Duplex CDHF, CDHG
Water Cooled CenTraVac
With CH530
™
CDHF-SVU01C-ENX39640670030
Warnings and
Cautions
Warnings and Cautions
Notice that warnings and cautions
appear at appropriate intervals
throughout this manual. Warnings
are provided to alert installing
contractors to potential hazards that
could result in personal injury or
death, while cautions are designed to
alert personnel to conditions that
could result in equipment damage.
Your personal safety and the proper
operation of this machine depend
upon the strict observance of these
precautions.
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.
WARNING – Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION – Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION – Indicates a situation that may result in equipment or property-damage-only accidents.
Operation and maintenance
information for models CDHF, CDHG
are covered in this manual. This
includes both 50 and 60 Hz. CDHF
and CDHG centrifugal chillers
equipped with the Tracer CH530
Chiller Controller system. Please note
that information pertains to all three
chiller types unless differences exist
in which case the sections are
broken down by Chiller type as
applicable and discussed separately.
By carefully reviewing this
information and following the
instructions given, the owner or
operator can successfully operate
and maintain a CDHF, or CDHG unit.
If mechanical problems do occur,
however, contact a qualified service
organization to ensure proper
diagnosis and repair of the unit.
Unit Nameplate
The unit nameplate is located on the
left side of the unit control panel.
The following information is
provided on the unit nameplate.
1. Serial Number
The unit serial number provides the
specific chiller identity. Always
provide this serial number when
calling for service or during parts
identification..
2. Service Model Number
The service model represents the unit
as built for service purposes . It
identifies the selections of variable
unit features required when ordering
replacements parts or requesting
service.
Note: Unit-mounted starters are
identified by a separate number
found on the starter.
3. Product Coding Block
The CDHF and CDHG models are
defined and built using the product
definition and selection (PDS)
system. This system describes the
product offerings in terms of a
product coding block which is made
up of feature categories and feature
codes. An example of a typical
product code block is given on this
page. The coding block precisely
identifies all characteristics of a unit.
4. Identifies unit electrical
requirements
5. Correct operating charges and type
of refrigerant
6. Unit Test Pressures and Maximum
Operating Pressures
7. Identifies unit Installation and
Operation and Maintenance manuals
A = Unit Voltage
A = 380V-60Hz-3Ph
B = 440V-60Hz-3Ph
C = 460V-60Hz-3Ph
D = 480V-60Hz-3Ph
E = 575V-60Hz-3Ph
F = 600V-60Hz-3Ph
G = 2300V-60Hz-3Ph
H = 2400V-60Hz 3Ph
J = 3300V-60Hz-3Ph
K = 4160V-60Hz-3Ph
L = 6600V-60Hz-3Ph
M = 380V-50Hz-3Ph
N = 400V-50Hz-3Ph
P = 415V-50Hz-3Ph
R = 3300V-50Hz-3Ph
T = 6000V-50Hz-3Ph
U = 6600V-50Hz-3Ph
th
10
-11th A0 = Design Sequence
th
12
B = Compressor Motor
Power, LH Circuit
th
13
C = Compressor Motor
Power, RH Circuit.
Compressor Motor codes:
A = 588 KW
B = 653 KW
C = 745 KW
D = 856 KW
E = 957 KW
F = 1062 KW
G = 1228 KW
H = 433 KW
J = 489 KW
K = 548 KW
L = 621 KW
M = 716 KW
N = 799 KW
P = 892 KW
R = 403 KW
S = 453 KW
T = 512 KW
U = 301 KW
V = 337 KW
W = 379 KW
X = 1340 KW
th
14
-16th 255 = Compressor Impeller
Diameter LH Circuit
th
17
-19th 261 = Compressor Impeller
Diameter RH Circuit
th
20
3 = Evaporator Tube Bundle
Size
1 = 2100 nominal ton
evaporator
2 = 2300 nominal ton
evaporator
3 = 2500 nominal ton
evaporator
4 = 1610 nominal ton
evaporator
5 = 1850 nominal ton
evaporator
st
21
C = Evaporator Tubes
A = I/E copper, 0.028” wall, 0.75” O.D.
B = I/E copper, 0.035” wall, 0.75” O.D.
C = S/B copper, 0.028” wall, 0.75”
O.D.
D = S/B copper, 0.035” wall, 0.75”
O.D.
E = I/E copper, 0.028” wall, 1.0” O.D.
F = I/E copper, 0.035” wall, 1.0” O.D.
nd
22
0 = Not Assigned
rd
B - Evaporator Waterbox
23
A = 150 psig 1 pass marine
B = 300 psig 1 pass marine
C = 150 psig 1 pass non-marine
D = 300 psig 1 pass non-marine
33
Orifice Nominal Tons:
A = 710
B = 790
C = 880
D = 990
E = 1100
F = 1265
G = 1400
H = 1540
K = 1810
J = 1660
L = 1970
M = 2150
N = 1045
P = 1185
R = 1335
T = 1605
U = 1735
A = Starter Type
A = Star-Delta Unit Mounted
C = Star Delta Remote Mounted
E = X-Line Full Volt Remote Mounted
F = Autotransformer Remote
Mounted
G = Primary Reactor Remote
Mounted
H = X-Line Full Volt Unit Mounted
J = Autotransformer Unit Mounted
K = Primary Reactor Unit Mounted
L = Solid State Unit Mounted
M = Solid State Floor Mounted
N = Solid State Wall Mounted
P = Adaptive Freq. Drive-Unit
Mounted
R = Customer Supplied
For convenience, a number of
acronyms are used throughout this
manual. These acronyms are listed
alphabetically below, along with the
“translation” of each:
AFD = Adaptive Frequency Drive
ASME = American Society of
Mechanical Engineers
ASHRAE = American Society of
Heating, Refrigerating and Air
Conditioning Engineers
BAS = Building Automation System
CABS = Auxiliary Condenser TubeBundle S
CDBS = Condenser Bundle Size
CDSZ = Condenser Shell Size
CH530 = Tracer CH530 Controller
DV = DynaView
Display, also know as the Main
Processor (MP)
CWR = Chilled Water Reset
CWR’ = Chilled Water Reset Prime
DTFL = Design Delta-T at Full Load
(i.e., the difference between entering
and leaving chilled water
temperatures)
ELWT = Evaporator Leaving Water
Temperature
ENT = Entering Chilled Water
Temperature
GPM = Gallons-per-minute
HGBP = Hot Gas Bypass
™
Clear Language
HVAC = Heating, Ventilating, and Air
Conditioning
IE = Internally-Enhanced Tubes
IPC = Interprocessor Communication
LBU = La Crosse Business Unit
LCD = Liquid Crystal Display
LED = Light Emitting Diode
MAR = Machine Shutdown Auto
Restart (Non-Latching where chiller
will restart when condition corrects
itself.)
MMR = Machine Shutdown Manual
Restart (Latching where chiller must
be manually reset.)
See Figure 1 for General Unit
components. Each Chiller unit is
composed of the following
components as viewed when facing
the control panel front side:
• Common Evaporator and Common
Condenser
Figure 1. General Duplex unit components - front view
• Compressors and Motor 1 (Left
hand), and 2 (Right hand)
• Economizers 1(LH), and 2 (RH),
• Purge 1(LH), and 2 (RH),
• Oil Tank/ Refrig. Pump 1 (LH), and 2
(RH),
• Control Panel 1 (LH), and 2 (RH)
• And when specified Unit mounted
Starters 1 (LH) and 2 (RH) (not
shown).
8
CDHF-SVU01C-EN
General
Information
Figure 2. General Duplex unit components (2 stage compressor)
CDHF-SVU01C-EN
9
General
Information
Cooling Cycle
Duplex Chillers have two refrigerant
circuits that operate as their own
independent circuits. These circuits
are discussed as individual chiller
refrigeration units in the following
discussion. The sequence of
operation of the two refrigeration
circuits is discussed in a later
section.
When in the cooling mode, liquid
refrigerant is distributed along the
length of the evaporator and sprayed
through small holes in a distributor
(i.e., running the entire length of the
shell) to uniformly coat each
evaporator tube. Here, the liquid
refrigerant absorbs enough heat from
the system water circulating through
the evaporator tubes to vaporize.
The gaseous refrigerant is then
drawn through the eliminators
(which remove droplets of liquid
refrigerant from the gas) and firststage variable inlet guide vanes, and
into the first stage impeller.
Note: Inlet guide vanes are designed
to modulate the flow of gaseous
refrigerant to meet system capacity
requirements; they also prerotate the
gas, allowing it to enter the impeller
at an optimal angle that maximizes
efficiency at all load conditions.
Compressor 1 or 2 (3 Stage)
Compressed gas from the first-stage
impeller flows through the fixed,
second-stage inlet vanes and into the
second-stage impeller.
Here, the refrigerant gas is again
compressed, and then discharged
through the third-stage variable guide
vanes and into the third stage
impeller.
Once the gas is compressed a third
time, it is discharged into the
condenser. Baffles within the
condenser shell distribute the
compressed refrigerant gas evenly
across the condenser tube bundle.
Cooling tower water circulated
through the condenser tubes absorbs
heat from the refrigerant, causing it to
condense. The liquid refrigerant then
passes through orifice plate ‘‘A’’ and
into the economizer.
The economizer reduces the energy
requirements of the refrigerant cycle
by eliminating the need to pass all
gaseous refrigerant through three
stages of compression. See Figure 3.
Notice that some of the liquid
refrigerant flashes to a gas because
of the pressure drop created by the
orifice plates, thus further cooling the
liquid refrigerant. This flash gas is
then drawn directly from the first
(Chamber A) and second (Chamber
B) stages of the economizer into the
third-and second-stage impellers of
the compressor, respectively.
All remaining liquid refrigerant flows
through another orifice plate ‘‘C’’ to
the evaporator.
Compressor 1 or 2 (2 Stage)
Compressed gas from the first-stage
impeller is discharged through the
second-stage variable guide vanes
and into the second-stage impeller.
Here, the refrigerant gas is again
compressed, and then discharged
into the condenser.
Baffles within the condenser shell
distribute the compressed refrigerant
gas evenly across the condenser
tube bundle. Cooling tower water,
circulated through the condenser
tubes, absorbs heat from the
refrigerant, causing it to condense.
The liquid refrigerant then flows out
of the bottom of the condenser,
passing through an orifice plate and
into the economizer.
The economizer reduces the energy
requirements of the refrigerant cycle
by eliminating the need to pass all
gaseous refrigerant through both
stages of compression. See Figure 6.
Notice that some of the liquid
refrigerant flashes to a gas because
of the pressure drop created by the
orifice plate, thus further cooling the
liquid refrigerant. This flash gas is
then drawn directly from the
economizer into the second-stage
impellers of the compressor.
All remaining liquid refrigerant flows
out of the economizer, passes
through another orifice plate and into
the evaporator.
Figure 6. Single stage economizer (2 stage compressor)
12
CDHF-SVU01C-EN
General
Information
Overview
Controls Operator Interface
Information is tailored to operators,
service technicians and owners.
When operating a chiller, there is
specific information you need on a
day-to-day basis — setpoints, limits,
diagnostic information, and reports.
When servicing a chiller, you need
different information and a lot more
of it — historic and active
diagnostics, configuration settings,
and customizable control algorithms,
as well as operation settings.
By providing two different tools –
one for daily operation and one for
periodic service — everyone has
easy access to pertinent and
appropriate information.
DynaView™ Human Interface
— For the operator
Day-to-day operational information is
presented at the panel. Up to seven
lines of data (English or SI units) are
simultaneously displayed on the ¼
VGA touch-sensitive screen.
Logically organized groups of
information — chiller modes of
operation, active diagnostics,
settings and reports put information
conveniently at your fingertips. See
Operator Interface Section for details.
TechView
— For the service technician or
advanced operator
All chiller status, machine
configuration settings, customizable
limits, and up to 60 active or historic
diagnostics are displayed through
the service tool interface. Without
changing any hardware, we give you
access to the latest and greatest
version of Tracer CH530! A new level
of serviceability using the innovative
TechView
technician can interact with an
individual device or a group of
devices for advanced
troubleshooting. LED lights and their
respective TechView
visually confirm the viability of each
device. Any PC that meets the system
requirements may download the
service interface software and Tracer
CH530 updates. For more information
on TechView
Service company, or The Trane
Company’s website at
www.trane.com.
™
Chiller Service Tool
™
chiller service tool. A
™
indicators
™
visit your local Trane
CDHF-SVU01C-EN
13
General
Information
CTV Duplex Sequence Of Operation
This section will provide basic
information on chiller operation for
common events. With
microelectronic controls, ladder
diagrams cannot show today’s
complex logic, as the control
functions are much more involved
than older pneumatic or solid state
controls. Adaptive control algorithms
can also complicate the exact
sequence of operation. This section
and its diagrams attempt to illustrate
common control sequences.
The Sequence of Events diagrams
use the following KEY:
Software States: (Figure 7)
There are five generic states that the
software can be in:
1. Power Up, Stopped, Starting,
Running, Stopping
Timeline Text: (Figures 8-11)
Figure 7. Sequence of operation overview.
The large timeline cylinder indicates
the upper level operating mode, as it
would be viewed on DynaView. Text
in Parentheses indicates sub-mode
text as viewed on DynaView. Text
above the timeline cylinder is used to
illustrate inputs to the Main
Processor. This may include User
input to the DynaView Touch pad,
Control inputs from sensors, or
Control Inputs from a Generic BAS.
Boxes indicate Control actions such
as Turning on Relays, or moving the
Inlet Guide Vanes. Smaller cylinders
indicate diagnostic checks, Text
indicates time based functions, Solid
double arrows indicate fixed timers,
Dashed double arrows indicate
variable timers
Power Up Diagram:
The Power up chart shows the
respective DynaView screens during
a power up of the main processor.
This process takes from 30 to 50
seconds depending on the number
of installed Options. On all power
ups, the software model always will
transition through the ‘Stopped’
Software state independent of the last
mode. If the last mode before power
down was ‘Auto’, the transition from
‘Stopped’ to ‘Starting’ occurs, but it
is not apparent to the user.
Software Operation Overview
Diagram:
The Software Operation Overview is
a diagram of the five possible
software states. This diagram can be
thought of as a State Chart, with the
arrows, and arrow text, depicting the
transitions between states.
The text in the circles are the internal
software designations for each State.
The first line of text in the Circles are
the visible top level operating modes
that can be displayed on Dyna View.
The shading of each software state
circle corresponds to the shading on
the timelines that show the state that
the chiller is in.
14
CDHF-SVU01C-EN
General
Information
Figure 8. CDHE/F/G sequence of operation: auto to running
This diagram shows the sequence of
operations for a start of the first
compressor on a duplex chiller. The
‘First’ compressor will be determined
by the type of duplex start selected.
Staging Second Compressor On:
This diagram shows the sequence of
operations where the ‘First’
compressor is all ready running, and
the ‘second’ compressor is staged
on. The ‘First’ and ‘Second’
compressor will be determined by
the type of duplex start selected
Figure 9. CDHE, CDHF, and CDHG sequence of operation: running
CDHF-SVU01C-EN
15
General
Information
Staging Second Compressor Off:
This diagram shows the sequence of operations where there is no longer a need to run the ‘Second’ compressor, so it
is staged off. The ‘First’ and ‘Second’ compressor will be determined by the type of duplex start selected
Figure 10. CDHE/F/G sequence of operation: staging second compressor off
Satisfied Setpoint:
This diagram shows the sequence of operations where the setpoint has been satisfied, and the last compressor is
staged off.
Figure 11. CDHE, CDHF and CDHG sequence of operation: normal shutdown to stopped and run inhibit
16
CDHF-SVU01C-EN
General
Information
Duplex Compressor Sequencing
Four methods (Two fixed sequence
methods, a balanced start and hour’s
method, and a no staging method)
are provided for order of a
compressor sequencing on CTV
Duplex chillers. The desired method
is selectable at startup via the service
tool. The application can decide to
either balance the wear burden
among the unit’s compressors, to
start the most efficient compressor,
or to simultaneously start and stop
both compressors to minimize
startup pull down time. Each method
has specific applications were it can
be used advantageously.
If one compressor is locked out, in
restart inhibit, or generally not ready
to start, the available compressor will
be started.
Note: The following description
assumes compressor 1 is the down
stream compressor.
If the chiller is in the Auto mode and
all interlocks have been satisfied,
compressor 1 will be started based
on the leaving water temperature
rising above the “Differential to Start”
setting. Compressors 2 will stage on
when the overall chiller average
capacity exceeds Stage ON Load
point for 30 seconds. The stage on
load point is adjustable (via service
tool) up to 50%. The default is 40%
which means that a single
compressor would have to load to
80% (the average would be 40%)
before the second compressor starts.
Both compressors will run until
chiller average capacity drops below
Stage off Load point for 30 seconds.
The Stage OFF load point is also
Figure 12. CDHF/G sequence of operation: lead 1/lag 2
adjustable (via service tool) (default =
30%, range from 0 to 50%).
Compressor 2 will be shut down and
compressor 1 will run until water
temperature drops below the
differential to stop. Before shutting
down, compressor 2 will be
unloaded and compressor 1 will be
loaded to maintain the same average
capacity command.
When running chilled water
temperature at selected conditions,
the downstream compressor usually
will be the most efficient compressor
to operate at part load because
compressors on Duplex chillers are
not sized exactly the same.
CDHF-SVU01C-EN
17
General
Information
Fixed Sequence – Compressor 2 /
Compressor 1
If the chiller is in the Auto mode and
all interlocks have been satisfied,
compressor 2 will be started based
on the leaving water temperature
rising above the “Differential to Start”
setting. Compressors 1 will stage on
when the overall chiller average
capacity exceeds Stage on Load
point for 30 seconds. The stage on
load point is adjustable up to 50%.
The default is 40% which means that
a single compressor would have to
load to 80% (the average would be
40%) before the second compressor
starts. Both compressors will run
until chiller average capacity drops
below Stage off Load point for 30
seconds. The stage off load point is
also adjustable. Compressor 1 will
be shut down and compressor 2 will
run until water temperature drops
below the differential to stop. Before
shutting down, compressor 1 will be
unloaded and compressor 2 will be
loaded to maintain the same average
capacity command.
Figure 13. CDHE/F/G sequence of operation: lead 2 lag 1
If chilled water reset is used, the
upstream compressor usually will be
the most efficient compressor to
operate at part load. If the leaving
water temperature is reset and the
chiller only needs one compressor,
then the upstream compressor
would be running closer to its
selection point and will be the most
efficient compressor to operate.
18
CDHF-SVU01C-EN
General
Information
Sequencing - Balanced Starts and
Hours
When desired to balance the wear
between the compressors. This
method will extend the time between
maintenance on the lead compressor.
When balanced starts and hours is
selected, the compressor with the
fewest starts will start. If that
compressor is unavailable to start
due to a circuit lockout (including
Figure 14. CDHF/G sequence of operation: equalize starts and hours
restart inhibit) or a circuit diagnostic,
then the other compressor will be
started. The second compressor will
stage on when chiller capacity
exceeds the Stage on Load point for
30 seconds. When chiller capacity
falls below Stage off Load point for
30 seconds, the compressor with the
most hours will be shut off.
CDHF-SVU01C-EN
19
General
Information
Simultaneous Compressor Start/
Stop
Both compressors will start in close
succession to minimize the time it
takes for the chiller to reach full load.
Some process applications need the
chiller to start and generate capacity
as fast as possible. This method will
start both compressors, slightly
staggered to prevent doubling of the
current inrush, but will generally
control the chiller as if there were
only one compressor.
Figure 15. CDHF/G sequence of operation: combined start
If the chiller is in the Auto mode and
all interlocks have been satisfied,
compressor 1 will be started based
on the leaving water temperature
rising above the “Differential to Start”
setting. When compressor 1 is at
speed, compressor 2 will start. Both
compressors will run until water
temperature falls below the
differential to stop, at that time both
compressors will be shut down.
20
CDHF-SVU01C-EN
General
Information
Compressor Load Balancing
Duplex chillers with CH530 control
will balance the compressor load by
giving each compressor the same
load command. The load command
will be converted to IGV position that
will be the same on each
compressor.
Balancing compressor load results in
the best overall efficiency and with
both circuits operating with nearly the
same refrigerant pressures.
When both compressors are running
the overall chiller load command will
be split evenly between the two
compressors unless limit control
overrides balancing. When
transitioning between one
compressor operation and twocompressor operation, the load
commands will be actively balanced
at a rate slow enough to minimize
capacity control disturbances
Restart Inhibit
The purpose of restart inhibit feature
is to provide short cycling protection
for the motor and starter.
The operation of the restart inhibit
function is dependent upon two
setpoints. The Restart Inhibit Free
Starts (1-5, 3 default), and the Restart
Inhibit Start to Start Timer (10-30min,
20 default). These settings are
adjustable via the service tool.
Restart Inhibit Free Starts
This setting will allow a number of
rapid restarts equal to its value. If the
number of free starts is set to “1”, this
will allow only one start within the
time period set by the Start to Start
Time Setting. The next start will be
allowed only after the start to start
timer has expired. If the number of
free starts is programmed to “3”, the
control will allow three starts in rapid
succession, but thereafter, it would
hold off on a compressor start until
the Start to Start timer expired.
Restart Inhibit Start to Start Time
Setting
This setting defines the shortest
chiller cycle period possible after the
free starts have been used. If the
number of free starts is programmed
to “1”, and the Start to Start Time
Setting is programmed to 20
minutes, then the compressor will be
allowed one start every 20 minutes.
The start-to-start time is the time from
when the motor was commanded to
energize to when the next command
to enter prestart is given.
Clear Restart Inhibit
A Clear Restart Inhibit “button” is
provided within Settings; Manual
Override on the DynaView display.
This provides a way for an operator
to allow a compressor start when
there is a currently active Restart
Inhibit that is prohibiting such a start.
The “button” press will have no
other function than to remove the
restart inhibit if there is one active. It
does not change the count of any
internal restart inhibit timers or
accumulators.
The restart inhibit function, setpoints
and clear features exist for each
compressor and operate
independently of other compressors
on that chiller.
During the time the start is inhibited
due to the start-to-start timer, the
DynaView shall display the mode
‘Restart Inhibit’ and the also display
the time remaining in the restart
inhibit.
A “Restart Inhibit Invoked” warning
diagnostic will exist when the
attempted restart of a compressor is
inhibited.
CDHF-SVU01C-EN
21
General
Information
Oil and Refrigerant Pump
Compressor Lubrication System -
A schematic diagram of the
compressor lubrication system is
illustrated in Figure 16. (This can be
applied to circuit 1 or 2.)
Oil is pumped from the oil tank (by a
pump and motor located within the
tank) through an oil pressureregulating valve designed to maintain
a net oil pressure of 18 to 22 psid. It
is then filtered and sent to the oil
cooler located in the economizer and
on to the bearings. From the
bearings, the oil drains back to the
manifold under the motor and then
on to the oil tank.
WARNING
Surface Temperatures!
MAY EXCEED 150°F. Use caution
while working on certain areas of
the unit, failure to do so may result
in death or personal injury.
To ensure proper lubrication and
prevent refrigerant from condensing
in the oil tank, a 750-watt heater is
immersed in the oil tank and is used
to warm the oil while the unit is off.
When the unit starts, the oil heater is
de-energized. This heater energizes
as needed to maintain 140° to 145° F
(60-63°C) when the chiller is not
running.
When the chiller is operating, the
temperature of the oil tank is typically
115° to 160°F (46-72°C). The oil return
lines from the thrust and journal
bearings, transport oil and some seal
leakage refrigerant. The oil return
lines are routed into a manifold
under the motor. Gas flow exits the
top of the manifold and is vented to
the Evaporator.
Note: A vent line solenoid is not
needed with the refrigerant pump. Oil
exits the bottom of the manifold and
returns to the tank. Separation of the
seal leakage gas in the manifold
keeps this gas out of the tank.
A dual eductor system is used to
reclaim oil from the suction cover
and the evaporator, and deposit it
back into the oil tank. These eductors
use high pressure condenser gas to
draw the oil from the suction cover
and evaporator to the eductors and
then discharged into the oil tank. The
evaporator eductor line has a shut off
valve mounted by the evaporator and
ships closed. Open two turns if
necessary.
Liquid refrigerant is used to cool the
oil supply to both the thrust bearing
and journal bearings. On refrigerant
pump units the oil cooler is located
inside the economizer and uses
refrigerant passing from the
condenser to evaporator to cool the
oil. Oil leaves the oil cooler and
flows to both the thrust and journal
bearings.
Motor Cooling System
Compressor motors are cooled with
liquid refrigerant, see Figure 16.
The refrigerant pump is located on
the front of the oil tank (motor inside
the oil tank). The refrigerant pump
inlet is connected to the well at the
bottom of the condenser. The
connection is on the side where a
weir assures a preferential supply of
liquid. Refrigerant is delivered to the
motor via the pump. Motor
refrigerant drain lines are routed to
the condenser.
22
CDHF-SVU01C-EN
General
Information
Figure 16. Oil refrigerant pump - circuit 1 or 2
CDHF-SVU01C-EN
23
General
Information
Base Loading Control
Algorithm:
This feature allows an external
controller to directly modulate the
capacity of the chiller. It is typically
used in applications where virtually
infinite sources of evaporator load
and condenser capacity are available
and it is desirable to control the
loading of the chiller. Two examples
are industrial process applications
and cogeneration plants. Industrialprocess applications might use this
feature to impose a specific load on
the facility’s elecrical system.
Cogeneration plants might use this
feature to balance the system’s
heating, cooling and electrical
generation.
All chiller safeties and adaptive
control functions are in full effect
when Base Loading control is
enabled. If the chiller approaches full
current, the evaporator temperature
drops too low, or the condenser
pressure rises too high, Tracer CH530
Adaptive Control logic limits the
loading of the chiller to prevent the
chiller from shutting down on a
safety limit. These limits may prevent
the chiller from reaching the load
requested by the Base Loading
signal.
Base Loading Control is basically a
variation of the current limit
algorithm. During base loading, the
leaving water control algorithm
provides a load command every 5
seconds. The current limit routine
may limit the loading when the
current is below setpoint. When the
current is within the deadband of the
setpoint the current limit algorithm
holds against this loading command.
If the current exceeds the setpoint,
the current limit algorithm unloads.
The “Capacity Limited By High
Current” message normally
displayed while the current limit
routine is active is suppressed while
base loading.
Base loading can occur via Tracer,
External signal, or front panel.
Tracer Base Loading:
Current Setpoint Range:
(20 - 100) percent RLA
Requires Tracer and Optional Tracer
Communications Module (LLID)
The Tracer commands the chiller to
enter the base load mode by sending
the base load mode request. If the
chiller is not running, it will start
regardless of the differential to start
(either chilled water or hot water). If
the chiller is already running, it will
continue to run regardless of the
differential to stop (either chilled
water or hot water), using the base
load control algorithm. While the unit
is running in base loading, it will
report that status back to the Tracer
by setting “Base Load Status = true”
in the Tracer Status Byte. When the
Tracer removes the base load mode
request (sets the bit to 0). The unit
will continue to run, using the
normal chilled or hot water control
algorithm, and will turn off, only
when the differential to stop has been
satisfied.
External Base Loading:
Current Setpoint Range:
(20 - 100) percent RLA
The UCP accepts 2 inputs to work
with external base loading. The
binary input is at 1A18 Terminals J2-1
and J2-2 (Ground) which acts as a
switch closure input to enter the
base-loading mode. The second
input, an analog input, is at 1A17
terminals J2 – 1 and 3 (Ground)
which sets the external base loading
setpoint, and can be controlled by
either a 2-10Vdc or 4-20ma Signal. At
startup the input type is configured.
The graphs in Figure 13 show the
relationship between input and
percent RLA. While in base loading
the active current limit setpoint is set
to the Tracer or external base load
setpoint, providing that the base load
setpoint is not equal to 0 (or out of
range). If it is out of range, the front
panel current limit setpoint is used.
During base loading, all limits are
enforced with the exception of
current limit. The human interface
displays the message “Unit is
Running Base Loaded”. Hot Gas
Bypass is not run during base
loading. If base loading and ice
making are commanded
simultaneously, ice making takes
precedence.
An alternative and less radical
approach to Base Loading indirectly
controls chiller capacity. Artifically
load the chiller by setting the chilled
water setpoint lower than it is
capable of achieving. Then, modify
the chiller’s load by adjusting the
current limit setpoint. This method
provides greater safety and control
stability in the operation of the chiller
because it has the advantage of
leaving the chilled water temperature
control logic in effect. The chilled
water temperature control logic
responds quicker to dramatic system
changes, and can limit the chiller
loading prior to reaching an Adaptive
Control limit point.
24
CDHF-SVU01C-EN
General
Information
Figure 17. Base loading with external mA input and with external voltage input
CDHF-SVU01C-EN
25
General
Information
Ice Machine Control
UCP provides a service level “Enable
or Disable” menu entry for the Ice
Building feature when the Ice
Building option is installed. Ice
Building can be entered from “Front
Panel”, or if hardware is specified the
UCP will accept either an isolated
contact closure (1A19 Terminals J2-1
and J2-2 (Ground) ) or a remote
communicated input (Tracer) to
initiate the ice building mode where
the unit runs fully loaded at all times.
Ice building will be terminated either
by opening the contact or based on
entering evaporator fluid
temperature. UCP will not permit the
Ice Building mode to be entered
again until the unit is switched to the
Non-ice building mode and back into
the ice building mode. It is not
acceptable to reset the chilled water
setpoint low to achieve a fully loaded
compressor. When entering icebuilding the compressor will be
loaded at its maximum rate and
when leaving ice building the
compressor will be unloaded at its
maximum rate. While loading and
unloading the compressor, all surge
detection will be ignored. While in
the ice building mode, current limit
setpoints less than the maximum will
be ignored. Ice Building can be
terminated by one of the following
means:
1. Front panel disable.
2. Opening the external Ice. Contacts/
Remote communicated input
(Tracer).
3. Satisfying an evaporator entering
fluid temperature setpoint. (Default
is 27°F)
4. Surging for 7 minutes at full open
IGV.
Figure 18. Sequence of operation: ice making: running to ice making
Figure 19. Sequence of operation: ice making: stopped to ice to ice building
complete
26
CDHF-SVU01C-EN
General
Information
Hot Water control
Occasionally CTV chillers are
selected to provide heating as a
primary mission. With hot water
temperature control, the chiller can
be used as a heating source or
cooling source. This feature provides
greater application flexibility. In this
case the operator selects a hot water
temperature and the chiller capacity
is modulated to maintain the hot
water setpoint. Heating is the primary
mission and cooling is a waste
product or is a secondary mission.
This type of operation requires an
endless source of evaporator load
(heat), such as well or lake water. The
chiller has only one condenser.
Note: Hot water temperature control
mode does not convert the chiller to
a heat pump. Heat pump refers to the
capability to change from a coolingdriven application to a heating-driven
application by changing the
refrigerant path on the chiller. This is
impractical for centrifugal chillers as
it would be much easier to switch
over the water side.
This is NOT heat recovery. Although
this feature could be used to recover
heat in some form, there’s not a
second heat exchanger on the
condenser side.
The DynaView
provides the hot water temperature
control mode as standard. The
leaving condenser water temperature
is controlled to a hot water setpoint
between 80 and 140°F (26.7 to 60°C)
The leaving evaporator water
temperature is left to drift to satisfy
the heating load of the condenser. In
this application the evaporator is
normally piped into a lake, well, or
other source of constant temperature
water for the purpose of extracting
heat.
In hot water temperature control
mode all the limit modes and
diagnostics operate as in normal
cooling with one exception; The
leaving condenser water temperature
sensor is an MMR diagnostic when
in hot water temperature control
mode. (It is an informational warning
in the normal cooling mode.)
In the hot water temperature control
mode the differential-to-start and
differential-to-stop setpoints are used
with respect to the hot water setpoint
instead of with the chilled water
setpoint.
UCP provides a separate entry at the
DV to set the hot water setpoint.
Tracer is also able to set the hot
water setpoint. In the hot water mode
™
Main Processor
the external chilled water setpoint is
the external hot water setpoint; that
is, a single analog input is shared at
the 1A16 –J2-1 to J2-3 (ground)
An external binary input to select
external hot water control mode is on
the EXOP OPTIONAL module 1A18
terminals J2-3 to J2-4 (ground). Tracer
also has a binary input to select
chilled water control or hot water
temperature control.
There is no additional leaving hot
water temperature cutout; the HPC
and condenser limit provide for high
temperature and pressure protection.
In hot water temperature control the
softloading pulldown rate limit
operates as a softloading pullup rate
limit. The setpoint for setting the
temperature rate limit is the same
setpoint for normal cooling as it is
for hot water temperature control.
The hot water temperature control
feature is not designed to run with
HGBP, AFD, or ice making.
The factory set PID tuning values for
the leaving water temperature control
are the same settings for both normal
cooling and hot water temperature
control.
CDHF-SVU01C-EN
27
Unit Control
Panel (UCP)
Control Panel Devices and Unit
Mounted Devices
Unit Control Panel (UCP)
Safety and operating controls are
housed in the unit control panel, the
starter panel and the purge control
panel. The UCP ‘s operator interface
and main processor is called the
DynaView
the UCP door. (See Operators
interface section for detailed
information)
Figure 20. Left control panel
™
(DV) and is located on
The UCP houses several other
controls modules called panel
mounted LLID (Low Level Intelligent
Device), power supply, terminal
block, fuse, circuit breakers, and
transformer. The IPC (Interprocessor
communication) bus provides
communication between LLID’s and
the main processor. Unit mounted
devices are called frame mounted
LLID’s and can be temperature
sensors or pressure transducers,
vane actuator. These and other
functional switches provide analog
and binary inputs to the control
system.
28
CDHF-SVU01C-EN
Unit Control
Panel (UCP)
Tracer CH530 Chiller Controller
Revolutionary control of the chiller,
chilled water system, and your entire
building with unprecedented
accuracy, reliability, efficiency, and
support for maintenance using the
chiller’s PC-based service tool.
Chiller reliability is all about
producing chilled water and keeping
it flowing, even when facing
conditions that ordinarily would shut
down the chiller — conditions that
often happen when you need cooling
the most.
Tracer CH530’s Main Processor,
DynaView
chiller online whenever possible.
Smart sensors collect three rounds of
data per second, 55 times the data
collection speed of its predecessor.
Each device (a sensor) has its own
microprocessor that simultaneously
converts and accurately calibrates its
own readings from analog to digital.
Because all devices are
communicating digitally with the
DynaView
no need for the main processor to
convert each analog signal one at a
time. This distributed logic allows
the main processor to focus on
responding to changing conditions
— in the load, the machine, its
ancillary equipment, or its power
supply. Tracer CH530 constantly
receives information about key data
parameters, temperatures and
™
, is fast and keeps the
™
main processor, there is
current. Every five seconds then a
multiple objective algorithm
compares each parameter to its
programmed limit. The chiller’s
Adaptive Control
™
capabilities
maintain overall system performance
by keeping its peak efficiency.
Whenever the controller senses a
situation that might trigger a
protective shutdown, it focuses on
bringing the critical parameter back
into control. When the parameter is
no longer critical, the controller
switches its objective back to
controlling the chilled water
temperature, or to another more
critical parameter should it exist.
Variable water flow through the
evaporator
Chilled-water systems that vary water
flow through chiller evaporators have
caught the attention of engineers,
contractors, building owners, and
operators. Varying the water flow
reduces the energy consumed by
pumps, while requiring no extra
energy for the chiller. This strategy
can be a significant source of energy
savings, depending on the
application. With its faster and more
intelligent response to changing
conditions, Tracer CH530 water flow
sensing option accommodates
variable evaporator water flow and its
effect on the chilled water
temperature. These improvements
keep chilled water flowing at a
temperature closer to its setpoint.
User-defined language support
DynaView
™
is capable of displaying
English text or one of the two
alternate languages that are stored in
DynaView
™
at one time. Switching
languages is simply accomplished
from a settings menu.
Similarly, TechView
™
accommodates
a primary and a secondary language
from the same list of available
languages.
CDHF-SVU01C-EN
29
Operator
Interface
Figure 21. DynaView™ main processor
DynaView
tabs across the top which are
labeled “MAIN, REPORTS, and
SETTINGS”.
The Main screen provides an overall
high level chiller status so the
operator can quickly understand the
mode of operation of the chiller.
The Chiller Operating Mode will
present a top level indication of the
chiller mode (Auto, Running, Inhibit,
Run Inhibit, etc.) The “additional
information” icon (arrow) will
present a subscreen that lists in
further detail the subsystem modes.
(See Machine Operating Modes.)
Main screen content can be viewed
by selecting the up or down arrow
icons. The Main screen is the default
screen and after an idle time of 30
minutes.
™
presents three menu
The DynaView™ (DV) Operator
Interface contains the “Main
Processor (MP)” and is mounted on
the unit control panel front door
where it communicates commands
to other modules, collecting data,
status and diagnostic information
from the other modules over the IPC
(Inter Processor Communications)
link. The Main Processor (MP)
software controls water flows by
starting pumps and sensing flow
inputs, establishes a need to heat or
cool, performs pre-lube, performing
post-lube, starts the compressor(s),
performs water temperature control,
establishes limits, and pre-positions
the inlet guide-vanes.
30
The MP contains non-volatile
memory both checking for valid set
points and retaining them on any
power loss. System data from
modules (LLID) can be viewed at the
DynaView
as evaporator and condenser water
temperatures, outdoor air
temperature, evaporator and
condenser water pump control,
status and alarm relays, external
auto-stop, emergency stop,
evaporator and condenser water
pressure drops and evaporator and
condenser water flow switches.
™
operator interface. Such
CDHF-SVU01C-EN
Loading...
+ 86 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.