Amprobe ACD-41PQ Specifications

Page 1
Data Sheet
600V
ACD-41PQ
1000A Power Quality Clamp­on with THD Measurement
The ACD-41PQ provides a simple and effective way to verify if the electrical system is affected by harmonics. Enhanced troubleshooting capabilities with the Power analysis functions. Increase your ability analyze the data with an optional PC interface kit.
TRMS sensing
Measurements: Total Harmonics Distortion THD, AC/DC Voltage up to 600V, AC Current up to 1000A, Resistance, Frequency, Temperature
ACD-41PQ also measures Active (W), Reactive (VAR) and Apparent (VA) Power with dual-display Power Factor readout
No hassle warranty
No waiting.
No shipping charges.
(note: $500 MSLP limit)
AutoTect™ - Auto Selection of AC Volts, DC Volts or AC Amps
Total Harmonic Distortion to 51st harmonic
Optional PC interface capability
Audible continuity
Auto power off
Automatic polarity
Low battery indication
Peak hold
Data hold
Large, easy to read LCD display with backlight
Accommodates conductors up to 1.77” (45mm) in diameter
Carrying case, test leads, batteries (installed), thermocouple and manual included
Voltage overload protection for all functions up to 600V AC/DC
Amprobe® Test Tools
www.Amprobe.com
Page 2
ACD-41PQ 1000A Power Quality Clamp-on with THD Measurement
Data Sheet
Specifications (valid for 23 °C ± 5 °C, for less than 70 % relative humidity).
Display
Voltage functions 6000 counts LCD display(s) Power, Ohm & Hz functions 9999 counts LCD display(s) ACA clamp-on function 4000 counts LCD display(s) Update Rate Power function 1 per second nominal Voltage, ACA clamp-on, Ohm, Hz &
Polarity Automatic Operating Temperature 0°C to 40°C; < 80% RH @ < 31°C; decreasing linearly to 50% RH @ 40°C Altitude Indoor operation, below 2000m. Storage Temperature -20°C to 60°C, < 80% R.H. (with battery removed) Temperature Coefficient nominal 0.15 x (specified accuracy)/ °C @ (0°C -18°C or 28°C -40°C) Sensing True RMS sensing Power Supply standard 1.5V AA A Size (NEDA 24A or IEC LR03) battery X 2 Low Battery Below approx. 2.4V Power Consumption Voltage, ACA, Hz & Power functions 10mA typical Ohm & Temperature functions 4mA typical APO Timing Idle for 17 minutes APO Consumption 10μA typical Jaw opening & Conductor
diameter 45mm max Dimension 224 x 78mm x 40mm (8.9 x 3.1 x 1.6 in.) Weight 224 gm approx Safety LVD Meets EN60101-1:2001; EN61010-2-032(2002), Category III- 600 Volts ac & dc; pollution degree : 2
Temperature functions 4 per second nominal
EMC EN 61326-1
Electrical Specifications
AC Voltage
Voltage Range Accuracy
600.0V 50Hz to 60Hz ± (0.5% rdg + 5d)
CMRR > 60 dB @ DC to 60 Hz, Rs = 1 k Input Impedance 2 M, 30 pF nominal Crest Factor < 2.3 : 1 at full scale; < 4.6 : 1 at half scale ACV AutoTechTM Threshold 30VAC (40 to 500 Hz) nominal
DC Voltage
Range 600.0 V Accuracy ± (0.5% rdg + 5d) NMRR > 50 dB @ 50/60 Hz CMRR >120 dB @ DC, 50/60 Hz, Rs = 1 k Input Impedance 2 M, 30 pF nominal DCV AutoTechTM Threshold 2.4VDC nominal
PEAK-rms HOLD (ACA & ACV only)
Response 65ms to 90% rdg
45 to 50Hz, 60 to 500Hz ± (1.5% rdg + 5d) 500Hz to 3.1kHz ± (2.5% rdg + 5d)
Amprobe® Test Tools
Page 3
ACD-41PQ 1000A Power Quality Clamp-on with THD Measurement
Electrical Specifications (continued)
Ohms
Range 000.0 to 999.9 Accuracy ± (1.0% rdg + 6d) Open Circuit Voltage 0.4VDC typical
Audible Continuity Tester
Audible threshold between 10and 300 Response time 250μs
Data Sheet
ACA Current (Clamp-on)
Range Frequency Accuracy
40.00A, 400.0A, 1000A 50 Hz / 60 Hz ± (0.5% rdg + 5d)
40.00A, 400.0A 45 to 50 Hz, 60 to 500 Hz ± (2.0% rdg + 5d) 1000A 45 to 50 Hz, 60 to 500 Hz ± (2.5% rdg + 5d)
40.00A, 400.0A 500 Hz to 3.1 kHz ± (2.5% rdg + 5d) 1000A 500 Hz to 3.1 kHz ± (3.0% rdg + 5d) ACA AutoTechTM Threshold 1A AC (40Hz ~ 500Hz only) nominal Crest Factor 40.00A & 400.0A: < 2.5 : 1 at full scale; < 5.0 : 1 at half scale
1)
Induced error from adjacent current-carrying conductor: < 0.06A/A
2)
Specified accuracy is from 1% rdg to 100% rdg of range and for measurements made at the jaw center. When the conductor is not
positioned at the jaw center, position errors introduced are: Add + 1% rdg to specified accuracy for measurements made WITHIN jaw marking lines (away from jaw opening) Add + 4% rdg to specified accuracy for measurements made BEYOND jaw marking lines (toward jaws opening)
Temperature
Range Accuracy
-50°C to -20°C ± (2.0% rdg + 6°C)
-20°C to 300°C ± (2.0% rdg + 3°C)
-58°F to -4°F ± (2.0% rdg + 12°F)
-4°F to 572°F ± (2.0% rdg + 6°F) Type-K thermocouple range & accuracy not included
Frequency
Range 5.00 Hz to 500.0 Hz Accuracy ± (0.5% rdg +4d Range Sensitivity (Sine RMS) 40A > 4A 400A > 40A 1000A > 400A
600V > 30V
1000A: < 1.4 : 1 at full scale; < 2.8 : 1 at half scale
1) 2)
THD% rdg-F (Total Harmonic RMS / Fundamental RMS) x 100%
Range: 0.0% to 999.9% (Range for Dual Display mode: 0% to 99%) Harmonic Accuracy (Specified accuracy @ ACA fundamental > 5A ; ACV fundamental > 50V) Fundamental ± (1.5% rdg + 6d) 2nd ~ 3rd ± (5.0% rdg + 6d) 4th ~ 16th ± (2.5% rdg + 6d) 17th ~ 46th ± (3.0% rdg + 6d) 47th ~ 51st ± (4.5% rdg + 6d)
www.Amprobe.com
Page 4
ACD-41PQ 1000A Power Quality Clamp-on with THD Measurement
Data Sheet
Electrical Specifications
Total Power Factor (PF)
Range Accuracy (Specified accuracy @ ACA fundamental > 2A ; ACV fundamental > 50V)
0.10 to 0.99 F to 21st harmonic 22nd to 51st harmonic
0.10 to 0.99 ± 3d ± 5d
Power (VA)
Range Accuracy 0 to 600.0 kVA F to 10th 11th to 46th 47th to 51st @ PF = 0.99 to 0.1 ± (2.0% rdg + 6d) ± (3.5% rdg + 6d) ± (5.5% rdg + 6d)
Power (kW and kVAR)
Range Accuracy 0 to 600.0 kW / kVAR F to 10th 11th to 25th 26th to 46th 47th to 51st @ PF = 0.99 to 0.70 ± (2.0% rdg + 6d) ± (3.5% rdg + 6d) ± (4.5% rdg + 6d) ± (10% rdg +6d) @ PF = 0.70 to 0.50 ± (3.0% rdg + 6d) ± (3.5% rdg + 6d) ± (4.5% rdg + 6d) ± (10% rdg +6d) @ PF = 0.50 to 0.30 ± (4.5% rdg + 6d) ± (4.5% rdg + 6d) ± (4.5% rdg + 6d) ± (10% rdg +6d) @ PF = 0.30 to 0.20 ± (10% rdg + 6d) ± (10% rdg + 6d) ± (10% rdg + 6d) ± (15% rdg +6d)
1)
Specified accuracy is for ACA clamp measurement at the center of jaws. When the conductor is not positioned at the jaw center, posi-
tion errors introduced are: Add 1% rdg to specified accuracy for ACA measurements made WITHIN jaw marking lines (away from jaw opening) Accuracy is not specified for ACA measurement made BEYOND jaw marking lines (toward jaws opening)
2)
Add 1% rdg to specified accuracy @ ACA fundamental < 5A or ACV fundamental < 90V.
Accuracy is not specified @ ACA fundamental < 1A or ACV fundamental < 30V
3)
Add 1% rdg to specified accuracy @ ACA fundamental < 5A or ACV fundamental < 90V.
Accuracy is not specified @ ACA fundamental < 2A or ACV fundamental < 50V
(continued)
1) 2)
1) 3)
OPTIONAL ACCESSORIES PART NUMBER
PC Interface kit (PC connection cable with software) RS-232 KIT2
Amprobe® Test Tools
website: www.Amprobe.com email: info@amprobe.com Everett, WA 98203 Tel: 877-AMPROBE
Amprobe® Test Tools Europe
Amprobe Test Tools Europe Beha-Amprobe GmbH In den Engematten 14 79286 Glottertal, Germany Tel.: +49 (0) 7684 8009 - 0
©2008 Amprobe Test Tools. All rights re served. 7/20 08 332010 8 Rev A