
1-8Infinity Smoke Control Guide
The Fundementals of Smoke Control
zones immediately surrounding the fire zone, it is possible that smoke
can find its way around the pressurized areas and infiltrate zones far
away. Depending on the size of your building, and the capacity you plan
to have in the smoke control system, you may decide you want to
pressurize more than just the surrounding zones. But, the more zones
you want to pressurize, the larger your air supply system needs to be.
Write down the state that all fans, dampers, and other smoke control
equipment should be in to control smoke in each zone. Later, you have
to program this information into the smoke control system. This
information gives the smoke control system a strategy for containing
smoke in each possible fire zone.
TOC
Andover Controls Corporation1-9
The Fundementals of Smoke Con trol
Determining the Amount of
Pressure Needed
Since air pressure is what keeps smoke from spreading, the primary
design factors are the amount of pressure that you need to confine the
smoke and the size of the system used to create this pressure.
For the smoke control system to create a barrier of air pressure between
the smoke zone and surrounding zones, the amount of pressure required
varies with the height of the ceiling and whether or not the building has
a sprinkler system. The next table shows the minimum pressure
differential needed to keep smoke out of surrounding rooms.
Table 1-1. Minimum Pressure Differential to
Pressu rize Fir e Zone
TOC
Sprinkler
System
YesAny0.05
No9 ft0.10
No15 ft0.14
No21 ft0.18
Ceiling
Height
Minimum Pressure
Differential (wg)
For buildings without sprinklers and with ceiling heights not shown in
the table, you can use the following formula to determine the minimum
amount of pressure needed to keep smoke out:
1
MinimumPressure7.64H×
-----
T
1
----–SafetyFactor+×=
T
o
f
H is the distance between the fire space and a surrounding space where
2
the pressure differential is zero. A figure of the floor to ceiling height
--
3
is a conservative estimate.
To is the absolute room temperature of t he surrounding zones measured
in °R (degrees Rankine). Typically, To = 530° R (70° F). The conversion
from °R to °F is: °R = °F + 460.
Tf is the absolute temperature of the hot gases in the fire z one. It is a lso
measured in °R. Typically, Tf is 2160° R (1700° F).
1-10Infinity Smoke Control Guide
The Fundementals of Smoke Control
SafetyFactor is a constant added to the results to make sure they are
sufficient. A value of 0.03 wg (inches water gauge) is recommended.
Pressure buildup in an area depends on how much leakage there is.
Leakage occurs through joints, cracks, openings for pipes and wires,
gaps between doors and their door jams, and so forth. The better the
zone is sealed off from its neighbors, the easier it is to maintain the
required pressure. Since larger openings, like doorways that are
normally open, require large amounts of air to maintain pressurization,
you should avoid this type of situation.
TOC
Andover Controls Corporation1-11
The Fundementals of Smoke Con trol
Separating Zones
You must separate smoke zones from one another by smoke barriers,
which prevent smoke from passing through them. Smoke barriers can be
a wall, a floor, or a ceiling. Any openings in the smoke barrier must be
closed with a smoke-proof fitting. For example, all duct work going
through a smoke barrier must have a smoke damper in it. A smoke damper is a damper that prevents smoke from passing through it when
fully closed. (Refer to the dampers section below for more information.)
During a smoke emergency all of the fittings should seal themselves, so
that smoke cannot penetrate the barrier.
Since the smoke control zones should be the same as the fire control
zones, you usually separate your zones with a fire ra ted partition. A fire
rated partition is a wall that is built of fire resistant materials and that
reaches from floor to ceiling. Different floors should be separated by a
fire rated ceiling, a ceiling made of fire resistant materia ls . Both fire
rated partitions and fire rated ceilings are rated for the amount of time
they can withstand a fire. Any openings in a fire rated partition or c eiling
must be sealable with a fire rated closure, such as fire rated doors or fire
damper.
TOC
Selecting Dampers
The dampers used to isolate the smoke zone must be smoke dampers.
Smoke dampers are dampers that meet the requirements given in UL
555S, Standard for Leakage Rated Dampers for Use in Smoke Control Systems. Following this standard ensures that the dampers are able to
block the smoke when they are fully closed. These dampers may be
different from those you might use in an HVAC system that does not
perform smoke control.
In a smoke control system, the dampers must be able to travel to their
desired setting in 75 seconds. All dampers must be fitted with end
position microswitches to provide feedback to the smoke control
system. These switches let the control system know the position of the
dampers, since smoke dampers are usually either fully closed or fully
open.
Dampers sometimes function as both smoke dampers and fire dampers.
Fire dampers are dampers that block a fire from penetrating a fire rated
partition via a duct. These dampers are normally open, held in place by
a fus ible link. The f usible link is a heat-sensitive device that releases the
1-12Infinity Smoke Control Guide
The Fundementals of Smoke Control
dampers when it is heated to a certain temperature. Once the fusible link
releases, the dampers close by the force of gravity. So, fire dampers
operate even if the electricity has failed. The specif ications for fire
dampers appear in the document UL555, Standard for Fire Dampers.
If you want a damper to function as both a smoke damper and a fire
damper, it must meet the requirements for both devices. These dampers
can be operated by electric motors or pneumatics. But it must, however,
also have a fusible link or other means of closing automatically, like a
regular fire damper. The control system can override the closure due to
temperature. The damper needs the fusible link in case the automatic
control of the damper by the control system is interrupted.
Choosing Fans and Duct Work
The fans and duct work used in the smoke control system must be
capable of providing the amount of pressure you calculated earlier. In a
nondedicated system, this may mean that you need to install fans that
have a higher capacity than the HVAC system calls for. The ducts must
be capable of taking the pressurization (or the depressurization, for the
fire zone’s return duct) that the smoke control system will exert.
TOC
Both the fans and the ducts should meet the requirements stated in
NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems.
Fans for a smoke control system normally do not have to meet any
special heat resistance rating. In a smoke control system, fans must be
able to reach the required setting in 60 seconds. Each fan must have a
pressure monitor mounted so that the smoke control system can receive
feedback on the status of the fan to determine whether it is actually
operating or not.
In some climates, the outside air can be so cold that drawing it directly
inside the building can damage the building’s interior (freeze pipes or
damage temperature-sensitive equipment, for example). In these cases,
some sort of preheater needs to be installed on the air inlet. The smoke
control system does not have to control the heater as closely as one in an
HVAC system, since maintaining comfort levels is not an issue. It
simply has to make sure the air sent into an area is not going to damage
the building’s interior.
Andover Controls Corporation1-13
The Fundementals of Smoke Con trol
Positioning Air Inlets and Outlets
You need to carefully consider the placement of the air inlets and outlets
on your building. If you place an outlet that vents smoke too close to an
air inlet, the air intake can draw the smoke back into the building.
Since smoke rises, the exhausts that vent smoke should be placed well
above air inlets. The exhausts should be placed at least 3 ft above the
roof level, to allow space for the smoke to rise and disperse.
Keeping smoke outlets far away from air inlets does not guarantee that
the air brought into the building is always smoke free. You may want to
place smoke detectors in air inlets that operate during a smoke
emergency. If the detector finds smoke in the incoming air, it alerts the
control system. The control system has to decide whether or not to shut
down the air inlet.
TOC
You should refer to NFPA 90A for more information on smoke
detectors in inlets and outlets.
1-14Infinity Smoke Control Guide
The Fundementals of Smoke Control
Employing Dedicated Smoke
Control Systems
Most of the systems discussed so far have been nondedicated systems.
Even in a building whose primary smoke control system is
nondedicated, you may have special zones or functions where you need
to use a dedicated system. The most common dedicated system is a
dedicated smoke control system for a stairtower.
StairTowers
Stairtowers are stairwells with a ventilation system and are isolated
from the main building. The only connection between the building and
the stairtower is fire-rated doors on each floor. Since the building’s
occupants should use the stairtower to leave during an evacuation,
keeping the stairtower smoke free is vital.
TOC
A stairtower has its own dedicated system that pressurizes the stairwell
to keep smoke out. This dedicated system can take several forms, from
a fan mounted in the roof of the stairtower, to a duct system that delivers
air to each level.
You must pressurize a stairtower enough to keep smoke out. However,
if the pressure in the stairtower is too great, then opening the doors
leading into the stairtower can be difficult. You must strike a balance.
The stairtower smoke control system must pressurize the stairway
enough to keep the smoke out, but it must not pressurize it so much that
the doors cannot be opened.
Figure 1-4. The Effects of Too Much and Too Little Pressure
Too Much Pressure
Too Little Pressure
StairtowerBuildingStairtowerBuilding
Andover Controls Corporation1-15
The Fundementals of Smoke Con trol
TOC
Figure 1-5. Parts of a Stairtower System
Exhaust Fan
or Vent
Air
Supply
Duct
Pressure
Vents
Fire Rated Door
Supply Fan
StairtowerBuilding
1-16Infinity Smoke Control Guide
The Fundementals of Smoke Control
Ensuring Doors Can Be Opened
The table below shows the maximum allowable pressure differential
across a door in inches water gauge based on how wide the door is and
how much force the automatic door closing mechanism exerts. At the
pressures shown in the table, the door requires 30 lbf (pound of force) to
open, the maximum limit suggested by the NFPA Life Safety Code.
Pressure Differential for Various
Door Widt h s (inches)
32 in36 in40 in44 in48 in
The table above assumes a door height of 7 ft and a distance from the
doorknob to the knob side of the door of 3 in. If your door does not meet
these requirements, or has opening hardware other than a doorknob,
such as panic hardware, then refer to the ASHRAE publication Design of Smoke Control Systems for Buildings for a formula to calculate the
proper opening force. The door widths in the table are only valid for
doors that are hinged at one end. For other types of doors, see the
ASHRAE document.
Many door closers vary the amount of force as the door opens. They
provide less resistance in the early stages of opening t he door than they
do later, when the door is almost fully open. The force to open the door
shown in the previous table represents the force needed to open the door
only enough to let air flow through the opening. Once air is able to flow,
the force exerted by the difference in air pressure on the door lessens.
Therefore, when calculating the force required to open the door, you
may need to lower the door closer force.
Andover Controls Corporation1-17
The Fundementals of Smoke Con trol
Controlling Pressure in a Stairtower
Stairtower smoke control systems are divided into two categories—
noncompensated and compensated. Noncompensated systems simply
turn on a fan to pressurize the stairtower. The fan’s speed does not
change to compensate for doors opening and closing. The more doors
that are open, the more the pressure differential between the stairwe ll
and the building drops.
Figure 1-6. Compensated and Noncompensated Stairtower
Systems
Constant
Speed
Fan
VariableSpeed
Fan
TOC
Vent
A compensated system adjusts the airflow to make up for pressure lost
through open doors. It can use dampers to relieve excess pressure in the
stairtower to ensure that the pressure does not go over the maximum
limit.
There are a number of ways compensated stairtower smoke control
systems can control pressurization. In a basic system with a roofmounted fan blowing air into the stairtower, pressure can be regulat ed by
varying the speed of the fan, the pitch of the fan’s blade, the inl et vanes,
or the number of fans operating (assuming there is more than one).
More sophisticated systems use ducts to deliver air to several points in
the stairtower. The dampers can be controlled to maintain the
appropriate pressure in their zone.
1-18Infinity Smoke Control Guide
The Fundementals of Smoke Control
TOC
Figure 1-7. Examples of Controlling Stairtower Pressure
Pressurizati o n Fan
Air Pressure
Duct
Duct systems can also use bypass dampers and ducts to control the
amount of air flowing from the fan to the outlets. The bypass dampers
are opened when the stairtower is at the proper pressure, so that excess
air flows not into the duct system, but into the bypass duct and back to
the air inlet. See the next diagram for an example of a bypass duct
system.
Figure 1-8. A Bypass Pressure Control System
Bypass Duct Dampers
Bypa ss Duct
Air Intake
Andover Controls Corporation1-19
The Fundementals of Smoke Con trol
There are also a number of ways a compensated stairtower smoke control
system can get rid of excess air pressure, to ensure that the doors leading into
the stairtower can open properly. One or more vents to the building’s
exterior (with dampers) can be used in the stairtower to release excess
pressure. These dampers can be barometrically controlled (being forced
open by the excess air pressure) or controlled by electric motors or
pneumatics as in conventional HVAC systems. In both cases, the dampers
must be placed far enough away from the air s upply to prevent venting of
air that has not yet been able to disperse through the stairtower. Vents can
also lead into the building, but you should consider carefully the impact of
venting extra pressure into the building before using this type of vent.
In some cases, a ground-level stairtower door can be used in place of
dampers. This door automatically opens and closes to maintain the
proper amount of pressure in the stairtower. The door is usually locked,
for security reasons. During an emergency, the smoke control system
has to be able to override the lock. Using a door in this manner has its
problems, since wind effects close to the base of a building could
prevent the air from escaping through the door.
TOC
Figure 1-9. Methods of Controlling Stairtower Pressure
Roof-mounted Exhaust Fan
Vent to Outside with Barometrically
or Automatically Controlled Dampers
Automatic Door Used to Vent Pressure
You can al so use an exhaust fan to vent th e excess pressure f r om t he
stairtower. Such a f an should be d esigned to op er ate only when th e
stairtower is overpressurized. It should never be on when the pressure
differential between t he building and the s tairtower i s below the lowest
limit.
1-20Infinity Smoke Control Guide
The Fundementals of Smoke Control
Elevators
Elevator shafts present a special menace with regards to smoke control.
The elevator shafts form perfect chimneys to draw smoke into the upper
levels of a building. Since elevators usually have openings on each floor,
and the seals on the elevator doors are often poor, the elevator shaft can
become a mechanism to spread smoke throughout a building. Smoke
control in an elevator shaft is an important consideration in the overall
smoke control plan.
Figure 1-10. Smoke Control For Elevator Shafts
Low Pressure Area
Created by Elevator
TOC
Speci a l Smoke
Proof Elevator
Doors
Low Pressure Area
Created by Elevator
Pressurization Fan
for Elevator Shaft
If you could manage to make them safe during smoke emergencies,
elevators would ease the evacuation of the building, especially for
people in wheelchairs. To have the elevators usable during a smoke
emergency, you need to pressurize the elevator shafts the same way you
pressurize a stairtower.
However, pressurizing the elevator shaft presents a number of problems.
While the elevator doors can be fitted with improved seals and rubber
sweeps, these systems will no t totally e liminate air leakage. Also, most
elevator shafts are not designed to be pressurized. They often have large
openings at the top where the cables feed into the winding room. Shafts
are often constructed of porous material that cannot contain the air
pressure. And since most shafts are not designed to be inspected after the
elevators are installed, finding and repairing cracks that would let smoke
infiltrate or pressure esc ap e is difficult.
Andover Controls Corporation1-21
The Fundementals of Smoke Con trol
Another primary problem with letting elevators run during a smoke
emergency is the localized pressure differences that the cars create as
they travel up and down the shafts. For example, a car moving down
from the top of the shaft may create a small low air pressure zone near
the shaft’s top, which can pull smoke from the fire zone into the shaft.
At the present time , these issues have not be en resolved. Pressur izing the
elevator shafts so that the elevators can operate during a smoke
emergency is still being studied. In general, elevators should not be used
as an escape route during an evacuation.
TOC
1-22Infinity Smoke Control Guide
The Fundementals of Smoke Control
Detecting Smoke
The fire control system is the system that is connected to the smoke and
fire detectors. Every smoke zone should have a Listed smoke and fire
detector installed in it. The detectors should be located so that they will
detect the presence of smoke or fire before it spreads beyond the zone.
Once the fire control system detects the fire, it relays to the smoke
control system the zone and the type of alarm that was triggered. The
smoke control system then takes action.
Never use manual pull stations to start the smoke control system. There
is no guarantee that the person pulling the alarm is in the same smoke
zone as the fire. The automatic smoke control system should take only
those actions that are common to all smoke strategies when a manual
pull station is activated. For example, the stairwell can be pressurized in
response to a manual pull box alarm. Implementing a specific smoke
control strategy must wait until the smoke detectors locate the fire zone.
TOC
Configuring and Mon itoring a S moke Control
System
The smoke control system should be able to act on its own in response
to detecting smoke. When it detects smoke, the system enacts the
strategy you planned out (as discussed in the design section of this
article). The automatic smoke control should stick with the strategy to
control smoke in the first zone that smoke is detected in. It would be
difficult for you to create strategies for controlling smoke in all possible
combination of zones.
The automatic smoke control system must have the highest priority over
all other automatic control systems in the building. It must override
energy management, occupancy schedules, or other controls. The
smoke emergency will probably last only several hours, so the impact
on energy management should be minimal. The only systems that
should be able to automatically override the smoke control system are
such safety systems as high pressure limiters.
Considering how unpredictable smoke is, you must have a manual
control panel from which the smoke control system can be monitored
and overridden. This panel, called a Firefighter’s Smoke Control Station
(FSCS), allows firefighting personnel to take manual control of the
smoke control system.
Andover Controls Corporation1-23
The Fundementals of Smoke Con trol
Firefighter’s Smoke Control Station
The Firefighter’s Smoke Control Station (FSCS) is a graphic
annunciating control panel that gives firefighters information about the
state of the smoke control system as well as manual control over all of
its components. The FSCS should be located in a secure room or cabinet
to prevent unauthorized personnel from tampering with it. The room or
cabinet should be clearly marked so that firefighters can quickly locate
the FSCS.
The Fireman’s Smoke Control Station panel has a diagram of the
building showing the entire smoke control system, along with status
lights and override switches for all of the system’s components. The
diagram of the building should include all smoke control zones, all of
the ducts leading to and from the zones with arrows indicating the
direction of air flow in the ducts, and a clear indication of which zone
each piece of equipment serves.
TOC
The panel must have controls to activate all fans, dampers, and other
equipment related to the smoke control system. These manual controls
must be able to override all automatic control of smoke control
equipment. In particular, the FSCS must be able to override:
•Hand/off/auto switches
•Local start/stop switches on fan motor controllers
•Freeze detection devices
•Duct smoke detectors
The FSCS must not override such safety controls as:
•Electrical overload protection
•Maintenance personnel’s electrical disconnects
•High limit pressure switches
•Any fire/smoke damper thermal control as required by UL33
(standard for heat responsive links for fire protection service), heat
responsive links, or UL555S (the standard used for leakage rated
dampers for use in smoke control systems).
In non-dedicated systems, local motor controller’s hand/off/auto
switches can remain in-circuit with the FSCS panel. But, they can
remain in-circuit only if the switches are in a locked room accessible
only to authorized personnel. Also, if such a switch is thrown, a trouble
alarm must sound in the building’s main control center.
1-24Infinity Smoke Control Guide
The Fundementals of Smoke Control
The indicator lights on the FSCS provide information about the
functioning of the system. The following colors should be used for the
FSCS indicators:
•Green—Fans and other equipment are running or dampers are open.
•Yellow—Dampers are in the closed position.
•Orange or Amber—The equipment has failed.
•Red—A fire has been detected in the area.
The FSCS has a lamp te st button that turns on all t he panel’s li ghts. Use
this button regularly to make sure none of the lights has burned out.
The FSCS gets information on the status of the smoke control system’s
equipment from proof monitors on the equipment itself. Each fan that
has a capacity over 2,000 cfm capacity should be mounted with a
pressure monitor. Smoke dampers should be fitted with end-range
microswitches to indicate that they are fully opened or fully closed.
TOC
All of the failure lights on the FSCS (the orange or amber ones)
represent the state of the equipment as determined by the proof sensors.
The failure light comes on if the piece of equipment is not in the state its
control is set for within its trouble indication time. This time is 60
seconds for a fan and 75 seconds for a damper. If, within that time, the
proof sensors do not report that the piece of equipment has responded to
the control system’s command, the FSCS indicates that the piece of
equipment has failed.
Andover Controls Corporation1-25
The Fundementals of Smoke Con trol
Testing the System
During the installation, you should perform operational tests that make
sure the components and subsystems of the smoke control system are
installed correctly. After the installation is done, you must perform
acceptance tests, to prove that the smoke control system is capable of
doing what it was designed to do. The testing procedures are covered in
a later chapter of this manual.
Bibliography
The National Fire Prot ection As sociation. NFP A 90A, Standard for the
Installation of Air Conditioning and Ventilating Systems. The National
Fire Protection Association.
The National Fire Protection Association. 1988. NFPA 92A, Recommended Practices for Smoke Control Systems. The National Fire
Protection Association.
TOC
Underwriters Laboratories, Inc. UL 555S, Standard for Leakage Rated
Dampers for Use in Smoke Control Systems. Underwriters Laboratories,
Inc.
Underwriters Laboratories, Inc. UL 555, Fire Dampers. Underwriters
Laboratories, Inc.
Underwriters Laboratories, Inc. UL 864, Control Units for Fire-Protective Signaling Systems. Underwriters Laboratories, Inc.
1-26Infinity Smoke Control Guide
Chapter 2
Infi nity Smoke Contr o l
System Components
This chapter presents a general overview of the Infinity smoke control
system and describes the UL listed system components used, the
features of each component, and their role within the system. The
following components are described:
•CX9200 main controller
•SCX920S controller
TOC
•TCX840 series controllers
•TCX850 series controllers
•TCX860/865 series controllers
•EnergyLink 2500 repeater
•InfiLink 200 repeater
•InfiLink 210 repeater
•FSCS (Firefighter’s Smoke Control Station)
•Fire Panel
Infinity Smoke Control System Components
Smoke Control System Overview
Figure 2-1 shows the components that are used in an Infinity smoke
control system and how they are connected together. The component
descriptions in the re mai nder of this chapter describe in more detail the
role of each component in the system. Notice that the smoke control
system itself is electricall y isol ated from the non-smoke control
components.
Figure 2-1. Smoke Control System Overview
Smoke Detectors,
Fire Detectors,
Manual Pull Boxes,
Etc.
TOC
RS-232
Cable
RS-232
Cable
fiber opti c
cable
SX8000
Workstation
CX9200
Infilink
200
Infi n et Cable
EnergyLink 2500
EnergyNet
Cable
SCX920S
UL Listed Smoke C ont rol Compon ents
Non-Sm oke Contr ol C omponent s
TCX 850
seriesseries
TCX 840
series
TCX 860/5
fiber optic
cable
Infilink
210
2-2Infinity Smoke Control Guide
Loading...
+ 160 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.