![](/html/8e/8e57/8e576c7c8f6be28bcfe8b7127be87abca32e3bccd03d7f15e5de973e0e54bbc1/bg1.png)
the installation and maintenance of the
AERCO storage tanks in AERCO and
AERCO Domestic Water Storage Tank
AERCO Domestic Water Storage Tank
Technical Instruction Document TID-0011_0B
AERCO Domestic
Water Storage Tank
Installation and
Maintenance
Any applicable water heater/boiler piping
system arrangement.
Description of Document:
This Technical Instruction Document
provides the instructions necessary for
non-AERCO systems.
Last Updated: 09/22/2014
VD2: 09/22/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 1 of 19
![](/html/8e/8e57/8e576c7c8f6be28bcfe8b7127be87abca32e3bccd03d7f15e5de973e0e54bbc1/bg2.png)
AERCO Domestic Water Storage Tank
Technical Instruction Document TID-0011_0B
TABLE OF CONTENTS
1. INTRODUCTION ................................................................................ 3
2. STORAGE TANK TYPES ................................................................... 3
3. STORAGE TANK MANWAY/HANDHOLD CLEANOUT ....................... 9
4. STORAGE TANK INSTALLATION ..................................................... 9
5. STORAGE TANK MAINTENANCE ................................................... 10
6. STORAGE TANK FIELD PIPING ...................................................... 10
LIMITED STORAGE TANK WARRANTY ................................................... 17
(Mon–Fri, 8am-5pm EST)
1-800-526-0288
www.aerco.com
Disclaimer
The information contained in this manual is subject to change without notice from
AERCO International, Inc. AERCO makes no warranty of any kind with respect to this
material, including, but not limited to, implied warrant ies of mer chantabilit y and fitness f or
a particular application. AERCO International is not liable for errors appearing in this
manual. Nor for incidental or consequential damages occurring in connection with the
VD2: 09/22/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 2 of 19
furnishing, performance, or use of this material.
![](/html/8e/8e57/8e576c7c8f6be28bcfe8b7127be87abca32e3bccd03d7f15e5de973e0e54bbc1/bg3.png)
AERCO Domestic Water Storage Tank
Technical Instruction Document TID-0011_0B
1. INTRODUCTION
AERCO storage tanks are ASME certified glass-lined pressure vessels designed for use with
instantaneous water heaters. When contending with challenging applications, they assure
consistent hot water service during peak demands. The AERCO storage tanks are available in
standard stratified or accumulator storage configurations.
IMORTANT NOTICE!
Incorrect installation can cause rapid failure of water tanks due to
electrolysis. It is vital that this risk is reduced by the use of
dielectric connections, isolation of the tank supports, and regular
anode servicing. Installers must be aware of correct pr ocedures.
For assistance please call: 1-800-526-0288.
Overspray on topcoated tanks may hide some fittings. Prior to
filling the system, check all fittings and connections and compare
fitting locations to the approved drawing to ensure all fittings are
capped, sealed or piped to.
2. STORAGE TANK TYPES
The AERCO water storage tanks come as standard, stratified storage tanks or accumulator
storage tanks.
Stratified storage tanks (see Figure 1):
• These tanks come with either a dispersion tube or baffle at the cold water inlet to
achieve a thermal boundary layer.
• Models with threaded cold water connection are equipped with a dispersion tube.
• Models with threaded cold water connection have a 3” Male NPT inlet
• Models with 150 lb. flanged cold water connections are equipped with a baffle.
Accumulator storage tanks (see Figure 2):
• These tanks DO NOT come with a dispersion tube or baffle.
• Models with threaded cold water connection have a 3” Female NPT inlet
Standard storage tanks (see Figures 3 – 5 for dimensions):
• Dispersion tank is optional.
VD2: 09/22/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 3 of 19
![](/html/8e/8e57/8e576c7c8f6be28bcfe8b7127be87abca32e3bccd03d7f15e5de973e0e54bbc1/bg4.png)
AERCO Domestic Water Storage Tank
Technical Instruction Document TID-0011_0B
Figure 1: AERCO Stratified Storage Tank – Port Designations
VD2: 09/22/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 4 of 19
![](/html/8e/8e57/8e576c7c8f6be28bcfe8b7127be87abca32e3bccd03d7f15e5de973e0e54bbc1/bg5.png)
AERCO Domestic Water Storage Tank
Technical Instruction Document TID-0011_0B
Figure 2: AERCO Accumulator Storage Tank – Port Designation
VD2: 09/22/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 5 of 19
![](/html/8e/8e57/8e576c7c8f6be28bcfe8b7127be87abca32e3bccd03d7f15e5de973e0e54bbc1/bg6.png)
AERCO Domestic Water Storage Tank
Technical Instruction Document TID-0011_0B
Figure 3: AERCO Large Standard Storage Tank – Jacketed
VD2: 09/22/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 6 of 19