AERCO Combination Control Panel User Manual

COMBINATION CONTROL PANEL
MODEL CCP
Domestic Water/Space Heating
Multiple Boiler Controller
Concept
AERCO International recommends individual KC water heating and space heating systems wherever possible.
Individual water heaters and boilers achieve maximum efficiency and precise temperature control. However, when factors such as existing indirect storage water
heaters, restricted fuel input, or space limitations are conditions to be met, AERCO KC Boilers can be used in a dual service role.
Combination System Description
In order to accommodate the requirements for both space
heating and the production of domestic hot water, multiple
KC style boilers can be used in a combination space
heating and domestic water heating plant. Boiler modules
are piped in a multiple boiler arrangement as they would
be in a multiple unit space heating plant. See Combination
Boiler Plant Sizing section for recommendations on num-
ber of modules required. The necessary number of mod-
ules for domestic water production are isolated from the
heating system in the supply piping by means of a nor-
mally closed two way motorized valve. An external hot
water storage generator is used to convert boiler water to
produce potable water through a closed loop coil. Upon
demand for domestic water, the isolated (combination
duty) boilers produce a constant temperature supply
(70.220F) by operating in the internal setpoint mode.
The AERCO Combination Control Panel (CCP) is an
accessory panel designed to work in conjunction with an
AERCO Model 168 Boiler Management System (BMS) to
control the firing of the combination boiler modules and
the associated accessories for domestic water production.
The CCP panel allows operation of the combination boiler
modules to produce domestic water through the external generator coil, and activates the circulating pump between
the boilers and the coil. The CCP uses a simple tank
aquastat to start domestic water production. It allows control of up to four KC Boilers (Boiler Control Code -6) in
the constant set point mode, and allows a transfer of the
motorized valve and the control of the modules to the BMS when the space heating requires their added input.
By utilizing a CCP Panel in tandem with a Model 168 Boiler Management System, the KC Boilers efficiency will be maximized. Only the required energy (input) for
domestic water will be used, and the heating plant can operate at lowest required temperatures for space heating to maximize condensing efficiency.
Domestic Water Mode
The tank aquastat, or domestic water demand device, is wired to the CCP to signal a demand for domestic water. The CCP supplies 12VDC to the dry contacts of the domestic water demand device (aquastat). Upon a demand for domestic water, the CCP enables the com­bination boiler modules to begin firing to their internal setpoint temperature. Each module will automatically modulate its input to meet the requirement of domestic water production. The closed motorized valve isolates the normally higher temperature boiler water from the heating system. The circulating pump between the combination modules and the coil is activated simultaneously with the combination modules. The boilers and pump will operate continually until the domestic water aquastat is satisfied.
Heating Mode
The Boiler Management System (BMS) will activate the heating plant and sequence/modulate the heating-only
boilers in the selected mode. When all dedicated heating
modules are operating at 100% input, the BMS will close the Auxiliary contacts wired to the CCP Panel. The CCP will then activate the motorized valve to open piping
between the heating system loop and the combination
boiler loop. The CCP supplies line voltage (120/1/60)
directly to the valve operator. The valve must be a three wire control type with power open/power closed operator.
Operator timing on motorized valves should be in the 8 to
45 second range, and must be equipped with a dry con­tact SPST N.O. end switch. When the valve reaches the full open position, the dry contact end switch of the valve
will close, signaling the supply piping between the heat-
ing-only and combination boilers is open. This transfers
control of the combination modules percentage of firing
input to the BMS. The BMS will then add the combination
modules to the heating system, and modulate them to
their required input level. The boiler modules will be
sequenced at the adjusted percentage as set in the BMS.
As the added input from the combination modules allow
the heating load (setpoint) to satisfy, the auxiliary contacts
of the BMS will open. The motorized valve will then be
driven closed by the CCP Panel. The combination boilers will be de-activated until needed either for domestic water or for heating again. If domestic water is called for while the valve is open for heating the CCP will automatically close the motorized valve and transfer the control of the combination modules back to domestic water production.
Example -
From conventional calculations on a typical design:
Space Heating Load = 2840 MBH Domestic Water Load = 1705 MBH Diversity = Factor
1705 MBH = .60 2840 MBH
Combination Plant Sizing
The required size of a combination boiler plant is not
necessarily the simple sum of the heating modules and the domestic water modules. ASHRAE has documented and developed a method of sizing combination plants
based on the diversity of the loads. ASHRAE Systems
1984 Handbook published a researched method of estab-
lishing a relationship of domestic water load to heating
load, and a table of recommended percentage of addi­tional BTUH to be added to the heating plant to handle
both loads.
Simply expressed,
Domestic Water Load = Diversity Factor
Heating Load
The diversity factor is then converted to a percentage
increase in the base heating load plant from Table A.
Table A
Diversity
.4
Factor Domestic
Heating % Load to be added to Heating Boiler
2
60%
1
.8
50% 40%
.6
30%
.5
20% 10%
.3
0%
From Table A, a diversity factor of .60 indicates a mini­mum of 30% of the domestic water heating load require­ment should be added to the heating load for Total Boiler
Plant Capacity.
Total Plant Capacity = 2840 MBH + (.30X 1705 MBH) = 3352 MBH
Total Load Output/Boiler
=
3352 MBH Output = 4KC Boilers 870 MBH/Boiler
Component Design
Domestic water sizing for a combination plant should be done in accordance with ASHRAE and ASPE standards. The storage tank size should be adequate for small
domestic water draws without short cycling the domestic tank aquastat. The combination of recovery and storage
should be as prescribed in the ASHRAE/ASPE methods. The recovery of the storage tank coil exchanger should
be based on a temperature drop of 2OF, or the same temperature drop as the heating system that the plant
supplies. When sizing the circulating pump between the
combination boiler(s) and the tank coil, the flow of the
pump must be greater than the minimum module flow of
25 gpm per module. The head of the pump must be
capable of overcoming the pressure drop of the boilers,
the tank coil, and the frictional resistance of all piping/
accessories between them. Air elimination and expansion
accessories may be required in the coil loop as well as the
main heating loop.
Loading...
+ 2 hidden pages