Alpha SY9-24 Instruction

Installation and Servicing
Instructions
Alpha SY9-24
Wall Mounted, Fan Assisted, Room Sealed, Gas Fired
System Boiler
For Technical help or for Service call ...
ALPHA HELPLINE
Tel: 0870 3001 964
Nepicar House, London Road,
Wrotham Heath, Sevenoaks,
Kent TN15 7RS
Service Listed
Alpha SY9-24 G.C. No. 41 532 01
For use with Natural Gas only
CONTENTS
1 Introduction ....................................... 2
2 Technical data...................................3
3 General boiler information..................6
4 Installation......................................... 10
5 Commissioning ................................. 15
6 Boiler operation ................................. 17
7 Routine servicing...............................18
8 Component replacement ................... 19
9 Wiring diagrams ................................ 25
10 Fault finding ...................................... 27
11 Short parts list ................................... 30
12 Service history .................................. 31
1 INTRODUCTION
The Alpha SY9-24 boiler is a wall mounted, fan assisted room-sealed system boiler. The burner is lit electronically and the heat output is controlled by a modulating gas valve.
The boiler, provides central heating, and is designed for use with a fully pumped, sealed and pressurised heating system using only Natural Gas.
The boiler is supplied with a pump, pressure relief valve, expansion vessel and pressure gauge fully assembled and tested. As supplied, the Alpha SY9-24 boiler will automatically modulate to provide central heating outputs between 9.3 and 23.3 kW
(31 700 and 79 500 Btu/h).
IMPORTANT
It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with the following recommendations:-
Current Gas Safety (Installation and Use) Regulations All current Building Regulations issued by the Department of the Environment i.e. Approved Document L1 Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department Health & Safety Document No. 635 (The Electricity At Work Regulations 1989) The installation should also be in accordance with the following British Standard Codes of Practice:­BS 5440:1:2000 Flues
BS 5449:1990 Forced circulation hot water systems BS 6798:2000 Installation of gas fired hot water boilers BS 6891:1989 Gas installation BS 7593:1992 Code of Practice for treatment of water in heating systems BS 7671:2001 Requirements for electrical installations, IEE Wiring Regulations
If installation is in a timber framed building, refer to the Institute of Gas Engineers document IGE/UP/7. This appliance meets the requirements of IPX4D, ie degree of protection against moisture. Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the
law is complied with. Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations.
Note: Ensure that the Benchmark Log Book has been completed after the boiler has been installed and commissioned.
Alpha SY9-24 - Contents/Introduction
2
2 TECHNICAL DATA
2.1 PERFORMANCE - NATURAL GAS
Central Heating
Heat Input kW (Gross) Btu/h Heat Output (modulating) kW
Btu/h
Burner Pressure mbar Settings in wg
Gas Rate m³/h
Room sealed chamber panel fitted
ft³/h
2.2 SYSTEM
Central Heating (Sealed System)
Max. Working System Pressure Min. System Pressure Max. System temperature Pressure Relief Valve Setting Expansion Vessel Size (pre-charge press.) Flow Connection Return Connection Relief Valve Connection Recommended System Pressure (cold) CH Water Temp. (Approx. max.)
MAX.
28.4
96 900
23.3
79 500
10.7
4.28
2.71
95.70
3 bar (44 PSI)
82°C (180°F)
41 300
31 700
40.96
2.5 bar
0.5 bar 82°C
8 L at 0.8 bar
22 mm 22 mm 15 mm
1.0 bar
MIN.
12.1
9.3
2.2
0.9
1.16
2.3 COMPONENTS
Burner Main Heat exchanger Main Burner Injectors Flue - Outer Duct Flue - Inner Duct
2.4 INSTALLATION
Min. Clearances for Servicing Top (from casing) Bottom
Sides
Front Flue Terminal Size Flue Terminal Protruding Hole Size Required For Flue Assy. Lift Weight
Stainless steel
Copper
1.30 mm (x12) White
Aluminium
220 mm 250 mm
5 mm
450 mm
100 mm Dia.
145 mm
110 mm Dia.
38 kg
Alpha SY9-24 - Technical Data
3
2.5 GENERAL 2.6 ELECTRICAL
Case Dimensions Height (without bottom tray) Width
Depth Gas Connection Primary Water Content Air Duct Diameter Flue Duct Diameter
720 mm 450 mm 330 mm
22 mm
1.6 L
100 mm
60 mm
Supply External Fuse Power Consumption Internal Fuse Electrode Spark Gap
230/240 V ~ 50 Hz
2.7 FLUE LENGTHS
Flue length = 0.75 m (not including the terminal, which is supplied with the boiler) Note: Additional flues (of the same length) are available. Length of Flue Required:-
Rear Flue = wall thickness + 175 mm Side Flue = wall thickness + distance between wall and side of boiler + 185 mm
Vertical Flue = distance from top of boiler side panel to required roof position minus 1 m for vertical terminal assembly Maximum flue length = 4 m Each additional 90° Bend is equivalent to 1 m of flue length
Each 45° Bend is equivalent to 0.5 m of flue length The Vertical Flue terminal assembly is equivalent to 1 m of flue length
3 A
170 W
F2 A
2 to 4 mm
2.8 AVAILABLE PUMP HEAD FOR CENTRAL HEATING
Output Available pump head
kW
23.3
17.58
14.65
11.63
9.3
This information is based on 17°C and 20°C system design temperature difference.
Btu/h
79 500 60 000 50 000 40 000 31 700
17°C 20°C
metres
2.4
3.8
4.5
5.1
5.45
feet
7.9
12.5
14.8
16.7
17.9
metres
3.2
4.4
4.8
5.35
5.65
feet
10.5
14.4
15.8
17.5
18.5
litre/min
19.6
14.8
12.3
9.8
7.8
Flow rate
17°C 20°C 17°C 20°C
4.3
3.3
2.7
2.2
1.7
litre/min
16.7
12.6
10.5
8.3
6.7
gal/min
2.9 ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
gal/min
3.7
2.8
2.3
1.8
1.5
Pressure loss across boiler
metres
metres
2.5
1.9
1.25
0.8
0.5
feet
8.2
6.2
4.1
2.6
1.6
2.3
1.3
0.95
0.65
0.4
feet
7.5
4.3
3.1
2.1
1.3
Alpha SY9-24 - Technical Data
4
Fig. 1 - Boiler terminal block
2.10 BOILER SCHEMATIC
1 - Gas valve 2 - Primary temperature sensor 3 - Main burner 4 - Main heat exchanger 5 - Room sealed chamber 6 - Fan 7 - Air pressure switch 8 - Flue hood 9 - Overheat thermostat 10 - Expansion vessel 11 - Automatic air vent
Fig. 2
12 - Pump 13 - Drain point 14 - Pressure relief valve 15 - Ignition electrodes 16 - Flame sensing electrode 17 - Flue sampling point 18 - Gas service cock 19 - Primary pressure switch 20 - On/off valve (2 off) 21 - Automatic by-pass
Alpha SY9-24 - Technical Data
5
3 GENERAL BOILER INFORMATION
3.1 GAS SUPPLY
The Alpha SY24 boiler requires a gas rate of 2.71 m³/h (95.7 ft³/h). The meter and supply pipes must be capable of delivering this quantity of gas in addition to the demand from any other
appliances in the house. The boiler requires at least a 22 mm gas supply pipe. The complete installation, including the meter, must be tested for gas soundness and purged as described in BS 6891.
3.2 ELECTRICAL SUPPLY
The boiler requires a 230/240 V ~ 50 Hz mains supply, fused at 3 A
The boiler must be earthed.
There must only be one common isolator, providing complete electrical isolation, for the boiler and any external controls. This boiler has been fitted with a supply cable, however, if it is necessary to fit a cable use PVC insulated cable not less than
0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16. The boiler should be connected to a fused three pin plug and unswitched shuttered socket outlet (both complying with BS 1363), or a fused double pole switch with a contact separation of at least 3 mm in both poles.
Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 7671). Note: If a room thermostat is fitted, it must be suitable for 230/240 V switching.
3.3 AIR SUPPLY
The boiler does not require any air vents for cooling in the room in which it is installed or when installed in a cupboard or compartment. The minimum clearances for servicing must always be maintained.
Note: A cupboard or compartment used to enclose the boiler must be designed and constructed specifically for the purpose, i.e. comply with the Building Regulations.
3.4 FLUE SYSTEM - Fig. 3
The flue system must be installed in accordance with BS 5440:1. For horizontal flues ensure there is a slight downward slope towards the terminal. Flue components are available as follows:­Top easy-flue 500 mm (includes 90° bend), refer to separate instructions
0.75 m flue 90° bend 45° bend Vertical flue terminal assembly. Refer to the separate installation instructions supplied with the assembly. A Twin Pipe Flue system is available for use with all the boilers in the range. Refer to the separate instructions for details.
The following methods determine the correct length of flue required.
For rear exit flue L = B + 175 mm For side exit flue L = B + C + 185 mm (min. side clearance required is 5 mm) For vertical flue L = H minus 1000 mm for vertical terminal assembly Where L = Required flue length
B = Finished wall thickness C = Distance from the inside wall to the side of the boiler H = Distance from top of boiler side panel to roof position
Note: 1. If an extra 90° bend is used, this reduces the maximum flue length by 1 m. Each 45° bend used reduces the maximum
flue length by 500 mm.
2. Under no circumstances must the flue length (including allowances for extra bends) exceed 4 metres.
3. Failure to use Alpha flue components with the boiler will invalidate the boilers CE approval, guarantee and may be unsafe.
Alpha SY9-24 - General Boiler Information
6
HORIZONTAL FLUE OPTIONS - Lmax = 4 metres
L = B + C + 185 mm
C
E
L = B + E + F + 185 mm + (90° bend = 1 metre)
B
B
F
L = B + C + E + 185 mm
C
E
C
B
B
VERTICAL FLUE OPTIONS
L = B + C + 185 mm + (2 x 45° bends = 1 metre)
Fig. 3
Alpha SY9-24 - General Boiler Information
7
3.5 FLUE TERMINAL LOCATION - Fig. 4
Fig. 4
Terminal position
A Directly below an opening, air brick, windows, etc. B Below gutters, soil pipes or drain pipes C Below eaves D Below balconies or car port roof E From a vertical drain pipe or soil pipe F From an internal or external corner G Above ground, roof or balcony level H From a surface facing the terminal I From a terminal facing the terminal J From an opening in the car port (e.g. door, window) into dwelling K Vertically from a terminal on the same wall L Horizontally from a terminal on the same wall M Horizontally from an opening, air brick, window, etc.
Min. distance
300 mm
75 mm 25 mm 25 mm 25 mm
25 mm 300 mm 600 mm
1200 mm 1200 mm 1500 mm
300 mm 300 mm
The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times. In certain weather conditions the terminal may emit a plume of steam. Avoid positioning the terminal where this may cause a nuisance.
If the terminal is fitted within 850 mm of a plastic or painted gutter or 450 mm of painted eaves or 300 mm of a plastic car port roof, an aluminium shield at least 1 m long should be fitted to the underside of the gutter or painted surface. If the terminal is fitted less than 2 m above a surface to which people have access, the terminal must be protected by a terminal guard. A suitable guard is available from: Tower Flue Components Ltd., Vale Rise, Tonbridge, Kent TN9 1TB
3.6 BOILER LOCATION
The boiler is not suitable for external installation. The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler. The boiler can be fitted
to or adjacent to a wall comprising of a combustible material without the need for a special thermal insulation barrier. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with the British Gas publication 'Guide for
Gas Installations in Timber Frame Housing', reference DM2. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the
current IEE Wiring (BS7671) Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. Where a room­sealed boiler is installed in a room containing a bath or shower, it must not be possible for a person using the bath or shower to touch any electrical switch or boiler control utilising mains electricity.
The boiler may be installed in a cupboard or compartment, provided it is correctly designed for that purpose, i.e. complies with the Building Regulations and the requirements of BS 6798.
Alpha SY9-24 - General Boiler Information
8
3.7 CENTRAL HEATING SYSTEM - Fig. 5
The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS 5449 and BS 6798. The system should be designed to operate with flow temperatures of up to 82°C. When designing the system, the pump head, expansion
vessel size, mean radiator temperature, etc must all be taken into account. Refer to the pump performance table for guidelines. System volume - The expansion vessel incorporated into the boiler is suitable for a sealed heating system with a maximum
water content of 80 litres (18 gal). For guidance on water contents contact Alpha Therm Ltd. for Technical Data Sheet 15. Above 80 litres, consideration should be given to fitting an additional expansion vessel fitted in the position shown in Fig. 5. To check correct operation of the expansion vessel(s) the system pressure should not be more than 2.5 bar when the system is at maximum operating temperature (for further guidance refer to BS 7074:1).
The boiler is supplied with the following components built in:­Pressure relief valve - complying with BS 6759 and set to operate at 3 bar. The discharge pipe must be routed clear of the boiler, in such a manner that it can be seen, but cannot cause injury to persons or property.
Pressure gauge - To indicate the system pressure to be maintained. Expansion vessel - Conforming to BS 4814 with a capacity of 8 litres and pre-charged to a pressure of 0.8 bar. By-pass - The boiler incorporates a by-pass. However, where all radiators are fitted with thermostatic radiator valves it is
recommended a system by-pass, preferably automatic, is fitted.
Make up vessel
Static head of system
Boiler casing
Automatic air vent
Additional expansion vessel (if required)
Double check valve assy.
Heating by-pass
(If required)
Note: If required, an automatic by-pass is preferred.
Heating flow
Heating return
Filling point
System
Note: A drain tap should be installed at the lowest
drain tap
point of the heating circuit and beneath the appliance.
Fig. 5
3.8 FILLING THE CENTRAL HEATING SYSTEM - Figs. 6, 7
The system design pressure (cold) should be set to 1.0 bar. This pressure is equivalent to a static head (see Fig. 5) of 10.2 metres of water. Provision should be made to replace water lost from the system. This can be by manual or automatic means, as shown in Figs.
6 and 7. The position for connecting an automatic make-up vessel is indicated in Fig. 5. A double check valve assembly must be used, as shown in Fig. 7.
Filling of the system must be carried out in a manner approved by the local Water Undertaking. Where allowed, the system may be filled via a temporary connection as shown in Fig. 6. After filling, always disconnect the flexible hose of the filling loop.
All fittings used in the system must be able to withstand pressures up to 3 bar. Drain taps (to BS 2879) must be used to allow the system to be completely drained. The heating system should be thoroughly flushed before the boiler is connected and again after the first heating. If it is required to add inhibitor to the system, refer to Alpha Therm Ltd. for guidance. Refer to BS 5449 and BS 6798 for further information.
Hose
Heating circuit
return
Stop valve
temporarily connected
unions
Filling loop
Double check
valve assembly
Test cock
Stop valve
Mains water supply
Heating circuit
return
Double check
valve assembly
Test cock
Overflow
Stop valve
Mains water supply
Feed cistern to be located above highest point in the system
Fig. 6 Fig. 7
Alpha SY9-24 - General Boiler Information
9
4 INSTALLATION
4.1 UNPACKING
1. The boxes required when the boiler is installed with a horizontal flue are as follows:­Box 1 Cased boiler fitted with water and gas valves, union bends and washers
Mounting bracket plus screws and wall plugs Flue terminal and flue sealing collar plus 2 screws
Literature pack and Wall template Box 2 90° flue bend (not required for vertical flue) Box 3 0.75 m flue (for side and rear flue) with two clamps and inner duct support Note: If an Easy flue 500 mm is ordered, this will be supplied instead of boxes 2 and 3.
2. Unpack boiler and remove the loose items packs, i.e. mounting bracket, flue terminal and collar. Note: The boiler can be stood in an upright position supported by the bottom tray, (to allow this, the union bends have
been turned upwards so that they do not protrude beneath the bottom tray - check this before standing the boiler on the bottom tray).
4.2 CLEARANCES REQUIRED - Fig. 8
Fig. 8
4.3 PREPARE THE WALL - Figs. 9, 10
1. Decide upon the position of the boiler taking into account the clearances required for servicing and the flue terminal position.
2. Tape the template to the wall (ensure it is level and the right way up) and mark the position of the holes for the boiler mounting bracket and bottom fixings. If rear exit flue is used, mark the position of the hole for the flue.
3. Side exit flue - Continue the horizontal centre line of the flue across the wall to the side wall, then along the side wall 215 mm (ensure the lines are horizontal). This will give the position of the centre of the hole for the flue.
4. Cut the 110 mm diameter hole (or use a 107 mm core drill) in the wall for the flue. Note: For internal fitting of the flue, using the flue sealing collar supplied, cut a 127 mm dia. flue hole using a 127 mm core drill.
5. Drill the fixing holes (10 mm dia.) to accept the No.10 plugs supplied. Using the screws supplied, fit the mounting bracket.
6. Top pipe connections - Preform the pipework at the back of the boiler before hanging the boiler, see Fig. 10, and secure in the clips provided.
Fig. 9
Alpha SY9-24 - Installation
10
Loading...
+ 22 hidden pages