Alpha SolarSmart 90 Instruction

Installation and Servicing
Instructions
Alpha SolarSmart 90
Pre-Heat Drain Back Solar System and Wall Mounted
Unvented Hot Water Solar Cylinder
for use with an Alpha Combination Boiler
For Technical help or for Service call ...
ALPHA HELPLINE
Tel: 0870 3001964
Nepicar House, London Road,
Wrotham Heath, Sevenoaks,
Kent TN15 7RS
Building Regulations Approved
THE NATIONAL FEDERATION OF
SOLAR Key Mark Certificated
Leave these instructions with the User
ROOFING CONTRACTORS LIMITED
CONTENTS
1 Introduction ....................................... 2
2 Technical data................................... 3
3 General information...........................6
4 Installation......................................... 12
5 Commissioning ................................. 18
6 System operation .............................. 20
7 Routine inspection.............................22
8 Component replacement ................... 22
9 Wiring diagram.................................. 24
10 Diagnostics and fault codes ............... 25
11 Checklist for unvented storage........... 26
12 Parts list ............................................ 27
13 Inspection history .............................. 28
1 INTRODUCTION
The Alpha SolarSmart 90 system is a pre-heat drain back solar collector system which includes a wall mounted 90 litre unvented cylinder to store water heated by the solar collector. The system must be used in conjunction with an Alpha combination boiler fitted with the Alpha Solar valve which is supplied with the system.
The SolarSmart 90 system consists of a 90 litre cylinder, a 2.5 m² flat plate drain back solar collector, drain back unit, unvented kit and solar valve. The 90 litre unvented cylinder is fitted with a pump, control box and temperature sensors. The drain back unit is fitted with a heat exchanger and pump.
The unvented kit must be fitted in the mains water supply to the cylinder. The kit includes a pressure reducing valve, expansion vessel, expansion relief valve, check valve and a tundish. The solar valve must be fitted directly to the mains water inlet of the Alpha combination boiler.
Note: In the northern hemisphere solar collectors should ideally face South. For more information see Section 3.6.
IMPORTANT
This System has been approved to the Building Regulations for unvented hot water storage systems and the Local Authority must be notified of the intention to install. Therefore the installation must be carried out by a person competent to install unvented hot water systems.
The installation must be carried out in accordance with the following recommendations:­All current Building Regulations issued by the Department of the Environment, i.e. Approved Document L1 Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department UK Water Regulations/Byelaws (Scotland) Health & Safety Document No. 635 (The Electricity At Work Regulations 1989) The installation should also be in accordance with the following British Standard Codes of Practice:-
BS 5449:1990 Forced circulation hot water systems BS 5546:2000 Installation of hot water supplies for domestic purposes BS 5918:1989 Solar heating systems for domestic hot water BS 6700:1997 Design, installation, testing and maintenance of services supplying water
Failure to install this appliance correctly could lead to prosecution and will invalidate the guarantee. It is in your own interest and that of safety to ensure that the law is complied with.
Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations. This appliance meets the requirements of IPX4D, i.e. degree of protection against moisture. Reference should be made to Criteria for gas fired combination boilers used as after heaters in solar thermal systems
and BRE Solar heating UK:1981. Note: 1) The Alpha SolarSmart system was a ClearSkies recognised product and is now a product recognised in the UK
Microgeneration Product Certification Scheme.Therefore the system is eligible for renewable energy grants.
2) The SolarSmart collector has been tested to DIN EN12975 and CEN Keymark certificated for Solar Thermal Products.
Alpha SolarSmart 90 - Contents/Introduction
2
2 TECHNICAL DA T A
2.1 DHW SYSTEM
Solar Cylinder
Max. Hot Water Working Pressure Max. Mains Inlet Pressure Min. Mains Water Pressure Mains Inlet Connection DHW Outlet Connection DHW Cylinder Capacity Expansion Vessel Size (pre-charge press.) Pressure Reducing Valve Setting Temperature and Pressure Relief Valve Expansion Relief Valve Setting Flow Rate L/min
Max. Outlet Water Temp. (Approx.) °C
Reference to WRC-NSF Test Procedure 1.50.220 using a 30 kW boiler. Time to reheat water store by 55°C - 25 minutes. Reheat time for 70% of store - 18 minutes
(inlet of pressure reducing valve)
gal/min
°F
5.5 bar 12 bar
0.1 bar
15 mm 15 mm
8 L at 2.5 bar
2.5 bar
90°C/7 bar
Max.18.0 Max. 4.0 Max. 70 Max. 158
91 L
6 bar
Min. 1.0 Min. 0.22 Min. 5 Min. 41
Drain Back Unit (DBU) DHW Circuit:
Flow Connection Return Connection Max. Working Pressure Heat Exchanger Coil Content
Collector Circuit:
Flow Connection Return Connection Max. Working Pressure Vessel Size Max. Filled Content Heat Transfer Capacity
2.2 SOLAR COLLECTOR SYSTEM
Type: Dimensions
Total Surface Area m² Aperture Area m² Length x Width x Thickness mm Water Content L Lift Weight kg Profile of collector when fitted using an Alpha flashing kit protrudes approximately 30 mm to 60 mm above the tiles (depends upon type of tile used)
Hydraulics
Maximum Pressure bar
Absorber
Aluminium Cover and Copper Pipe (Length x Width x Depth) mm
Spectral Selective Layer
Absorption Coefficient % Emission f %
Glass
Transparent, Hardened - Thickness mm
Collector Housing
Material
Insulation
Thickness mm Thermal conduction coefficient W/mk
Cover Frame
Material
Temperature Sensor
Type - NTC Ohm
Connections
Pre-mounted Flexible Hoses Return to DBU mm
Flow from DBU mm
Minimum Roof Slope Energy Performance (System with 90L tank)GJ/yr Zero Loss Collector Efficiency (No) Collector Heat Loss Coefficient (a1) W/m²k Aperture to Gross Collector Area Ratio
Portrait
2230 x 1120 x 92
1.16
2140 x 1030 x 0.5
Aluminium Pressing
0.037
Aluminium Black Powder Coated
12 mm 15 mm
20°
3.629
Landscape
2.5
2.26 1120 x 2230 x 92
40
8
1030 x 2140 x 0.5
94
5
4
50
10 k
3.5
74%
0.9
1.10
30°
15 mm 15 mm
8 bar
0.32 L
15 mm 12 mm
6 bar
3.6 L
2.8 L
110 W/kg
Alpha SolarSmart 90 - Technical Data
3
2.3 INSTALLATION
Solar Cylinder Min. Clearances for Servicing Top
Bottom Sides Front
DBU Min. Clearances for Servicing Top
Bottom Side
Front Lift Weight - Cylinder Assembly Lift Weight DBU Weight Full and Operational - Cylinder Assemby Weight Full and Operational - DBU
Supply External Fuse Power Consumption Max.
Min.
230/240 V ~ 50 Hz
3 A
165 W
5 W
100 mm 300 mm
10 mm 450 mm 100 mm 100 mm
10 mm 450 mm
22 kg
6 kg
113 kg
8.8 kg
2.5 GENERAL2.4 ELECTRICAL
Solar Cylinder Dimensions Height
Width Depth
DBU Dimensions Height
Width
Depth Solar Cylinder - Material DBU Heat Exchanger - Material Covers/Insulation Material Solar Cylinder Insulation Thickness Standing Energy Loss of Solar Cylinder
1110 mm
540 mm 530 mm 460 mm 365 mm 270 mm
Stainless Steel
Copper
EPP Foam
50 mm
0.92 kWh/24hr
0.43 watts/litre
2.6 LOCATION
Max. Height Between Top of Solar Collector and Bottom of DBU (see Note below) Max. Distance Between DBU and Bottom of Solar Cylinder Max. Distance Between Top of Solar Collector and Bottom of Solar Cylinder
Note: Whenever possible, always fit the DBU to the flexible hoses from the solar collector. If this is not possible, do not use more than 2 m of 15 mm pipe for each of the flow and return between the DBU and collector.
3 m 6 m 6 m
2.7 ELECTRICAL CONNECTIONS
Notes: This Appliance Must Be Earthed.
Do Not Connect Any Other Controls.
Alpha SolarSmart 90 - Technical Data
4
Fig. 1
2.8 SOLAR SYSTEM SCHEMATIC
1
24
10
15
21
5
6
14
9
2
8
4
14
3
12
13
11
16
Cold water
7
inlet
1 Solar collector 2 Drain back unit (DBU) 3 DBU pump 4 DBU heat exchanger 5 Collector temperature sensor 6 Solar cylinder 7 Solar cylinder pump 8 Filter 9 Diffuser 10 DHW outlet pipe 11 Solar valve 12 Flow to boiler
25
13 Flow to tap 14 Temperature sensors 15 Insulation/casing 16 Bottom tray 17 Unvented kit 18 Tundish 19 Non-return valve 20 Expansion relief valve 21 Temperature and pressure relief valve 22 Expansion vessel 23 Pressure reducing valve with filter 24 Drain point for cylinder 25 Overheat thermostat
Fig. 2
Alpha SolarSmart 90 - Technical Data
5
3 GENERAL INFORMATION
3.1 ELECTRICAL SUPPLY
The Solar system requires a 230/240 V ~ 50 Hz mains supply, fused at 3 A - The system must be earthed. There must only be one common isolator, providing complete electrical isolation, for the Solar system. This system has been fitted with a supply cable, however, if it is necessary to fit a cable use PVC insulated cable not less
than 0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16. The system should be connected to a fused three pin plug and unswitched shuttered socket outlet (both complying with BS 1363), or a fused double pole switch with a contact separation of at least 3 mm in both poles.
Note: There is no electrical connections between the boiler and the Solar system. Therefore, it is recommended that the
Solar system electrical isolation is completely separate to the boiler and any external controls isolation.
All wiring must be in accordance with the current IEE Wiring Regulations (BS 7671).
3.2 DOMESTIC HOT WATER SYSTEM
The mains water supply must be first connected to the components detailed in Section 3.3 before the Solar cylinder. No valves must be fitted between these components and the cylinder. The incoming mains water pressure to the cylinder is regulated to 2.5 bar by the pressure reducing valve supplied in the unvented package. However, all taps and mixing valves used with the hot water system must be suitable for operating at a pressure of up to 8 bar.
The Solar valve, supplied in the unvented package, must always be fitted directly to the cold water inlet of an Alpha combination boiler.
Note: The hot water control thermostat on the combination boiler must always be turned to maximum. To ensure economic use, the pipe runs to the Alpha combination boiler and taps should be in 15 mm copper pipe and be
as short as possible. Where possible the pipework should be insulated to reduce heat loss. Before the mains water supply pipe is connected to the boiler, it should be thoroughly flushed out to avoid the danger of
dirt or foreign matter entering the boiler and the filter incorporated within the pressure reducing valve cleaned. The stored water temperature is controlled to a maximum of 70°C. To prevent high temperatures at the hot water taps, it is recommended that a thermostatically controlled mixing valve is fitted
after the boiler.
3.3 UNVENTED HOT WATER STORAGE SYSTEM
To comply with the Building Regulations for unvented hot water storage, it is required that the unvented kit components detailed in Fig. 3 are fitted before the mains cold water inlet to the Solar cylinder. No isolating valves must be fitted between these components and the cylinder.
All these components are supplied with the Solar system in a separate package and must be fitted by a competant person in accordance with the instructions.
The installation is subject to Building Regulations approval and the Local Authority must be notified of the intention to install. Discharge pipe - The discharge pipes from the temperature/pressure and expansion relief valves must be routed to the
tundish supplied and in 15 mm pipe. The discharge pipework from both relief valves may be joined together in the same sized pipe, providing at least 22 mm pipework is connected downstream of the tundish.
Tundish - The tundish must be positioned within 500 mm of the appliance, so that it is visible to the User and away from electrical devices. The minimum size of the discharge pipe downstream of the tundish is given in the following table.
The discharge pipework from the tundish:-
Sizing of copper discharge pipe 'D2' - refer also to Fig. 4A and 4B
Valve
outlet size
Minimum size of discharge
pipe 'D1' to tundish
15 mm
Minimum size of discharge
pipe 'D2' from tundish
22 mm 28 mm 35 mm
Maximum resistance allowed,
expressed as a length of straight
pipe (i.e. no elbows or bends)
up to 9 m up to 18 m up to 27 m
1. Shall fall continuously through its length.
2. Shall be of a heat resistant material, e.g. metal.
3. Shall not be fitted with any valves or taps.
4. Shall discharge to a safe visible position, e.g. into a gulley.
5. Shall have a minimum of 300 mm straight pipework directly from the tundish.
Note: Where children may play or otherwise come into contact with discharges, a wire cage or similar guard must be positioned to prevent contact whilst maintaining visibility.
Resistance created
by each elbow
or bend
0.8 m
1.0 m
1.4 m
Alpha SolarSmart 90 - General Information
6
Combination boiler
Thermostat sensor
Solar collector
Hot tap
Thermostatically
controlled
mixing valve
Cold water
supply
Outlet water temperature
60°C
Water temperature
less than 60°C
Solar valve
Water temperature
more than 60°C
Drain point
Temperature/pressure
relief valve
Drain back
unit pump
Thermostat
sensor
Unvented
cylinder
Thermostat
sensor
Cylinder
pump
Heat
exchanger
Drain back
unit
Overheat
thermostat
Stop
valve
Filter
Mains water
supply
Pressure
reducing
valve
Check
valve
Expansion
vessel
Expansion relief valve
Tundish
Discharge
pipe
Fig. 3
Unvented kit
Alpha SolarSmart 90 - General Information
7
Given below are suggested methods of terminating the discharge pipe safely. Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to not
more than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected.
If the system is installed where discharges from safety devices may not be apparent, i.e. in dwellings occupied by blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place.
a. Low level termination
Solar cylinder
temperature/pressure
relief valve
Metal discharge pipe (D1)
To expansion
relief valve
500 mm max.
from relief valve to tundish
Tundish
300 mm
minimum
D1
Pipe close to wall to allow water to fan out safely
300 mm
minimum
Metal discharge pipe (D2) from
tundish with continuous fall
D2
100 mm max.
70 mm min.
Ground level
Gulley if available
Fig. 4a
b. High level termination
At high level, discharge onto a roof is acceptable providing the roof is capable of withstanding high temperatures and there is a distance of 3 m from any plastic guttering systems that would collect such discharge.
Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may be damaged by such discharges.
c. Termination into a hopper
300 mm
minimum
D1
D2
Tundish
Type 'A'
air gap
End of pipe to be clearly visible
Worked example:-
The example below is for a G½ temperature relief valve with a discharge pipe (D2) having four elbows and a length of 7 m from the tundish to the point of discharge.
From the table on page 6:-
Maximum resistance allowed for a straight length of 22 mm copper discharge pipe (D2) from a G½ temperature relief valve is 9 m.
Subtract the resistance for four 22 mm elbows of 0.8 m each = 3.2 m. Therefore the maximum permitted length equates to 9 - 3.2 = 5.8 m
5.8 m is less than the actual length of 7 m therefore calculate the next largest size. Maximum resistance allowed for a straight length of 28 mm pipe (D2) from a G½
temperature relief valve equates to 18 m. Subtract the resistance for four 28 mm elbows at 1.0 m each = 4 m. Therefore the maximum permitted length equates to 18 - 4 = 14 m As the actual length is 7 m, a 28 mm (D2) copper pipe will be satisfactory.
Alpha SolarSmart 90 - General Information
8
Fig. 4b
3.4 SOLAR CYLINDER INFORMATION - Figs. 5a and 5b
Positioning
The Solar cylinder must be installed on a flat vertical wall which is capable of supporting the weight of the cylinder when full (113 kg).
The cylinder may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring (BS7671) Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the cylinder in a room or internal space containing a bath or shower. When the cylinder is installed in a room containing a bath or shower, it must not be possible for a person using the bath or shower to touch any electrical switch or cylinder control utilising mains electricity.
The bottom of the Solar cylinder must be located within 6 metres of the top of the Solar collector and of the drain back unit.
Dimensions
The dimensions of the cylinder and clearances required for servicing are shown in Fig. 5a.
Serial No. under cover
100
530
450
10
540
10
Side
1110
187
300
Fig. 5a
Water connections
The connections at the bottom of the cylinder are shown in Fig. 5b.
Note: Use compression fittings only on the cylinder connections.
Cylinder Connections A Water outlet to boiler 15 mm
B Cold water inlet 15 mm C Return from DBU 15 mm D Flow from cylinder to DBU 15 mm
Front
Serial Number
Fig. 5b
Alpha SolarSmart 90 - General Information
9
Loading...
+ 19 hidden pages