ACC EMX 150
Installation Guide
Your warranty is effective for 18 months starting on the
date the system is shipped.
Before You Begin
You can connect one or more EMX modules to most Infinet
controllers that have an expansion port. The particular controllers are covered in the ACC EMX Modules Configuration
Guide (also enclosed with this product).The configuration
guide also tells how many inputs and outputs are allowed for
any a particular controller. Before you proceed, be sure the
controller allows modules and the number and type of modules you plan to use.
Warning
Be sure wiring and installations comply with local, state,
and national electrical codes.
Figure 1 shows the EMX 150 module.
Version 1.2
ternal power supply source of 24 VDC and properly
connect the modules to it. See the ACC EMX Modules
Configuration Guide for more information.
The EMX 150 consumes up to 55 mA at 24 VDC.
Environmental Requirements
The EMX 150 operates in the same environment that any
Infinet controller operates in.
Output Characteristics
The voltage output has 5 mA maximum output over the
range of 0 to 20 VDC. The input impedance of the device
being controlled can be no less than 4000
Resolution of each voltage output is 0.100 V or 100 mV.
The current output has a 0 to 20 mA control signal. The
input impedance of the device being controlled can be no
greater than 750
Ω.
Ω.
Figure 1. The EMX 150 Module
BOARD
1
EMX150
OVERRIDE
A
AUTO MAN
B
A
B
2
OUTPUT
A
OUTPUT
B
EXTERNAL
POWER
RET
RET
I
V
I
V
Dimensions
Each EMX 150 module is approximately 6.13 × 4.88 × 1.52 in.
Power Requirements
The first two modules receive power from the controller
and operate on 24 to 26 VDC. You can add additional
EMX modules other than an EMX 150 if you have an ex-
The circuitry that produces the 0 to 20 mA signal acts as a
“current sourcing device.” It sources the current to ground.
Resolution of each current output is 100
µA or 0.1 mA.
Install the EMX 150
1. Unpack
Be careful when unpacking the unit or units to not damage
the packaging material—you must reuse it if you ship the
product back for repair.
2. Connect to the Infinet Controller
Connect the module to the Infinet controller as outlined in
the steps that follow.
Caution
Be sure you disconnect the Infinet controller’s AC power
source before you connect any modules.
Downloaded from - http://www.guardianalarms.net
Click for EMX Menu
1.Look at the bottom panel of your Infinet controller. On
that panel is an expansion port in approximately the
center of the panel.
2.Look at the EMX 150 module. Notice that it has a
connector on the top and on the bottom. Plug the top
connector into the Infinet controller.
3.If you are connecting more than one EMX 150 module
to your Infinet controller, connect the second one to the
bottom of the first.
4.Set the BOARD switch to 1 on the first EMX 150 on the
controller, and the BOARD switch to 2 on the second
EMX 150. If you do not plan to connect more than one
EMX 150, you should set the BOARD switch to 1.
Never set two modules of the same model number to the
same board number.
3. Connect the External Power Supply
(if necessary)
4. Reposition Jumper on One Module
The Berg type connector immediately below the external
power supply connection has a jumper that you reposition
to indicate you are using external power.
Figure 3 shows the jumper in the two possible positions,
one for the internal power supply, the other for the external.
Figure 3. Jumper Positions for Internal and External
Power Supplies
Jumper Position,
Internal Power
Supply
Each is set to the internal position when you receive it.
You change the jumper position only on the module or modules connected to the external power supply, not on any other
modules.
Jumper Position,
External Power
Supply
If you are installing multiple modules, you may need an
external power supply. To determine what you need, refer
to the ACC EMX Modules Configuration Guide.
Figure 2 shows where you connect the external power supply
to the 2-pin Berg type connector on the EMX 150. It also
shows outputs, their potentiometers and override switches.
Figure 2. Location of External Power Connection
and Jumper for External Power
BOARD
1
EMX150
OVERRIDE
A
AUTO MAN
B
A
B
Potentiometers
2
OUTPUT
A
OUTPUT
B
EXTERNAL
POWER
Connect
External
Power
Supply
Here
RET
RET
I
V
Power
I
V
Supply
Jumper
Note
You need to change the jumper position only on the module(s) actually connected to an external power supply. Never
change the jumper position of other modules.
Wire the Outputs
You can wire the outputs to either voltage or current sensors.
Wire Voltage Outputs
You wire the outputs for voltage as follows:
1. Slip the appropriate wire under the V screw and tighten
the screw down on it.
Figure 4 illustrates the wiring for voltage outputs.
Figure 4. Wiring Diagram for Voltage Outputs
V
+
RL > or = 4 KΩ
RET
2. Slip the ground wire under the RET screw and tighten
the screw down on it.