Hydraulic Downforce
To create a conguration, make the following button presses to start the Conguration Wizard and then follow the
instructions given on the display.
Enter Settings
Planting
Conguration Product
Planting
Press to Highlight Conguration
8360,1770,3dr
Gauge Wheel Load Alarm
Start of Conguration Wizard
Down
Force
Select planter type (drop down menu)
If using uplift springs, enter value as dened
in installation instructions
Places an upper limit on the amount of
supplemental down force
Alarm will trigger if any monitored gauge wheel
load is below this value for a duration of time
Alarm will trigger if any monitored gauge wheel
load is below Minimum Load for this amount of
time
Down Force Control Mode (drop down menu)
Monitor Only: Select this option if only using gauge wheel sensors in conjunction with other
supplemental down force products (i.e. manually adjusted springs or airbags)
Control: Select this option is using Ag Leader hydraulic down force actuator and gauge
Control Settings
Note: Some planters may have a combination of long and short parallel arms depending on accessories. In this case use
the value that represents the majority of the rows.
wheel sensors. This option allows for active down force control
Enabling this option will disengage active control (hold) when any portion of the planter enters
a no plant zone, such as boundaries, or previously planted areas. Use caution with this option if
planting long point rows. Alarms are disabled when system is in hold.
Value must be entered for your specic planter and parallel arm combination
Kinze 3000 series 4.2 PSI/lb
John Deere Max Emerge/XP with short parallel arms
John Deere Max Emerge/XP with long parallel arms 3.8 PSI/lb
4.5 PSI/lb
Quick Reference Guide
AL: 2006350 ENG Rev B
1
Hydraulic Downforce
Manually entered values depicting
tractor’s hydraulic pressure. Values shown
are for a 3000 PSI system (most common)
Select Channel to Calibrate
1. Set Point: Enter value here that matches value displayed on the corresponding channel’s
mechanical gauge attached to Ag Leader Down Force valve. (This can be done at 0 PSI)
2. Slope: value is dependent on manufacture of pressure transducer. Use 0.75 PSI/mV for
transducer supplied with valve.
Pressure Sensor Enabled: must be enabled to display “Down Force” on run screen.
Duty Cycle
Minimum/Medium/Maximum: Manually entered values correlating PWM duty cycle to
hydraulic pressure supplied to Down Force actuators. Values shown are for the Ag
Leader supplied hydraulic down force valve.
PWM Frequency: Number of PWM signals per second (Hz)
Row Unit Sensors
Enabled sensors will be used to calculate required supplemental down force
To start the Field Operation Wizard and load a conguration:
Conguration
To view run screen:
Quick Reference Guide
Start Field Operation
AL: 2006350 ENG Rev B
2
Hydraulic Downforce
Gauge Wheel (bar graph): Each bar displays gauge wheel load for monitored rows
Down Force (bar graph): Each bar displays supplemental down force for monitored
rows
Down Force
a. Gauge Wheel: Planter average gauge wheel load
b. Down Force: Planter average supplemental down force
Planter Options - Down Force tab
Status: displays current status of control system
Active: System is actively controlling down force
Inactive: System is not actively controlling down force
Hold: Pressure is being held constant due to manual hold or
automatic hold
Gauge Wheel: Instantaneous channel average gauge wheel
load
Down Force: Instantaneous hydraulic pressure
Pressure: Pressure reading from corresponding channel
pressure transducer
Gauge Wheel By Row (table): Instantaneous gauge wheel load
for each monitored row
Automatic Control (button): Active down force control mode.
Gauge Wheel Load: User selected aggressiveness. Higher
aggressiveness will equate to higher gauge wheel loads
Manual Control (button): Allows user to manually adjust
pressure supplied to down force actuators across planter. Active
down force is disabled when in this mode.
Active Manual Inactive Manual
Hold
Quick Reference Guide
AL: 2006350 ENG Rev B
3
Hydraulic Downforce
CAN A
HIGH POWER
LOCAL CAN BUS
SIGNAL/CONTROL
At least one implement switch must be installed on the
Seed Command system.
Terminator
P/N 4002871
Right End of Planter
Terminating
Plug P/N
4002871 must
be installed on
the right end of
the planter.
Channel Cable
Channel Cable
Row Module
P/N 4002912-1
Row Module Breakout
Row Module
P/N 4002912-1
Row Module Breakout
Cable Diagram
Load Sensor
Load Sensor
Channel 2 Solenoid Valve
Channel 2 Pressure
Channel 1 Solenoid Valve
Channel 1 Pressure
Down Force Control Module
Control module and Implement Switch module(s) can
be placed anywhere in series on the local CAN Bus.
CAN Implement Switch
P/N 4002911
P/N 4002920-008
Dust Cap
Row Module
P/N 4002912-1
Row Module Breakout
P/N 4002658
Row Module
P/N 4002912-1
Load Sensor
P/N 4000726-12
Implement Switch
Terminator
P/N 4002870
Left End of Planter
Row Module Breakout
Terminating Plug P/N 4002870 must be
installed on the left end of the planter.
Quick Reference Guide
AL: 2006350 ENG Rev B
Load Sensor
4