American Standard Fan Belt Maintenance Manual

Maintenance
Make sure all personnel are standing clear of the unit before proceeding. The system components will start when the power is applied.
Fan Belt Adjustment - Belt Drive Units
WARNING
Rotating Components!
The following procedure involves working with rotating components. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury.
The fan belts must be inspected periodically to assure proper unit operation.
When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base.
Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent) illustrated in
Figure 29, p. 37; adjust the belt tension as follows;
1. To determine the appropriate belt deflection;
a. Measure the center-to-center shaft distance (in
inches) between the fan and motor sheaves.
b. Divide the distance measured in Step 1a by 64; the
resulting value represents the amount of belt deflection that corresponds to the proper belt tension.
2. Set the large O-ring on the belt tension gauge at the deflection value determined in Step 1b.
3. Set the small O-ring at zero on the force scale of the gauge plunger.
4. Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large O­ring is even with the top of the next belt or even with a straightedge placed across the fan and motor sheaves. Refer to Figure 29, p. 37.
5. Remove the belt tension gauge. The small O-ring now indicates a number other than zero on the plunger’s force scale. This number represents the force (in pounds) required to give the needed deflection.
6. Compare the “force” scale reading (Step 5) with the appropriate “force” value listed in Table 10, p. 37. If the “force” reading is outside the range, readjust the belt tension.
Note: Actual belt deflection “force” must not exceed the
maximum “force” value shown in Table 10, p. 37.
Table 10. Belt tension measurement and deflection
ranges
Deflection Force (Lbs.)
Belts
Cross
Section
A
B
Small
P.D
Range
3.0 - 3.6 3 4 1/2 3 7/8 5 1/2 3 1/4 4
3.8 - 4.8 3 1/2 5 4 1/2 6 1/4 3 3/4 4 3/4
5.0 - 7.0 4 5 1/2 5 6 7/8 4 1/4 5 1/4
3.4 - 4.2 4 5 1/2 5 3/4 8 4 1/2 5 1/2
4.4 - 5.6 5 1/8 7 1/8 6 1/2 9 1/8 5 3/4 7 1/4
5.8 - 8.8 6 3/8 8 3/4 7 3/8 10 1/8 7 8 3/4
Super
Gripbelts Gripnotch
Min. Max. Min. Max. Min. Max
Steel Cable
Gripbelts
7. Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension may decrease until the new belts are “run in”.
Figure 29. Belt tension gauge
Monthly Maintenance
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open. Failure to disconnect power before servicing can cause severe personal injury or death.
RT-SVX33G-EN 37
Maintenance
Filters
Inspect the return air filters. Clean or replace them if necessary. Refer to the unit Service Facts for filter information.
Condensate Overflow Switch
During maintenance, the switch float (black ring) must be checked to ensure free movement up and down.
Return Air Smoke Detector Maintenance
Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required.
Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit.
Cooling Season
Check the unit’s drain pans and condensate piping to ensure that there are no blockages.
Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Coil Cleaning” later in this section.
Manually rotate the condenser fan(s) to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight.
Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary.
Verify that all damper linkages move freely; lubricate with white grease, if necessary.
Check supply fan motor bearings; repair or replace the motor as necessary.
Check the fan shaft bearings for wear. Replace the bearings as necessary.
Check the supply fan belt. If the belt is frayed or worn, replace it. Refer to the “Fan Belt Adjustment” section for belt replacement and adjustments.
Verify that all wire terminal connections are tight.
Remove any corrosion present on the exterior surfaces of the unit and repaint these areas.
Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.)
Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete.
With the unit running, check and record the: ambient temperature; compressor suction and discharge pressures (each circuit); superheat (each circuit);
Record this data on an “operator’s maintenance log” like the one shown in Table 11, p. 39. If the operating pressures indicate a refrigerant shortage, measure the system superheat. For guidelines, refer to the “Compressor Start­Up” section.
Note: Do not release refrigerant to the atmosphere! If
adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws.
Heating Season
Inspect the unit’s air filters. If necessary, clean or replace them.
Check supply fan motor bearings; repair or replace the motor as necessary.
Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs.
Verify that the electric heat system operates properly.
Coil Cleaning
Regular coil maintenance, including annual cleaning, enhances the unit’s operating efficiency by minimizing: compressor head pressure and amperage draw; evaporator water carryover; fan brake horsepower, due to increase static pressure losses; airflow reduction.
At least once each year, or more often if the unit is located in a “dirty” environment, clean the evaporator and condenser coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils.
To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump-up type or a high-pressure sprayer). A high-quality detergent is also required; suggested brands include “SPREX A.C.”, “OAKITE 161”, “OAKITE 166” and “COILOX”. If the detergent selected is strongly alkaline (ph value exceeds 8.5), add an inhibitor.
1. Remove enough panels from the unit to gain access to the coil. Remove the access panel from the roof located next to the rear condenser fan.
2. Protect all electrical devices such as motors and controllers from any over spray.
3. Straighten any bent coil fins with a fin comb.
4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution to 150° F maximum to improve its cleansing capability.
38 RT-SVX33G-EN
WARN IN G
Hazardous Pressures!
If a heat source is required to raise the tank pressure during removal of refrigerant from cylinders, use only warm water or heat blankets to raise the tank temperature. Do not exceed a temperature of 150°F. Do not, under any circumstances apply direct flame to any portion of the cylinder. Failure to follow these safety precautions could result in a sudden rise of pressure possibly resulting in a violent explosion which could result in death or serious injury.
Do not heat the detergent-and-water solution above 150°F. Hot liquids sprayed on the exterior of the coil will raise the coil’s internal pressure and may cause it to burst. Failure to follow proper procedures can result in personal illness or injury or severe equipment damage.
5. Pour the cleaning solution into the sprayer. If a high­pressure sprayer is used:
a. do not allow sprayer pressure to exceed 600 psi.
b. the minimum nozzle spray angle is 15 degrees.
c. maintain a minimum clearance of 6" between the
sprayer nozzle and the coil.
d. spray the solution perpendicular (at 90 degrees) to
the coil face.
6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for five minutes.
7. Rinse both sides of the coil with cool, clean water.
Maintenance
8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7.
9. Reinstall all of the components and panels removed in Step 1 and any protective covers installed in step 2.
10. Restore the unit to it’s operational status and check system operation.
Final Process
For future reference, you may find it helpful to record the unit data requested below in the blanks provided.
(1) Complete Unit Model Number:
_____________________________________________________ __________________
(2) Unit Serial Number:
_____________________________________________________ __________________
(3) Wiring Diagram Numbers (from unit control panel):
— schematic(s)
_____________________________________________________ __________________
_____________________________________________________ __________________
— connection(s)
_____________________________________________________ __________________
_____________________________________________________ __________________
Table 11. Sample maintenance log
Refrigerant Circuit #1 Refrigerant Circuit #2
Current
Date
Ambient temp F/C
RT-SVX33G-EN 39
Compr. Oil Level
Suction Pressure Psig/kPa
Dischcharge Pressure Psig/kpa
Super heat F/C
Sub cool F/C
Compr. Oil Level
Suction Pressure Psig/kPa
Dischcharge Pressure Psig/kpa
Super heat F/C
Sub cool F/C
Loading...
+ 6 hidden pages