06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 1 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
Technical Support:
1-800-526-0288
www.aerco.com
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
(Mon–Fri, 8am-5pm EST)
Disclaimer
The information containe d in this manual is subject to c hange without notice from AERCO International,
Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to
implied warranties of merchantability and fitness f or a particular application. A ERCO International is not
liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in
connection with the furnishing, performance, or use of this material.
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 2 of 112
GF-115-C
OMM-0084_0D
Table of Contents
Table of Contents .......................................................................................... 3
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 5 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
(This page left intentionally blank)
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 6 of 112
GF-115-C
OMM-0084_0D
1.INTRODUCTION
The information in this manual provides a guide to the operation of the Modulex Boiler using
the E8 Controller and the Boiler Communications Module (BCM) mounted on the front of the
unit. Sections 3, 4, 5, 6, and 8 provide descriptions and procedures for the E8 Controller.
Sections 7, 9, and 10 provide similar inf ormation for the BCM.
It is imperative that the initial startup procedures be performed by factory trained personnel.
Operation by untrained personnel, prior to the initial startup, will void the equipment warranty.
In addition, CAUTIONS and WARNINGS in this manual must be observed at all times.
1.1 Safety and Warnings
The following defined symbols are used throughout this manual to notif y the reader of potential
hazards of varying risk levels.
Indicates an imminently hazardous situation, which if not avoided,
!
DANGER
!
WILL result in death or serious injury.
Indicates a potentially hazardous situation, which if not avoided,
!
WARNING
!
DANGER
Note that all hazard notifications and notes are presented enclosed in a rectangle with filleted
(round) corners, as shown below, in order to differentiate them from the main text.
It is of utmost importance to observe all CAUTIONS and WARNINGS presented in this manual to avoid injury, death, and
damage to the equipment. Failure to properly heed safety
warnings and cautions may result in the voiding of applicable
warranties.
!
MAY result in death or serious injury.
Indicates a potential hazardous situation, which if not avoided,
COULD result in minor or moderate injury. Also may caution
!
against unsafe practices.
!
CAUTION
!
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 7 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
(This page left intentionally blank)
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 8 of 112
GF-115-C
OMM-0084_0D
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
Rotary Knob
LCD Display
Hinged Cover
2. E8 CONTROLLER AND BCM DESCRIPTION
Modulex boilers contain advanced and reliable electronic controls, which includes the E8
Controller and the BCM (Boiler Communications Module), providing comprehensive
programming and monitoring of the Modulex boiler and its functions. Features and functions of
the E8 Controller are described in the following sections.
2.1 E8 Controller Featur e s And Functions
A standard component included in Modulex units, the E8 Controller is responsible for the
staging and modulation of individual thermal heating modules in a Modulex boiler and also
monitors supply and return water temperatures and domestic hot water zones.
The E8 Controller is housed in a compact enclosure measuring 5.7” (145 mm) x 3.9” (100 mm).
The Controller is mounted on the front of the Modulex Boiler and contains all of the controls,
indicators and displays necessary to adjust, operate and troubleshoot the Modulex Boiler. T he
E8 features the following functions for Modulex boilers:
• Shares the heating load among as many of the boiler's thermal heating modules as
possible. maximizing the overall operating efficiency of the boiler.
• Provides access t o all testing/programming parameters of each individual heating module:
operation test, operation time, boiler freeze protection and pump's anti seize program.
• Drives lead-lag burner operation based on operating hours. The boiler module with the least
burner operating hours is the first to start and the burner with the most operating hours is the
first to stop.
• Supports DHW (Domestic Hot Water) production using a dedicated sensor to control a
dedicated pump or 3-way diverting valve for storage tank temperature control.
• Supports a manual operation service mode to control individual modules during
troubleshooting or combustion calibration procedures.
• Drives diagnostics such as relay and senor testing.
• Supports Modbus integration with AERCO BMS
Building Automation Systems. AERCO also offers a Communication Gateway to support
BACnet, Lonworks and N2 system integration.
II and AERCO Control System (ACS) or
Window
(in closed
position)
Figure 2-1: Modulex E8 Controller Front Panel
PR1: 02/23/12 Page 9 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
2.2 BCM Features And Functions
The BCM (Boiler Communications Module) is an electronic module in Modulex boilers (one per
burner), which supports full interoperability to BAS (Building Automation Systems) via Modbus
protocol to make remote communications and control possible. In addition, it provides
customers with a remote alarm contact to notify customers of faults detected within any of
boiler's multiple thermal modules. Finally, in the event the boiler's master controller stops
working, the BCM also takes over operations of the boiler.
As a back-up controller, the BCM further increases the reliability of a product line already known
for its uniquely redundant design. Each Modulex boiler combines between two and seven
independent, 151,500 BTU/hr., pre-assembled thermal modules housed in a common
enclosure. Each module has its own dedicated controller with a com bustion safeguard, variablespeed fan, modulating gas valve, electronic ignition, modulating burner, flow temperature
sensor, thermostat and heat exchanger. The independent operation of these thermal modules
increases each boiler's overall reliability. If a single module requires maintenance or repair, the
other module(s) in the boiler can maintain the system load requirements -- thereby providing a
level of redundancy that was previously only realized in multi-boiler installations.
A photo of the module is shown in Figure 2-2 below. Additional information for the BCM
component can be found in Section 7, 9, and 10.
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 10 of 112
GF-115-C
OMM-0084_0D
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
Heating Mode display symbol. The display symbols apply to all internal heating
circuits for which a separate heating mode has been selected. Note that each
H B E D I G F C A
3. E8 CONTROLLER OPERATION
The E8 Controller operates in NORMAL Mode when the controller door is closed, which allows
for monitoring the boiler status through the display window and setting the HEATING Mode.
When the door is opened, the unit enters MENU Mode, and in this mode the boiler may be
initialized, configured, and adjusted. The controls and display for the E8 controller are described
in the following sub-sections.
3.1 NORMAL Mode Operation ( Door Clos e d)
When the hinged door is closed on the E8, the unit is in NORMAL Mode.
3.1.1 NORMAL Mode Display Functions
Figure 3-1 des cribes the types of information provided on the LCD display when in NORMAL
Mode (door closed). Note that the display in the illustration is only an example, and that an E8
Controller in service will show information a ppropri ate for its configuration.
Figure 3-1: E8 LCD Display in NORMAL Mode (Door Closed)
E8 Controller Display in NORMAL Mode
Item Functions
A
Current time (24 hour format)
B
DCF reception OK (only if receiver is connected via eBUS)
Display of the active heating program for the first heating circuit (here: 6:00 to 08:00
C
a.m. and 4:00 to 10:00 p.m.)
Bus icon (if this icon does not appear, check data line to connected CAN controllers
D
=> check eBUS via DISPLAY level)
E
Status display: Shows symbols for Internal Burner 1 Relay ON; Heating Mode; Hot Water Preparation.
F
symbol occupies a different space across the display bottom. See Figure 3-2.
G
Display of current temperature of HS 1 or header temperature when cascading.
H
Display of number of active burners (only applies when cascading).
Selectable display and Error Codes (refer to "DISPLAY SEL" parameter in the USER
I
menu).
PR1: 02/23/12 Page 11 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
E8 Controller HEATING Modes
Turn the Rotary Knob to select the heating mode
heating mode is indicated by a symbol at
is not changed for 5 seconds.
HEATING Mode Symbols:
3.1.2 HEATING Mode Selection (in NORMAL Mode)
Heating modes may be selected using the Rotary Knob on the controller when the hinged door
is in the closed position (NORMAL Mode). As the Rotary Knob is turned, each appropriate
heating mode symbol is displayed, in turn, along the lower edge of the display.
Mode changes take effect when the setting is not changed for 5 seconds. The symbols and
description for the available heating modes are shown in Figure 3-2.
Only currently selected
mode will be displayed.
Figure 3-2: Heating Mode Display Symbols and Description
SYMBOL MODE NAME DESCRIPTION
Heating Mode
Selection
Standby / OFF
Automatic Mode 1
Automatic Mode 2
Summer Mode
Day
Mode
Night
Mode
Service Mode
requir ed. The
the bottom of the display. It takes effect when the setting
(Heat OFF and hot water (HW) preparation OFF, only
frost protection mode)
(Heat a c c or di ng to t im er pr og r a m 1; HW acc or d ing to
HW prog ram)
(Heat a ccordi ng to timer program 2; HW accord ing to
HW prog ram)
(Heating OFF, HW according to HW program)
(24 Hour heating with comfort temperature 1; HW
according to HW program)
(24 Hour heating with reduced temperature; HW
according to program)
(Automatic reset after 15 minutes. Boiler regulated at
max bo iler tem peratur e)
3.1.3 MENU Mode Operation (Door Open)
Opening the E8 controller hinged door reveals the E8 controls (Figure 3-3) and initiates the
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 12 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
Insert narrow screwdriver deep into holes and lift up
When lit, this LED indicates that the value shown in the display can be
D
position (10/2 o’clock) screwdriver adjustable switch.
FLOW (in EXPERT/HEAT
F
E D C B A
G
MENU Mode, which enables access to an extensive set of software menus.
INSTALLATI
ON
Figure 3-3: E8 Controller Controls (cover open in MENU Mode)
E8 Controller Controls and Indicators
ITEM FUNCTION
A
B
C
E
LCD display: Selected Menu/Sub-menus, parameter names/values, and selected
busses are indicated in the LCD display when in MENU Mode.
Mounting Key Access Holes:
controller to remove.
Change LED:
changed using the Rotary Knob (G).
Optical Adaptor: For PC connection
Program Key: Used to select a sub-menu level, select a parameter value to change, or
save a new parameter value.
Manual/Automatic Switch: A 2-
Normally, this switch is set to the Automatic (2 o’clock) position to allow program control
of the boiler. When set to the Manual (10 o’clock) position, a flashing “EMERG –
MODE” message is displayed. Heating Circuit 1 (HC1) pump and the first burner stage
are switched on. Pumps for Heating Circuit 2 (HC2) and Domestic Hot Water (DHW) will
F
also be switched on if sensors are installed and enabled. The pump(s) will turn off when
the flow temperature reaches the value set for MAX TCIRCUIT 1 menu). The first burner stage will cut off when the boiler temperature
reaches the value set for MAX T-MODUL (in EXPERT/INSTALLATION menu).
G Rotary Knob: Used to navigate through menus and parameters or adjust parameters.
3.2 Software Menus
Software menus are divided into five main menus, each with a set of sub-menus (Table 3-1).
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 13 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
CIRCL TIME
HOTW-PROG
HTG-PROG 1
HTG-PROG 2
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
SERVICE
DATE/TIME
HOLIDAY
CLOCK CHANGE
Sub-MENU Name
The rotary knob on the front of the E8 Controller is used to sequentially cycle through the
menus and the sub-menus. Two small arrows at the bottom of the display point to the selected
menu and sub-menu name, respectively. Note that some menus and sub-menus are read-only
or not available, according to the boiler used and the initial startup configuration.
NOTE
The menu processing steps presented in this manual assume that all required
(one-time) INSTALLATION menu items have already been entered at setup. It
should be noted that whenever the unit is powered down and then powered up
again, the INSTALLATION menu will reappear. When this occurs, the
INSTALLATION menu items DO NOT need to be reentered. Normally, after entry
of the required initial INSTALLATION menu entries, turning the Rotary Knob
clockwise will automatically advance the Controller to t he DISPLAY menu group.
All items in this group are “Read Only” and cannot be changed.
See Sub-section 4.7, E8 Contr oller Initial Startup f or more information about
initial setup and configuration of the E8 Controller.
Table 3-1: Main Menus and Sub-Menus
MAIN MENUSSUB-MENUS
DISPLAY
USER
TIME
PROGRAMS
EXPERT
EXPERT HS
GENERAL
INSTALLATION
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 14 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
INSTALLATI
Points down to
Points right to
Points left to
Points down to
Sub-MENU
MENU
Selected
Buss(es)
Selected Bus(es)
Selected
Selected
MENU Name
Names
Sub-MENU
Name
Names
Figure 3-4: E8 Display in MENU Mode (after first opening hinged door)
3.2.1 Basic Menu/Sub-Menu Navigation and Selection
Selected Menu and Sub-menu are indicated by two black arrows at display bottom pointing to
the Menu and Sub-menu names s ilk-screened below the display (see Figure 3-4).
Following initial startup and one-time entry of the required INSTALLATION menu items (see
E8 Controller Initial Startup, sub-section 4.7), to access, view and/or change menu items
follow these instructions:
Menu/Sub-Menu Navigation and S election
1. When the ON/OFF switch on the front of the boiler is turned O N and the swing-down hing ed
panel is opened, the controller will enter MENU Mode and INSTALLATION will be displayed
(Figure 3-4) in the LCD. This is the initial INSTALLAT ION menu and it is assumed that all
entries have already been made. See sub-section 4.8 for INSTALLATION menu initial entry
information.
2. Turn the Rotary Knob clockwise until the display advances to the DISPLAY menu. The dial
on the clock face will rotate one revolution counter clockwise and t hen go off. The display will
then show INSTALLATION, which is the first sub-menu in the DISPLAY menu group (Figure 3-4). The two small black arrows at bottom of the display will point down to the menu and
submenu names, in this case DISPLAY and INSTALLATION, respectively.
3. To view functions included in the INSTALLATION sub-menu, press the Program Key (Item E, Figure 3-3). If desired, turn the Rotary Knob to scroll through the functions in the
INSTALLATION sub-menu. As previously mentioned, these display functions are read-only
and cannot be changed. Once you reach the end of the sub-menu, RETURN will appear in
the display.
4. To exit this sub-menu and advance to the next sub-menu in the DISPLAY menu, press the
Program Key. INSTALLATION will again be displayed. Turn the Rotary Knob clockwise until
the next sub-menu is displayed.
5. Repeat steps 2, 3 and 4 to view the remaining main menus and their associated sub-menus.
The remaining main menus are: USER, TIME PROGRAM, EXPERT, EXPERT HS (Not
Applicable to Modulex), and GENERAL.
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 15 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
Parameter Change Pro cedu re
Use Rotary Knob to navigate to desired Menu/Sub-
Press Program Key to access parameters in the
selected (displayed) sub-menu.
Turn Rotary Knob to sequence through the available
parameters.
To change a parameter value, press the Program Key
To change the displayed parameter value, turn Rotary
To save the displayed parameter value to the controller
will turn off indicating the new value has been saved.
HOT-WATER
T-DHW
T-DHW
141.0
142.0
HOT-WATER
T-DHW
displayed
sub-menu
displayed
values
accessed
displayed
value
Displayed
Example: User Menu & Hot Water Sub-menu
parameters
Cycle thru
cycle thru
push!
push!
push!
142.0
Display Detail
Description
Examples
140.0
Displayed
Sub-menu
3.2.2 Basic Parameter Navig at io n, Select io n, and Revision
When in the USER, TIME PROGRAM, EXPERT, or GENERAL Main Menu, virtually all sub-
menu items can be changed if the desired. Perform the following steps to access, view, and/or
change menu item parameters:
menu. Menu and sub-menu are indicated by two small
black arrows at bottom of LCD display pointing down to
menu/sub-menu names below display (see Figure 3-
when desired parameter is displayed. The Change LED
will light up indicating the displayed parameter may now
be changed.
Knob; clockwise to increase value and counterclockwise to decrease the value.
memory, press the Program Key. The Change LED
accessed
parameters
parameter
values
Value Saved!
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 16 of 112
GF-115-C
OMM-0084_0D
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
4.E8 CONTROLLER MENUS AND SUB-MENUS
This section provides flow-chart illustrations and tabular listings of all Menu and Sub-Menu functions.
Overall menu hierarchy is shown below:
1. DISPLAY
a. INSTALLATION
b. HOT WATER
c. HEAT CIRCUIT I
d. HEAT CIRCUIT II
e. SOLAR/MF
2. USER
a. INSTALLATION
b. HOT WATER
c. HEAT CIRCUIT I
d. HEAT CIRCUIT II
e. SOLAR/MF
3. TIME PROGRAMS
a. CIRCL TIME
b. HOTW-PROG
c. HTG-PROG 1
d. HTG-PROG 2
4. EXPERT
a. INSTALLATION
b. HOT WATER
c. HEAT CIRCUIT I
d. HEAT CIRCUIT II
e. SOLAR/MF
5. EXPERT HS
a. INSTALLATION
6. GENERAL
a. SERVICE
b. DATE/TIME
c. HOLIDAY
d. CLOCK CHANGE
IMPORTANT!
In the following flow-chart illustrations and t abular listings, descriptions, entry
ranges, and default values are provided for only the commonly used functions
which are referenced in Section 5, titled E8 Operating Mode: Set-Up & Programming. These commonly used functions are shown in Bold Italics in
the illustrations and tables which follow. Refer to Section 8 for additional
information on functions marked “Not Applicable” in the illustrations and tables
provided.
PR1: 02/23/12 Page 17 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
DISPLAY
INSTALLATION
T-OUTSIDE
T-EXT DES
T-COLL DES
T-COLLECTOR
T-BOIL
T-SOLID FUEL
T-RETURN 1
T-RETURN 2
T-BUFFER T
T-BUFFER M
T-BUFFER L
T-STORAGE 3
MODGRAD
RETURN
HOT WATER
T-DHW RATED
T-DHW
T-DHW L
RETURN
HTG CIRCUIT 2
T-ROOM DES A
T-ROOM
HUMIDITY
T-FLOW RATED
T-FLOW
N-OPT-TIME
RETURN
SOLAR M/F
T-MF1
T-MF2
T-MF3
T-MF4
T-COLLECTOR
T-DHW
T-DHW L
RETURN
HTG CIRCUIT 1
T-ROOM DES A
T-ROOM
HUMIDITY
T-FLOW RATED
T-FLOW
N-OPT-TIME
RETURN
4.1 DISPLAY Menu
The DISPLAY Menu contains an INSTALLATION, HOT WATER, HEATING (HTG) CIRCUIT 1
& 2 and a SOLA R M/ F Su b-Menu as shown in Figure 4-1 and in Table 4-1.
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 18 of 112
Figure 4-1: DISPLAY Menu Flow Chart
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
Reset and Constant Set Point modes.
T-COLLECTOR
Header Set Point temperature (cascade)
sequence between Heat Modules.
T-SOLID FUEL
Not Applicable
T-RETURN 1
Not Applicable
T-RETURN 2
Not Applicable
T-BUFFER T
Not Applicable
T-BUFFER M
Not Applicable
T-BUFFER L
Not Applicable
T-STORAGE 3
Not Applicable
Knob to sequence between Heat Modules.
Sub-Menu.
Based on heating prog and
USER/HOT WATER menu.
WATER Sub-Menu.
All DISPLAY Menu & Sub-Menu functions are READ ONLY and
cannot be changed. Temperature readings shown are in °F.
FUNCTIONDESCRIPTIONREMARKS
INSTALLATION Sub-Menu
NOTE
Table 4-1: DISPLAY Menu Listing
T-OUTSIDE Outside air temperature
T-EXT DES
T-COLL DES
T-BOIL
Boiler Set Point setting in 0 to 10 volt input
mode
Boiler Set Point temperature in Indoor/ Outdoor
Press Program Key to display temperature
and ON/OFF status of individual Heat
Modules (HS) which range from 2 (EXT
321) to 8 (EXT 3060). Turn Rotary Knob to
Displayed only if outside
air sensor is installed.
A 0 to 10 volt external input
signal can be used to change the
Boiler set point.
The Burner symbol ( )
is displayed when the
respective Heat Module is
ON.
Press Prog Key to display Modulation % for
MODGRAD
RETURN
individual Heat Modules (HS). Turn Rotary
Press Program Key to exit INSTALLATION
HOT WATER Sub-Menu
T-DHW RATED
T-DHW Actual hot water temperature
T-DHW L Not Applicable
T-CIRCL Not Applicable
RETURN
DHW set point temperature
Press Program Key to exit the HOT
Table 4-1: DISPLAY Menu Listing (Continued)
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 19 of 112
operating mode. Actual
DHW set point as set in
Only if tank sensor is
installed
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
T-DHW
Current hot water temperature
FLOW
N-OPT-TIME
Not Applicable
CIRCUIT 1 Sub-Menu.
T-MF1
Not Applicable
T-MF2
Not Applicable
Currently not used
1
T-DHW L
Not Applicable
M/F Sub-Menu.
FUNCTION DESCRIPTION REMARKS
HTG CIRCUIT 1 Sub-Menu
T-ROOM DES ANot Applicable
T-ROOMCurrent room air temperature.
HUMIDITYRoom humidity (%).
T-DHW RATED Hot water set point temperature
T-FLOW RATED Current flow set point temperature
Current flow temperature
RETURN
HTG CIRCUIT 2 Sub-Menu
Functions for HTG (Heating) Circuit 2 are identical to HTG Circuit 1 Functions
above.
Press Program Key to exit HTG
Only if indoor sensor is
connected
Only if humidity sensor
is installed and
parameters set for
heating circuit.
Appears only if heating
circuit is programmed
as hot water circuit
Same as above
Not applicable
SOLAR M/F Sub-Menu
T-MF3
T-MF4
T-COLLECTOR
T-DHW
RETURN
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Press Program Key to exit SOLAR
Currently not used
Currently not used
Currently not used
Currently not used
Currently not used
Currently not used
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 20 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
USER
INSTALLATION
LANGUAGE
CONTRAST
DISPLAY SEL
RETURN
HOT WATER
1X DHW
T-DHW 1
T-DHW 2
T-DHW 3
BOB VALUE
CIRCL-P-DHW
ANTILEGION
RETURN
SOLAR M/F
RETURN
HTG CIRCUIT 1
MODE
T-ROOM DES 1
T-ROOM DES 2
T-ROOM DES 3
T-REDUCED
T-ABSENCE
T-LIMIT DAY
T-LIMIT N
HEATSLOPE
OPTIM HEAT
MAX OPT-TIME
ECONO OPTI
PC ENABLE
RETURN
HTG CIRCUIT 1
MODE
T-ROOM DES 1
T-ROOM DES 2
T-ROOM DES 3
T-REDUCED
T-ABSENCE
T-LIMIT DAY
T-LIMIT N
HEATSLOPE
OPTIM HEAT
MAX OPT-TIME
ECONO OPTI
PC ENABLE
RETURN
4.2 USER Menu
The USER Menu (Figure 4-2) contains the same Sub-Menus as the DISPLAY Menu.
However, the USER Menu items are not “Read Only” and therefore can be changed. The SubMenu functions in the USER Menu also differ from those contained in the DISPLAY Menu.
Tabular listings for the USER Menu items are provided in Table 4-2.
Figure 4-2: USER Menu Flow Chart
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 21 of 112
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
CONTRAST
00
Domestic Hot Water
connected).
Menu.
1X DHW
Not Applicable
T-DHW 1
Hot Water set point
50°F - 158°F
140°F
T-DHW 2
Not Applicable
BOB-VALUE
Not Applicable
DHW
Menu.
Table 4-2: USER Menu Listing
FUNCTION
INSTALLATION Sub-Menu
LANGUAGESelects display language.
Adjusts display contrast
Sets the day of the week or the sensor
temperature (°F) to appear in the display when
the swing-down panel is closed.
DESCRIPTION
Day: SUN – SAT
T-OUTSIDE: Outside Temperature
FLOW TEMP (1/2): Flow Temp. For Heating
Circuit 1 or 2 supply
DISPLAY
SEL
water temperature. (Only
if sensor is installed)
T-DHW:
Temperature.
T-BOILER; Boiler Outlet Temperature.
T-ROOM (1 / 2): Room Temp, Heating
Circuit 1 or 2 (ONLY if
Remote Control is
ENTRY RANGE DEFAULT
12 languages are
available.
-20 to 20
ENGLISH
See
DESCRIPTION
Column
- - - -
RETURN
HOT WATER Sub-Menu
T-DHW 3
CIRCL-P-
RETURN
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 22 of 112
Press Program Key to exit INSTALLATION Sub-
Not Applicable
Not Applicable
Press Program Key exit HOT WATER Sub-
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
Night
T-ROOM DES 2
Not Applicable
T-ROOM DES 3
Not Applicable
-23.0°F–104.0°F
periods.
-23.0°F–104.0°F
1°F.
MAX OPT-TIME
Not Applicable
ECONO OPTI
Not Applicable
CIRCUIT 1 (or 2) sub-menu.
display to the TIME PROGRAM Menu.
Table 4-2: USER Menu Listing (Continued)
FUNCTION
HTG CIRCUIT 1 Sub-Menu
MODEDisplays Timer Mode for Boiler
T-ROOM DES 1
T-REDUCED
T-ABSENCE
T-LIMIT DAYApplies during day-time heating periods
T-LIMIT N
HEATSLOPE
Not Applicable
Not Applicable
Not Applicable
Applies during reduced night-time
Indicate number of degrees that the flow
temperature changes if the outside
temperature increases or decreases by
DESCRIPTION
ENTRY RANGE
- - - -, Standby,
Auto 1, Auto 2, Day,
- - - -,
- - - -,
0.00 – 3.001.20
DEFAULT
- - - -
66.0°F
50.0°F
OPTIM HEAT
PC-ENABLE
RETURN
HTG CIRCUIT 2 Sub-Menu
Functions for HTG Circuit 2 are identical to HTG Circuit 1 Functions listed above.
SOLAR M / F Sub-Menu (No Functions Currently In This Sub-Menu)
RETURN
Not Applicable
Not Applicable
Press Program Key to exit HTG
Pressing the Program Key with SOLAR
M/F displayed will change display to
RETURN . Press Progr am Key again to
redisplay SOLAR M/F. Turning the
Rotary Knob clockwise will advance thd
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 23 of 112
Day and Time-related functions can be set using the TIME PROGRAM Menu and its
associated Sub-Menus. However, at the present time, none of the Sub-Menus and functions
in the TIME PROGRAM Menu are being utilized. This menu is shown in Figure 4-3.
Refer to Secti on 8 for additional information on these Menu and Sub-Menu functions.
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 24 of 112
Figure 4-3: TIME PROGRAM Menu Flow Chart
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
EXPERT
INSTALLATION
CODE-NO
BUS ID HS
BUS ID 1
BUS ID 2
AF SUPPLY
BUS TERM
EBUS SUPPLY
TIME MASTER
MAX T COLL
MIN T COLL
MAX T-HS2
MIN T-HS2
V-CURVE
CURVE 11-U1
CURVE 11-U2
CURVE 11-T1
CURVE 11-T2
CURVE 11-UA
HYSTERESIS
FOUND MODULS
CAP/MODULE
NEW CONFIG
MIN MOD CASC
HW-BOILER
CONTR DEVIAT
DES OUTPUT
BLOCK TIME
MAX T-MODUL
DYN UPWARD
DYN DOWNWARD
RESET TIME
MODULAT MAX
MODULAT MIN
MIN MOD HS
SEQUENCE 1
SEQUENCE 2
SEQU CHANGE
SEQ SW TIME
LOCK TIME
HYST BURNER 2
HS COOL FUNC
T-HS COOL
HEATSOURCE 1
HS1 BUS
HEATSOURCE 2
STORAGE HS 2
BUFFER
RETURN
CONTINUED ON SHEET
2
4.4 EXPERT Menu and Sub-Menus
The EXPERT Menu contains the following Sub-Menus: INSTALLATION, HOT WATER, HEAT
CIRCUIT 1, HEAT CIRCUIT 2 and SOLAR M/F as shown in Figure 4-4. As this figure shows,
the EXPERT Menu includes an extensive list of Sub-Menu functions, particularly in the
INSTALLATION Sub-Menu. Tabular listings for the EXPERT Menu and Sub-Menu items are
provided in Table 4-3.
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 25 of 112
Figure 4-4: EXPERT Menu Flow Chart (Sheet 1 of 2)
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
EXPERT
HTG CIRCUIT 1
HC FUNCTION
PUMP MODE
MIXER OPEN
MIXER CLOSE
MAX T-FLOW
MIN T-FLOW
T-FROST PROT
OUT-TEMP-DEL
SLOPE OFFSET
B-HEAT SINK
RETURN
HOT-WATER
DHW RELIEF
PARALLEL
T-BOILER DHW
HYST DHW
DHW FOLLOWUP
THERM INPUT
WALL HUNG
LOAD THROUGH
RETURN
HTG CIRCUIT 2
HC FUNCTION
PUMP MODE
MAX T-FLOW
MIN T-FLOW
T-FROST PROT
00 = Hot Water Priority
01 = Hot Water Partial Priority
Boiler temperature increase during Hot Water
operation.
Boiler Temp = (DHW Temp Setting) + (T-BOILER
Storage Tank With Sensor = 00
Table 4-3: EXPERT Menu Listing (Continued)
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 29 of 112
00, 01, 02
32°F – 194°F 97°F
00 min. – 30
00, 01
01
00 min.
00
GF-115-C
Modulex E8 Controller a nd BCM
Operations and Maintenance Manual
OMM-0084_0D
ENTRY
RANGE
valve.
Circulation pump mode control for ON/OFF
03 = Continuous pump operation
MIXER OPEN
Not Applicable
MIXER CLOSE
Not Applicable
Maximum allowable water temperature setting
for the heating circuit.
68°F –
230°F
Minimum allowable water temperature setting
for the heat circuit.
50°F –
230°F
Specifies the minimum allowable outside air
INSTALLATION Mode)
DEL
OFFSET
B-HEAT SINK
Press Program Key to exit HEAT CI RCUIT 1
(or 2) Sub-Menu.
FUNCTION DESCRIPTION
HEAT CIRCUIT 1 & 2 Sub-Menus
The Sub-Menu Functions for HEAT CIRCUIT 1 & HEAT CIRCUIT 2 are identical, except for
the MIXER OPEN & MIXER CLOSE Functions which apply only to HEAT CIRCUIT 1. The
Function values in this Sub-Menu level will change, depending on the Heat Circuit Function
(HC FUNCTION) selected.
Heat Circuit Function defines type of circuit:
00 = Standard Heat Circuit (indoor / outdoor reset)
01 = Control to fixed flow temperature (constant setpoint)
HC FUNCTION
PUMP MODE
02 = Swimming pool control (HC 2 ONLY)
03 = Hot Water Circuit
04 = Return flow temp. Increase via mixing
switching of pumps.
00 = Standard pump control
01 = Pump switching per heating limits
02 = Pump switching per heating program
00 – 04
00 – 0300
DEFAULT
00
(Standard
Heat
Circuit)
MAX T-FLOW
MIN T-FLOW
temperature setting for the Frost Protection
Mode. If temperature drops below this value,
T-FROST PROT
OUT-TEMP-
SLOPE
RETURN
the system switches to the Frost Protect Mode
and the pumps are switched ON.
(This Function should be set to 0°F in the
Not ApplicableN/AN/A
Not ApplicableN/AN/A
Not Applicable
Table 4-3: EXPERT Menu Listing (Continued)
FUNCTION DESCRIPTION ENTRY DEFAULT
176°F
50°F
-5°F –
41°F
N/A
32°F
N/A
06/05/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 Page 30 of 112