AERCO Coil & Riser Replacement User Manual

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
HE-109
Hardware Procedure:
Heaters
Applies to:
removal and replacement of Coil Assemblies and Risers contained in
ry safety precautions when working with high temperature, pressurized steam and
Coil Assembly in Water Heater Heat Exchanger
TECHNICAL INSTRUCTIONS
Coil and Riser
Replacement
Procedures for All Styles
of A, B, C, and D
Indirect-Fired Water
Indirect-Fire Water Heaters.
Description of Document: This Technical Instruction Document
provides the instructions necessary for
AERCO Indirect-Fired Heat Exchangers. These instructions must be performed by a skilled service technician capable of exercising the necessa
water systems.
The original document was formatted as
HE-109, but has now been changed
To a Technical Instruction Document
(TID-0004), to better conform to the new
an Application Guide,
document definitions.
Revised: 06/20/2011
NOTE
Coil/Riser Replace Instructions for Helitherm Water Heaters
Technical instructions
Technical Support:
1-800-526-0288
www.aerco.com
HE-109
TID-0038_0A
(Mon–Fri, 8am-5pm EST)
Disclaimer
The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
PR2: 04/01/11 Page 2 of 16
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Coil/Riser Replace Instructions for Helitherm Water Heaters
Technical instructions
HE-104
SW1B-Plus Heat Exchanger Installation, Operation & Maintenance Instructions.
HE-110
B-Plus II Water Wizard Heat Exchanger Installation, Operation & Maintenance
VA-109
For removal of CXT-S 1” thru 2” Control Valve prior to hydrostatically testing and
VA-110
For removal of CXT-S 2.5” thru 4” Control Valve prior to hydrostatically testing
VA-106
For removal of CXT-P Control Valve prior to hydrostatically testing and for
AC-103
For adjusting Barber-Coleman Temperature Controller for re-commissioning unit.
HE-109
TID-0038_0A

1. Introduction

This document provides the instructions necessary for removal and replacement of Coil Assemblies and Risers contained in AERCO Indirect-Fired Heat Exchangers. These instructions must be performed by a skilled service technician capable of exercising the necessary safety precautions when working with high temperature, pressurized steam and water systems. It is imperative that the following Safety Warnings and Precautions be observed at all times:

2. Overview of Procedure

Installation, maintenance and operating personnel must, at all times observe all safety regulations. The following warnings are general and must be given the same attention as specific precautions included in these instructions.
FLUIDS UNDER PRESSURE MAY CAUSE INJURY TO PERSONNEL OR DAMAGE
TO EQUIPMENT WHEN RELEASED
Shut off all incoming and outgoing steam and water stop valves and carefully decrease
all trapped pressures to zero before performing any maintenance.
WARNING!
Never search for leakage in a live steam line by sight alone or by “feel”. Use a
Always provide yourself with personal protective equipment, (PPE) such as
LIVE STEAM CAN CAUSE SEVERE BURNS
mirror or other suitable polished object.
gloves, eye protection, dust mask, hard hat, etc.
WARNING!

3. Reference Documents

Refer to the following AERCO documents when removing, replacing or adjusting the indicated components and assemblies:
HE-107
SW1A-Plus Heat Exchanger Installation, Operation & Maintenance Instructions.
Instructions.
for re-commisioning unit.
and for re-commisioning unit.
re-commissioning unit.
PR2: 04/01/11 Page 3 of 16
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Coil/Riser Replace Instructions for Helitherm Water Heaters
Technical instructions
HE-109
TID-0038_0A

4. Tools and Equipment Required

The following common and special tools and equipment are required to perform the instructions contained in this document:
Common Tools and Equipment
Combination Wrenches: 7/16”, 5/8”, 13/16”, 1-1/16”, 1-1/8”
Pipe Wrenches: 12” and 24”
Chain Hoist
Voltmeter:
Brass Wire Brush
Special
Tools and Equipment
Hydrostatic Pressure Pump: Range= Up to 235 psig
Torque Wrench, 75 ft.-lbs. With 1-1/4”, 1-5/16” & 1-1/2” Open-End Spanners (1-1/4” Open-End Spanner required for “A” Heater Only)
Needle-Nose Pliers
Gasket Removal Tool
Carpenter’s Square
Teflon Tape
Orange Citric Cleaner
Black Marker
Coil Retaining Tool (Figure 1)
Coil Spacing Tool (Figure 1)
Short-Length Wrenches: 1-1 /4”, 1-
5/16”, 1-1/2” (Overall wrench lengths should be approx. 6 inches or less)
Figure 1: Tool Fabrication Details: Coil Spacing and Retaining Tools
Recommended Material: 1018 steel
PR2: 04/01/11 Page 4 of 16
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Coil/Riser Replace Instructions for Helitherm Water Heaters
Technical instructions
procedures should be performed in the order specified to minimize repair time.
Section 5.1 Instructions
END
HE-109
TID-0038_0A

5. Heater Isolation and Disassembly

The procedures in the following paragraphs are arranged to isolate, disconnect and
disassemble the unit to the extent necessary to repair or replace defective items. These
NOTE

5.1 Isolating Heater

To isolate the Heater from all facility energy sources (steam, water, electrical, etc.), proceed as follows:
1) Disconnect and Lock-Out/Tag-Out external AC power supplied to the Control Box and any other devices connected to the Heater.
2) Using a voltmeter, check to ensure that all incoming voltage readings are zero Before
3) If the Heater is equipped with a Pneumatic Steam Valve, close the valve supplying air inlet pressure to the Pneumatic Controller.
4) Close all stop valves in the Steam Inlet and Condensate Outlet lines
5) On the water-side, close the stop valves in the following order
6) Carefully open the Relief Valve located on the Top Head to relieve pressure in the Heater Shell.
7) While holding the Relief Valve open to prevent creating a vacuum in the Shell, open the Drain
Hot water outlet line
Recirculation line
Cold water inlet line
Water should stop flowing from the valve within one minute. If water continues to flow from the Relief Valve, one of the water stop valves is not securely closed.
Valve in the Bottom Head on the Heater. Completely drain the potable water from the Heater.
Isolating the Heater
continuing.
:
PR2: 04/01/11 Page 5 of 16
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Loading...
+ 11 hidden pages