Andover Controls ACC EMX 150 Installation Guide

Copyright © 1991 Andover Controls Corporation, 300 Brickstone Square, Andover, MA 01810 All Rights Reserved.
Click for EMX Menu
Order No. 30-3001-198
ACC EMX 150 Installation Guide
Your warranty is effective for 18 months starting on the date the system is shipped.
Before You Begin
You can connect one or more EMX modules to most Infinet controllers that have an expansion port. The particular con­trollers are covered in the ACC EMX Modules Configuration Guide (also enclosed with this product).The configuration guide also tells how many inputs and outputs are allowed for any a particular controller. Before you proceed, be sure the controller allows modules and the number and type of mod­ules you plan to use.
Warning
Be sure wiring and installations comply with local, state, and national electrical codes.
Figure 1 shows the EMX 150 module.
Version 1.2
ternal power supply source of 24 VDC and properly connect the modules to it. See the ACC EMX Modules Configuration Guide for more information.
The EMX 150 consumes up to 55 mA at 24 VDC.
Environmental Requirements
The EMX 150 operates in the same environment that any Infinet controller operates in.
Output Characteristics
The voltage output has 5 mA maximum output over the range of 0 to 20 VDC. The input impedance of the device being controlled can be no less than 4000
Resolution of each voltage output is 0.100 V or 100 mV.
The current output has a 0 to 20 mA control signal. The input impedance of the device being controlled can be no
greater than 750
Ω.
Ω.
Figure 1. The EMX 150 Module
BOARD
1
EMX150
OVERRIDE
A
AUTO MAN
B A
B
2
OUTPUT
A
OUTPUT
B
EXTERNAL
POWER
RET
RET
I V
I V
Dimensions
Each EMX 150 module is approximately 6.13 × 4.88 × 1.52 in.
Power Requirements
The first two modules receive power from the controller and operate on 24 to 26 VDC. You can add additional EMX modules other than an EMX 150 if you have an ex-
The circuitry that produces the 0 to 20 mA signal acts as a “current sourcing device.” It sources the current to ground.
Resolution of each current output is 100
µA or 0.1 mA.
Install the EMX 150
1. Unpack
Be careful when unpacking the unit or units to not damage the packaging material—you must reuse it if you ship the product back for repair.
2. Connect to the Infinet Controller
Connect the module to the Infinet controller as outlined in the steps that follow.
Caution
Be sure you disconnect the Infinet controller’s AC power source before you connect any modules.
Downloaded from - http://www.guardianalarms.net
Click for EMX Menu
1.Look at the bottom panel of your Infinet controller. On that panel is an expansion port in approximately the center of the panel.
2.Look at the EMX 150 module. Notice that it has a connector on the top and on the bottom. Plug the top connector into the Infinet controller.
3.If you are connecting more than one EMX 150 module to your Infinet controller, connect the second one to the bottom of the first.
4.Set the BOARD switch to 1 on the first EMX 150 on the controller, and the BOARD switch to 2 on the second
EMX 150. If you do not plan to connect more than one EMX 150, you should set the BOARD switch to 1.
Never set two modules of the same model number to the same board number.
3. Connect the External Power Supply
(if necessary)
4. Reposition Jumper on One Module
The Berg type connector immediately below the external power supply connection has a jumper that you reposition to indicate you are using external power.
Figure 3 shows the jumper in the two possible positions, one for the internal power supply, the other for the external.
Figure 3. Jumper Positions for Internal and External Power Supplies
Jumper Position, Internal Power Supply
Each is set to the internal position when you receive it.
You change the jumper position only on the module or mod­ules connected to the external power supply, not on any other modules.
Jumper Position, External Power Supply
If you are installing multiple modules, you may need an external power supply. To determine what you need, refer to the ACC EMX Modules Configuration Guide.
Figure 2 shows where you connect the external power supply to the 2-pin Berg type connector on the EMX 150. It also shows outputs, their potentiometers and override switches.
Figure 2. Location of External Power Connection and Jumper for External Power
BOARD
1
EMX150
OVERRIDE
A
AUTO MAN
B A
B
Potentiometers
2
OUTPUT
A
OUTPUT
B
EXTERNAL
POWER
Connect External Power Supply Here
RET
RET
I V
Power
I V
Supply Jumper
Note
You need to change the jumper position only on the mod­ule(s) actually connected to an external power supply. Never change the jumper position of other modules.
Wire the Outputs
You can wire the outputs to either voltage or current sensors.
Wire Voltage Outputs
You wire the outputs for voltage as follows:
1. Slip the appropriate wire under the V screw and tighten the screw down on it.
Figure 4 illustrates the wiring for voltage outputs.
Figure 4. Wiring Diagram for Voltage Outputs
V
+
RL > or = 4 K
RET
2. Slip the ground wire under the RET screw and tighten the screw down on it.