AERCO C-More Controls User Manual

structio In n
AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA
No.
C-MORE CONTROL PANEL
OPERATION
For
Benchmark Series
&
KC Series
Systems
Printed in U.S.A. REVISED JANUARY, 2009
C-MORE CONTROL PANEL OPERATION
TABLE OF CONTENTS
PARA. PAGE
SECTION 1 – GENERAL INFORMATION 1
1.1 INTRODUCTION 1
1.2 SAFETY PRECAUTIONS AND WARNINGS 1
1.3 FEATURES AND BENEFITS 1
1.4 CONTROL PANEL DESCRIPTION 2
SECTION 2 – CONTROL PANEL MENU STRUCTURE 6
2.1 CONTROL PANEL MENUS 6
2.2 MENU PROCESSING PROCEDURES 6
2.3 OPERATING MENU 7
2.4 SETUP MENU 7
2.5 CONFIGURATION MENU 8
2.6 TUNING MENU 10
2.7 CALIBRATION MENU 11
2.8 DIAGNOSTICS MENU 11
SECTION 3 – CONTROL PANEL MENU DESCRIPTIONS 13
3.1 MENU ITEM DESCRIPTIONS 13
3.2 FACTORY DEFAULTS 13
SECTION 4 – CONTROL PANEL DISPLAY MESSAGES 21
4.1 STARTUP AND STATUS MESSAGES 21
4.2 FAULT MESSAGES 21
SECTION 5 –INPUT/OUTPUT INTERFACES & OPERATING MODES 24
5.1 INTRODUCTION 24
5.2 I/O INTERFACES 24
5.3 MODES OF OPERATION 26
5.4 START SEQUENCE 31
i
C-MORE CONTROL PANEL OPERATION
TABLE OF CONTENTS - Continued
SECTION 6 – CALIBRATION AND DIAGNOSTIC MENUS 33
6.1 INTRODUCTION 33
6.2 CALIBRATION PROCEDURES 33
6.3 DIAGNOSTICS PROCEDURES 35
SECTION 7 – RS232 COMMUNICATION 38
7.1 INTRODUCTION 38
7.2 RS232 COMMUNICATION SETUP 38
7.3 MENU PROCESSING UTILIZING RS232 COMMUNICATION
7.4 DATA LOGGING 39
APPENDIX A - C-MORE CONTROL PANEL VIEWS A-1
APPENDIX B - TROUBLESHOOTING GUIDE B-1
APPENDIX C - INDOOR/OUTDOOR RESET RATIO CHARTS C-1
APPENDIX D - TEMPERATURE SENSOR RESISTANCE CHART D-1
APPENDIX E - WIRING DIAGRAMS E-1
APPENDIX F - C-MORE CONTROL PANEL DIP SWITCH SETTINGS
38
F-1
ii
C-MORE CONTROL PANEL OPERATION

SECTION 1 - GENERAL INFORMATION

1.1 INTRODUCTION

The information in this Section provides a guide to the operation of KC and Benchmark Series
units using the C-More Control Panel. In
addition, it provides information describing the numerous types of external sensors and control devices which can be interfaced to the unit using terminals provided in the Input/Output (I/O) Box utilized with the Control Panel. Information regarding the set up of all Water Heater and Boiler Operating Modes is also included herein.

1.2 SAFETY PRECAUTIONS AND WARNINGS

It is imperative that the initial startup of KC and Benchmark Series units be performed by factory trained personnel. Operation prior to initial startup by factory trained personnel will void the equipment warranty. In addition, the following WARNINGS and CAUTIONS must be observed at all times.
CAUTION:
All initial installation procedures must be satisfied before attempting to start the unit.
WARNING:
ELECTRICAL VOLTAGES IN KC SERIES UNITS INCLUDE 120 AND 24 VOLTS AC. VOLTAGES IN BENCHMARK SERIES UNITS MAY ALSO INCLUDE 460 AND 220 VOLTS AC. THEREFORE, THESE UNITS MUST BE SERVICED ONLY BY FACTORY CERTIFIED
SERVICE TECHNICIANS.
WARNING:
DO NOT ATTEMPT TO DRY FIRE THE UNIT. STARTING THE UNIT WITHOUT A FULL WATER LEVEL CAN SERIOUSLY DAMAGE THE UNIT AND MAY RESULT IN PERSONNEL INJURY OR PROPERTY DAMAGE. THIS SITUATION WILL VOID ANY WARRANTY.

FEATURES AND BENEFITS

KC and Benchmark Series units equipped the new C-More Control Panel include a number of additional features and benefits. These include:

1.3.1 System Start Temperature

The Sy tem Start Temperature feature s allows a boiler to be enabled or disabled based on the outside air temperature. When the outside air temperature goes below the System Start Temperature, the boiler is enabled. When the outside air temperature is above the System Start Temperature, the boiler is disabled. This feature may be used in any boiler mode of operation. It requires that an outdoor air temperature sensor be connected to the boiler.

1.3.2 Setpoint Low Limit

This option allows the user to unit’s setpoint can be set. The allowable range is 40°F to 240°F. The factory default is set at 60°F.
limit how low the

1.3.3 Setpoint High Limit

This option has two functions. In the Indoor/Outdoor Reset, Constant Setpoint and 4 to 20 mA Remote Setpoint Modes, the Setpoint High Limit option limits how high the unit’s setpoint can be set. The allowable range is 40°F to 240°F.
In the 4 to 20 mA Direct Drive, Combination or BMS Mode of operation, the Setpoint High Limit acts as a temperature limiting governor. Should the unit’s outlet temperature equal the Setpoint High Limit Setting, a PID function will intervene and maintain the outlet temperature at the Setpoint High Limit minus the Setpoint Limit Band.
To use the Setpoint High Limit feature, the Setpoint Limiting option must be enabled and a Setpoint Limit Band selected. This Band is preset at 5°F, however it is adjustable from 0°F to 10°F.
1.3.4
with
1.3
1
C-MORE CONTROL PANEL OPERATION

Temp Hi Limit

The Temp Hi Limit is a te e The F that will shut down the unit and generate an alarm if the if the outlet temperature exceeds its setting. It is preset at 210°F, however it is adjustable from 40°F to 240°F.
mperature limit featur

1.3.5 Max Fire Rate

This feature allows the firing rate. This feature can be useful if site or equipment limitations require that less BTU’s be input into the system. This feature is meant to be used only on a temporary basis until the system or equipment limitations are resolved.
user to limit the unit’s

1.3.6 Pump Delay Timer

The C-More control system a turn a pump on and off as the boiler cycles on and off on demand. The Pump Delay Timer feature allows the user to keep the pump running up to 30 minutes after the unit has shut down and the demand satisfied.
llows the user to

1.3.7 Aux Start On Delay

The AUX START ON DELAY conjunction with the Auxiliary Relay. When a call for heat is produced, the Aux Relay will energize and can be used to start a system or gas booster pump, open a louver or valve, or start some other necessary system process. The Aux Start On Delay is a timer that can be set from 0 to 120 seconds. It tells the combustion control system to wait a specified period of time for the device started by the Aux Relay to come up to speed, open or make a proving switch. Once the waiting period expires, the start sequence will resume. Should the device not prove within the preset time interval, the unit will shut down and generate an alarm.
feature works in
1.3.8

Failsafe Mode

whether the unit shuts down or switches to the Constant Setpoint mode of operation in the event that a loss of signal causes the unit to become inoperable. For example, if a 4 to 20 mA Remote Setpoint signal is being sent, but is not seen by the unit, the unit will shut down or automatically switch to the Constant Setpoint mode and work off the unit’s internal setpoint. The default setting for this option is Shutdown.

1.3.9 RS232 Monitoring

This feature allows a laptop co suitable device to be connected to the RS232 port on the Control Panel front panel. This permits the unit to be monitored either locally or remotely via a Modem.

1.3.10 Aux Temp

This feature permits a connected to the Aux Sensor In terminals in the I/O Box. The sensor must be within the resistance range used with the C-More Control system. It can be used to monitor the user’s parameter of choice. This feature is always enabled. This is strictly a monitoring function and plays no role in control of the unit.

1.4 CONTROL PANEL DESCRIPTION

The C-More Control Panel is available in t models. One model has a horizontal panel control layout as shown in Figure 1-1A and is used on KC Series units. The other model has a vertical panel control layout as shown in Figure 1-1B and is used on Benchmark Series units. These models contain identical controls, indicators and displays and are functionally identical. These controls, indicators and displays are listed and described in Table 1-1.
ailsafe mode allows
temperature sensor to be
the user to select
mputer or other
wo
2
C-MORE CONTROL PANEL OPERATION
Figure 1-1A. C-More Control Panel For KC Series Units
12
10
7
11
3
1
2
4
8
9
5
6
Figure 1-1B. C-More Control Panel For Benchmark Series Units
3
C-MORE CONTROL PANEL OPERATION
Table 1-1. Operating Controls, Indicators and Displays
ITEM
NO.
CONTROL, INDICATOR
OR DISPLAY
1 LED Status Indicators Four Status LEDs indicate the current operating status as
follows:
COMM
MANUAL
REMOTE
DEMAND
2 VFD Display Vacuum Fluorescent Display (VFD) consists of 2 lines each
OUTLET
3
TEMPERATURE
Display
RS232 Port
4
READY Indicator
5
ON/OFF Switch
6
LOW WATER LEVEL
7
TEST/RESET Switches
FAULT Indicator Red FAULT LED indicator lights when a boiler alarm
8
CLEAR Key
9
10 MENU Keypad Consists of 6 keys which provide the following functions for
MENU
BACK
Lights when RS232 communication is occurring Lights when the unit is being controlled using the front panel
keypad. Lights when the unit is being controlled by an external signal
from an Energy Management System Lights when there is a demand for heat.
capable of displaying up to 16 alphanumeric characters. The information displayed includes:
Startup Messages Alarm Messages Operating Status Messages Menu Selections
3–Digit, 7–Segment LED display continuously displays the outlet water temperature. The °F or °C LED next to the display lights to indicate whether the displayed temperature is in degrees Fahrenheit or degrees Celsius.
Port permits a Laptop Computer or External Modem to be connected to the unit’s Control Panel.
Lights when ON/OFF switch is set to ON and all Pre-Purge conditions have been satisified.
Enables and disables boiler operation.
Allow the operator to test the operation of the water level monitor.
Pressing TEST opens the water level probe circuit and simulates a Low Water Level alarm.
Pressing RESET resets the water level monitor circuit. Pressing CLEAR resets the display.
condition occurs. An alarm message will appear in the VFD.
Turns off the FAULT indicator and clears the alarm message if the alarm is no longer valid. Lockout type alarms will be latched and cannot be cleared by simply pressing this key. Troubleshooting may be required to clear these types of alarms
the Control Panel Menus: Steps through the main menu categories shown in Figure 2-1.
The Menu categories wrap around in the order shown. Allows you to go back to the previous menu level without
changing any information. Continuously pressing this key will bring you back to the default status display in the VFD. Also, this key allows you to go back to the top of a main menu category.
FUNCTION
4
ITEM
NO.
10
(Cont.)
C-MORE CONTROL PANEL OPERATION
Table 1-1. Operating Controls, Indicators and Displays - Continued
CONTROL, INDICATOR
OR DISPLAY
(Up) Arrow When in one of the main menu categories (Figure 1-2),
pressing this key will select the displayed menu category. If the CHANGE key was pressed and the menu item is flashing, pressing the arrow key will increment the selected setting.
(Down) Arrow When in one of the main menu categories (Figure 1-2),
pressing this key will select the displayed menu category. If the CHANGE key was pressed and the menu item is flashing, pressing the (Down) arrow key will increment the selected setting.
FUNCTION
CHANGE
ENTER
11
12
AUTO/MAN Switch
FIRE RATE Bargraph
Permits a setting to be changed (edited). A valid password must be entered before changing most menu items. When the CHANGE key is pressed, the displayed menu item will begin to flash. Pressing the or arrow key when the item is flashing will increment or decrement the displayed setting.
Saves the modified menu information in memory. The display will stop flashing.
This switch toggles the boiler between the Automatic and Manual modes of operation. When in the Manual (MAN) mode, the front panel controls are enabled and the MANUAL status LED lights.
When in the Automatic (AUTO) mode, the MANUAL status LED will be off and the front panel controls disabled.
20 segment red LED bargraph continuously shows the Fire Rate in 5% increments from 0 to 100%
5
C-MORE CONTROL PANEL OPERATION

SECTION 2 - CONTROL PANEL MENU STRUCTURE

2.1 CONTROL PANEL MENUS

The Control Panel incorporates an extensive menu structure which permits the operator to set up, and configure the unit. The menu structure consists of six major menu categories as shown in Figure 2-1. Each of the menus shown, contain options which permit operating parameters to be viewed or changed. The menus are protected by two different password levels to prevent unauthorized use.
Password Level 1 allows viewing of all menu categories and also allows the Setup, Configuration and Tuning Menu options to be changed.
Password Level 2 allows viewing and changing of all Level 1 menu categories and also allows access to the Calibration and Diagnostic Menus. These two additional menu categories should only be used by factory trained personnel to calibrate and troubleshoot the unit.
A third Password Level called the Factory Password also exists. However, access to this menu is restricted to Factory Authorized personnel only.
Prior to entering the correct password, the options contained in the Operating, Setup, Configuration and Tuning Menu categories can be viewed. However, except for Internal Setpoint Temperature (Configuration Menu), none of the viewable menu options can be changed.
Once the valid Level 1 (159) or Level 2 (6817) password is entered, the options listed in the available menus can be viewed and changed, if desired.
2. Press the MENU key. The display will show the Setup Menu which is the next menu category shown in Figure 2-1. This menu contains the Password option which must be entered if other menu options will be changed.
3. Continue pressing the MENU key until the desired menu is displayed.
4. With the desired menu displayed, press the or arrow key. The first option in the selected menu will be displayed.
OPERATING
LEVEL 1 PWD
SETUP
CONFIGURATION
TUNING
LEVEL 2 PWD
CALIBRATION

2.2 MENU PROCESSING PROCEDURE

Accessing each menu and option is accomplished using the Menu Keys shown in Figure 1-1. Therefore, it is imperative that you be thoroughly familiar with the following basic steps before attempting to perform specific menu processing procedures.
1. The Control Panel will normally be in the Operating Menu and the VFD will display the current unit status. Pressing the or arrow key will display the other available data in the Operating Menu.
6
DIAGNOSTICS
Figure 2-1. Menu Structure
C-MORE CONTROL PANEL OPERATION
5. Continue pressing the ▲or ▼ arrow key until the desired menu option is displayed. Pressing the arrow key will display the available menu options in the Top-Down sequence. Pressing the arrow key will display the options in the Bottom-Up sequence. The menu options will wrap­around after the first or last available option.
6. To change the value or setting of a displayed menu option, press the CHANGE key. The displayed option will begin to flash. Press the or arrow key to scroll through the available menu option choices for the option to be changed. The menu option choices do not wrap around.
7. To select and store a changed menu option, press the ENTER key.
NOTE:
Paragraphs 2.3 through 2.8 provide brief descriptions of the options contained in each menu. Refer to Section 3 for detailed descriptions of each menu option.

2.3 OPERATING MENU

The Operating Menu displays the unit status and a number of key operating parameters for the unit as listed in Table 2-1. This menu is “Read­Only” and does not allow personnel to change or adjust any of the displayed items. Since this
menu is “Read-Only”, it can be viewed at any time without entering a password. Press the arrow key to display the menu item in the order listed (Top-Down). Pressing the arrow key will display the menu items in reverse order (Bottom-Up).

2.4 SETUP MENU

The Setup Menu (Table 2-2) permits the operator to set the unit password which is required to change any of the menu options. To prevent unauthorized use, a previously entered password entry will time-out after 1 hour.
Therefore, the password must be reentered when required. In addition to permitting password entries, the Setup Menu is also used to enter date and time, language to be used for display messages, units of temperature measurements and entries required for external communication and control of the unit via the RS232 port. A view-only software version display is also provided to indicate the current Control Box software version,
NOTE
The Outdoor Temp display item shown with an asterisk in Table 2-1 will not be displayed unless the Outdoor Sensor function has been enabled in the Configuration Menu (Table 2-3).
Table 2-1. Operating Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Status Message Active Setpoint 40°F 240°F Aux Temp 30°F 245°F Outdoor Temp* -70°F 130°F Fire Rate In 0% Max Fire Rate Flame Strength 0% 100% Run Cycles 0 999,999 Run Hours 0 999,999 Fault Log 0 9 0
7
C-MORE CONTROL PANEL OPERATION
Table 2-2. Setup Menu
Available Choices or Limits Menu Item Display Minimum Maximum Default
Passsword Level 1 = 159 Level 2 = 6817 Language English English Time 12:00 am 11:59 pm Date 01/01/00 12/31/99 Unit of Temp Fahrenheit
Comm Address 0 127 0 Baud Rate 2400
Software Ver 0.0 Ver 9.9

2.5 CONFIGURATION MENU

The Configuration Menu shown in Table 2-3 permits adjustment of the Internal Setpoint (Setpt) temperature regardless of whether the valid password has been entered. Setpt is required for operation in the Constant Setpoint mode. The remaining options in this menu require the valid password to be entered, prior to changing existing entries. This menu contains a number of other configuration settings which may or may not be displayed, depending on the current operating mode setting.
0 9999 0
Celsius
4800 9600
19.2K
The Configuration Menu settings shown in Table 2-3 are Factory-Set in accordance with the requirements specified for each individual order. Therefore, under normal operating conditions, no changes will be required.
Fahrenheit
9600
NOTE:
8
C-MORE CONTROL PANEL OPERATION
Table 2-3. Configuration Menu
Available Choices or Limits Menu Item Display Minimum Maximum Default
Internal Setpt Lo Temp Limit Hi Temp Limit 130°F Unit Type Boiler
Unit Size 0.5 MBTU
Boiler Mode (If Unit Type = Boiler)
Heater Mode (If Unit Type = Water Heater) Remote Signal (If Mode = Remote Setpoint, Direct Drive or Combination)
Bldg Ref Temp (If Boiler Mode = Outdoor Reset) Reset Ratio (If Boiler Mode = Outdoor Reset) Outdoor Sensor Enabled or Disabled Disabled System Start Tmp (If Outdoor Sensor = Enabled) Setpt Lo Limit 40°F Setpt Hi Limit 60°F Setpt Hi Limit Setpt Lo Limit 240°F 200°F Temp Hi Limit 40°F 240°F 210°F Max Fire Rate 40% 100% 100% Pump Delay Timer (If Unit Type = Boiler) Aux Start On Dly 0 sec 120 sec 0 sec Failsafe Mode Shutdown or Constant Setpt Shutdown mA Output Setpoint
Low Fire Timer 2 sec 120 sec 2 sec Setpt Limiting Enabled or Disabled Disabled Setpt Limit Band 0°F 10°F 5°F
Boiler
Water Heater
1.0 MBTU
1.0 MBTU
1.5 MBTU
2.0 MBTU
2.5 MBTU
3.0 MBTU
Constant Setpoint
Remote Setpoint
Direct Drive
Combination
Outdoor Reset
Constant Setpoint
Remote Setpoint
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
40°F 230°F 70°F
0.1 9.9 1.2
30°F 100°F 60°F
0 min 30 min 0 min
Outlet Temp
Fire Rate Out
Off
Constant Setpoint
Constant Setpoint 4 to 20 mA/ 1-5V
Off
9
C-MORE CONTROL PANEL OPERATION

2.6 TUNING MENU

The Tuning Menu items in Table 2-4 are Factory set for each individual unit. Do not change these menu entries unless specifically requested to do so by Factory-Trained personnel.
The Breakpoint Menu items shown in the following Table with an asterisk are displayed only if Unit Type = Water Heater and the Heatr Bkpt Dsp option in the Calibration Menu (Table 2-5) is Enabled. These Breakpoint values correspond to a 130°F default setpoint
Table 2-4. Tuning Menu
Available Choices or Limits Menu Item Display Minimum Maximum Default
Prop Band 1°F 120°F 70°F (Boiler)
Integral Gain 0.00 2.00 1.00 (Boiler)
Derivative Time (If Unit Type = Boiler) Min Load Adj (If Unit Type = Water Heater) Max Load Adj (If Unit Type = Water Heater) FFWD Temp (If Unit Type = Water Heater) Outlet Feedback (If Unit Type = Water Heater) Feedback Gain (If Unit Type = Water Heater & Heatr Tuning Dsp is Enabled) Breakpt at 100%* 30°F 240°F 77°F Breakpt at 90%* 30°F 240°F 81°F Breakpt at 80%* 30°F 240°F 85°F Breakpt at 70%* 30°F 240°F 91°F Breakpt at 60%* 30°F 240°F 95F Breakpt at 50%* 30°F 240°F 102F Breakpt at 40%* 30°F 240°F 110°F Breakpt at 30%* 30°F 240°F 112°F Breakpt at 20%* 30°F 240°F 114°F Breakpt at 10%* 30°F 240°F 130°F Breakpt at 0%* 30°F 240°F 135°F Reset Defaults? Yes
0.00 min 2.00 min 0.00 min (Boiler)
-50°F 50°F 0°F
-50°F 50°F 0°F
30°F 245°F
.01 1.00 0.05
Are You Sure?
NOTE
On (Yes)
Off (No)
No
8°F (Water Heater)
1.60 (Water Heater)
0.10 min (Water Heater)
On (Yes)
No
10
C-MORE CONTROL PANEL OPERATION

2.7 CALIBRATION MENU

The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the parameters listed in Table 2-5.
Table 2-5. Calibration Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Stepper Fbk (Not adjustable via RS232 serial communication) PWM In Adj -5.0% 5.0% 0.0% Analog In Adj -5.0% 5.0% 0.0% Flow In Adj -5.0% 5.0% 0.0% CO In Adj -5.0% 5.0% 0.0% O2 In Adj -5.0% 5.0% 0.0% mA Out Adj -1.0 mA 1.0 mA 0.0 mA A/F Sensitivity 1% 5% 2% Power Reset Automatic
Water Temp Reset Automatic
Gas Press Reset Automatic
Min Off Time 0 Min 15 Min 1 Min (Boiler)
Heatr Tuning Dsp (If Unit Type = Water Heater) Heatr Bkpt Dsp (If Unit Type = Water Heater) Stop Level 0% Start Level 16 Start Level Stop Level 40% 20
Cal 100%
Verify 50%
Enabled or Disabled Disabled
Enabled or Disabled Disabled
Cal 0%
Manual
Manual
Manual
Cal 0%
Automatic
Automatic
Manual
0 Min (Water Heater)

2.8 DIAGNOSTICS MENU

The Diagnostics Menu shown in Table 2-6 is used by Factory-Trained Service personnel to troubleshoot the unit. This menu category contains a number of Built In Test (BIT) test routines to be used to check the operational status of the Control Panel displays and keypad keys. It also allows the operator to activate relays, view switch status and increment the stepper motor contained in the Air/Fuel Valve.
NOTE
With the exception of the Sensor Log Interval (Int) setting, none of the following Diagnostic Menu items can be initiated via a remote serial communications link.
11
C-MORE CONTROL PANEL OPERATION
Table 2-6. Diagnostics Menu
Available Choices or Limits Menu Item Display Minimum Maximum Default
Display Test Off
LEDs
7-Seg
Bar-graph
Keypad Test Off
Manual, Menu
Up, Down
Change, Enter
Clear
(Back Key exits test mode) Relay Test (Allows user to force outputs ON or OFF)
Switch Test (Allows user to view the status of all switch inputs)
Stepper Test (Allows user to adjust the stepper motor position using
the and keys) Sensor Log Int
(Allows user to set the time interval for logging Sensor inputs in Database)
Igniter ON/Igniter OFF
Blower ON/Blower OFF
Pump ON/Pump OFF
Aux ON/Aux OFF
Fault ON/Fault OFF
Exhaust sw ON/Exhaust sw OFF
SSOV sw ON/SSOV sw OFF
Blower Proof ON/Blower Proof OFF
Ignition sw ON/Ignition sw OFF
Over Temp sw ON/Over Temp sw OFF
Low Gas Pres ON/Low Gas Pres OFF
Hi Gas Pres ON/Hi Gas Pres OFF
Water Lev sw ON/Water Lev sw OFF
Rem Int sw ON/Rem Int sw OFF
Front Pnl sw ON/Front Pnl sw OFF
Delayed Int ON/Delayed Int OFF
Purge sw ON/Purge sw OFF
0% 100% 0%
12 Hrs, or 24 Hrs
Off
Off
Off
1 Min, 5 Min
15 Min, 30 Min
1 Hr, 6 Hrs
Off
Off
Off
Off
30 Min.
12
C-MORE CONTROL PANEL OPERATION

SECTION 3 - CONTROL PANEL MENU DESCRIPTIONS

3.1 MENU ITEM DESCRIPTIONS

Descriptions of the menu items and options contained in each of the six major menu categories are listed and described in Table 3-1. Factory Default values for each of these items are summarized in Table 3-2.

3.2 FACTORY DEFAULTS

The factory default values for each menu item are summarized in Table 3-2.
Table 3-1. Menu Item Descriptions
MENU LEVEL & OPTION DESCRIPTION
OPERATING MENU Active Setpoint This is the setpoint temperature to which the control
is operating when operating in the Constant Setpoint, Remote Setpoint or Outdoor Reset (Boiler Only) Mode. When in the Constant Setpoint Mode, this value is equal to the Internal Setpoint setting in the Configuration Menu. When in the Remote Setpoint Mode, this value is the setpoint equivalent to the remote analog signal supplied to the unit. When operating a Boiler in the Outdoor Reset Mode, this is
the derived value from the charts in Appendix C. Aux Temp For monitoring purposes only Outdoor Temp Displayed only if outdoor sensor is installed and
enabled. Fire Rate In Desired input fire rate. This would normally be the
same as the fire rate shown on the bar-graph (fire
rate out) when the boiler is operating. Flame Strength Displays flame strength from 0 to 100%. Run Cycles Displays the total number of run cycles from 0 to
999,999. Run Hours Displays total run time of unit in hours from 0 to
999,999. Fault Log Displays information on the last 10 faults (numbered
0 through 9).
13
C-MORE CONTROL PANEL OPERATION
Table 3-1. Menu Item Descriptions - Continued
MENU LEVEL & OPTION DESCRIPTION
SETUP MENU
Password
Level 1
Level 2
Language English is the ONLY language available Time Displays time from 12:00am to 11:59pm. Date Displays dates from 01/01/00 to 12/31/99 Unit of Temp Permits selection of temperature displays in degrees
Comm Address For RS485 MODBUS communications (0 to 127).
Baud Rate Allows the RS232 communication Baud Rate to be
Software Version Identifies the current software version of the control
Allows Level 1 or 2 password to be entered.
Entering the Level 1 Password (159) allows options in
the Setup, Configuration and Tuning Menus to be
modified.
Entering the Level 2 Password (6817) allows options
in the Calibration and Diagnostics Menus to be
changed/activated, in addition to all Level 1 Menu
options.
Fahrenheit (°F) or degrees Celsius (°C). Default is
°F.
Default address is 0.
set (2400 to 19.2K). Default is 9600.
box (Ver 0.0 to Ver 9.9).
CONFIGURATION MENU Internal Setpoint Allows internal setpoint to be set (40°F to 240°F).
Unit Type Allows selection of Boiler or Water Heater. Default is
Unit Size Sets unit size from 0.5 to 3.0 MBTUs. Default is 1.0
Boiler Mode (If Unit Type = Boiler)
Heater Mode (If Unit Type = Water Heater) Remote Signal (If Mode = Remote Setpoint,
Direct Drive or Combination)
Bldg Ref Temp (If Boiler Mode = Outdoor
Reset)
Default is 130°F.
Boiler.
MBTU.
Allows selection of: Constant Setpoint, Remote
Setpoint, Direct Drive, Combination, or Outdoor Reset
Mode. Default is Constant Setpoint Mode.
Allows selection of Constant Setpoint or Remote
Setpoint Mode. Default is Constant Setpoint Mode.
Used to set the type of external signal which will be
used when operating in the Remote Setpoint, Direct
Drive or Combination Mode. Default is 4 to 20 mA /
1 to 5V.
Allows the building reference temperature to be set
when operating a Boiler in the Outdoor Reset Mode.
Default is 70°F
14
C-MORE CONTROL PANEL OPERATION
Table 3-1. Menu Item Descriptions - Continued
MENU LEVEL & OPTION DESCRIPTION
CONFIGURATION MENU
(Continued) Reset Ratio (If Boiler Mode = Outdoor
Reset) Outdoor Sensor Allows outdoor sensor function to be enabled or
System Start Tmp (If Outdoor Sensor is Enabled)
Setpoint Lo Limit Used to set the minimum allowable setpoint (40°F to
Setpoint Hi Limit Used to set the maximum allowable setpoint (Setpoint
Temp Hi Limit This is the maximum allowable outlet temperature
Max Fire Rate Sets the maximum allowable fire rate for the unit
Pump Delay Timer (If Unit Type = Boiler)
Aux Start On Dly Specifies the amount of time to wait (0 to 120 sec.)
Failsafe Mode Allows the Failsafe Mode to be set to either Constant
mA Output Can be set to allow this output to monitor Setpoint,
Low Fire Timer Specifies how long (2 to 120 sec.) to remain in the
Setpt Limiting Allows Setpt Limiting to be enabled or disabled.
Setpt Limit Band When Setpt Limiting is enabled, this menu item
Permits setting of Reset Ratio when operating Boiler
in the Outdoor Reset Mode. Reset Ratio is
adjustable from 0.1 to 9.9. Default is 1.2.
disabled. Default is Disabled.
If outdoor sensor is enabled, this menu item allows
the system start temperature to be set from 30°F to
100°F. Default is 60°F.
Setpoint Hi Limit). Default is 60°F
Lo Limit to 240°F). Default is 200°F.
(40°F to 240°F). Any temperature above this setting
will turn off the unit. The temperature must then drop
5°F below this setting to allow the unit to run. Default
Hi Limit is 210°F.
(40% to 100%). Default is 100%.
Specifies the amount of time (0 to 30 min.) to keep
the pump running after the unit turns off. Default is
zero.
between activating the Aux Relay (due to a demand)
and checking the pre-purge string to start the unit.
Default is 0 sec.
Setpoint or Shutdown. Default is Shutdown.
Outlet Temperature, Fire Rate Out, or be set to OFF.
Default is OFF.
low fire position after ignition, before going to the
desired output. Default is 2 sec.
Default is disabled.
allows the Setpt Limit Band to be set from 0°F to
10°F. Default is 5°F.
15
C-MORE CONTROL PANEL OPERATION
MENU LEVEL & OPTION DESCRIPTION
`Table 3-1. Menu Item Descriptions - Continued
TUNING MENU
Prop Band Generates a fire rate based on the error that exists
Integral Gain This sets the fraction of the output, due to setpoint
Derivative Time This value (0.00 to 2.00 min.) responds to the rate of
Min Load Adj (If Unit Type = Water Heater)
Max Load Adj (If Unit Type = Water Heater)
FFWD Temp (If Unit Type = Water Heater) Outlet Feedback Used to Enable or Disable feedback. Disable this
Feedback Gain (If Unit Type = Water Heater) Breakpoint at 100% Thru Breakpoint at 0% (If Unit Type = Water Heater)
Reset Defaults? Resets Tuning Menu options to Factory Defaults
between the setpoint temperature and the actual outlet temperature. If the actual error is less than the proportional band setting (1 to 120°F), the fire rate will be less than 100%. If the error is equal to or greater than the proportional band setting, the fire rate will be 100%. Defaults are 70°F (Boiler), 8°F (Water Heater)
error, to add or subtract from the output each minute to move towards the setpoint. Gain is adjustable from 0.00 to 2.00 (Defaults are 1.00 for Boilers, 1.60 for Water Heaters).
change of the setpoint error. This is the time that this action advances the output. (Defaults are 0.0 min. for Boilers, 0.10 min. for Water Heaters)
Setting is adjustable from -50°F to +50°F (Default is zero). It adjusts the output by adding an offset to the breakpoint chart at minimum flow. This is used to fine tune Feed-Forward (FFWD) output at low flow levels.
Setting is adjustable from -50°F to +50°F (Default is zero). It adjusts the output by changing the scaling of the breakpoint chart at maximum flow.
Displays the Feed-Forward temperature.
function for Feed-Forward control only. Adjustable from 0.01 to 1.00 (Default is 0.05).
Allows breakpoint temperature settings to be entered for 100% to 0% in 10% increments. The Bkpt Dsp options in the Calibration Menu must be enabled to view breakpoint temperatures. See Table 2-4 for breakpoint default values.
16
C-MORE CONTROL PANEL OPERATION
Table 3-1. Menu Item Descriptions – Continued
MENU LEVEL & OPTION DESCRIPTION
CALIBRATION MENU
Stepper Fbk (Not adjustable via RS232
serial communication)
PWM In Adj Allows the Pulse Width Modulation (PWM) duty cycle
Analog In Adj Allows adjustment of the analog input from -5.0% to
Flow In Adj Allows adjustment of the water Flow Rate Input from
CO In Adj Allows adjustment of the Carbon Monoxide level from
O2 In Adj Allows adjustment of the Oxygen level from -5.0% to
mA Out Adj Allows adjustment of the milliamp output from -5.0
A/F Sensitivity Allows adjustment of the Air/Fuel (A/F) Valve stepper
Power Reset Allows the Power Reset Option to be set to Auto or
Water Temp Reset Allows the Water Temperature Reset function to be
Gas Press Reset Allows the Gas Pressure Reset function to be set to
Min Off Time Allows the minimum Off time to be set from 0 to 10
Heatr Tuning Dsp (Water Heater Only)
Heatr Bkpt Dsp Allows Heater Breakpoint Display to be Enabled or
Stop Level Allows the Stop Level to be set to a firing rate ranging
Start Level Allows the Start Level to be set to a firing rate ranging
Allows the Air/Fuel Valve stepper motor feedback
current to be calibrated at the 0% (fully closed) and
100% (fully open) positions. Verification can also be
accomplished at the 50% position.
to be adjusted from -5.0% to +5.0% in 0.1%
increments. Default = 0.0%.
+5.0%. Default = 0.0%.
-5.0% to +5.0%. Default = 0.0%.
-5.0% to +5.0% in 0.1 % increments. Default = 0.0%.
+5.0% in 0.1% increments. Default = 0.0%
mA to +5.0 mA. Default = 0.0 mA
motor sensitivity to be adjusted from 1% to 5% in 1%
increments. Default is 2%.
Manual. Default is Auto.
set to Auto or Manual. Default is Auto.
Auto or Manual. Default is Manual.
minutes. Default = 1 min.(Boiler), 0 min. (Water
Heater).
Allows Heater Tuning Display to be Enabled or
Disabled. Default is Disabled.
Disabled. When Enabled, Breakpoints can be viewed
and/or changed. Default is Disabled.
from 0% to the presently set Start Level. Default is
16%.
from the presently set Stop Level to a maximum of
40%. Default is 20%.
17
C-MORE CONTROL PANEL OPERATION
Table 3-1. Menu Item Descriptions – Continued
MENU LEVEL & OPTION DESCRIPTION
DIAGNOSTICS MENU
Display Test*
Keypad Test*
Relay Test*
Switch Test*
Stepper Test*
Sensor Log Int Allows the Sensor Log Interval to be set to: 1 Min, 5
* Not adjustable via RS232 serial communication
Allows testing of the front panel LED indicators, 3­character, 7-segment LED display and 20-segment LED Bargraph.
Allows testing of the operational status of each front panel key. The VFD will display the name of each key as it is pressed.
Allows user to force relay outputs ON or OFF. The relays tested include: Igniter, Blower, Pump, Aux and Fault relay.
Allows the ON/OFF status of all switch inputs to be viewed. These switches include: Exhaust, SSOV, Blower Proof, Ignition, Over-Temp, Low Gas Pres, Hi Gas Pres, Water Lev, Rem Int, Front Pnl, Delayed Int and Purge switches.
Allows adjustment of the Air/Fuel Valve stepper motor position using the and keys. The Bargraph
display will light to indicate the current stepper motor position.
Min, 15 Min, 30 Min, 1 Hr, 6 Hrs, 12 Hrs or 24 Hrs. Default setting is 30 Min.
18
Table 3-2. Default Settings
MENU & OPTION
Setup Menu
Password Language Unit of Temp Comm Address Baud Rate
Configuration Menu
Internal Setpt Unit Type Unit Size Boiler Mode
(If Unit Type = Boiler) Heater Mode
(If Unit Type = Water Heater) Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
Bldg Ref Temp (If Boiler Mode = Outdoor Reset)
Reset Ratio (If Boiler Mode = Outdoor Reset)
Outdoor Sensor System Start Tmp
(If Outdoor Sensor = Enabled) Temp Hi Limit Max Fire Rate Pump Delay Timer (If Unit Type = Boiler) Aux Start On Dly Failsafe Mode mA Output Low Fire Timer Setpt Limiting Setpt Limit Band
Tuning Menu
Prop Band Integral Gain Derivative Time Min Load Adj (If Unit Type = Water Heater) Max Load Adj (If Unit Type = Water Heater) FFWD Temp Adj (If Unit Type = Water Heater) Outlet Feedback (If Unit Type = Water Heater) Feedback Gain (If Unit Type = Water Heater)
C-MORE CONTROL PANEL OPERATION
FACTORY DEFAULT
0
English
Fahrenheit
0
9600
130°F Boiler
1.0 MBTU
Constant Setpoint
Constant Setpoint
4 – 20 mA / 1-5V
70°F
1.2
Disabled
60°F
210°F 100%
0 min 0 sec
Shutdown
Off
2 sec
Disabled
5°F
70°F (Boiler), 8°F (Water Heater)
1.00 (Boiler), 1.60 (Water Heater)
0.00 min (Boiler), 0.10 min (Water Heater) 0°F 0°F
N/A
On
0.05
19
C-MORE CONTROL PANEL OPERATION
Table 3-2. Default Settings – Continued
MENU & OPTION
Breakpoint At 100% (If Unit Type = Water Heater) Breakpoint At 90% (If Unit Type = Water Heater) Breakpoint At 80% (If Unit Type = Water Heater) Breakpoint At 70% (If Unit Type = Water Heater) Breakpoint At 60% (If Unit Type = Water Heater) Breakpoint At 50% (If Unit Type = Water Heater) Breakpoint At 40% (If Unit Type = Water Heater) Breakpoint At 30% (If Unit Type = Water Heater) Breakpoint At 20% (If Unit Type = Water Heater) Breakpoint At 10% (If Unit Type = Water Heater) Breakpoint At 0% (If Unit Type = Water Heater) Reset Defaults?
Calibration Menu
Stepper Fbk PWM Adj Analog In Adj Flow In Adj CO In Adj O2 In Adj mA Out Adj A/F Sensitivity Power Reset Water Temp Reset Gas Press Reset Min Off Time Heatr Tuning Dsp (If Unit Type = Water Heater) Heatr Bkpt Dsp (If Unit Type = Water Heater) Stop Level Start Level
Diagnostics Menu
Display Test Keypad Test Relay Test Switch Test Stepper Test Sensor Log Int
FACTORY DEFAULT
77°F 81°F 85°F 91°F
95°F 102°F 110°F 112°F 114°F 130°F 135°F
No
Cal 0%
0.0%
0.0%
0.0%
0.0%
0.0%
0.0 mA 2%
Auto Auto
Manual
1 Min (Boiler), 0 Min (Water Heater)
Disabled Disabled
16 20
Off Off Off Off
0%
30 min.
20
C-MORE CONTROL PANEL OPERATION

SECTION 4 - CONTROL PANEL DISPLAY MESSAGES

4.1 STARTUP & STATUS MESSAGES.

Startup and status messages are displayed on the VFD display on the front panel of the C-More Control Panel. This display is comprised of two lines with 16 characters per line. The startup and status messages which may appear in the display are listed in Tables 4-1.
.2
4
Table 4-1. Startup and Status Messages
MESSAGE DESCRIPTION
DISABLED
HH:M D/YY
M pm MM/D
STANDBY
DEM AY AND DEL
XX sec
P
URGING Displayed during the purge cycle during startup. The
XX sec
IGNI IAL
TION TR Displayed during ignition trial of startup sequence. The
XX sec
FLAME PROVEN
W he initial warm-up only. ARMUP
XX sec
WAIT Prompts the oper tor to wait. a
Displayed if ON/OFF switch is set to OFF. The displ shows the time and date that the unit was disabled. Displayed when ON/OFF switch is in the ON position, but there is no demand for heat. The time displayed. Displayed if Demand Delay is active.
duration of the purge cycle counts up in seconds.
duration of cycle counts up in seconds. Displayed after flame has been detected for a period of 2 seconds. Initially, the flame strength is shown in %. After 5 seconds has elaps of flame strength. Displayed for 2 minutes during t

FAULT MESSAGES.

Fault messages which may appear in the VFD display are listed in Table 4-2.
ay also
and date are also
ed, the time and date are shown in place
21
C-MORE CONTROL PANEL OPERATION
Table 4-2. Fault Messages
FAULT MESSAGE FAULT DESCRIPTION
HIGH WATER TEMP
SWITCH OPEN
LOW WATER
LEVEL
LOW GAS
PRESSURE
HIGH GAS
PRESSURE
INTERLOCK
OPEN
DELAYED
INTERLOCK OPEN
AIRFLOW FAULT
DURING PURGE
PRG SWTCH OPEN
DURING PURGE
IGN SWTCH OPEN
DURING IGNITION
IGN SWTCH CLOSED
DURING PURGE
PRG SWTCH CLOSED
DURING IGNITION
AIRFLOW FAULT
DURING IGN
AIRFLOW FAULT
DURING RUN
SSOV
SWITCH OPEN
SSOV FAULT
DURING PURGE
SSOV FAULT
DURING IGN
SSOV FAULT DURING RUN SSOV RELAY
FAILURE
FLAME LOSS
DURING IGN FLAME LOSS DURING RUN
HIGH EXHAUST TEMPERATURE
The High Water Temperature Limit Switch is open.
The Water Level Control board is indicating low water level.
The Low Gas Pressure Limit Switch is open.
The High Gas Pressure Limit Switch is open.
The Remote Interlock is open.
The Delayed Interlock is open.
The Blower Proof Switch opened during purge.
The Purge Position Limit switch on the air/fuel valve opened during purge. The Ignition Position Limit switch on the air/fuel valve opened during ignition. The Ignition Position Limit switch on the air/fuel valve closed during purge. The Purge Position Limit switch on the air/fuel valve closed during ignition. The Blower Proof Switch opened during ignition.
The Blower Proof Switch opened during run.
The SSOV switch opened during standby.
The SSOV switch opened during purge.
The SSOV switch closed or failed to open during ignition.
The SSOV switch closed for more than 15 seconds during run. A failure has been detected in one of the relays that control the SSOV. The Flame signal was not seen during ignition or lost within 5 seconds after ignition. The Flame signal was lost during run.
The High Exhaust Temperature Limit Switch is closed.
22
C-MORE CONTROL PANEL OPERATION
Table 4-2. Fault Messages - Continued
FAULT MESSAGE
RESIDUAL
FLAME
HEAT DEMAND
FAILURE
IGN BOARD
COMM FAULT
DIRECT DRIVE SIGNAL FAULT
REMOTE SETPT
SIGNAL FAULT
OUTDOOR TEMP
SENSOR FAULT
OUTLET TEMP
SENSOR FAULT
FFWD TEMP
SENSOR FAULT
HIGH WATER
TEMPERATURE
LINE VOLTAGE
OUT OF PHASE
STEPPER MOTOR
FAILURE
MODBUS COMM
FAULT
The Flame signal was seen for more than 30 seconds during standby. The Heat Demand Relay on the Ignition/Stepper (IGST) board failed to activate when commanded. A communication fault has occurred between the Primary Micro-Controller (PMC) board and Ignition/Stepper (IGST) board. The direct drive signal is not present or is out of range.
The remote setpoint signal is not present or is out of range.
The temperature measured by the Outdoor Air Sensor is out of range. The temperature measured by the Outlet Sensor is out of range. The temperature measured by the Feed-Forward (FFWD) Sensor is out of range. The temperature measured by the Outlet Sensor exceeded the Temp Hi Limit setting. The High AC voltage is out of phase from the low AC voltage.
The stepper motor failed to move the valve to the desired position. The RS485 (MODBUS) network information is not present or is corrupted.
FAULT DESCRIPTION
23
C-MORE CONTROL PANEL OPERATION

SECTION 5 - INPUT/OUTPUT INTERFACES & OPERATING MODES

5.1 INTRODUCTION

This Section provides descriptions of the Input/Output (I/O) wiring connections which can be made at the Input/Output (I/O) Box included with the C-More Control Panel. For KC Series units, the I/O Box is located on the left side of the unit. For Benchmark Series units, the I/O Box is located on the front of the unit behind the door.
Also included in this Section are descriptions of the available operating modes which can be set up for Water Heaters and Boilers utilizing the C­More menus.

5.2 I/O INTERFACES

All wiring connections are made at the terminal strips contained in the I/O Box. The I/O Box cover contains a connection diagram as shown in Figure 5-1. Refer to this diagram when making all field wiring connections to the I/O Box. The connections shown in Figure 5-1 are described in the following paragraphs.
CAUTION!
DO NOT make any connections to the I/O Box terminals labeled “NOT USED”. Attempting to do so may cause equipment damage.

5.2.1 OUTDOOR SENSOR IN

An outdoor air temperature sensor (AERCO Part No. 122790) will be required mainly for the Indoor/Outdoor Reset Mode of operation for boilers. It can also be used with another mode if it is desired to use the outdoor sensor enable/disable feature. This feature allows the boiler to be enabled or disabled based on the outdoor air temperature. The factory default for the outdoor sensor is DISABLED. To enable the sensor or choose a system start temperature, see the Configuration Menu in Table 2-3.
The outdoor sensor may be wired up to 200 feet from the boiler. It is connected to the OUTDOOR SENSOR IN and SENSOR COMMON terminals in the I/O Box (see Figure. 5-1). Wire the sensor using a twisted shielded pair cable of 18-22 AWG wire. There is no polarity to observe when
terminating the wires. The shield is to be connected only to the terminals labeled SHEILD in the I/O Box. The sensor end of the shield must be left free and ungrounded.
When mounting the sensor, it must be located on the North side of the building where an average outside air temperature is expected. The sensor must be shielded from direct sunlight as well as impingement by the elements. If a shield is used, it must allow for free air
circulation
.

5.2.2 AUX SENSOR IN

The AUX SENSOR IN terminals can be used to add an additional temperature sensor for monitoring purposes. This input is always enabled and is a view only input that can be seen in the operating menu. The sensor must be wired to the AUX SENSOR IN and SENSOR COMMON terminals. It must be similar to AERCO BALCO wire sensor P/N 123449. A resistance chart for this sensor is provided in Appendix D.

5.2.3 ANALOG IN

The ANALOG IN + and – terminals are used when an external signal is used to drive the firing rate (Direct Drive Mode- Boiler Only) or change the setpoint (Remote Setpoint Mode) of the unit.
Either a 4 to 20 mA / 1 to 5 VDC or a 0 to 20 mA/ 0 to 5 VDC signal may be used to vary the setpoint or firing rate. The factory default setting is for 4 to 20 mA / 1 to 5 VDC, however this may be changed to 0 to 20 mA / 0 to 5 VDC using the Configuration Menu described in Sections 2 and
3. If voltage rather than current is selected as the drive signal, a DIP switch must be set on the PMC Board located inside the Control Box. Refer to Appendix F for information on setting DIP switches.
All supplied signals must be floating (unground­ed) signals. Connections between the source and the unit’s I/O Box must be made using twisted shielded pair wire of 18 – 22 AWG, such as Belden 9841(see Fig. 5-1). Polarity must be maintained and the shield must be connected
24
C-MORE CONTROL PANEL OPERATION
only at the source end and must be left floating (not connected) at the unit’s I/O Box.
Whether using voltage or current for the drive signal, they are linearly mapped to a 40°F to 240°F setpoint or a 0% to 100% firing rate. No scaling for
these signals is provided.

5.2.4 B.M.S. (PWM) IN

interlocks which are labeled REMOTE INTL’K IN and DELAYED INTL’K IN. Both interlocks, described below, are factory wired in the closed position.
NOTE:
Both the Delayed Interlock and the Remote Interlock must be in the closed position to allow the unit to fire.
NOTE
Only BMS Model 168 can utilize pulse width
modulation, not
These terminals are used to connect the AERCO Boiler Management System (BMS Model 168) to the unit. The BMS Model 168 utilizes a 12 millisecond, ON/OFF duty cycle. This duty cycle is Pulse Width Modulated (PWM) to control firing rate. A 0% firing rate = a 5% ON pulse and a 100% firing rate = a 95% ON pulse.
the BMS II Model 5R5-384.

5.2.5 SHIELD

The SHIELD terminals are used to terminate any shields used on sensor wires connected to the unit. Shields must only be connected to these terminals.

5.2.6 mA OUT

These terminals provide a 4 to 20 mA output that can be used to monitor setpoint ( 40°F to 240°F), outlet temperature (30°F to 245°F), or fire rate (0% to 100%). This function is enabled in the Configuration Menu (Table 2-3).
5.2.9.1 REMOTE INTERLOCK IN
The remote interlock circuit (REMOTE INTL’K IN) is provided to remotely start (enable) and stop (disable) the Boiler if desired. The circuit is 24 VAC and comes factory pre-wired closed (jumpered).
5.2.9.2 DELAYED INTERLOCK IN
The delayed interlock circuit (DELAYED INTL’K IN) is typically used in conjunction with the auxiliary relay described in paragraph 5.2.11. This interlock circuit is located in the purge section of the start string. It can be connected to the proving device (end switch, flow switch etc.) of an auxiliary piece of equipment started by the unit’s auxiliary relay. The delayed interlock must be closed for the unit to fire. If the delayed interlock is connected to a proving device that requires time to close (make), a time delay (Aux Start On Dly) that holds the start sequence of the unit long enough for a proving switch to make can be programmed. Should the proving switch not prove within the programmed time frame, the unit will shut down. The Aux Start On Dly can be programmed from 0 to 120 seconds. This option is locate in the Configuration Menu.

5.2.7 RS485 COMM

These terminals are used for RS485 MODBUS serial communication between the unit and an external “Master”, such as a Boiler Management System or other suitable device.

5.2.8 EXHAUST SWITCH IN

These terminals permit an external exhaust switch to be connected to the exhaust manifold of the unit. The exhaust sensor should be a normally open type switch (such as AERCO Part No.
123463) that closes (trips) at 500°F.

5.2.9 INTERLOCKS

The unit offers two interlock circuits for interfacing with Energy Management Systems and auxiliary equipment such as pumps or louvers. These interlocks are called the Remote Interlock and Delayed Interlock. The wiring terminals for these interlocks are located inside the I/O Box. The I/O Box cover contains a wiring diagram (Figure 5-1) which shows the terminal strip locations for these

5.2.10 FAULT RELAY

The fault relay is a single pole double throw (SPDT) relay having a normally open and normally closed set of relay contacts that are rated for 5 amps at 120 VAC and 5 amps at 30 VDC, resistive. The relay energizes when any fault condition occurs and remains energized until the fault is cleared and the CLEAR button is depressed.

5.2.11 AUXILIARY RELAY CONTACTS

Each unit is equipped with a single pole double throw (SPDT) relay that is energized when there is a demand for heat and de-energized after the demand for heat is satisfied. The relay is provided for the control of auxiliary equipment, such as pumps and louvers, or can be used as a unit status indictor (firing or not firing). Its contacts are rated for 120 VAC @ 5 amps resistive. Refer to Figure 5-1 to locate the AUX RELAY terminals for wiring connections.
25
C-MORE CONTROL PANEL OPERATION
Figure 5-1. I/O Box Terminal Strip Connections
5.3 MODES OF OPERATION
KC Series Water Heaters are capable of being operated in either the Constant Setpoint Mode or Remote Setpoint Mode. In addition to the Constant and Remote Setpoint Modes, KC and Benchmark Series Boilers can also be operated in the Direct Drive Mode, Boiler Management System (BMS) Mode, Indoor/Outdoor Reset Mode or Combination Mode.
The following paragraphs briefly describe the required connections and menu settings to place the unit in each of these modes.

5.3.1 Constant Setpoint Mode

The Constant Setpoint mode is used when a fixed header temperature is desired. Common uses of this mode of operation include water source heat pump loops, and indirect heat exchangers for potable hot water systems or processes.
There are no external sensors necessary to operate in this mode. While it is necessary to set the desired setpoint temperature, it is not necessary to change any other temperature­related functions. The unit is factory preset with settings that work well in most applications. Prior to changing any temperature-related parameters, other than the setpoint, it is suggested that an AERCO representative be
contacted. See Sections 2 and 3 for complete listings of temperature related menu functions and factory defaults.
5.3.1.1 Setting The Setpoint
The setpoint temperature of the unit is adjustable from 40°F to 240°F.. To set the unit for operation in the Constant Setpoint Mode, the following menu settings must be made in the Configuration Menu:
MENU OPTION SETTING
Boiler (or Heater)
Constant Setpoint Mode Internal Setpt Select desired setpoint
using and arrow
keys (40° to 240°F)
Refer to paragraph 2.2 for detailed instructions on changing menu options.

5.3.2 Remote Setpoint Modes

The unit’s setpoint can be remotely controlled by an Energy Management System utilizing either a current or voltage signal level.
26
Loading...
+ 68 hidden pages