Photographs contained in this manual are for illustrative purposes only. These photographs may not match your installation.
NOTE:
Operator is cautioned to review the drawings and illustrations contained in this manual
before proceeding. If there are questions regarding the safe operation of this powering
system, contact Alpha Technologies or your nearest Alpha representative.
NOTE:
Alpha shall not be held liable for any damage or injury involving its enclosures, power
supplies, generators, batteries, or other hardware if used or operated in any manner or
subject to any condition inconsistent with its intended purpose, or if installed or operated in an unapproved manner, or improperly maintained.
For technical support, contact Alpha Technologies:
No part of this documentation shall be reproduced, stored in a retrieval system, translated, transcribed, or
transmitted in any form or by any means manual, electric, electronic, electromechanical, chemical, optical, or
otherwise without prior explicit written permission from Alpha Technologies.
This document, the software it describes, and the information and know-how they contain constitute the proprietary, confidential and valuable trade secret information of Alpha Technologies, and may not be used for
any unauthorized purpose, or disclosed to others without the prior written permission of Alpha Technologies.
The material contained in this document is for information only and is subject to change without notice.
While reasonable efforts have been made in the preparation of this document to assure its accuracy, Alpha
Technologies assumes no liability resulting from errors or omissions in this document, or from the use of the
information contained herein. Alpha Technologies reserves the right to make changes in the product design
without reservation and without notification to its users.
Table K — Setting the Timer Contact .................................................................................................... 83
Table L — Setting the Date and Time ................................................................................................... 85
Table M — Event Codes ....................................................................................................................... 87
Table N — Battery Temperature Compensation Values ........................................................................ 93
Table O — Alarm Submenu .................................................................................................................. 96
Table P — Fault Submenu .................................................................................................................... 97
Table Q — Problems Not Reported by System..................................................................................... 97
Table R — Mechanical Specications ................................................................................................... 98
Table S — Electrical Specications....................................................................................................... 99
Table T — Boost/Buck/Line Transfer Thresholds ................................................................................ 100
Table U — Regulatory ......................................................................................................................... 100
6
017-241-B0 Rev B
1. Safety
SAVE THESE INSTRUCTIONS: This manual contains important safety instructions
that must be followed during the installation, servicing, and maintenance of the product. Keep it in a safe
place. Review the drawings and illustrations contained in this manual before proceeding. If there are any
questions regarding the safe installation or operation of this product, contact Alpha Technologies or the nearest Alpha representative. Save this document for future reference.
1.1 Safety Symbols
To reduce the risk of injury or death, and to ensure the continued safe operation of this product, the following
symbols have been placed throughout this manual. Where these symbols appear, use extra care and attention.
The use of ATTENTION indicates specic regulatory/code requirements that may affect the
placement of equipment and /or installation procedures.
NOTE:
A NOTE provides additional information to help complete a specic task or procedure.
Notes are designated with a checkmark, the word NOTE, and a rule beneath which the
information appears.
CAUTION!
CAUTION indicates safety information intended to PREVENT DAMAGE to material or
equipment. Cautions are designated with a yellow warning triangle, the word CAUTION,
and a rule beneath which the information appears.
WARNING!
WARNING presents safety information to PREVENT INJURY OR DEATH to personnel.
Warnings are indicated by a shock hazard icon, the word WARNING, and a rule beneath
which the information appears.
HOT!
The use of HOT presents safety information to PREVENT BURNS to the technician or
user.
017-241-B0 Rev B
7
1.2 General Warnings
You must read and understand the following warnings before installing the product. Failure to do so could
result in personal injury or death.
• Read and follow all instructions included in this manual.
• Only qualified personnel are allowed to install, operate and service this system and its components.
CAUTION!
Risk of Electric Shock. See Installation Instruction before connecting to the supply.
• The FXM350/ Micro350 is only intended for restricted access locations
• The UPS shall be connected only to a dedicated branch circuit.
CAUTION!
To reduce the risk of re, connect only to a maximum branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.
• Always assume electrical connections or conductors are live. Switch all circuit breakers and double
check connections with a voltmeter before performing installation or maintenance.
• A disconnect switch shall be provided by others for the AC input and AC output circuits.
• The branch circuit overcurrent protection for the AC input and AC output circuit shall be provided in the
end installation.
• Place warning label(s) on the utility panel to tell emergency personnel that a UPS is installed.
• Use only proper lifting techniques whenever handling equipment, parts, or batteries.
• Ferules or the equivalent must be used when stranded wire is used on the AC input and output terminal
blocks.
WARNING!
The Alpha FXM350/ Micro350 have more than one live input circuit. AC power may be
present at the outputs even if the system is disconnected from line or battery power.
CAUTION!
The Alpha FXM350/ Micro350 metal surfaces can be very hot to the touch.
1.3 Battery Safety
• Battery Installation and servicing should be performed or supervised by personnel knowledgeable about
batteries and the required precautions performed.
• Be extra cautious when connecting or adjusting battery cabling. An improperly connected battery cable
or an unconnected battery cable can result in arching, fire or explosion.
• Before attaching the batteries to the Alpha FXM350/ Micro350, make sure that the polarity is correct.
• Use new batteries when installing a new unit. Verify that all batteries are the same type with identical
date codes.
• When replacing batteries, use sealed lead acid batteries, rated 12 V. Never install old or untested batteries.
• Batteries that show signs of cracking, leaking or swelling must be replaced immediately by authorized
personnel using a battery of identical type and rating.
8
017-241-B0 Rev B
CAUTION!
Never open, damage or mutilate batteries. Released Electrolyte is harmful to the skin
and eyes. It may be toxic and hazardous to the environment.
• Never dispose of batteries in a fire. The batteries may explode. Follow the manufacturer’s directions and
check with your local jurisdictions for safe battery disposal.
• If electrolyte splashes on your skin, immediately wash the affected area with water. If electrolyte gets into
your eyes, wash them for at least 10 minutes with clean running water or special neutralizing eye wash
solution. Seek medical attention at once.
• Neutralize spilled electrolyte with special neutralizing solution and a “spill kit” or solution of 1 lbs
(0.45KG) of baking soda (bicarbonate of soda) in 1 gallon (3.8 L) of water.
CAUTION!
A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
a. Remove watches, rings, or other metal objects.
b. Use tools with insulated handles.
c. Wear rubber gloves and boots.
d. Do not lay tools or metal parts on top of batteries.
e. Disconnect the charging source before connecting or disconnecting battery terminals.
f. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the source from
the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if the grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).Never
let live battery wires touch the Alpha FXM350/ Micro350, the enclosure or any other metal objects.
This can cause a fire or explosion.
• Do not smoke or introduce sparks in the vicinity of a battery.
• If the batteries have been in storage for more than 3 months, recharge them for at least 24 hours and
then test them with a load before installation.
• Each AlphaCellTM battery has a date code found on the warning label which must be recorded in the
maintenance log. If non-Alpha batteries are used, see the manufacturer’s documentation for date code
type and placement.
1.4 Work Environment Safety
• Do not work alone under hazardous conditions.
• Keep the chassis area clear and dust-free during and after the installation.
• Keep tools away from walk areas where you or others could fall over them.
• Wear safety glasses when working under any conditions that might be hazardous to your eyes.
• Do not work on the unit or connect or disconnect cables during periods of lightning activity.
017-241-B0 Rev B
9
1.5 Certifications and Compliances
The Alpha FXM350 and Micro350, has been designed, manufactured, and tested to the requirements of the
following national and international safety standards:
• UL 1778 (Edition 4) – Uninterruptible Power Systems; additional requirements (RD): UL 60950-1 (Edition
1) - Information Technology Equipment - Safety.
• FCC CFR47 Part 15 Class A – This equipment has been tested and found to comply with the limits for a
Class A digital device pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own expense.
• Industry Canada - This Class A digital device apparatus complies with Canadian ICES-003.
• Industry Canada - Cet appareil numrique de la Classe A est conformé la norme NMB-003 du Canada.
10
017-241-B0 Rev B
2. General Description
2.1 Alpha FXM350
The Alpha FXM350 is available in 24Vdc and 48Vdc models. It provides up to 350W of regulated AC Power
to the load, when utility power is available, and provides back up power from the batteries in case of a utility
power failure. Noteworthy features include:
• Local or remote monitoring and control via USB and SNMP communication
• Small footprint for wall, rack or enclosure mounting
• Dependable operation in extreme operating environments (-40 to 74°C or -40 to 165°F)
• Powerful firmware with enhanced features such as battery run-time information
2.2 Micro350/ Alpha FXM350
The Micro350 contains a standard FXM350 along with batteries—Figure 1 shows three options for the enclosure. These enclosures are designed with a NEMA 3R rating for outdoor applications.
Figure 2 shows the FXM350 installed in a standard-sized Micro350 cabinet. Power is distributed through
terminal blocks mounted on a DIN rail.
(a)Standard Micro350
(1 battery tray)
017-241-B0 Rev B
(b) Micro350 XL
(2 battery trays)
Figure 1 — Micro350 cabinets
(c) Micro350 XL3
(4 battery trays)
11
In addition to the FXM350 standard features, the unit also includes the following:
• Three additional user-configurable dry contacts and two additional user inputs (top panel in Figure 2)
• Door sensor switch for increased security
• AC Input and outputs on an easy to install terminal block
• Flexible dual AC and DC output for multiple loads up to 350W with distribution
AC inputBattery bus voltageAC output (dual)
120Vac48V or 24V120/24Vac
230Vac24V230/24Vac
Micro350 top panel
FXM350 front panel
AC power distribution
terminal blocks
Wire management
panel
Attachment holes for
mounting bracket
Ground stud
Knockouts for wiring
12
Figure 2 — FXM350 mounted in a standard Micro350 cabinet
017-241-B0 Rev B
2.3 FXM350 Front Panel
The following table and Figure 3 identify the main features of the FXM350 which are described in detail in the
following pages.
ItemDescriptionItemDescription
1Battery breaker8Optically isolated user inputs
2Battery connector9Additional user inputs and dry contacts connector
3RJ45 communication module connector10Status and alarm LEDs
4LCD control panel and menu navigation buttons11Configurable dry contacts, C1 and C2
5USB communication connector12Replaceable fan assembly
6Battery temperature sensor connector13AC input circuit breaker
7Battery voltage test points14Battery heater mat connector
15AC input/output connections
1
4
10
12
2
13
3
7
5
6
1
Battery breaker
This circuit breaker provides over-current protection and is used as an on/off switch for the battery power. It
must be switched on for proper Alpha FXM operation.
Battery connector
2
The battery connector connects the external batteries to the Alpha FXM.
RJ45 communication module connector
3
This RJ-45 connector is the Alpha FXM Ethernet connector.
9
8
Figure 3 — FXM 350 front panel description
11
14
15
4 LCD control panel a nd menu navigation buttons
The LCD control panel together with the cancel, scroll and select buttons are used to monitor and control the
Alpha FXM350.
USB communication connector
5
This USB communication connector provides a direct connection to the USB port of a standard computer
USB port (USB 2) for remote monitoring.
017-241-B0 Rev B
13
Battery temperature sensor connecto r
6
The battery charging voltage is temperature dependant. A battery temperature sensor connects to the Alpha
FXM so that the Alpha FXM microprocessor can adjust the charging voltage for optimum charging.
The sensor MUST be attached to the Alpha FXM for normal operation. If the sensor is not attached, a “Temperature Probe Unplugged” alarm appears on the LCD.
7
Battery voltage test points
These test points let you measure the battery voltage. They accept 2 mm diameter test probe tips. The battery circuit breaker must be on to measure the voltage.
The battery voltage test points are not to be used as a power outlet.
8
Optically isolat ed user inputs
These optically isolated inputs are used to attach an external switch panel for remote control of the
Alpha FXM.
The User Input connector has three contacts (Figure 4) that are used to control the Alpha FXM. The default
settings for the user inputs are as follows:
1 (S1): Shorting this contact to Common starts the Alpha FXM battery test. See "Battery Test" on page 95.
2 (S2): Shorting this contact to Common activates an alarm. See "7.3.4.9 Maintenance > User Input" on
page 63.
3 (SC): Isolated return for contacts S1, and S2.
123
SC:CommonS1:Self TestS2:Alarm
Figure 4 — User input layout
9
Additional user inputs and dry contacts connector
Enables connection to 3 dry contacts and 2 user inputs on the Micro350 top panel or to optional rack mounting ears (see Figure 20).
10
Status and Alarm LEDs
Status:
Green LED solidly illuminated: the Alpha FXM is in Line mode and line power is provided to the load.
Green LED flashing: the unit is in Inverter mode and backup battery power is provided to the load.
Alarm:
Red LED solidly illuminated: fault in the Alpha FXM. (See "Table P — Fault Submenu" on page 97.)
Red LED flashing indicates an alarm. ( See "Table O — Alarm Submenu" on page 96.)
14
017-241-B0 Rev B
11
Configurabl e dry contacts, C1 and C2
Contacts C1 and C2 allow the Alpha FXM to be connected to an external monitoring panel or to traffic control
equipment.
The factory default settings can be reprogrammed to meet your requirements. See "7.3.3.3 Monitoring > Relay & Load Shed" on page 53 for web and Alpha UPS Monitor, and "7.5.4 Programming the Dry Contacts" on
page 82 for HyperTerminal.
C1: The C1 contact is energized when line power is unqualified and the Alpha FXM provides backup battery
power to the load(s). Can be used to generate an “On Battery” alarm.
C2 : This contact is energized when the battery drops below a pre-set voltage level. Can be used to generate
a “Low Battery” alarm. You can change the pre-programmed level to match the batteries used and the actual
operating conditions. See "Adjusting and Controlling the Alpha FXM" on page 81: #35 Low Battery Warning
Voltage.
Microprocessor
UPS
The contacts have
a maximum rating
of 1A at 250V.
Interior
Normally
Closed (NC)
Replaceable fan assembly
12
Normally
Open (NO)
Common (C)
Figure 5 — Contact Layout (Standard for C1 and C2)
This microprocessor-controlled fan regulates the Alpha FXM internal temperature for optimum performance.
Microprocessor-control of the fan speed increases the life of the internal electronics and the fan.
Take care that the fan is not blocked. Failure of the fan generates an alarm; the internal fan assembly is designed so it can be replaced if it fails.
13
AC input circuit breaker
This circuit breaker is an on/off switch for the line power into the Alpha FXM ,which also provides input protection. It must be switched on for proper Alpha FXM operation.
14
Battery heater mat connector
This connector plugs into a 55W heater mat (optional). The Alpha FXM senses the battery temperature
through the battery temperature sensor (explained in 6 above) and controls the battery heater mat. The
heater mat is set to turn on at 5°C or less and turns off at 15°C.
15
AC input/output conn ections
The terminal blocks provide connections to the AC input and loads for dual outputs.
017-241-B0 Rev B
15
2.4 Micro350 Top Panel
The Micro350 top panel has three additional dry contacts and two user inputs.
The panel also has a door interlock and auxiliary contacts, which can be wired to a user input to generate an
alarm when the door is open.
Dry contacts
C3, C4, and C5
Additional signals connector.
Connects to #9 of gure 3
User inputs
S3 and S4
Door interlock
Open door
switch signal
Figure 6 — Micro350 Top Panel
16
017-241-B0 Rev B
3. Site Planning
WARNING!
Restricted Access: The Alpha FXM350 and Micro350 must be installed in a restricted
area accessible only by qualied service personnel.
The Alpha FXM350 and Micro350 are intended for permanent AC connection only.
The Alpha FXM350 and Micro350 must be correctly grounded for proper operation.
Older facilities may have inadequate electrical grounding. Inspection must be performed
by a qualied electrician before installation to ensure that grounding meets the local
electrical code.
The utility line attached to the Alpha FXM input MUST be protected by a circuit breaker
certied for this use in accordance with the local electrical code. The UPS must be connected only to a dedicated branch circuit.
The UPS equipment that is powered by this service panel requires the neutral to be permanently bonded to the ground. Always disconnect the batteries before servicing the
circuit breaker panel.
The input and output lines to and from the Alpha FXM MUST have disconnect devices
attached.
The Alpha FXM is suitable for installations in network telecommunication facilities and locations where the
National Electrical Code applies.
Grounding: The Alpha FXM is suitable both for installation as part of a common bonding network (CBN) and
an isolated bonding network.
For installations above 1400 m (4500 ft) elevation, additional cooling may be needed to reduce the operating temperature of the Alpha FXM. The maximum allowable operating temperature must be reduced by 2°C
(3.5 °F) for every 300 m (1000 ft) above 1400 m (4500 ft).
3.1 Safety Precautions
• Install the Alpha FXM350 and Micro350 and batteries on a surface that can support the total weight. See
Chapter "10. Specifications" on page 98.
• The input wiring must reach a suitably grounded power outlet and the load wiring must reach the
Alpha FXM350 and Micro350 output terminal blocks.
• Place the Alpha FXM350 in a properly sheltered location or inside a weather-proof enclosure to protect
the electronics from water, dust and other possible contamination.
• Backup Generator (If used)
In Generator mode, the Alpha FXM range of acceptable input frequency and voltage is expanded to
accept the fluctuations created by a generator. See "7.2.2 The LCD Control Menu" on page 45, Table B,
Sense Type.
Use a generator with electronic speed and voltage controls which produces less than 10% voltage total
harmonic distortion (THD). Mechanical governors can force the Alpha FXM to run continuously in Battery
mode. Before installation, make sure the generator’s output voltage is compatible with the Alpha FXM
input voltage requirements. To make sure the system runs smoothly, use a generator that supplies twice
as much power as drawn by the total load.
Observe the following EMC requirements when setting up the Alpha FXM and its internal equipment:
• All AC mains and external supply conductors must be enclosed in a metal conduit or raceway when
specified by local, national, and/or other applicable government codes and regulations.
• The customer facilities must provide suitable surge protection.
• To meet FCC Class B requirements, follow the instructions in section 5.1.4 to attach a ferrite ring to the
connector end of your RJ45 network cable.
3.3 Mounting Options for the Micro350 (XL and XL3)
Figure 7 shows the mounting hardware for the various configurations of the Micro350.
Choose from the following options for mounting the Micro350:
• Mounting to a wooden pole, 5.1.1.1 on page 24.
• Mounting to a steel or concrete pole, 5.1.1.3 on page 26.
• Mounting to a wall, 5.1.1.4 on page 27.
Optional pedestal mounting is shown in Figure 8.
18
Micro Standard
Micro XL3
NOTE: To install a Micro XL3 enclosure, rst attach
the XL to an XL3 kit.
Micro XL
Figure 7 — Mounting the Micro350
017-241-B0 Rev B
Figure 8 — Mounting on optional pedestal
3.3.1 Battery Heater Mats
The FXM350 and Micro350 allow connection, on its front panel, of a battery heater mat without a thermostat
(#14 in Figure 3). Maximum power of the battery heater mat for use with the FXM350 connector is 55W. The
FXM turns the heater mat on when the temperature measured by the battery temperature sensor senses a
temperature < 5°C. It turns the heater mat off when the temperature raises to >15°C. For the Micro350XL or
bigger systems needing more than one heater mat, it is recommended to use the heater mats with built in
thermostat and daughter heater mats that can be daisy chained. These heater mats may be wired to the AC
in the terminal block on the distribution panel. Ensure that the input breaker is appropriately rated.
017-241-B0 Rev B
19
3.3.2 Mounting options for the FXM350
Figure 9 and Figure 11 provide dimensions for mounting the FXM350 UPS as a standalone device.
198
[7.8]
13.7
[0.5]
[3.5]
88
Figure 9 — FXM350 Mounting Dimensions
3.3.2.1 Standalone Configurations:
• Wall mounted, with front access, onto a 19"
mounting tray that includes a battery cabinet
• Rack mounted in a 19" or 23" rack with add-on
ears and a wiring box (Figure 10). An optional
signals assembly can be ordered, which provides two user inputs and three dry contacts.
342
[13.5]
Standard
ears and
wiring box
Optional signals
assembly
20
Figure 10 — Rack-mount options
017-241-B0 Rev B
43.7 1.72
46.0 1.81
9.53[0.375]
X
OBROUND THRU
6.35[0.250]
TYP.
566.7 22.31
584.1 23.00
& OPTIONAL EXTERNAL DRY CONTACTS MODULE
FXM 350 w/RACK MOUNT KIT CONFIGURED FOR A 19" RACK
88.1 3.4776.2 3.00
& OPTIONAL EXTERNAL DRY CONTACTS MODULE
FXM 350 w/RACK MOUNT KIT CONFIGURED FOR A 23" RACK
465.1 18.31
482.5 19.00
Figure 11 — FXM350 with ears for rack mounting
017-241-B0 Rev B
21
3.4 Options for Communicating with the FXM
There are several ways to communicate with the Alpha FXM UPS:
1. The control panel page 42).
2. Window®’s HyperTerminal or other terminal emulation program to access the UPS command line system
over the USB interface (page 76).
3. Alpha UPS Monitor installed on your computer and connected to the FXM over the USB interface . The
Alpha UPS Monitor software can be downloaded from www.alpha.ca./downloads/.
4. Factory-installed FXM communication module to communicate with the Alpha FXM using any of the
following:
• On site PC
• Company intranet or the internet using a web browser (page 49).
• SNMP communications
Option 4
Option 5
On-Site
Ethernet Connection
Ethernet
Port
USB Port
Option 4
(Use a Web browser for
Ethernet connection
to on-site computer)
FXM350 UPS
Option 1:
Control Panel
Options
2 and 3
User’s PC
(Use Alpha UPS Monitor
or HyperTerminal)
22
Figure 12 — Alpha FXM Communication Options
017-241-B0 Rev B
4. Unpacking the Equipment
4.1 Alpha FXM350/Micro350 Configuration
The Alpha FXM is factory installed inside the Micro350 prior to shipping.
WARNING!
The Alpha FXM350/Micro350 combination is heavy, up to 12 kg (26 lb). Use proper lifting
techniques.
4.2 Unpacking
1. Select a suitable area for unpacking.
2. Store all the packing material and boxes for possible equipment returns.
4.2.1 FXM350 Standalone or Micro350 (XL)
1. Check the contents in your product package. The following standard items are shipped together in a
plastic bag:
• Terminal blocks and labels for the dry contacts
• Temperature sensor cable
• Battery clip with screws
• AC plate with screws and bushing
• Ferrite ring
• Cable tie
• Operator’s manual
• USB cable
2. Compare the packing slip and the list of parts with the items you received. If the list of parts on your
packing slip does not match the items you received, or any items appear damaged, immediately notify
your carrier agent and the supplier who prepared your shipment.
4.3 Optional Items
Optional items may include:
• Battery heating mats
• Battery cable kit
• Rack mount ears and wiring box kit for mounting in a 19" or 23" rack (Figure 10)
• Optional signals assembly for FXM350 (Figure 20)
• Distribution panel
Batteries, if ordered from Alpha, will ship separately.
017-241-B0 Rev B
23
5. Installation
WARNING!
To avoid personal injury or damage to the equipment, always use at least two installation personnel to remove the unit from its container.
5.1 Installation of the Micro350
WARNING!
Batteries or other components (with the exception of factory-installed components)
must not be installed until the Micro350 cabinet has been securely set in place at its permanent location. Transporting the unit with batteries installed may cause a short circuit,
re, explosion, and/or damage to the battery pack, enclosure and installed equipment.
Damage caused by improper shipping or transporting a unit with batteries installed is
not covered by the warranty.
5.1.1 M ounting the Micro350 Enclosure
5.1.1.1 Mounting to a wooden pole
Have the following tools and materials on hand:
• 13 mm nut driver for the bolts that attach the cabinet to the mounting bracket.
• Two 5/8 inch diameter machine bolts (UNC tread); SAE (Grade 5 or better), length to suit the pole (not
provided).
• Two 5/8 inch diameter zinc-plated flat washers.
• Two 5/8 inch diameter hex nuts (UNC thread).
• Auger or drill for boring 3/4 inch diameter holes in the wood pole.
24
017-241-B0 Rev B
5.1.1.2 Procedure:
1. Using the mounting bracket as a template, drill 2 holes into the pole to accept the machine bolts.
2. Secure the mounting bracket to the pole with the machine bolts as shown in Figure 13.
3. Secure the Micro350 cabinet to the mounting bracket with the supplied bolts (Figure 14).
FrontSideWood
Pole
Figure 13 — Mounting to a wooden pole
a. Hook the top of the mounting bracket under the case’s attachment tting.
b. Secure the cabinet to the mounting bracket.
Figure 14 — Securing the enclosure to the mounting bracket
017-241-B0 Rev B
25
5.1.1.3 Mounting to a Steel or Concrete Pole
Have the following tools and materials on hand:
• 13 mm nut driver for the bolts that attach the cabinet to the mounting bracket.
• Two pole mount straps that fit the pole. Straps must be stainless or galvanized.
• C001 Band-It tool or equivalent.
• C206 3/4 inch stainless steel Band-It band or equivalent.
• C256 3/4 inch stainless steel Band-It buckles or equivalent.
Procedure:
1. Secure the mounting bracket to the pole with
the straps.
Steel or Concrete
Pole
2. Secure the Micro350 cabinet to the mounting bracket with the supplied bolts.
26
a. Hook the top of the mounting bracket under
the case’s attachment tting.
b. Secure the cabinet to the mounting bracket.
017-241-B0 Rev B
5.1.1.4 Mounting to a Wall
Have the following tools and materials on hand:
• 13 mm nut driver for the bolts that attach the cabinet to the mounting bracket.
• Four 1/4" x 1-1/8" lag bolts.
• Four 1/4" diameter flat washers.
• Drill with 1/8" bit for drilling pilot holes.
• Assorted sockets and wrenches.
Procedure:
NOTE:
If the wall structure is not strong enough to support the weight of the Micro350 enclosure and batteries, use a wooden backing plate that has a minimum thickness of 1-1/4"
and a maximum width of 4" that is securely mounted to a wall stud or studs.
1. Using the mounting bracket as a template, drill 4 pilot holes (indicated by the arrows in the following
diagram) into the wall to accept 1/4" bolts.
2. Secure the mounting bracket to the wall with the 4 bolts and washers.
3. Secure the Micro350 enclosure to the mounting bracket with the supplied bolts.
NOTE:
To install a Micro XL3 enclosure,
rst attach the XL to an XL3 kit.
Figure 15 — Attaching the mounting bracket to the wall studs
FrontSide
Wall or
studs
017-241-B0 Rev B
27
5.1.2 Wiring the Micro350
OUTPUT
PUSH BUTTON TO
INSERT/REMOVE WIRES
INPUT
PUSH BUTTON TO
INSERT/REMOVE WIRES
L
N
STRIPWIRE7/16 in (11mm)
USE
MAXIMUM
12 AWG
2
(4mm)
L
24V
N
WARNING!
Before starting, disconnect the Line power.
If stranded wires are used for connection at the input terminal block, ferrules or equivalent crimping terminals must be used.
Separate the AC input power cables from the output power cables within the Alpha FXM
enclosure. Route them through separate conduit openings in the enclosure.
Separate the DC Battery cable from the AC Input and Output power cables. Route the
cable through its own opening.
The AC power distribution terminal blocks in the Micro350 enclosure are located in the below the FXM350
(see Figure 16). Refer to Table S for detailed electrical specifications.
Figure 16 — AC Power distribution terminal blocks
Have the following tools and materials on hand:
• Hammer for removing the knockouts
• Slot head screwdriver, 3/16 or smaller, to attach wires to the terminal blocks for the dry contacts / user
inputs on the front panel
• Slot head screwdriver, 1/4 or larger, for removing the knockouts
• DC voltmeter
• Battery terminal corrosion inhibitor such as NOCO Company’s NCP-2 or Sanchem Inc. No-Ox ID Grease
“A”
• Maximum of 12 AWG wire for wiring the input and output terminal blocks
• If used, 1/2" conduit connectors to fit the knockouts (7/8" diameter) and armored conduit to fit
• Optional battery heater mats
28
017-241-B0 Rev B
Loading...
+ 82 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.