AERCO Esteem 399 Installation and Maintenance Manual

Instruction
No.
AERCO INTERNATIONAL, Inc. Northvale, New Jersey, 07647 USA
Installation and Maintenance
Manual
Esteem 399
GF-125
Low NOx Gas Fired Boiler
Visit www.aerco.com to View the Latest
Product Manuals and Information.
Printed in U.S.A. REVISED MAY 2010
Telephone Support
(800) 526-0288
Direct to AERCO Technical Support
(8 to 5 pm EST, Monday through Friday)
Please have the unit’s model number and the serial number from the rating la­bel on the backside of the control panel when calling about service or trouble­shooting.
Model #_________________________
Serial #__________________________
AERCO International, Inc. 159 Paris Avenue Northvale, NJ 07647-0128
www.aerco.com
© AERCO International, Inc., 2010
The information contained in this document is subject to change without notice from AERCO International, Inc.
AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of mer­chantability and fitness for a particular application. AERCO International is not lia­ble for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
Esteem 399 Low NOx Installation and Maintenance Manual GF-125
Contents
Chapter 1 Warnings and Cautions 1
Emergency Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Prolonged Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
IF YOU SMELL GAS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2 Pre-Installation Items 4
Code Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Determining Product Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Boiler Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Recommended Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Residential Garage Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Boiler Freeze Protection Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 3 Combustion Air and Venting 7
Combustion Air Contamination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Potential contaminating products. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Areas likely to have contaminants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Ventilation and Combustion Air Requirements - Direct Vent. . . . . . . . . . . . . . . . . . . . . . . . 8
Ventilation and Combustion Air Requirements - Category IV . . . . . . . . . . . . . . . . . . . . . . . 8
Indoor Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Outdoor Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Combination of Indoor and Outdoor Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Combustion Air and Vent Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Removal of an Existing Boiler from a Common Vent System . . . . . . . . . . . . . . . . . . . . . . 11
Commonwealth of Massachusetts Installations Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 4 Unit Preparations 14
Handling Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wall Mounting Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wall Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Stud Wall Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Boiler Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Chapter 5 Boiler Piping 16
General Piping Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Low Water Cutoff Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Additional Limit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Backflow Preventer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Boiler System Piping Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Expansion Tank and Makeup Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Diaphragm Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Closed-Type Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Circulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Sizing Primary Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
i
Domestic Hot Water System Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System Piping - Zone Circulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
System Piping - Zone Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System Piping - Through Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System Piping - Radiant Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System Piping - Special Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
System Piping - Multiple Units Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 6 Installing Vent, Air Intake & Drain 27
Installing Vent and Combustion Air Intake. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installing Condensate Drain Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Chapter 7 Gas Piping 29
Gas Supply Piping Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Pipe Sizing - Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Natural Gas Supply Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Pipe Sizing - Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Propane Gas Supply Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Chapter 8 Internal Wiring 33
General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Control Module Circulator AMP Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Wiring Tool Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Internal Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Chapter 9 External Wiring 35
Installation Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Line Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Domestic Hot Water Aquastat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
CH and DHW Circulator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
System Circulator - Zone Valve Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
External Modulating Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Outdoor Reset Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Additional 24V Limit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
External Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Chapter 10 Start-Up Preparation 39
Check Boiler System Water Chemistry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Water pH Level 6.0 to 8.0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Water Hardness Less Than 7 Grains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Chlorinated Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Flush Boiler and Domestic System to Remove Sediment . . . . . . . . . . . . . . . . . . . . . . . . . 39
Check and Test Antifreeze. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
ii
Use of Antifreeze in the Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Filling the Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Check Low Water Cut-Off Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Check For Gas Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Check Thermostat Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Inspect the Condensate Drain Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Chapter 11 Start-Up Procedures 42
Final Checks Before Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Esteem 399 Low NOx Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
If Esteem 399 Low NOx Does Not Start Correctly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
First Run Check of the Unit and System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Set Boiler CH Set Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Operation Verification - Space Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Operation Verification - Domestic Hot Water. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter 12 Operating Instructions 47
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
TO TURN OFF GAS TO APPLIANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Boiler Control Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
To temporarily place the burner into high fire test mode: . . . . . . . . . . . . . . . . . . . . . . 49
Parameter mode—Setting The Boiler Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Information Mode—Accessing Boiler Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Error (Hard Lockout) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chapter 13 Outdoor Reset Control 54
Mounting the Outdoor Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Wiring the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Summer / Winter Switch at Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Adjusting Outdoor Reset Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
CH Maximum Boiler Operating Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
CH Minimum Boiler Operating Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
CH Reset Curve Coldest Day . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Entering MCBA Access Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Chapter 14 External Modulating Control 58
Wiring the Modulating Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Parameter Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Programming of External Modulating Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Factory Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Chapter 15 Check-Out Procedures 60
Check-Out Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Chapter 16 Installation Record 61
iii
Chapter 17 Maintenance Schedule 62
Professional Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Owner Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Chapter 18 Maintenance Procedures 63
Attend to Reported Problems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Check Surrounding Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Inspect Burner Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Check System Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Clean Condensate Drain Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Check Ventilation Air Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Inspect Vent and Combustion Air Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Check Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Check Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Check Boiler Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Inspect Ignition Electrode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Check Ignition Wiring and Ground Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Check Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Check Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
Check Burner Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Check Flame Signal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Check Combustion Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Check Flue Gas Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Clean Heat Exchanger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Start-up and Checkout Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Review With Owner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
Chapter 19 Troubleshooting 69
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Control Module Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Soft Lockout Error Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Hard Lockout Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
Insulation Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
Appendices 87
Appendix A: Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Appendix B: Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Appendix C: Pressure Drop Comparison Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
iv
Chapter 1 Warnings and Cautions
Installers and operating personnel MUST, at all times, observe all safety
regulations.
The following general warnings and cautions must be given the same attention as specific precautions included in these instructions. In addition to the requirements included in this Manual, the installation MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54). Where ASME CSD-1 is required by local jurisdiction, the installation must conform to CSD-1.
Where applicable, the equipment must be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CGA B149, and applicable Provincial regulations for the class. Authorities having jurisdiction should be consulted before installations are made.
CAUTIONS!
Must be observed to prevent damage or loss of operating effectiveness.
NOTICE
Indicates special instructions on instal­lation, operation or maintenance, which are important to equipment but not re­lated to personal injury hazards.
WARNING!
BEFORE ATTEMPTING TO PERFORM ANY MAIN-
TENANCE ON THE UNIT, SHUT OFF ALL GAS AND ELECTRICAL INPUTS TO THE UNIT.
WARNING!
THE EXHAUST VENT PIPE OF THE UNIT OPER-
ATES UNDER A POSITIVE PRESSURE AND THERE- FORE MUST BE COMPLETELY SEALED TO PRE- VENT LEAKAGE OF COMBUSTION PRODUCTS INTO LIVING SPACES.
IMPORTANT
This Instruction Manual is an integral
part of the product and must be main-
tained in legible condition. It must be giv-
en to the user by the installer and kept in
a safe place for future reference.
DANGER!
INDICATES THE PRESENCE OF A HAZARDOUS
SITUATION WHICH, IF IGNORED, WILL RESULT IN DEATH, SERIOUS INJURY OR SUBSTANTIAL PROP- ERTY DAMAGE.
WARNINGS!
MUST BE OBSERVED TO PREVENT SERIOUS IN-
JURY OR SUBSTANTIAL PROPERTY DAMAGE.
WARNING!
FLUIDS UNDER PRESSURE MAY CAUSE INJURY
OR DAMAGE TO EQUIPMENT WHEN RELEASED.
E SURE TO SHUT OFF ALL INCOMING AND OUT-
B
GOING WATER SHUT OFF VALVES. CAREFULLY DECREASE ALL TRAPPED PRESSURES TO ZERO BEFORE PERFORMING ANY BOILER MAINTE- NANCE.
WARNING!
DO NOT USE MATCHES, CANDLES, FLAMES, OR
OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS.
GF-125
1
Emergency Shutdown
CAUTION!
Many soaps used for gas pipe leak test­ing are corrosive to metals. The piping must be rinsed thoroughly with clean water after leak checks have been com­pleted.
CAUTION!
DO NOT use this boiler if any part has been under water. Call a qualifi ed serv- ice technician to inspect and replace
any part that has been underwater.
IMPORTANT
The Installer must identify and indicate the location of the emergency shutdown manual gas valve to operating person­nel.
Emergency Shutdown
To shut Down the Unit
Turn the service switch on the Esteem 399 Low NOx control panel to “OFF”
Turn the external manual gas valve handle clockwise
to “CLOSE”.
If overheating occurs or the gas supply fails to shut off, close the manual gas shutoff valve (Figure 1) located external to the unit.
Prolonged Shutdown
After prolonged shutdown, it is recommended that the startup procedures in Chapter 10 of this manual be performed, to verify all system operating parameters. If there is an emergen­cy, turn off the electrical power supply to the AERCO boiler and close the manual gas valve located upstream the unit. The installer must identify the emergency shut-off device.
Figure 1: Typical Manual Gas Shutoff Valve
2
GF-125
IF YOU SMELL GAS
DANGER!
IF YOU SMELL GAS
• Do Not try to light any appliance
• Do Not touch any electrical switch
• Do Not use any phone or cell phone in your building.
Immediately call your gas supplier from a different location.
Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fi re department.
IMPORTANT
Installation and service must be per­formed by a qualifi ed installer, service agency or the gas supplier.
DANGER!
DO NOT USE THIS APPLIANCE IF ANY PART
HAS BEEN UNDER WATER. IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM WHICH HAS BEEN UNDER WATER.
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS
SUPPLY FAILS TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE EXTERNAL TO THE APPLIANCE.
WARNING
DO NOT ADD COLD MAKE UP WATER WHEN THE
BOILER IS HOT. THERMAL SHOCK CAN CAUSE POTENTIAL CRACKS IN THE HEAT EXCHANGER.
CAUTION
Avoid electrical shock by disconnecting the electrical supply prior to performing maintenance when servicing the boiler:
WARNING
PRIOR TO INSTALLING THIS PRODUCT READ ALL
INSTRUCTIONS INCLUDED IN THIS MANUAL AND ALL ACCOMPANYING MANUALS/DOCUMENTS.
ERFORM ALL INSTALLATION STEPS REQUIRED
P
IN THESE MANUALS IN THE PROPER ORDER GIV- EN. FAILURE TO ADHERE TO THE GUIDELINES WITHIN THESE MANUALS CAN RESULT IN SEVERE PERSONAL INJURY, DEATH OR SUBSTANTIAL PROPERTY DAMAGE.
Please have the unit’s model number and the serial number from the rating label, on the backside of the control panel when inquiring about service or troubleshooting.
AERCO International accepts no liability for any damage resulting from incorrect installa­tion or from the use of components or fi ttings not specifi ed by AERCO International.
GF-125
3
Chapter 2 Pre-Installation Items
Code Compliance
This product must be installed in accordance to the following:
• All applicable local, state, national and provincial codes, ordinances, regulations and laws.
• For installations in Massachusetts, code requires the boiler to be installed by a licensed plumber or gas fi tter, and if anti- freeze is utilized, the installation of a re­duced pressure backfl ow preventer device is required in the boiler’s cold water fi ll or make up water supply line.
• For installation in Massachusetts all direct vented appliances must comply with the guidelines as outlined on page 13.
• The National Fuel Gas Code NFPA54/ ANSI Z 223.1 - Latest edition.
• National Electric Code ANSI/NFPA 70.
• For installations in Canada -“Installation Code for Gas Burning Equipment” CGA/ B149.1 or B149.2 Canadian Electrical Code Part 1 CSA C22.1.
Standards for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD­1, when required.
Determining Product Location
Before locating the Esteem 399 Low NOx check for convenient locations to:
• Heating system piping
• Venting
• Gas supply piping
• Electrical service
Ensure the boiler location allows the com­bustion air/vent piping to be routed directly through the building and terminate properly outside with a minimum amount of length and bends.
Ensure the area chosen for the installation of the Esteem 399 Low NOx is free of any com­bustible materials, gasoline and other flam­mable liquids.
WARNING
FAILURE TO REMOVE OR MAINTAIN THE AREA
FREE OF COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE LIQUIDS OR VAPORS CAN RESULT IN SEVERE PERSONAL INJURY, DEATH OR SUBSTANTIAL PROPERTY DAMAGE.
NOTICE
The Esteem 399 Low NOx boiler gas manifold and gas controls meet the safe lighting and other performance re­quirements as specifi ed in ANSI Z21.13 latest edition.
4
Ensure the Esteem 399 Low NOx and its con­trols are protected from dripping or spraying water during normal operation or service.
The Esteem 399 Low NOx should be installed in a location so that any water leaking from the boiler or piping connections or relief valve will not cause damage to the area surrounding the unit or any lower floors in the structure.
GF-125
Boiler Replacement
If the Esteem 399 Low NOx is replacing an existing boiler, the following items should be checked and corrected prior to installation:
• Boiler piping leaks and corrosion.
• Improper location and sizing of the expansion tank on the boiler heating loop.
• If applicable, level and quality of freeze protection within the boiler system.
See Warning on ”Handling Previously Fired Combustion Chamber Insulation” on page 67
Recommended Clearances
Boiler Replacement
The Esteem 399 Low NOx is approved for zero clearance to combustibles, excluding vent and boiler piping.
• Boiler Piping - 1/4 inch from combustible materials.
• See Concentric Vent System Installation Supplement GF-125V for vent clearance requirements.
To provide service access to the unit it is rec­ommended that the following clearances be maintained:
Top jacket 24 inches [610 mm]. Front 24 inches [610 mm]. Rear 0 inches Sides 6 inches [153 mm] Bottom piping 24 inches [610 mm].
WARNING
IF THE CLEARANCES LISTED ABOVE CANNOT BE
MAINTAINED OR THE ENCLOSURE IN WHICH THE BOILER IS INSTALLED IS LESS THAN 85 CUBIC FEET, THE SPACE MUST BE VENTILATED. SEEP- AGE 8 FOR REQUIREMENTS.
GF-125
5
NOTICE
CAUTION
When maintaining zero clearance or less than recommended clearances, some product labeling may become hidden and unreadable.
WARNING
WHEN INSTALLING THE ESTEEM 399 LOW NOX
IN A CONFINED SPACE, SUFFICIENT AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTING AND TO ALLOW, UNDER NORMAL OPER- ATING CONDITIONS, PROPER AIR FLOW AROUND THE PRODUCT TO MAINTAIN AMBIENT TEMPERA- TURES WITHIN SAFE LIMITS TO COMPLY WITH THE NATIONAL FUEL GAS CODE NFPA 54 - LATEST EDITION.
Residential Garage Installations
When installing the Esteem 399 Low NOx in a residential garage, the following special precautions per NFPA 54/ANSI Z223.1 must be taken:
The boiler freeze protection feature is disabled during a hard lockout, how­ever the space heating circulator will operate.
CAUTION
The boiler freeze protection feature is designed to protect the boiler. The boiler should be installed in a primary/ secondary piping arrangement if it is installed in an unheated space or ex­posed to water temperatures of 46ºF or less. See “Chapter 5 Boiler Piping” on page 16 for primary/secondary piping ex­amples. See Chapter 10 for antifreeze guides.
• Mount the unit a minimum 18 inches [458 mm] above the floor level of the garage. Ensure the burner and ignition devices / controls are no less than 18 inches [458 mm] above the floor level.
• Locate or protect the unit in a manner so it cannot be damaged by a moving vehicle.
Boiler Freeze Protection Feature
The boiler control has a freeze protection fea­ture built in. This feature monitors the boiler temperature and responds as follows when no call for heat is present:
• 46ºF Boiler circulator is ON
• 38ºF Boiler circulator is ON and burner operates at low fire
• 50ºF Burner OFF and boiler circulator operates for approximately 10 minutes
66
GF-125 GF-125
Chapter 3 Combustion Air and Venting
Combustion Air Contamination
WARNING
IF THE ESTEEM 399 LOW NOX COMBUSTION
AIR INLET IS LOCATED IN ANY AREA LIKELY TO CAUSE OR CONTAIN CONTAMINATION, OR IF PRODUCTS, WHICH WOULD CONTAMINATE THE AIR CANNOT BE REMOVED, THE COMBUSTION AIR MUST BE RE-PIPED AND TERMINATED TO ANOTHER LOCATION. CONTAMINATED COMBUS- TION AIR WILL DAMAGE THE UNIT AND ITS BURN- ER SYSTEM, RESULTING IN POSSIBLE SEVERE PERSONAL INJURY, DEATH OR SUBSTANTIAL PROPERTY DAMAGE.
WARNING
DO NOT OPERATE AN ESTEEM 399 LOW NOX
IF ITS COMBUSTION AIR INLET IS LOCATED NEAR A LAUNDRY ROOM OR POOL FACILITY. THESE AREAS WILL ALWAYS CONTAIN HAZARDOUS CONTAMINANTS.
Pool and laundry products and common house­hold and hobby products often contain fluorine or chlorine compounds. When these chemi­cals pass through the burner and vent system, they can form strong acids. These acids can create corrosion of the heat exchanger, burner components and vent system, causing serious damage and presenting a possible threat of flue gas spillage or water leakage into the sur­rounding area.
Please read the information listed below. If contaminating chemicals are located near the area of the combustion air inlet, the installer should pipe the combustion air inlet to an out­side area free of these chemicals per Chapter 5 of this installation manual.
Potential contaminating products
• Spray cans containing chloro/fl uorocar- bons
• Permanent Wave Solutions
• Chlorinated wax
• Chlorine - based swimming pool chemicals / cleaners
• Calcium Chloride for melting ice
• Sodium Chloride for water softening
• Refrigerant leaks
• Paint or varnish removers
• Hydrochloric acid / muriatic acid
• Cements and glues
• Antistatic fabric softeners used in clothes dryers
• Chlorine-type bleaches, detergents, and cleaning solvents
• Adhesives and other similar products
Areas likely to have contaminants
• Dry cleaning / laundry areas and establish­ments
• Beauty salons
• Metal fabrication shops
• Swimming pools and health spas
• Refrigeration Repair shops
• Photo processing plants
• Auto body shops
• Plastic manufacturing plants
• Furniture refi nishing areas and establish- ments
• New building construction
• Remodeling areas
• Garages with workshops
The above lists are NOT comprehensive. Installer, The end user and service personnel are responsible for certifying the safety of any and all materials that may affect the quality of
the combustion air.
GF-125
7
Ventilation and Combustion Air Requirements - Direct Vent
Ventilation and Combustion Air Requirements - Direct Vent
A Direct Vent appliance uses uncontaminated outdoor air (piped directly to the appliance) for combustion.
For Direct Vent installations, involving only the Esteem 399 Low NOx , in which the minimum service clearances are maintained as listed on page 5, no ventilation openings are required.
For Direct Vent, zero clearance installations involving only the Esteem 399 Low NOx , the space / enclosure must have two openings for ventilation. The openings must be sized to
provide 1 square inch of free area per 1,000 BTUH of boiler input. The openings must be
placed 12 inches from the top of the space and 12 inches from the floor of the space.
For installations where the Esteem 399 Low NOx shares the space with air movers (exhaust fan, clothes dryers, fireplaces, etc.) and other combustion equipment (gas or oil) the space must be provided with adequate air openings to provide ventilation and combustion air to all the equipment. Sizing of the ventilation / combustion air openings must comply with the National Fuel Gas Code NFPA 54, ANSI Z223.1 for installations in the U.S. or CSA B149.1 and B149.2 for installations in Canada.
INGS IS NOT REQUIRED. FAILURE TO PROVIDE PROPERLY SIZED OPENINGS COULD RESULT IN SEVERE PERSONAL INJURY, DEATH OR PROP- ERTY DAMAGE.
Ventilation and Combustion Air Requirements - Category IV
A Category IV appliance uses uncontaminated indoor or outdoor air (surrounding the appli­ance) for combustion.
Piping uncontaminated combustion air directly from the outdoors to the appliance is recom­mended. This reduces the risks associated with indoor contaminates, flammable vapors and tight housing construction. This practice also promotes higher system efficiency.
For installations in which the Esteem 399 Low NOx shares the space with air movers (exhaust fan, clothes dryers, fireplaces, etc.) and other combustion equipment (gas or oil) the space must be provided with adequate air openings to provide ventilation and combustion air to all the equipment. Sizing of the ventilation / combustion air openings must comply with the National Fuel Gas Code NFPA 54, ANSI Z223.1 for installations in the U.S. or CSA B149.1 and B149.2 for installations in Canada, as referenced in this chapter of the manual and titled Methods of Supplying Combustion Air to a Space.
WARNING
THE SPACE MUST BE PROVIDED WITH VENTILA-
TION / COMBUSTION AIR OPENINGS PROPERLY SIZED FOR ALL MAKE-UP AIR REQUIREMENTS
EXHAUST FANS, CLOTHES DRYERS, ETC.) AND
(
THE TOTAL INPUT OF ALL APPLIANCES LOCATED IN THE SAME SPACE AS THE ESTEEM 399 LOW
X , EXCLUDING THE INPUT OF A DIRECT
NO
ENT ESTEEM 399 LOW NOX WHICH USES
V
COMBUSTION AIR DIRECTLY FROM THE OUTSIDE, THUS ADDITIONAL FREE AREA FOR THE OPEN-
8
WARNING
THE SPACE MUST BE PROVIDED WITH VENTILA-
TION / COMBUSTION AIR OPENINGS PROPERLY SIZED FOR ALL MAKE-UP AIR REQUIREMENTS
EXHAUST FANS, CLOTHES DRYERS, ETC.) AND
(
THE TOTAL INPUT OF ALL APPLIANCES, INCLUD- ING THE ESTEEM 399 LOW NOX WHEN LOCAT- ED IN THE SAME SPACE. FAILURE TO PROVIDE PROPERLY SIZED OPENINGS COULD RESULT IN SEVERE PERSONAL INJURY, DEATH OR PROP- ERTY DAMAGE.
GF-125
Ventilation and Combustion Air Requirements - Category IV
Methods of Supplying Combustion Air to a Confined Space - Category IV
INDOOR COMBUSTION AIR
NOTICE
The methods listed in this section for ac­cessing Indoor Combustion Air assume that the infi ltration rate is adequate and not less than .40 ACH. For infi ltration rates less than .40 ACH, reference the NFPA 54 National Fuel Gas Code for additional guidance.
Opening Size and Location
Openings used to connect indoor spaces shall be sized and located in accordance with the following see Figure 2
• Combining spaces on the same story.
one opening shall commence within 12 inches of the bottom of the enclosure. The minimum dimension of air openings shall be not less than 3 inches.
• Combining spaces in different stories. The volumes of spaces in different sto­ries shall be considered as communi­cating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 sq. in./1000 Btu/hr of total input rating of all gas utilization equip­ment.
OUTDOOR COMBUSTION AIR
Isolating the combustion appliance room from the rest of the building and bringing in uncon­taminated outside air for combustion and venti­lation is always preferred.
Opening Size and Location
Figure 2: : All Combustion Air from Adjacent Indoor Spaces Through Indoor Combustion Openings
Each opening shall have a minimum free area of 1 sq. in./1000 Btu/hr of the total input rating of all gas utilization equip­ment in the space, but not less than 100 sq. inches. One opening shall com­mence within 12 inches of the top, and
The minimum dimension of air openings shall be not less than 3 inches
Openings used to supply combustion and ventilation air shall be sized and located in accordance with the following:
One Permanent Opening Method. See Figure 3
One permanent opening, commencing within 12 inches of the top of the enclosure, shall be provided. The equipment shall have clearances of at least 1 inch from the sides and 6 inches from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or hori­zontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
GF-125
9
Ventilation and Combustion Air Requirements - Category IV
Figure 3: : All Combustion Air from Outdoors Through One Permanent Air Opening
• 1 sq. in./3000 Btu/hr of the total input rating of all equipment located in the enclosures, and
• Not less than the sum of the areas of all vent connectors in the space.
Two Permanent Openings Method.
Two permanent openings, one commencing within 12 inches of the top and one commenc­ing within 12 inches of the bottom of the enclo­sure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as follows:
• Where directly communicating with the outdoors or where communication to the outdoors is through vertical ducts, each opening shall have a minimum free area of 1 sq. in./4000 Btu/hr of total input rating for all equipment in the enclosure. See Figure 4.
Figure 4: : All Combustion Air from Outdoors Through Ventilated Attic
• Where communicating with the outdoors is through horizontal ducts, each opening shall have a minimum free area of not less than 1 sq. in./2000 Btu/hr of total input rat­ing of all equipment in the enclosure. See
Figure 5.
Figure 5: : All Combustion Air from Outdoors through Horizontal Ducts
10
GF-125
Combustion Air and Vent Piping
COMBINATION OF INDOOR AND OUTDOOR
OMBUSTION AIR
C
Indoor Openings: Where used, openings con­necting the interior spaces shall comply with the Indoor Combustion Air section on page 9.
Outdoor Opening(s) Location. Outdoor opening(s) shall be located in accordance with the Outdoor Combustion Air section.
Outdoor Opening(s) Size. Outdoor opening(s) shall be calculated in accordance with the following:
• The ratio of the interior spaces shall be the available volume of all communicating spaces divided by the required volume.
• The outdoor size reduction factor shall be 1 minus the ratio of interior spaces.
• The minimum size of outdoor opening(s) calculated in accordance with the above outdoor air section multiplied by the reduc­tion factor. The minimum dimension of air openings shall not be less than 3 in.
The Esteem 399 Low NOx is certified per ANSI Z21.13 as a Category IV or Direct Vent (sealed combustion) appliance. A Category IV appliance utilizes uncontaminated indoor or outdoor air (surrounding the appliance) for combustion. A Direct Vent appliance utilizes uncontaminated outdoor air (piped directly to the appliance) for combustion.
Piping uncontaminated combustion air directly from the outdoors to the appliance is recom­mended. This reduces the risks associated with indoor contaminates, flammable vapors and tight housing construction. This practice also promotes higher system efficiency.
NOTICE
Install combustion air and vent pipe as detailed in the Esteem 399 Low NOx Vent Supplement included in the boiler installation envelope. Refer to optional vent kit instructions for addition vent in­stallation instructions.
DANGER!
DO NOT INSTALL THE ESTEEM 399 LOW NOX
INTO A COMMON VENT WITH OTHER GAS OR OIL APPLIANCES. THIS MAY CAUSE FLUE GAS SPILL- AGE OR APPLIANCE MALFUNCTION, RESULTING IN POSSIBLE SEVERE PERSONAL INJURY, DEATH OR SUBSTANTIAL PROPERTY DAMAGE.
Combustion Air and Vent Piping
DANGER!
COMBUSTION AIR AND VENT PIPING MUST BE
SEALED GAS TIGHT AND MEET ALL PROVIDED IN- STRUCTIONS AND APPLICABLE CODES, FAILURE TO COMPLY WILL RESULT IN SEVERE PERSONAL INJURY OR DEATH.
The Esteem 399 Low NOx requires a Category IV venting system, which is designed for pres­surized venting and condensate.
Removal of an Existing Boiler from a Common Vent System
DANGER!
DO NOT INSTALL THE ESTEEM 399 LOW NOX
INTO A COMMON VENT WITH OTHER GAS OR OIL APPLIANCES. THIS MAY CAUSE FLUE GAS SPILL- AGE OR APPLIANCE MALFUNCTION, RESULTING IN POSSIBLE SEVERE PERSONAL INJURY, DEATH OR SUBSTANTIAL PROPERTY DAMAGE.
NOTICE
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the re­maining appliances.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the com-
GF-125
11
Removal of an Existing Boiler from a Common Vent System
mon venting system placed in operation, while the other appliances remaining connected to the common venting system are not in opera­tion.
• Seal any unused openings in the common venting system.
• Visually inspect the venting system for proper size and horizontal pitch and de­termine there is no blockage or restriction, leakage, corrosion and other defi ciencies which could cause an unsafe condition.
• Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remain­ing connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the com­mon venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fi replace dampers.
• Operate the appliance being inspect­ed. Follow the lighting instructions. Adjust thermostat so appliance will operate con­tinuously.
• Test for spillage at the draft hood relief opening after 5 minutes of main burner op­eration. Use the fl ame of a match or candle, or smoke from a cigarette, cigar or pipe.
• After it has been determined that each ap­pliance remaining connected to the com­mon venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fi replace dampers, and any other gas-burning appliance to their previous condition of use.
• Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation codes. When re-sizing any portion of the common vent­ing system, the common venting system should be re-sized to approach the appro­priate tables in Part II of the National Fuel Gas Code ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation codes.
12
GF-125
Commonwealth of Massachusetts Installations Only
For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the vent ter­minal and the air intake is installed below four feet above grade the following requirements must be satisfied:
• 1. If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detec­tor and alarm shall be placed in the liv­ing area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
• 2. A carbon monoxide detector shall also be located in the room that houses the appliance or equipment and shall:
a. Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services both the appliance and the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and
d. Have been approved and listed by the Nationally Recognized Testing Laboratory as recognized under 527 CMR.
• 3. A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in strict com­pliance with the manufacturer’s instruc­tions. A copy of the installation instruc­tions shall remain with the appliance or equipment at the completion of the installation.
location of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
NOTICE
Installer must provide tag identifi cation plate and ensure the lettering meets code requirements.
For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the vent termi­nal and the air intake are installed above four feet above grade the following requirements must be satisfied:
• 1. If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detec­tor and alarm shall be placed in the liv­ing area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
• 2. A carbon monoxide detector shall:
a. Be located in the room that houses the appliances or equip­ment;
b. Be either hard wired or bat­tery powered or both; and
c. Shall comply with NFPA 720 (2005 Edition)
• 3. A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in strict com­pliance with the manufacturer’s instruc­tions. A copy of the installation instruc­tions shall remain with the appliance or equipment at the completion of the installation.
• 4. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the
GF-125
13
Chapter 4 Unit Preparations
Handling Instructions
The Esteem 399 Low NOx is generally easier to handle and maneuver once removed from the shipping carton.
To remove the shipping carton:
CAUTION
Use care not to lift the unit from, or place the unit on the front plastic con­trol panel, damage can occur. Use care not to drop, bump or rotate the boiler upside down, as damage to the boiler will result.
1. Remove any shipping straps and open the side of the shipping carton.
2. Slide the unit with the foam inserts out of the carton.
3. Discard all packing materials.
Wall Mounting Installation
The Esteem 399 Low NOx should be wall mounted using the bracket provided with the boiler. The Esteem 399 Low NOx is not designed for floor installation. If floor installa­tion is required an optional floor stand is avail­able through AERCO International.
WARNING
THE WALL USED FOR MOUNTING THE ESTEEM 399 L
AND CAPABLE OF SUPPORTING A MINIMUM 250 POUNDS [115 KG] FOR ESTEEM 399 LOW NOX
. F
MENTS COULD RESULT IN PERSONAL INJURY, DEATH OR SUBSTANTIAL PROPERTY DAMAGE.
Wall Mounting Guidelines
• The boiler is heavy and bulky. A minimum
• DO NOT mount or attempt to mount the
OW NOX MUST BE VERTICALLY PLUMBED
AILURE TO COMPLY WITH THESE REQUIRE-
of 2 people is required for mounting the boiler.
wall bracket to hollow sheet rock or lath
walls using anchors. Only install boiler to studs or equivalent wood structure.
• The wall-mounting bracket is designed for stud spacing of 12 inch or 16 inch on centers. For unconventional stud spacing, a solid / secure mounting surface must be provided for installation of the bracket.
• For mounting on wood studs, install the bracket using the lag screws provided with the boiler. Ensure both lag screws are installed securely in the studs.
• For mounting on metal studs, install the bracket to the studs using 3/16” toggle bolts and washers.
• For mounting on solid walls (rock, concrete, brick, cinder block, etc.), install the wall bracket using anchors (double expansion shields) and bolts with washers provided with the boiler.
WARNING
USE EXTREME CARE NOT TO DROP THE BOILER
OR CAUSE BODILY INJURY WHILE LIFTING OR MOUNTING THE BOILER ONTO THE BRACKET.
NCE MOUNTED VERIFY THAT THE BOILER IS
O
SECURELY ATTACHED TO THE BRACKET AND WALL. FAILURE TO COMPLY WITH THE ABOVE GUIDELINES COULD RESULT IN PROPERTY DAM- AGE, PERSONAL INJURY OR DEATH.
Stud Wall Installation
• To distribute the weight of the boiler evenly when mounting onto a stud wall it is rec­ommended to use the Esteem 399 Low NOx Wall Frame kit.
• When using the wall frame to mount the boiler reference the kit installation instruc­tions and ensure the frame is securely fastened to the wall.
• If the structure of wall is questionable, in supporting a minimum weight of 250 pounds [115 kg.], it is recommended to use the optional fl oor stand.
Wall Bracket Installation - Solid Walls
14
GF-125
Boiler Mounting
• Locate the general area of the boiler place­ment.
• Place the wall-mounting bracket on the wall ensuring the upper edge of the brack­et is away from the wall.
• Level the bracket and use a pencil to mark the location of the mounting slots on the wall.
• Remove the bracket from the wall and drill a 5/8” diameter hole by 1-3/8” deep posi­tioned in the center of each mark.
• Install the anchors (provided) fl ush or slightly recessed in the drilled holes with threaded side facing down.
• Reposition the bracket on the wall and align mounting slots/holes. Insert the two bolts (provided) through the mounting slots/holes and loosely tighten.
• Level bracket and tighten bolts securely.
Boiler Mounting
• Obtain assistance in lifting the boiler onto the wall bracket.
• Install the boiler making sure the boiler mounting lip located along the upper edge of the rear jacket panel engages the wall­mounting bracket. Ensure the boiler is
seated properly and is secure.
GF-125
15
Chapter 5 Boiler Piping
General Piping Requirements
• All plumbing must meet or exceed all local, state and national plumbing codes.
• Support all piping using hangers. DO NOT support piping by the unit or its compo­nents.
• Use isolation valves to isolate system com­ponents.
• Install unions for easy removal of the Esteem 399 Low NOx from the system piping.
WARNING!
USE A TWO WRENCH METHOD WHEN TIGHTEN-
ING PIPING ONTO THE BOILER CONNECTIONS.
SE ONE WRENCH TO PREVENT THE BOILER
U
PIPING FROM TURNING / TWISTING. FAILURE TO SUPPORT THE BOILER PIPING AND CONNEC- TIONS IN THIS MANNER COULD CAUSE DAMAGE TO THE BOILER AND ITS COMPONENTS.
Pressure Relief Valve
• Length should be as short and direct as possible. The size of the discharge line should not be reduced, maintain the same size as the outlet of the relief valve.
Should be directed downward towards the floor at all times. The piping should termi­nate at least 6 inches [153 mm] above any drain connection to allow clear visibility of the discharge.
Should terminate with a plain end, not with a threaded end. The material of the piping should have a serviceable temperature rat­ing of 250ºF or greater.
Should not be subject to conditions where freezing could occur.
• Should not contain any shut-off valves or obstructions. No shut-off valve should be piped between the boiler and relief valve.
WARNING!
FAILURE TO COMPLY WITH THE GUIDELINES ON
INSTALLING THE PRESSURE RELIEF VALVE AND DISCHARGE PIPING CAN RESULT IN PERSONAL INJURY, DEATH OR SUBSTANTIAL PROPERTY DAMAGE.
The Esteem 399 Low NOx is supplied with a 30 psi pressure relief valve and must be piped using the PRV connection as shown in Figure 6, page 17.
To avoid potential water damage to the sur­rounding area or potential scalding hazard due to the operation of the relief valve, the discharge piping:
Must be connected to the discharge outlet of the relief valve and directed to a safe place of disposal.
Low Water Cutoff Device
• The Esteem 399 Low NOx is equipped with a factory installed pressure switch type Low Water Cut Off device.
• The minimum operating system pressure allowable with this device is 10 psig.
• Check local codes if a Low Water Cutoff Device is required. If so, determine if this device meets the requirements of the local codes.
WARNING!
THE ESTEEM 399 LOW NOX CONTROL SYSTEM
SENSES THE SYSTEM WATER TEMPERATURES ENTERING AND EXITING THE HEAT EXCHANGER TO PROVIDE PROTECTION AGAINST LOW WATER CONDITIONS WHERE LOCAL CODES AND JURIS- DICTION DO NOT ACCEPT A PRESSURE DEVICE FOR LOW WATER PROTECTION, THEY MAY AC- CEPT THESE INTEGRAL CONTROL FUNCTIONS AS A MEANS OF PROVIDING LOW WATER PROTEC- TION.
16
GF-125
Additional Limit Control
Additional Limit Control
If a separate LWCO device is required by certain local jurisdictions or when the boiler is installed above the system piping, the follow­ing guidelines must be followed:
• The LWCO device must be designed for water installations, electrode probe-type is recommended.
• The LWCO device must be installed in a tee connection on the boiler supply pip­ing above the boiler.
• Wiring of the LWCO device to the Esteem 399 Low NOx is done directly onto the 24V terminal strip, see Figure 20, page 34 for available terminals for an external limit (manual or auto reset).
If the installation is to comply with ASME or Canadian requirements, an additional high temperature limit may be needed. Consult local code requirements to determine compli-
ance. The limit should be installed as follows:
• Install the limit in the boiler supply pip­ing between the boiler and any isolation valve.
• Maximum set point for the limit is 194ºF.
• For wiring of the limit, see Figure 20, page 34, using the external limit/manual reset terminals on the 24V terminal strip. This will provide a “hard” lockout requir­ing a manual reset of the control.
Backfl ow Preventer
• Use a backflow preventer valve in the make-up water supply to the unit as required by local codes.
Boiler System Piping Applications
All piping applications should use a primary/ secondary piping arrangement as a means to provide freeze protection of the boiler, which is an integral function of the boiler control. Maintain the minimum boiler flow rate, see
Figure 6: Pressure Relief Valve and Boiler Drain Installation
GF-125
17
Expansion Tank and Makeup Water
Graph 2 and Graph 3 on page 91 For other piping arrangements, consult the Engineering Department at AERCO International.
On piping applications using a single zone or other recognized piping design arrangements, it is recommended that the installer uses flow/ check valves with weighted seats at or near the appliance to prevent gravity circulation.
Expansion Tank and Makeup Water
Ensure the expansion tank is properly sized for the boiler volume 7 gallons [26 L] for Esteem 399 Low NOx and the system volume and temperature.
CAUTION
Undersized expansion tanks will cause system water to be lost through the pressure relief valve and cause addi­tional makeup water to be added to the system. Eventual boiler heat exchanger failure can result due to this excessive makeup water addition.
The expansion tank must be located as shown in Figure 7 and Figure 8 on page 21 when using a primary/secondary piping arrangement or as per recognized design methods. Refer to the expansion tank manufacturer instructions for additional installation details.
Connect the expansion tank to an air separa­tor only if the air separator is located on the suction side (inlet) of the system circulator. Always locate and install the system fill con­nection at the same location as the expansion tank connection to the system.
DIAPHRAGM EXPANSION TANK
Always install an automatic air vent on the top of the air separator to remove residual air from the system.
CLOSED-TYPE EXPANSION TANK
It is recommended to pitch any horizontal pip­ing upwards toward the expansion tank 1 inch per 5 feet of piping. Use 3/4” piping for the expansion tank to allow air within the system to rise.
CAUTION
DO NOT install automatic air vents on a closed-type expansion tank system. Air must remain in the system and be returned to the expansion tank to pro­vide an air cushion. An automatic air vent would cause air to be vented from the system resulting in a water-logged expansion tank.
Circulator
The Esteem 399 Low NOx must be supplied with a Central Heating (CH) circulator. The circulator when wired directly to the Esteem 399 Low NOx will allow for domestic hot water priority and to provide circulation for the freeze protection feature of the boiler control. See Graph 2 and Graph 3 on page 91 for pressure drop and minimum flow rate through the boiler.
Sizing Primary Piping
See Figure 9 through Figure 15, page 22 and following, for recommended piping arrange­ments based on various applications. Size the piping and system components required in the space heating system, using recognized design methods.
18
GF-125
Domestic Hot Water System Piping
Domestic Hot Water System Piping
See Figure 9, page 22 for recommended piping to a DHW system. This recommended piping configuration ensures priority is given to the production and recovery of the DHW.
The piping for the DHW is separate from the boiler system piping and does not require a primary / secondary piping configuration.
To wire the DHW circulator to the boiler control module, see Chapter 9 External Wiring.
System Piping - Zone Circulators
Connect the Esteem 399 Low NOx to the sys­tem piping as shown in Figure 10 page 23 when zoning with zone circulators.
The installer must provide a separate circula­tor for each zone of space heating as well as the boiler circulator.
System Piping - Through Boiler
In new or retrofit applications in which primary/ secondary arrangement is not used, the Esteem 399 Low NOx allows this flexibility due to a lower boiler pressure drop, see Graph 2 and Graph 3 on page 91.
Figure 12, page 24 illustrates a multiple zone valve system with a single system/boiler circu­lator. A by-pass loop with a pressure differential valve must be installed on the system piping.
Figure 13, page 24 illustrates a single zone utilizing the boiler circulator as the system circulator.
System Piping - Radiant Heating
The heat exchanger design of the Esteem 399 Low NOx allows operation in a condens­ing mode. This feature requires no return water temperature regulation in radiant heat­ing applications.
NOTICE
To ensure an adequate fl ow rate through the Esteem 399 Low NOx , the boiler supply and return piping size must be a minimum 1-1/2 inch for the Esteem 399 Low NOx .
System Piping - Zone Valves
Connect the Esteem 399 Low NOx to the system piping as shown in Figure 11, page 23 when zon­ing with zone valves. The primary / secondary piping ensures that the boiler loop has sufficient flow.
NOTICE
To ensure an adequate fl ow rate through the Esteem 399 Low NOx , the boiler supply and return piping size must be a minimum of 1-1/2 inch for the Esteem 399 Low NOx .
Esteem 399 Low NOx can maintained the boil­er water supply temperature, eliminating the need for a mix system to achieve the desired temperature.
A high temperature limit as shown in Figure 14, page 25 should be installed to ensure that the primary supply temperature does not exceed the maximum allowable temperature for the radiant tubing.
The addition of the high temperature limit is important if the Esteem 399 Low NOx is con­nected to a domestic hot water system, which requires a high primary supply water tempera­ture.
Size the system piping and circulator to provide the flow needed for the radiant system.
NOTICE
GF-125
The Esteem 399 Low NOx supply and return piping must be a minimum of 1-1/2 inch .
19
System Piping - Special Application
System Piping - Special Application
If the boiler is used in conjunction with a chilled water/medium system, the boiler and chiller must be piped in parallel. Install flow/ check valves to prevent the chilled medium from entering into the boiler.
If the boiler is used to supply hot water to the heating coils of an air handler where they may be exposed to chilled air circulation, install flow/check valves or other automatic means to prevent gravity circulation of the boiler water during cooling cycles.
System Piping - Multiple Units Installation
Use a balanced manifold system as the pri­mary / secondary connection to the space heating piping as shown in Figure 15 page 26.
Maintain a minimum of 6 inches [153 mm] of clearance between units to allow for servicing.
Refer to Figure 7 and Figure 8, page 21 to install air separator and expansion tank.
For the space heating piping refer to the appli­cations mentioned in this manual or use recog­nized design methods..
20
GF-125
Figure 7: Near Boiler Piping - Diaphragm Expansion Tank
System Piping - Special Application
Figure 8: Near Boiler Piping - Closed Type Expansion Tank
1. System circulator
2. Automatic air vent
3. Air separator
4. Automatic fill valve
5. Diaphragm expansion tank
6. Isolation valve
GF-125
Note: Pitch horizontal piping upwards (1” of pitch per 5 ft of piping) towards expansion tank.
7. Drain/purge valve
8. Tank fitting
9. Closed type expansion tank
10. Primary/secondary connection
11. Boiler circulator
12. Flow/check valve
21
System Piping - Special Application
Figure 9: DHW Boiler Piping with an Esteem 399 Low NOx
1. Esteem 399 Low NOx boiler
2. water heater
3. Isolation valve
4. DHW circulator
5. CH circulator
NOTICE
The boiler system piping shown in Figure 8 must be a “closed” system to avoid any oxygen contamination and potential failure of the outer tank of the water heater.
6. Flow/check valve
7. Pressure relief valve
8. Drain/purge valve
22
GF-125
Figure 10: CH System Piping - Zoning with
Zone Circulators
System Piping - Special Application
1. Esteem 399 Low NOx boiler
2. CH circulator
3. Flow/check valve 4 Isolation valve
5. Zone circulator
6. Drain/purge valve
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
Figure 11: CH System Piping - Zoning with Zone
Valves
1. Esteem 399 Low NOx boiler
2. CH circulator
3. Flow/check valve 4 Isolation valve
5. Zone valve
6. Drain/purge valve
GF-125
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
12. System circulator
23
System Piping - Special Application
Figure 12: CH System Piping - Multiple Zone Valve with Single System/Boiler Circulator
Note: Verify CH circu­lator is properly sized to overcome the sys­tem pressure drop and provide adequate flow through the boiler sys­tem.
1. Esteem 399 Low NOx boiler
2. CH circulator
4. Isolation valve
5. Zone valve
6. Drain/purge valve
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
12. Pressure Differential Valve
Note: Verify CH circu­lator is properly sized to overcome the sys­tem pressure drop and provide adequate flow through the boiler sys­tem.
Figure 13: CH System Piping - Single Zone System with Single System/Boiler Circulator
1. Esteem 399 Low NOx boiler
2. CH circulator
3. Flow/check valve 4 Isolation valve
5. Zone valve
6. Drain/purge valve
7. Pressure relief valve
8. Air separator
9. Automatic air vent
10. Diaphragm expansion tank
11. Automatic fill valve
24
GF-125
Loading...
+ 68 hidden pages