AERCO BMS 168 User Manual

Boiler Management
System
Installation
Instructions
Boiler Management
System
Operation &
Troubleshooting
DISPLAY MODE
HDR
TEMP
AIR
TEMP
%
LOAD
FOR USE W/ INDOOR TEMP. SENS.
SET
POINT
OFF SET
PROP BAND
CONFG
SYS
Hold Key for
Display Header
Header Set
Temp., oF
Display Outside Air Temp., oF
Display % Load & No. of Units Operating
Display/Change Indoor Sensor Reference Temp.,
Display/Change Setpoint Temp when Activated
Display/Change Hdr. Temp. / Indoor Ref. Temp.
System Configuration
o
F
FIELD ADJUSTMENT MODE
FIELD
L.E.D. "On" Enables Field Adjustment
ADJ
Select System Start Option
SYS
Display/Change Outside Air
START
Temp. for System Start
TEMP
Display/Change Bldg Ref Temp — Indoor/Outdoor
REF
TEMP
Hdr Set Temp — Constant Set
HDR
Display/Change
TEMP
Minimum Or Maximum
LIMIT
Header Temp. Display/Change
RESET
Header Temp. / Outside Air Temp.
RATIO
(Alarm Cancel) Reset Alarm Contact
%
Set Date
LOAD
And Time
Set Up
OFF
Set Back
SET
Clock Select Fault
CONFG
Alarm Relay
SYS
Options
Enable BMS
ON
Disable BMS
OFF
Reset Mode Point Mode
Raise/Lower
To Change
HEADER SET INDOOR AIR
DISPLAY
ADJ
HDR
TEMP
TEMP
SYS
REF
START
TEMP
LEVEL
PROP
SET
BAND
POINT
OFF SET
ON OFF
CONFIG
AERCO INTERNATIONAL INC., NORTHVALE, N.J.
AIR
SYS
HDR TEMP LIMIT
RESET RATIO
%
LOAD
FIELD
ADJ
Applicable to Serial Numbers 329985 and above (EPROM Rev. K and above)
AERCO International, Inc.
AERCO International, Inc.
159 Paris Avenue
159 Paris Avenue Northvale, NJ 07647-0128
Northvale, NJ 07647-0128
GF-108M
Telephone Support
Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday):
1-800-526-0288
AERCO International, Inc. 159 Paris Avenue Northvale, NJ 07647-0128
www.aerco,com
© AERCO International, Inc., 2008
The information contained in this installation, operation and mainte­nance manual is subject to change without notice from AERCO International, Inc.
AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.

Table of Contents

Page
SECTION 1 ABOUT YOUR NEW BOILER MANAGEMENT SYSTEM (BMS) 1-1
SECTION 2 FEATURES OF THE BMS 2-1
SECTION 3 INSTALLING THE BMS 3-1
3.1 MOUNTING THE BMS 3-1
3.2 GENERAL WIRING 3-1
3.3 PULSE WIDTH MODULATION WIRING 3=2
3.3.1 PWM Wiring at BMS 3-2
3.3.2 PWM Wiring at Boilers 3-2
3.4 RS485 (MODBUS) WIRING 3-2
3.4.1 RS485 Wiring at BMS 3-2
3.4.2 RS485 Wiring at Boilers 3-3
3.5 SENSOR INSTALLATION AND WIRING 3-3
3.5.1 Header Sensor 3-3
3.5.2 Outside Air Sensor 3-3
3.6 INTERLOCK WIRING 3-4
3.6.1 Interlock 1 Wiring 3-4
3.6.2 Interlock 2 Wiring 3-4
3.7 RELAY WIRING 3-4
3.7.1 System Start Relay 3-4
3.7.2 Fault Alarm Relay 3-4
3.7.3 Auxiliary Relay 3-4
3.8 SET BACK 3-4
SECTION 4 FAMILIARIZING YOURSELF WITH THE BMS 4-1
4.1 ABOUT BMS MODES 4-1
4.1.1 Selecting and Viewing Functions 4-1
4.1.2 Changing Function Settings 4-1
4.2 NORMAL MODE FUNCTIONS 4-4
4.2.1 HDR TEMP 4-4
4.2.2 AIR TEMP 4-4
4.2.3 % LOAD 4-4
4.2.4 SYS START TEMP 4-4
4.2.5 REF TEMP 4-4
4.2.6 HDR TEMP LIMIT 4-4
4.2.7 FIELD ADJ 4-4
4.2.8 SET POINT 4-4
4.2.9 PROP BAND 4-4
4.2.10 OFF SET 4-4
4.2.11 RESET RATIO 4-4
4.2.12 and Arrow Keys 4-5
i
Table of Contents
(Continued)
4.2.13 ON and OFF Keys 4-5
4.2.14 CONFIG SYS 4-5
4.3 FIELD ADJUST MODE FUNCTIONS 4-5
4.3.1 HDR TEMP 4-5
4.3.2 AIR TEMP 4-6
4.3.3 % LOAD 4-6
4.3.4 Setting the Internal Clock With the % LOAD Key 4-6
4.3.5 SYS START TEMP 4-7
4.3.6 REF TEMP 4-7
4.3.7 HDR TEMP LIMIT 4-7
4.3.8 FIELD ADJ 4-8
4.3.9 SET POINT 4-8
4.3.10 PROP BAND 4-8
4.3.11 OFFSET 4-8
4.3.12 Setting Up a Reset Schedule 4-8
4.3.13 Manual Set Back 4-9
4.3.14 RESET RATIO 4-9
4.3.15 and Arrow Keys 4-9
4.3.16 ON and OFF Keys 4-9
4.3.17 CONFIG SYS 4-9
4.4 SYSTEM CONFIGURATION MODE FUNCTIONS 4-10
4.4.1 TEMP FAIL MODE 4-10
4.4.2 SYS ENABLE 4-11
4.4.3 MAX PWR INPUT 4-11
4.4.4 START AND STOP LEVEL Keys 4-12
4.4.5 BLR OP MODE 4-12
4.4.5.1 Sequential Mode 4-12
4.4.5.2 Parallel Mode 4-13
4.4.5.3 Combination Mode 4-13
4.4.5.4 Designating the Number of Combination Boilers 4-13
4.4.6 HDR SET MODE 4-13
4.4.7 INTGL RATE GAIN and DERIV GAIN Keys 4-13
4.4.7.1 TEMP BANDWIDTH 4-14
4.4.7.2 INTGL RATE GAIN 4-14
4.4.7.3 DERIV GAIN 4-14
4.4.8 AUX RELAY 4-15
4.4.9 ▲ and ▼ Arrow Keys 4-15
4.4.10 ON and OFF Keys 4-15
4.4.11 CONFIG SYS 4-15
ii
Table of Contents
(Continued)
SECTION 5 PROGRAMMING THE BMS MODE OF OPERAT
5.1 INDOOR/OUTDOOR RESET MODE 5-1
5.1.1 Selecting Indoor/Outdoor Reset Mode 5-1
5.1.2 Entering System Start Temperature 5-1
5.1.3 Determining the Reset Schedule 5-1
5.1.4 Entering the Building Reference Temperature 5-2
5.1.5 Entering the Reset Ratio 5-2
5.2 SETUP FOR REMOTE SETPOINT MODE 5-2
5.2.1 Entering Header Set and Boiler Operating Modes 5-2
5.2.2 Entering Remote Signal Type and Header Temperature Limits 5-2
5.3 SETUP FOR CONSTANT SETPOINT MODE 5-3
5.3.1 Entering Header Set and Boiler Operating Mode 5-3
5.3.2 Entering Header Reference Temperature 5-3
5.4 CONFIGURING BOILERS FOR PULSE WIDTH MODULATION (PWM) 5-3
5.4.1 C-More Control System PWM Setup 5-4
5.4.2 Configuring the Temperature Controller 5-4
5.5 SYSTEM INITIALIZATION AND POLLING 5-4
5.6 TESTING THE SYSTEM 5-5
ION
APPENDICES
Appendix A Specifications A-1 Appendix B Methods for Determining Reset Schedule and Indoor/Outdoor Reset Ratio Charts B-1 Appendix C Normal (Read-Only) Mode Display Messages and Defaults C-1 Appendix D Field Adjust Mode Display Messages and Defaults D-1 Appendix E Config Sys Mode Display Messages and Defaults E-1 Appendix F Sensor Resistance Data Sheet F-1 Appendix G Parts List G-1 Appendix H Troubleshooting H-1 Appendix I General BMS Wiring I-1 Appendix J Programming the BMS Using RS-232 Communication J-1
iii
List of Figures
Figure 1 Typical BMS Installation 3-5 Figure 2 BMS Mounting 3-6 Figure 3 Wire Routing Locations at the BMS 3-7 Figure 4 PWM Communication Outputs at the BMS 3-8 Figure 5 Pulse Width Modulation Connections at KC Series Boiler Boiler With Modular Control Box 3-9 Figure 6 PWM & RS485 Connections at KC Series Boiler With C-More Control Box 3-10 Figure 7 Pulse Width Modulation Connections at the Benchmark Boiler With Modular Control Box 3-11 Figure 8 PWM & RS485 Connections at the Benchmark Boiler With C-More Control Box 3-12 Figure 9 BMS RS485 & RS232 Connector Locations 3-13 Figure 10 BMS RS485 & RS232 Connector Pin Assignments 3-14 Figure 11 Header Sensor Installation With Well 3-15 Figure 12 Outside Air Sensor Mounting and Connections 3-16 Figure 13 Normal and Field Adjust Mode Overlay 4-2 Figure 14 System Configuration Mode Overlay 4-3
iv
Section 1 ______________________________
SIMPLE INSTALLATION AND
About Your New Boiler Management System (BMS)
AERCO’s Boiler Management System (BMS), stages and modulates AERCO KC Series and Benchmark Boilers, allowing them to operate efficiently as a system. It provides a broad array of operating modes, so that the nuances of specific applications can be easily accommodated. The BMS can control up to 40 boilers; 8 via pulse width modulation (PWM) and up to 32 via Modbus (RS485) communication. For Modbus control, the AERCO Boilers must be equipped with C-More Control Systems.
PRECISE CONTROL
Utilizing PWM or Modbus control, the BMS fully exploits the condensing and modulating ability and efficiency of each boiler and regulates the output of the boiler plant with water supply temperature variation of no more than ±2°F
Staging can be performed sequentially or in parallel. The BMS can sample building reference temperatures to modulate boiler plant output, and will perform water supply temperature night setback automatically referenced to its internal clock.
OPERATION
Installation of the BMS is simple, and low­voltage wiring is employed between the BMS panel and boiler modules. There are no complex design steps to be performed, since a keypad in conjunction with the LCD allows the operator to acquire, change, and program settings through easy-to-use labeled buttons. Each BMS function consists only of selecting the function and toggling values, which generally requires no more than pressing four keys.
The instant a parameter is programmed, it is automatically entered into the BMS memory, avoiding multiple programming steps to store information. In the event of power loss, most factory default settings remain in nonvolatile memory for up to 10 years and need not be reprogrammed. However, date and time remain in memory for about 30 days.
BMS PROGRAMMING VIA RS232 PORT
If desired, the BMS can be programmed by connecting a Laptop Computer, or other type of terminal emulation device, to the RS232 connector on the left side of the BMS. See Appendix J for programming using RS232 communication.
1-1
Section 2 ______________________________
SEQUENTIAL OR PARALLEL
Features of
OPERATION
the BMS____
APPLICATION FLEXIBILITY
Three different system or control options can be selected at setup to match the needs of any closed-loop system - Indoor/Outdoor Reset, 4-to-20 mA Remote Setpoint, and Constant Setpoint.
CONTINUOUS COMMUNICATIONS
The BMS continually sends information to the boilers and receives information from them, providing total control of boiler plant dynamics.
EXCEPTIONAL ACCURACY
The BMS control system uses a PID (Proportional Integral Derivative) control algorithm to respond dynamically to system changes. Water temperatures are precisely controlled by modulating energy in put. A supply water temperature of ±2°F is assured.
BUILDING INDOOR AIR TEMPERATURE INPUTS
The BMS accepts building indoor air temperatures directly from a thermistor sensor or from a 4-to-20 mA signal. Adjustments can be made to the header setpoint temperature to compensate for varying building temperatures and conditions.
Modules can be either sequenced on, or run in parallel, by selection from the front panel. In sequential mode, boilers are brought on one at a time, so turn-down ratio is 14 multiplied by the number of KC Series boilers, or 20 multiplied by the number of Benchmark boilers. This provides higher energy savings and seasonal efficiency. In parallel mode, all of the boilers are modulated together at the same firing rate. The turn-down ratio of the system is fixed at 14:1 for the KC Series boilers and 20:1 for the Benchmark boilers.
BUMPLESS TRANSFER
When in sequential mode, the BMS stages boilers on and off, one at a time, at selectable percentages of firing rate. The result is a seamless transition and undetectable room temperature changes. Sequential mode has several other unique features:
Run-Time Equalization: The BMS se-
quences boilers on a first on-first off basis, which automatically equalizes the run time of all boilers in the plant.
Automatic Load Distribution: The BMS
continuously monitors the number of modules that are available for operation. In the event of a boiler malfunction or when service is performed, the BMS automatically compensates for a lack of response from any unit and brings on the next available boiler to satisfy demand. This feature operates in both parallel and sequential modes.
2-1
Time Delay Between Boiler Starts:
A fixed, 30-second time delay between boiler starts ensures smooth energy input without spikes in electrical, gas, or venting conditions.
AUTOMATIC SYSTEM START
Automatic system start contacts for controlling auxiliary equipment such as pumps and dampers can be selected to close between 32°F and 100°F outside air temperature, eliminating the need for the plant operator to turn auxiliary equipment on and off.
MINIMUM AND MAXIMUM HEADER SET CLAMPING
The supply water temperature can be clamped at a maximum high temperature or minimum low temperature, to ensure that the building temperature is optimal for the greatest comfort.
Two Interlock Circuits (Enable/Disable Contacts)
The BMS contains two normally-open interlock circuits that require only a set of dry contacts to enable or disable the boiler plant. They can be used to monitor pumps, combustion air dampers, or other equip­ment. Out-of-limit conditions trip the interlocks, shutting down the boiler plant, and providing a high level of protection.
ADJUSTABLE OFFSET
The Offset feature can allow the temperature of the supply water to be offset in 1° increments over a range of -50°F below to +50°F above its current temperature. This feature is employed for night setback or morning warmup. The BMS lets you select, over a 7-day period, the time when the offset begins and ends.
CONTROL OF AUXILIARY EQUIPMENT
The auxiliary relay uses a dry set of contacts to operate auxiliary equipment. For example, when the boiler plant is at 100% load, these contacts close and can start an auxiliary boiler, or notify an energy manage­ment system of a full-load condition.
FAULT ALARM SURVEILLANCE
The BMS continually monitors its sensors for opens and shorts and the interlock circuits for opens. However, the BMS fault alarm relay does not close or indicate a fault when a boiler has failed. The fault alarm circuit consists of a dry set of 120 VAC contacts rated at 5 A.
SIMPLE INSTALLATION
The BMS operates from 120 VAC, 50 to 60 Hz, and uses Belden 9841 or equivalent wiring between modules for control and monitoring. The lightweight panel can be mounted up to 200 feet from the boilers when using pulse width modulation communication.
RUGGED AND RELIABLE
The BMS is housed in a NEMA 13-grade enclosure and operates in ambient tempera­tures as high as 131°F (55°C).
POWER-OFF MEMORY
Most system configuration values are retained in nonvolatile memory for up to 10 years. Date and time remain in memory for approximately 30 days.
MODBUS COMMUNICATION
The BMS can monitor or control C-More Boilers using Modbus communication via its RS485 port. It can also be monitored or controlled by a Building Automation System (BAS) or a PC connected to its RS232 port.
2-2
Section 3 ______________________________
3.2 GENERAL WIRING
Installing the BMS________
Please follow the installation procedure in the order presented. Incorrect wiring may damage the unit and void the AERCO warranty Do not omit steps, and do not substitute other types of wiring for those specified. Figure 1 shows a typical BMS installation.
3.1 MOUNTING THE BMS
Use the mounting plate (Figure 2) supplied with the BMS to securely mount the unit away from moisture, and at an appropriate height for easy reading of the display. To reduce the possibility of electrical noise entering the system, mount the BMS at least 6 feet away from electrical devices such as power panels, high voltage transformers and transmission lines, motors, and fluorescent lights.
All wiring and fusing must be in compliance with the National Electrical Code and with local electrical codes. Control wiring for the sensors and communications links must run in separate conduit and not in the conduit providing line voltage in order to ensure immunity from electrical noise.
All wiring should be installed in conduit leading up to the bottom of the BMS panel. There are five knock-outs in the bottom of the panel by which wiring must enter the BMS.
Shielded, twisted-pair cable should be used for sensor and communication wiring. This wiring should be 18 to 24 AWG. Examples of suitable sensor and communication wire are: Belden 9841, 8761, 3105A or equiv­alent. AC power wiring should be 16 to 18 AWG. A BMS wiring diagram is included in Appendix I. Once mounting is complete and the BMS is secured in place, loosen the two captive screws on the wiring cover plate with a Phillips screwdriver. Feed all wiring through the knock-outs provided on the bottom of the panel. All pulse width modulation (PWM) and RS485 control wires should be fed through the two knock-outs furthest to the left.
Shock Hazard!
Extreme caution must be exercised when connecting power wiring to the BMS. The external circuit breaker supplying Line voltage to the the BMS must be turned off to avoid electrical shock
Power wiring should be fed through the right-most knock-out in the bottom of the panel (Figure 3). The remaining knockouts are for control wiring located on the middle terminal block. The terminal blocks can be detached from the BMS headers to simplify field wiring.
Once power wiring is completed, apply line voltage to the BMS, and press the ON key on the BMS keypad to verify proper connection. The display should show INITIALIZING EPROM REV. n where n is the current EPROM version.
3-1
WARNING!
Turn off AC input power to the BMS to avoid electrical shock.
3.3 PULSE WIDTH MODULATION WIRING
Pulse width modulation (PWM) wiring connections are made between the BMS JP2 terminal block and the Relay or I/O Box terminals at each AERCO Boiler. Shielded twisted-pair wire is recommended.
3.3.1 PWM Wiring At BMS
To wire boilers for pulse width modulation (PWM), connect the boiler control wires in ascending order according to the numbers on the BMS (Figure 4). For example, the control wiring for boiler 1 at the BMS would be connected as follows:
Positive control wire connects to JP 2, terminal 1 (+).
Negative control wire connects to JP 2, terminal 2 (-).
Shield wiring connects to the negative (-) control wire at Section BLR 1, terminal 2. The shield is not terminated at the boiler. All shields must be terminated on the BMS end. The wiring terminals labeled SHIELD at terminal block JP3 of the BMS are not internally connected to ground and are only used as a place to terminate the sensor shields. The pulse width modulation shield can be connected to any minus (-) terminal of the PWM terminal strip (JP2).
3.3.2 PWM Wiring At The Boilers
The pulse-width modulation (PWM) control wiring from the BMS to each boiler is connected at each boiler’s relay box or input/output (I/O) box, depending on the type of control system used. Modular control systems utilize a relay box as shown in Figure 5 (KC1000) and Figure 7 (Benchmark). The newer C-More control system utilizes an I/O box as shown in Figure 6 and Figure 8.
Regardless of the type of control system used, the PWM wiring is connected to the BMS + and – terminals as shown in the respective illustrations. It is imperative that positive (+) and negative (-) polarity be observed when making these connections. All boilers follow the same control wiring scheme.
When using pulse width modulation, the BMS may be mounted up to 200 feet from the boilers.
3.4 RS485 (MODBUS) WIRING
All Modbus Networks are implemented using a “Master - Slave” technique. The BMS can function as either a “Master” controlling C-More Slaves or a “Slave” controlled by a “Master” Energy Management System (EMS) or Building Automation System (BAS). Therefore, the following paragraphs provide only an over­view of the required wiring connections. Detailed information and setup procedures for RS485 Modbus networks are provided in Modbus Communication Manual GF-114. Refer to GF-114 prior to implementing any RS485 networks using Modbus.
RS485 wiring connections are made using a “Daisy-Chain” configuration. Shielded twisted-pair wire from 18 to 24 AWG is required for all RS485 wiring.
3.4.1 RS485 Wiring At BMS
RS485 wiring connections are made at the BMS at connector JP11 which is labeled RS485 TO BLRS. The location of this RS485 connector is shown in Figure 9. In addition, Figure 9 also shows the locations of the external and internal RS232 connectors which are used to interface the BMS to an EMS Master if required. The pin assignments for the RS485 and RS232 connectors are shown in Figure 10.
3-2
Connect the RS485 wiring at the BMS as follows:
Connect the positive (+) lead to the +(B) terminal of JP11.
Connect the negative (-) lead to the -(A) terminal of JP11.
Connect the shield to the SHLD terminal of JP11.
3.4.2 RS485 Wiring At Boilers
RS485 wiring connections are made at the RS485 COMM terminals of each boiler’s I/O Box as shown in Figures 6 (KC1000) and Figure 8 (Benchmark). Connect the wiring as follows:
Connect the positive lead to the + terminal
Connect the negative lead to the ­terminal
DO NOT terminate the shields to the Ground (G) terminal at the Boiler end of the RS485 loop. Connect the shields of the incoming and outgoing leads together. The RS485 loop should only be terminated at the BMS.
RS485 loops should not exceed 4000 feet.
Detailed wiring diagrams for RS485 Modbus communication networks are provided in the Modbus Communication Manual GF-114.
3.5 SENSOR INSTALLATION
AND
There are two types of sensors that may be installed -- header sensors and outside air sensors. While an outside air sensor is required for Indoor/Outdoor Reset mode, it is not required for Constant Setpoint or 4-to­20-mA modes of operation. However, it is recommended to take full advantage of all BMS features. The header sensor is required for all modes of operation.
Sensor wiring and power wiring should be run separately to reduce the chance of electrical noise entering the sensor wiring.
WIRING
3.5.1 Header Sensor
The header sensor to be used with the BMS is a sensor that requires a well as shown in Figure 11. When installing the sensor, use a 1/2 inch NPT tapped coupling or a 4 x 4 x 1/2 Tee fitting. Use heat-conductive grease when installing to aid in its response. The sensor probe must be inserted at least 2 inches into the flow of water for proper response. The header sensor must be installed between 2 and 10 feet downstream of the LAST boiler in the plant’s supply water header.
The header sensor is a thermistor type sensor. The Resistance vs. Temperature Chart for the sensor is provided in Appendix F. See Figure 11 for installation details.
Shielded pair 18 AWG cable (Belden # 8760 or equiv.) is recommended for header sensor wiring. There is no polarity to be observed. Connect the wires from the sensor to BMS terminals 4 and 5 on JP3. The ground for the shield is at BMS end of the link, not the header sensor. Connect the ground to JP3, terminal 8 (SHIELD). The header sensor can be installed up to 600 feet from the BMS.
3.5.2 Outside Air Sensor
The Outside Air Sensor, AERCO part no. 122662, must be mounted on the North side of the building, shielded from direct sunlight, and away from air intakes or outlets from the building. See Figure 12 for a typical installation. The sensor includes a plate for wall mounting. Shielded pair 18 AWG cable (Belden # 8760 or equiv.) is recommended for sensor wiring. There is no polarity to be observed. Connect the sensor wires to BMS terminals 1 and 2 on JP3. Connect the shield to JP3, terminal 3 (SHIELD) at the BMS. The shield must not be grounded on the sensor end. The sensor can be mounted up to 600 feet from the BMS.
3-3
3.6 INTERLOCK WIRING
The BMS is equipped with two interlocks designated Interlock 1 (INT 1) and Interlock 2 (INT 2). Since both interlocks must be closed for the BMS to operate the boiler plant, the associated wiring terminals are jumpered, prior to shipment. If desired, proving device switches can be connected to either used, interlock wiring connections are made as described in the following paragraphs.
3.6.1 Interlock 1 Wiring
Interlock 1 is often used with auxiliary equipment, such as air dampers or flow switches. If used, connect the end proving switch to INT 1 terminals 11 and 12 as shown in the wiring diagram in Appendix I.
3.6.2 Interlock 2 Wiring
Interlock 2 is a general purpose interlock which can be used with a variety of devices or equipment or conditions that must be proved prior to enabling the boiler plant. If used, connect the end proving switch to INT 2 terminals 13 and 14 as shown in the wiring diagram in Appendix I.
interlock in place of the jumper. If
NOTE
If necessary, Interlock 1 can be programmed to operate the boilers only when the outside air temperature falls below the system start temperature. See para. 4.4.2 for details. Interlock 2 cannot programmed with this feature.
be
3.7 RELAY WIRING
The BMS contains a System Start Relay, a Fault Alarm Relay and an Auxiliary Relay which can be connected to external monitoring or control devices. The contacts for each of these relays are rated at 120 VAC, 5A and are fused internally at 5A with replaceable fuses. The contact terminals for these relays are shown in the wiring diagram in Appendix I.
3.7 1 System Start Relay
The state of the System Start (SYS START) relay contacts are controlled by the value set for the SYS START TEMP function in the Field Adjust Mode (para. 4.3.5). The contacts are closed only when the outside air temperature is less than the System Start Temperature (SYS START TEMP) which is set in the Field Adjust Mode. The default for this temperature setting is 70°F.
3.7.2 Fault Alarm Relay
The state of the Fault Alarm (FLT ALARM) relay contacts are controlled by the option selected by pressing the CONFIG SYS key when in the Field Adjust mode (para.
4.3.16). Contact closure can be set to ALL FAULTS, INTERLOCK 1, INTERLOCK 2, or NO INTERLOCK.
3.7.3 Auxiliary Relay
The state of the Auxiliary (AUX) relay contacts are controlled by the AUX RELAY CLOSE option selected when in the System Configuration mode (para. 4.4.8). Contact closure can be set to occur either when all available boilers are at the maximum power input or no boilers are available (all boilers faulted or turned off).
NOTE
The SET BACK function is used only if the header supply temperature will be offset manually as described in para. 4.3.13. Disregard para. 3.8 if an automatic header temperature reset schedule is used as described in para. 4.3.12.
3.8 SET BACK
The SET BACK terminals shown in the wiring diagram in Appendix I are used only when implementing a manually-controlled header temperature offset. If used, connect a dry contact switch across SET BACK terminals 15 and 16 on JP3.
3-4 3-5
Figure 2
BMS MOUNTING
3-6
Figure 3
RECOMMENDED WIRE ROUTING LOCATIONS AT THE BMS
3-7
Figure 4
PWM COMMUNICATION OUTPUTS AT THE BMS
3-8
Figure 5
PULSE WIDTH MODULATION CONNECTIONS AT
KC SERIES BOILER WITH MODULAR CONTROL BOX
3-9
Remove sheet metal cover to access I/O Box
OUTDOOR SENSOR IN
SENSOR COMMON
AUX SENSOR IN
NOT USED
ANALOG IN
B.M.S. (PWM) IN
SHIELD
mA OUT
RS-485 COMM.
NOT USED
REMOTE INTL'K IN
EXHAUST SWITCH IN
DELAYED INTL'K IN
NOT USED
NC
FAULT RELAY
COM
120 VAC, 5A, RES
+
­+
-
+
-
+
G
-
NO
NC
AUX RELAY
COM NO
120 VAC, 5A, RES
NOT USED
PWM Connections
RS485 COMM Connections
Figure 6
PWM & RS485 CONNECTIONS AT
KC SERIES BOILER WITH C-MORE CONTROL BOX
3-10
Figure 7
PWM CONNECTIONS AT
BENCHMARK BOILER WITH MODULAR CONTROL BOX
3-11
Open Door To Access I/O Box
OUTDOOR SENSOR IN
SENSOR COMMON
AUX SENSOR IN
NOT USED
ANALOG IN
B.M.S. (PWM) IN
SHIELD
mA OUT
RS-485 COMM.
NOT USED
REMOTE INTL'K IN
EXHAUST SWITCH IN
DELAYED INTL'K IN
NOT USED
NC
FAULT RELAY
COM
120 VAC, 5A, RES
+
­+
-
+
­+
G
-
NO
NC
AUX RELAY
COM NO
120 VAC, 5A, RES
NOT USED
PWM Connections
RS485 COMM Connections
Figure 8
PWM & RS485 CONNECTIONS AT
BENCHMARK BOILER WITH C-MORE CONTROL BOX
3-12
Figure 9
BMS RS485 & RS232 CONNECTOR LOCATIONS
3-13
Figure 10
BMS RS485 & RS232 CONNECTOR PIN ASSIGNMENTS
3-14
1/2 “ NPT
Figure 11
HEADER SENSOR INSTALLATION WITH WELL
3-15
Figure 12
OUTSIDE AIR SENSOR MOUNTING AND CONNECTIONS
3-16
Section 4 ______________________________
Familiarizing Yourself With the BMS_____
4.1 ABOUT BMS MODES
The BMS has three basic modes: Normal Mode, Field Adjust Mode and Configure System Mode. The Normal Mode is a “Read-Only” mode which only allows you to view system settings. The Field Adjust (FIELD ADJ) Mode and System Configuration (CONFIG SYS) Mode allow you to view or change BMS settings to customize and tune the system to the specific needs of your site. The BMS keypad normally displays the functions applicable to the Normal and Field Adjust Mode. However, the keys perform slightly different functions for Normal and Field Adjust Modes. When operating in the System Configuration Mode, you must install the SYSTEM CONFIGURATION OVERLAY sheet, supplied with the BMS, over the keypad. Figures 13 and 14 show the Normal/Field Adjust layout and the System Configuration keypad layouts respectively.
The following paragraphs describe the operation of the BMS keypad for each mode. In addition, tabular listings summarizing keypad operation for each mode are provided in Appendices C, D and E. Ensure that 120 Vac power is supplied to the BMS and the ON key LED is illuminated. If the LED is not illuminated, press the ON key.
4.1.1 Selecting and Viewing Functions
As previously mentioned, the Normal mode, is a read-only mode which allows functions to be viewed, but not changed. However, functions associated with the keypad keys can also be viewed in the FIELD ADJ and CONFIG SYS modes, provided the appropriate mode key (FIELD ADJ or CONFIG SYS) is first selected. For example, pressing the HDR TEMP key displays the supply water temperature. You can view all mode functions by simply pressing its associated key. You must be in the System Configuration mode (CONFIG SYS) to view the functions associated with the SYSTEM CONFIGURATION OVER-
LAY.
4.1.2 Changing Function Settings
To change, rather than simply display settings and functions, the BMS must be in the FIELD ADJ or CONFIG SYS mode. To change a function value, press the ▲ and arrow keys until the display shows the desired selection. Once you change the value, associated with one or more function keys they are automatically stored in non­volatile memory. For example, if you change the values for three separate functions in the Field Adjust mode, you don’t need to exit and then re-enter the mode for each function change.
4-1 4-2
Figure 13
NORMAL & FIELD ADJUST MODE OVERLAY
Figure 14
SYSTEM CONFIGURATION MODE OVERLAY
4-3
NOTE
Sample Normal Mode displays with their Factory Default values are provided in Appendix C.
4.2 NORMAL MODE DISPLAYS
AND FUNCTIONS
When power is applied to the BMS, it is automatically placed in the Normal Mode. It allows you to view the settings currently stored in memory for BMS parameters. In addition, you can enter the Field Adjust or System Configuration Mode by pressing the FIELD ADJ or CONFIG SYS key. The functions provided by the keypad keys are described in the following paragraphs.
4.2.1 HDR TEMP
Pressing and releasing this key displays the actual header sensor water temperature in °F. Pressing and holding this key displays the header setpoint temperature presently stored in memory.
4.2.2 AIR TEMP
Pressing and releasing this key displays the actual outside air temperature. Pressing and holding this key displays the actual inside air temperature, only if an indoor air temperature sensor is installed. If an indoor air sensor is not installed, INDOOR AIR TEMP NOT CONNECTED will be displayed.
4.2.3 % LOAD
Pressing and releasing this key displays the actual firing rate percentage (% Load) for the boiler plant. It also displays the number of boilers presently operating.
4.2.4 SYS START TEMP
Pressing and holding this key displays the System Start Relay temperature setting in °F presently stored in memory. The system will start whenever the outside air temperatures drops below this setting.
4.2.5 REF TEMP
Pressing and holding this key displays the Header Reference Temperature in °F presently stored in memory.
4.2.6 HDR TEMP LIMIT
Pressing and holding this key displays the header high limit temperature setting (°F) stored in memory.
4.2.7 FIELD ADJ
Pressing and releasing this key places the BMS in the Field Adjust Mode and lights the FIELD ADJ key LED. When this key is pressed, the display will read FLD ADJUSTMENT MAKE SELECTION. Refer to paragraph 4.3 for key functions when in this mode.
4.2.8 SET POINT
Pressing and holding this key displays the indoor setpoint temperature (°F) stored in memory.
4.2.9 PROP BAND
Pressing this key displays the indoor air proportional bandwidth. This bandwidth is a variable used in an equation that solves for the proper offset of supply water temperature based on an indoor air temperature. Normally the display will read INDOOR PROP BAND 00.0°F/°F. See paragraph 4.3.9 for additional information.
4.2.10 OFFSET
Pressing and holding this key displays the Header Temperature Offset (°F) for the present time and day-of-the-week. See paragraph 4.3.10 for additional information on setting up an offset schedule.
4.2.11 RESET RATIO
Pressing and holding this key will display the header reset ratio if a value is currently stored in memory. This function is only used in the Indoor/Outdoor Reset Mode. If this function is not set, or the Constant Setpoint or Remote (4-20 mA) mode is used, the display will show FUNCTION NOT VALID.
Also, ALARM CANCEL is printed directly above this key. Pressing and releasing this key will open the Alarm Relay contacts until the Alarm condition reappears.
4-4
4.2.12 ▲ and ▼ Arrow Keys
The and arrow keys are not active in this mode, since no changes can be made to the displayed settings
4.2.13 ON and OFF Keys
Pressing and releasing the ON or OFF key enables or disables the BMS. In addition, the corresponding key LED will light when the key is pressed.
4.2.14 CONFIG SYS
Pressing and releasing this key places the BMS in the System Configuration Mode and lights the CONFIG SYS key LED. When this key is pressed, the display will read
CONFIG. SYSTEM MAKE SELECTION.
Refer to paragraph 4.4 for key functions when in this mode.
NOTE
Sample Field Adjust Mode displays with their Factory Default values and allowable entry ranges are provided in Appendix D.
4.3 FIELD ADJUST MODE
DISPLAYS AND FUNCTIONS
The Field Adjust Mode allows you to view or change settings currently stored in memory for BMS parameters. Many of the settings in this mode have been preset by AERCO to their Factory Defaults. However, you can reset many functions to suit the specific needs of your BMS installation.
The Field Adjust Mode is entered by simply pressing the FIELD ADJ key and verifying that the FIELD ADJ key LED lights. When this key is pressed, the display will read
FLD. ADJUSTMENTS MAKE SELECTION.
The following paragraphs describe the functions of the keys when in the Field Adjust Mode.
NOTE
When in the Field Adjust Mode, the HDR TEMP and AIR TEMP keys are used to set multiple functions required for Modbus Network operation. Refer to Modbus Communication Manual GF-114 for additional information on set-up and installation of Modbus (RS485) Networks.
4.3.1 HDR TEMP
The HDR TEMP key is used to set multiple Modbus functions when the BMS is configured as the Modbus Master and is directly controlling C-More Boiler Controller Slaves on the RS485 Network. This key is used to set functions as follows:
NOTE
Default values for each function are indicated below. Refer to Modbus Communication Manual GF-114 for required settings. Use the and arrow keys to increment or decrement the displayed value.
1. Press key once. RS485 BAUDRATE is displayed. Default = 9600.
2. Press key again. MIN SLAVE ADDR is displayed. Default = 0.
3. Press key again. MAX SLAVE ADDR is displayed. Default = 0.
4. Press key again. NUMBER OF NETW BLRS is displayed. Default=0. This key is used to set the maximum number of C-More Boilers that will be controlled on the Modbus Network.
5. Press key again. MODBUS CNTL TYPE is displayed. Default = Round Robin.
6. Press key again. NETW BOILER 1 ADDRESS=0 is displayed. Default = 0. This address must be the same as the Comm Address stored in the C-More Boiler Controller.
4-5
7. Repeatedly pressing the HDR TEMP key allows the NETW BOILER ADDRESS to be set for each boiler being controlled on the Modbus Net­work.
4.3.2 AIR TEMP
The AIR TEMP key is used to set multiple Modbus functions when the BMS is configured as a Modbus Slave to an EMS (or BAS) Master. This key is used to set functions as follows:
NOTE
Default values for each function are indicated below. Refer to Modbus Communication Manual GF-114 for required settings. Use the and arrow keys to increment or decrement the displayed value.
1. Press key once. RS232 MODE is
displayed. This function can be set to NORMAL or MODBUS SLAVE. The
Default = MODBUS SLAVE.
2. Press key again. RS232 BAUDRATE is displayed. Default = 9600.
3. Press key again. MODBUS ADDRESS is displayed. Default = 128.
4. Press key again. NETWORK TIMEOUT is displayed. Default = 60 sec.
5. Press key again. REMOTE SIGNAL. is displayed. This function can be set to 4­20MA or MODBUS. Default = 4-20MA.
6. Press key again. MODBUS PASS THRU is displayed. This function can be set to ENABLED or DISABLED. Default = DISABLED.
4.3.3 % LOAD
The % LOAD key has two separate and distinct functions in the Field Adjust Mode. Pressing and holding this key displays the actual firing rate (load) percentage and the number of boilers presently operating. Releasing the % LOAD key changes its function to Setting the Internal Clock as described in the following paragraph.
4.3.4 Setting the Internal Clock With The % LOAD Key
Pressing and releasing the % LOAD key changes the first line of the display to SET TIME CLOCK. The second line of the display will show: MONTH, DATE, YEAR, DAY, HOURS, or MINS. Since these functions wrap around, it is strongly suggested that you repeatedly press the % LOAD key until the display shows MONTH: in the second line. This will make the following steps easier to follow:
NOTE
When performing the following steps, use the and arrow keys to increment or decrement the displayed value. Pressing and holding the or key will change the displayed value at a rapid rate.
1. Press key until MONTH: is displayed. Set the actual number of the month (1-
12).
2. Press key again to display DATE:. Set the actual day of the current month (1-31).
3. Press key again to display YEAR:. Set the last 2 digits of the year.
4. Press key again to display DAY:. Set the day that you want to be the first day of the week. AERCO normally sets Sunday as DAY 1, however any day of the week can be set as DAY 1.
For example, if the actual DATE (day of month) entered in step 2 is a Monday, and you want Monday to be the first day of the week, set DAY: to 1. Conversely, if you want to retain Sunday as the first day of the week, set DAY: to 2 to indicate you are currently in the second day of the week.
5. Press key again to display HOURS:. Set the hours using the 24-hour format (0 to
23).
6. Press key again to display MINS. Set the minutes (0 to 59).
7. This completes the Internal Clock settings.
4-6
4.3.5 SYS START TEMP
When in the Field Adjust Mode, the SYS START TEMP key has two functions. First,
It lets you select the outdoor temperature at which the system starts. Second, it lets you select the system start option (TEMP ONLY or TEMP AND LOAD).
For example, with the system start temperature set at 70°F (SYS. START RELAY 70°F), the system start relay will close and enable the boilers when the outside air temperature falls to 69°F (or lower).
To always enable the boilers, regardless of the system start temperature, or if an outside air temperature sensor is not used, see paragraph 4.4.2 in the System Configuration Mode section.
Pressing and releasing the SYS START TEMP key once displays the System
Start Relay temperature. (AERCO presets System Start to an outside air temperature of 70°F). To change the displayed start temperature, press the or arrow key.
Pressing and releasing this key a second time displays the System Start Option which can be set to either outside air temperature only (TEMP ONLY) or outside air temperature and load (TEMP AND LOAD). To change Start Option, press or key to toggle the setting.
If TEMP ONLY is chosen, the BMS will close the system start relay contacts when the outdoor air temperature drops below the system start temperature setting, without regard to load.
The TEMP AND LOAD feature is used when the System Start Relay will control dampers. It keeps dampers closed until it is necessary to open them for combustion. This is designed to ensure that cold air is not always entering the boiler room.
If TEMP AND LOAD is chosen, two conditions are necessary for the system start relay contacts to close and enable the boilers. First, the firing rate (displayed as %
LOAD) must be above 11%. Second the outdoor air temperature must be below the system start temperature. The system start relay contacts will open when the load percentage falls below 7%.
4.3.6 REF TEMP
The REF TEMP key has two functions, depending on the operating mode used by the boilers connected to the BMS.
In the Indoor/Outdoor Reset or Remote Setpoint Mode, pressing and releasing this key displays the Building Reference Temperature (BLDG REF TEMP).
In the Constant Setpoint Mode, pressing this key displays the header supply water temperature setpoint (HEADER REF. TEMP).
To change the displayed Reference Temperature, press the or arrow key.
4.3.7 HDR TEMP LIMIT
This key allows you to view or change the low and high temperature limits for the header supply water temperature.
In addition, when in the 4-to-20 mA Remote Setpoint Mode, it automatically scales the 4­to-20 mA signal. Accordingly, 4 mA will be equal to the header low limit setting and 20 mA will be equal to the header high limit setting.
Pressing and releasing this key once displays the header high limit temperature (HDR HIGH LIMIT).
Pressing and releasing this key a second time displays the header low limit temperature (HDR LOW LIMIT).
Pressing and releasing this key a third time displays the header offset temperature (HEADER OFFSET).
To change the displayed header high, low or offset temperature limits, press the or arrow key.
4-7
4.3.8 FIELD ADJ
The FIELD ADJ key LED should be lit to indicate that the BMS is already in the Field Adjust Mode. Pressing and releasing this key when already in the Field Adjust Mode will cause the BMS to exit the Field Adjust Mode and switch the BMS to the Normal (Read-Only) Mode.
4.3.9 SET POINT
Pressing and releasing this key allows you to view or change the indoor setpoint temperature. This function is only used when an indoor air temperature sensor is connected to the BMS. If used, the input can be provided by a resistive type sensor, or a 4-to-20 mA input.
4.3.10 PROP BAND
Pressing this key displays the indoor air proportional bandwidth. This bandwidth is a variable used in an equation that solves for the proper offset of supply water temperature based on an indoor air temperature. Normally, the display will read INDOOR PROP BAND 00.0°F/°F.
AERCO presets the proportional bandwidth to 00.00°F/°F. It should NOT be readjusted unless your system has an indoor air temperature sensor and is operating in the Indoor Setpoint mode. If the indoor temperature feature is not being used, PROP BAND MUST be set to 00.00°F/°F or the BMS will not run the boiler plant.
4.3.11 OFFSET
The OFFSET key is used to enable and set up an Offset Schedule for the header supply temperature. The schedule can be set up for a 7-day period.
Pressing and releasing this key once will display OFFSET ENABLE followed by OFF or ON (Default is OFF). If an Offset Schedule will be used, toggle the display to ON using the ▲ or arrow key.
Normally, if an Offset Schedule is used, it is controlled automatically using the set-up procedures described in paragraph 4.3.12. However, if desired, the header offset can
be controlled manually by connecting a switch across the SET BACK wiring terminals (see para. 3.8). If a manual offset is used, refer to paragraph 4.3.13
IMPORTANT
Prior to setting up an automatic Reset Schedule (para. 4.3.12) or manual Set Back (para. 4.3.13), refer to the paragraph 4.3.4 to determine which Day of the Week has been set as Day 1. AERCO presets Day 1 of the week as Sunday. However, any day of the week can be specified as Day 1 by performing the steps outlined in paragraph 4.3.4.
4.3.12 Setting Up A Reset Schedule
The basic steps for setting up an automatic Reset Schedule consist of first selecting the temperature offset and then entering the start and stop times for which the offset will be in effect. Keep in mind that the BMS uses a 24-hour clock (00:00 to 23:59).
In the following example, for Day 1, we want to offset the setpoint temperature by -15°F starting at 12:30 am (00:30) and return it to the normal setpoint at 8:15 am (08:15). Proceed as follows:
1. Press OFFSET key once and toggle the
display to OFFSET ENABLE ON.
2. Press key a second time. OFFSET
TEMP DAY 1
entry of the offset temperature. Set the offset temperature to -15 using the and arrow keys.
3. Press key a third time. OFFSET ON
TIME DAY 1
prompting Hours to be entered for the start time. Set the Hours to zero
(midnight) using the ▲ and arrow keys.
4. Press key a fourth time. OFFSET ON
TIME DAY 1: 0
prompting Minutes to be entered for the start time. Set the Minutes to 30 using the and arrow keys.
Æ
is displayed prompting
Æ
0: 0 is displayed
Æ
0 is displayed,
4-8
5. Press key a fifth time. OFFSET OFF
TIME DAY 1
prompting Hours to be entered for off time. Since the BMS uses a 24-hour clock format, set the Hours to 8 using the and arrow keys.
6. Press key a sixth time. OFFSET OFF
TIME DAY 1: 8
prompting Minutes to be entered. Set the Minutes to 15 using the and arrow keys.
7. This completes the steps for setting the Offset Temperature, and Start/Stop Times for Day 1.
For a 7-Day Schedule, steps 2 through 7 would be repeated as needed. Offset Schedule entries stored in memory can be reviewed by repeatedly pressing the
OFFSET key as necessary.
4.3.13 Manual Set Back
If a switch is connected across the SET BACK terminals (para. 3.8), the header offset temperature can be controlled manually by setting all offset times to zero. Using the OFFSET key:
1. Toggle the display to OFFSET ENABLE ON.
2. Set the desired OFFSET TEMP. A different OFFSET TEMP can be entered for each day if desired.
3. Set the OFFSET ON TIME and OFFSET OFF TIME to zero for each day.
Once programmed as described above, closing the SET BACK switch will enable the programmed OFFSET TEMP for that day. Opening the SET BACK switch will disable the OFFSET.
Æ
0: 0 is displayed
Æ
0 is displayed
4.3.14 RESET RATIO
The Reset Ratio is only used in the Indoor/Outdoor Reset Mode of operation. This ratio the amount that the supply water temperature will rise for each degree drop in outside air temperature. A reset ratio of 2.0 means that the supply water temperature will increase 2°F for every 1°F decrease in
outdoor air temperature. For example, if the building reference temperature is set at 70°F, when outside air temperature drops to 69°F, and the reset ratio is 1.8, the water supply temperature will increase to 71.8°F. AERCO presets the Reset Ratio to
1.2°F/°F. See Appendix B for Reset Ratio Charts.
Pressing and releasing this key will display the Header Reset Ratio (°F/°F) if a value is currently stored in memory. When operating in the Constant Setpoint or Remote (4-20 mA) mode, the display will show FUNCTION NOT VALID.
4.3.15 and Arrow Keys
These keys are used to increment () or decrement () the displayed variable, or toggle the display through available options. When these keys are depressed and held the displayed value will increment or decrement at a rapid rate.
4.3.16 ON and OFF Keys
Pressing and releasing the ON or OFF key enables or disables the BMS. In addition, the corresponding LED will light when the corresponding key is pressed.
4.3.17 CONFIG SYS
When the BMS is in the Field Adjust Mode, this key has two functions. First, it allows you to select the types of faults which will cause an alarm. Second, it allows you to select how alarms are cleared.
Pressing and releasing the CONFIG SYS key once displays the FAULT ALARM RELAY status and allows you to select the types of faults which will cause an alarm. The choices are: ALL FAULTS,
NO INTERLOCK, INTERLOCK 2 or INTERLOCK 1.
Selecting ALL FAULTS causes the BMS Fault Relay to close and generate an alarm when either Interlock 1 or 2 opens. It also closes the Fault Relay when any of the fault messages listed in Appendix H, Table H-1 are displayed.
4-9
Selecting INTERLOCK 2 causes the Fault Relay to close and generate an alarm only when Interlock 2 opens. However, if INTERLOCK 1 opens, a fault message will be generated but the Fault Relay will not be closed.
Selecting INTERLOCK 1 causes the Fault Relay to close and generate an alarm only when Interlock 1 opens. However, if INTERLOCK 2 opens, a fault message will be generated but the Fault Relay will not be closed.
Selecting NO INTERLOCK causes the Fault Relay to remain open and not generate an alarm when either Interlock 1 or Interlock 2 opens.
It should be noted that the BMS will always Interlock 1 or 2 opens, regardless selected Fault Relay option.
Select the desired option using the or arrow key.
Pressing and releasing the CONFIG SYS key a second time displays FAULT ALARM CLEAR and allows you to select how faults are cleared. The available choices are MANUAL RESET or AUTOMATIC. Toggle to the desired option using the or arrow key.
Prior to placing the BMS in the System Configuration Mode, the FIELD ADJ key must be pressed to exit the Field Adjust Mode. Pressing and releasing the CONFIG SYS key places the BMS in the System Configuration Mode and lights the CONFIG SYS key LED. When this key is pressed, the display will read CONFIG. SYSTEM MAKE SELECTION. Refer to paragraph 4.4 for key functions when in this mode.
Sample System Configuration mode displays with their Factory Default values are provided in Appendix E.
shut down the boilers when
of the
NOTE
4.4 SYSTEM CONFIGURATION MODE DISPLAYS AND FUNCTIONS
The System Configuration Mode allows you to program and operate the BMS to effectively run and manage the performance of the boiler plant. In order to effectively use this mode, the SYSTEM CONFIGURATION OVERLAY provided with the BMS must be placed over the keypad for proper identification of key functions (Figure 12).
The System Configuration Mode is entered by simply pressing the CONFIG SYS key and verifying that the CONFIG SYS key LED lights.
The keys described in the following paragraphs allow you to view or change settings currently stored in memory. If the desired setting is not displayed for the selected BMS parameter, press the or arrow key to increase, decrease or toggle the displayed setting. All changes made will be stored in memory.
4.4.1 TEMP FAIL MODE
Pressing and holding this key displays the actual header sensor water temperature in °F. This is a “Read Only” display and cannot be changed.
Pressing and releasing this key allows you to display and select a Temperature Failure Mode (TEMP FAIL MODE) of either SHUTDOWN or SWITCH INPUTS.
If SHUTDOWN is selected, regardless of the operating mode, the BMS will shut down the boiler plant whenever a temperature sensor fails or either interlock opens. If the BMS is operating in the Remote Setpoint mode, the BMS will also shut down the boiler plant if the remote 4-to-20-mA input signal drops below 3 mA. If any of these failures occur, the fault relay will close and the BMS will display the appropriate failure message.
4-10
If SWITCH INPUTS is selected, the BMS will automatically switch to Constant Setpoint mode if a sensor or remote input error occurs. Once the sensor or remote input error has been cleared, the BMS will automatically switch to the previous mode.
When selecting SWITCH INPUTS, the reference temperature for the Constant Setpoint mode must be preset. See Section 5 for programming steps.
Regardless of whether SHUTDOWN or SWITCH INPUTS is selected, the BMS will shut down and close the fault relay contacts if the header sensor circuit fails.
4.4.2 SYS ENABLE
Pressing and releasing this key allows you to select the INTERLOCK 1 enable setting of START ENABLED or ALWAYS ENABLED.
The START ENABLED feature will not enable the boiler plant until the outside air temperature falls below the system start temperature. If the boiler plant begins to operate and Interlock 1 is open, the BMS will wait 30 seconds before stopping the boilers and displaying a fault message.
This feature is intended for use with auxiliary equipment having limit switches. For instance, dampers with proving end switches, can be triggered by the BMS system start relay as the boilers start. If the dampers do not open, the end switch wired to Interlock 1 will not make (close) and the BMS will shut down the boilers.
The ALWAYS ENABLED feature allows the boilers to run, regardless of the system start and outside air temperature settings. This feature is used when there is a loss of an outside air sensor or one is not installed. It will also function if an outside air temperature sensor is present. It should be noted that if either Interlock 1 or 2 opens, the BMS will shut down the boilers.
The system start relay will close only after the outside air temperature falls below the system start temperature, whether START
ENABLED or ALWAYS ENABLED is selected. AERCO recommends that the system be equipped with a flow switch that is interlocked to the BMS. This is especially important if ALWAYS ENABLED is selected and the BMS is controlling the pumps based on outside air temperature, or the BMS is interfaced with an energy management system that is controlling the pumps.
4.4.3 MAX PWR INPUT
This key provides two distinct functions. First, it is used to establish the maximum firing rate percentage for the boilers being controlled by the BMS. Second, it permits adjustment of the pulse width modulation (PWM) signal supplied to the boilers.
Pressing and releasing the MAX PWR INPUT key once displays the maximum
allowable firing rate percentage for the boilers (MAX POWER INPUT 100%). If desired, the maximum firing rate of the boilers can be limited to values below 100%. This is useful if there is a problem with gas supply pressure.
For example, if gas pressure is too low, the boilers can be run at a lower firing rate temporarily until proper gas pressure can be restored. If necessary, adjust the firing rate using the or arrow key.
Pressing and releasing the MAX PWR INPUT key a second time displays a
PWM TIMEBASE CAL message. If necessary, the PWM pulse width ON time can be adjusted using the and arrow keys. Pressing the arrow key increases the pulse width ON time and pressing the key reduces the ON time. The PWM TIMEBASE CAL is adjustable from -30 to 30 (Default = 0).
The PWM TIMEBASE CAL should only be adjusted when all boilers are indicating a firing rate above or below the firing rate being supplied by the BMS PWM signal. If necessary, individual boilers can be adjusted via their respective C-More Control Systems.
4-11
4.4.4 START LEVEL and STOP LEVEL Keys
These keys allow you to set the energy levels (firing rate percentages) at which additional boilers are staged-in or staged­out of the system during Sequential or Combination mode operation. While the start level can be set at any percentage up to 100%, it is best to keep it below 60%. This allows the system to operate at optimum efficiency under low loads. The BMS is preset with 45% start and 18% stop levels, which generally provide the best performance.
When changing the start or stop levels, it is important to remember that load-balancing affects bumpless transfer. A sufficiently wide gap between the start and stop levels must be maintained to prevent cycling between units. For example, in a two-boiler system with a start level of 60% and a stop level of 30%, when the first boiler reaches 60%, the BMS will distribute the load between the two boilers, so that each will have a firing rate of 30%. However, since the stop level is 30%, the BMS will automatically shut down one boiler and allow the firing rate of the second boiler to increase to 60%. The BMS will then repeat this undesirable cycling. To avoid this, the start level could be set to 65%, leaving the stop level at 30%. When the BMS distributes the load after the first boiler reaches a 65% firing rate, the individual load would be 32.5%, sufficiently above the stop level. Conversely, the stop level could be changed to 25%, leaving the start level at 60%. In this case, when the BMS distributes the load, there will be 5% margin between this load (30%) and the stop level (25%).
Pressing the START LEVEL key displays firing rate percentage at which the boilers will start.
Pressing the STOP LEVEL key displays firing rate percentage at which the boilers will stop.
4.4.5 BLR OP MODE
This key is used to select the Boiler Operating Mode. It allows you to make choices concerning the effective and efficient way to fire the boilers based on the building load. The mode choices include: Parallel, Sequential, or Combination Mode.
Pressing the BLR OP MODE key displays BOILER OP MODE followed by the currently selected mode (PARALLEL, SEQUENTIAL or COMBINATION). AERCO presets the mode to SEQUENTIAL. If necessary, use the and arrow keys to toggle between the 3 available modes. The following paragraphs describe the advantages of each mode selection.
4.4.5.1 Sequential Mode
The Sequential Mode provides a greater turn-down ratio than Parallel Mode. This is because the turn-down ratio in Sequential Mode is equal to the number of boilers multiplied by 14 for KC Series boilers and by 15 for Benchmark boilers. In Parallel Mode, the turn-down ratio is fixed at 14:1 for KC Series boilers and 15:1 for Benchmark boilers, and does not consider the number of boilers in the plant.
In Sequential Mode, each boiler is started one at a time based on the load and start/stop levels programmed in the BMS. The BMS will start a single boiler when there is a load demand. Once the first boiler reaches the start level, a second boiler will be started and the load will be distributed evenly between the two boilers.
For instance, if a start level of 50% is chosen, when the first boiler reaches 50% a second boiler will start (after a 30 second delay), and the BMS will distribute the load 25% for each boiler. If the firing rate of both boilers reach the start level, a third boiler is started by the BMS (after a 30 second delay), and the load will be distributed across all three boilers. This sequence will continue base on load demand and the number of boilers connected to the BMS.
4-12
As the load drops off, the firing rates decrease. When all boilers reach the stop level, the first boiler turned on will be shut off by the BMS and its load will be evenly distributed to the remaining firing boilers. This off-sequencing continues until only one boiler is left firing. The last boiler will turn off when its stop level is reached.
4.4.5.2 Parallel Mode
When operating in Parallel Mode, the boilers are simultaneously started by the BMS. The start and stop levels have no effect when in Parallel Mode. The turn-down ratio in Parallel Mode is fixed at 14:1 for KC 1000 Series boilers and 15:1 for Benchmark boilers, regardless of the number of boilers in the plant.
4.4.5.3 Combination Mode
Combination mode is used only when the boiler plant will be used to satisfy both space heating and domestic hot water needs. This configuration, known as a Combination System, is used in conjunction with an AERCO Combination Control Panel (CCP). This system uses BMS-mode boilers dedicated to space heating and Combination boilers that are primarily used to satisfy the domestic hot water need. The domestic combination boilers are also available for the space heating load when the domestic hot water load is satisfied. This is accomplished using a motorized valve and storage tank equipped with a heat exchanger. For additional information on the Combination System, see AERCO’s CCP-1 literature.
4.4.5.4 Designating the Number of
Combination Boilers
A maximum of 4 combination boilers can be connected to the BMS. However, when using the Combination Mode, it is necessary to tell the BMS how many combination boilers there are. This is accomplished as follows:
IMPORTANT
When connecting combination boilers to the BMS, it is important that you start at the BLR 8 terminals on Terminal Strip JP2 and work towards BLR 5.
1. With the COMBINATION MODE selected, press the BLR OP MODE key. The display will read: COMBINATION MODE X OF CCP BOILERS, (where X is the number of combination boilers).
2. Enter the number of combination boilers connected to the BMS using the and arrow keys.
4.4.6 HDR SET MODE
This key has two functions. First, it is used to select the Indoor/Outdoor Reset, Constant Setpoint, or Remote Setpoint boiler mode operation. Second, it is used to select the type of indoor temperature sensor used with the BMS, if one is installed. The type of sensor can be either resistive (thermistor) or a constant voltage signal with current varying from 4 to 20 mA.
Pressing the HDR SET MODE key once selects the Header Set Mode function. If the desired mode is not displayed, toggle the display to the desired mode (IN/OUTDOOR
RESET, REMOTE SET TEMP or CONSTANT SETTEMP) using the or
arrow key.
Pressing the HDR SET MODE key a second time toggles the display to indicate the type of indoor temperature sensor which will be used with the BMS (THERMISTOR or 4-20 mA). If necessary, toggle the display to the desired sensor type using the or arrow key.
If the REMOTE SET TEMP mode is selected and the Indoor Temperature Sensor feature is used, the Sensor input type must be THERMISTOR (resistive) since the BMS has only one 4-to-20 mA input.
4.4.7 INTGL RATE GAIN, TEMP
BANDWIDTH and DERIV GAIN Keys
These three keys provide PID (Proportional Integral Derivative) control functions which govern temperature control and response of the BMS to the boiler system. Since each system is different, these PID controls can tune the BMS to the characteristics of your
4-13
specific installation. The factory defaults preset by AERCO work well for most applications. In instances when there is a large error between the setpoint and the actual supply water temperature, the BMS may appear to require PID tuning. However, It is best to observe BMS operation over a period of time prior to making any PID changes. Contact AERCO or an AERCO representative prior to making any PID setting changes.
The functions provided by the PID function keys are described in the following paragraphs.
4.4.7.1 TEMP BANDWIDTH
Header Temperature Bandwidth (HDR TEMP B.W.) concerns the system’s
response to the setpoint error. Setpoint error is the difference between the supply water temperature setpoint and the actual supply water temperature. A constant setpoint error will yield a constant and proportionate correction factor for the duration of the error. If there is a deviation from the constant error, the correction factor will be changed in proportion to the deviation. For instance, a temperature bandwidth of 50°F is chosen. The header temperature setpoint is 180°F and the actual incoming supply water temperature is 130°F
. This is a 50° error and the following
is true:
Temp. Error_____
X 100 = Firing Rate in %
Prop Bandwidth
Therefore:
50 X 100% = Firing Rate 50
1 X 100 = 100 % Firing Rate
With an error of 30° and a bandwidth of 50, the following would be true:
30/50 X 100 = .6 X 100 = 60% Firing Rate.
4.4.7.2 INTGL RATE GAIN
Integral gain responds to the setpoint error over a period of time. Integral references the proportional bandwidth error signal and sums itself with respect to the period of time that an error exists. Based on the example in the previous paragraph (4.4.7.1), if the integral is 0.15 repeats per minute and the firing rate is 60%, and a temperature error exists for 1 minute, then the following is true:
(0.15 reps/min.) x (60% firing rate) = 9% actual firing rate
60% firing rate +9% firing rate = 69% firing rate
If the error continues and is present for another minute, another 9% correction factor will be added:
69% firing rate +9% firing rate = 78% firing rate
If, after a load change, the supply water temperature stabilizes at a temperature above or below the setpoint, the integral gain should be increased. If, after a load change, the supply water temperature overshoots and oscillates excessively, integral gain should be reduced.
4.4.7.3 DERIV GAIN
Derivative gain is a function of time. It senses and responds to the rate of change of the setpoint error. A slow rate of change will yield a small amount of derivative gain. Conversely, a fast rate of change will yield a large derivative gain. Too high a derivative gain setting will produce a large output for a short time. This can result in overshoot of the setpoint. Too low a derivative gain setting will have the opposite effect, producing a small output for a longer period, and may result in slow system response or the system undershooting the setpoint.
4-14
4.4.8 AUX RELAY
This key is used to display or change the firing rate at which the Auxiliary Relay opens and closes. The Auxiliary Relay is typically used with AERCO’s Combination Control Panel (CCP) system or to start an auxiliary boiler for use under peak load conditions. If this boiler is of the non­condensing type, the OFF firing rate percentage must be high enough to prevent the boiler from operation in condensing mode.
Pressing the AUX RELAY key once displays the firing rate percentage at which the relay opens (AUX RELAY OPEN). The default value of 45% is acceptable for a CCP system. However, to run another non­condensing boiler, this percentage may need to be changed to approximately 70%. The displayed percentage can be changed in 1% increments from 1 to 99%.
Pressing the AUX RELAY key again displays the firing rate percentage at which the relay closes (AUX RELAY CLOSE). Two options are available for this function: 100%
FIRING RATE, or 100% AND OFF
(default). Pressing the or arrow key will toggle the display. If 100% RATE is selected, the Auxiliary Relay contacts close when the BMS indicates that all boilers are at a 100% firing rate. If the default setting of 100% AND OFF is selected, the Auxiliary contacts close when the BMS indicates that all boilers are at a
100% firing rate determines that all boilers are off. The off­state is when each boiler has either faulted, or someone has pressed the off button on the boilers. This function allows a boiler that is wired to the Auxiliary Relay contacts to fire when all of the other boilers have faulted or have been turned off.
, or when the BMS
FIRING
When in Combination Control Panel (CCP) mode, care must be taken to ensure that the
AUX
RELAY OPEN percentage is set so
that the system does not oscillate turning boilers on and off. A maximum open percentage of 45% is recommended for Combination Control mode. If using the AUX contacts to fire an auxiliary boiler, the recommended open percentage is 70%.
4.4.9 and Arrow Keys
These keys are used to increment () or decrement () the displayed variable, or toggle the display through available options. Pressing and holding these keys will increment or decrement the displayed value at a rapid rate.
4.4.10 ON and OFF Keys
Pressing and releasing the ON or OFF key enables or disables the BMS. In addition, the corresponding LED will light when the corresponding key is pressed.
4.4.11 CONFIG SYS
When the CONFIG SYS key LED is lit, pressing this key will exit the System Configuration Mode and place the BMS in the Normal Mode. When this occurs, the display will show HEADER TEMP (°F) which is the default Normal Mode display. See paragraph 4.2 for key functions in Normal Mode.
4-15
Section 5 ______________________________
Programming the BMS Mode of Operation__
Prior to programming, the BMS must be mounted and all required wiring completed. In addition, all connections should be checked for accuracy. The BMS is now ready to be programmed for the desired mode of operation of the boiler plant. The steps for programming will vary somewhat, depending on whether the Indoor/Outdoor Reset, Remote Setpoint or Constant Setpoint operating mode is selected.
5.1 INDOOR/OUTDOOR RESET MODE
The Indoor/Outdoor Reset mode is based on outside air temperature. The header supply water temperature will vary up or down in accordance with outside air temperature. This mode requires that, as a minimum, a System Start Temperature (SYS.START RELAY), Building Reference Temperature (BLDG REF. TEMP) and Reset Ratio be programmed into the BMS. This data is based on the degree days for your geographic area. An outdoor air sensor MUST be installed when operating in this mode (refer to paragraph 3.3.2).
5.1.1 Selecting Indoor/Outdoor Reset Mode
To select Indoor/Outdoor Reset mode, perform the following steps:
1. Press the CONFIG SYS key to enter the System Configuration mode. The CONFIG SYS key LED will illuminate.
2. Place SYSTEM CONFIGURATION OVERLAY on the BMS front panel.
3. Press the HDR SET MODE key once. HEADER SET MODE is displayed with the present mode selection.
4. While observing the display, toggle the
HDR SET MODE using the or key to IN/OUTDOOR RESET.
5. Press the CONFIG SYS key to exit the System Configuration mode. The key LED will go off.
6. Remove the SYSTEM CONFIGURA-
TION OVERLAY from the front panel.
5.1.2 Entering System Start
Temperature
The system start temperature is the outside temperature at which the boiler plant begins to operate. AERCO presets the system start temperature at 70°F. However, temper­atures from 32 to 120°F can be selected using the and arrow keys on the keypad. Proceed as follows to enter the system start temperature:
1. Press FIELD ADJ mode key. Verify that the FIELD ADJ key LED illuminates.
2. Press the SYS START TEMP key.
3. Using the ▲ and ▼arrow keys, select the desired Start Temperature for the boiler plant.
5.1.3 Determining Reset Schedule
There are two possible variables that must be considered when determining reset schedule; reset ratio and building reference temperature. There are two methods for determining reset ratio. The first method uses the charts in Appendix B. This method is suitable for most installations. However, if a special reset schedule is desired for reheat or other purposes, the calculation method must be used. In this method, both reset ratio and building reference temperature must be calculated. See Appendix B for further instructions concerning both of these methods.
5-1
5.1.4 Entering the Building Reference Temperature
To enter the Building Reference Temperature, perform the following steps:
1. Enter Field Adjust mode by pressing the FIELD ADJ key. Verify that the key LED illuminates.
2. Press the REF TEMP key. The display will show the present BLDG REF. TEMP.
3. Using the ▲ and ▼ arrow keys, select the desired Building Reference Temperature.
5.1.5 Entering the Reset Ratio
Enter the Reset Ratio as follows:
1. Ensure that the BMS is in the Field Adjust mode.
2. Press the RESET RATIO key. The display will show RESET RATIO
1.2°F/°F which is the default setting.
3. Using the ▲ and ▼ arrow keys, select the desired Reset Ratio.
4. Initialize the system as described in paragraph 5.5.
NOTE
For Remote Setpoint control utilizing a RS485 Modbus network, refer to Modbus Communication Manual GF-114.
5.2 SETUP FOR REMOTE
SETPOINT MODE
In order to set up the BMS to operate in this mode, a 4-to-20 mA communication line from an Energy Management System with a floating ground is required. In addition, a BMS header sensor is required. This mode may be used with or without an outdoor air temperature sensor installed. Entries in this mode are required for the following items:
Header Set Mode
5.2.1 Entering Header Set Mode and Boiler Operating Mode
These selections are made with the BMS in the System Configuration mode. Proceed as follows:
1. Press the CONFIG SYS key to enter the System Configuration mode. The CONFIG SYS key LED will illuminate.
2. Place SYSTEM CONFIGURATION OVERLAY on the BMS front panel.
3. Press the HDR SET MODE key once. HDR SET MODE is displayed with the present mode selection.
4. While observing the display, toggle the
HDR SET MODE to REMOTE SET TEMP using the or arrow key.
5. Press the BLR OP MODE key. BOILER OP MODE is displayed with the present
mode selection.
6. Select either the PARALLEL MODE or SEQUENTIAL MODE using the or arrow key.
7. Press the CONFIG SYS key to exit the System Configuration mode. The CONFIG SYS LED will go off.
8. Remove the SYSTEM CONFIGUR- ATION overlay from the BMS front panel.
5.2.2 Entering Remote Signal Type and
Header Temperature Limits
These selections are made with the BMS in the Field Adjust mode. Proceed as follows:
1. Enter Field Adjust mode by pressing the FIELD ADJ key. Verify that the key LED illuminates.
2. Press the AIR TEMP key five times until the first line of the display reads REMOTE SIGNAL.
3. Using the ▲ or ▼arrow key, toggle the second line of the display to read 4-20MA.
Boiler Operating Mode
Remote Signal Type
Header Temperature Limits.
4. Next, press and release the HDR TEMP
key once. HDR HIGH LIMIT is
LIMIT
displayed with the present high temperature limit setting.
5-2
NOTE
Steps 5, 6 and 7 scale the 20 mA Remote Signal to the selected HDR HIGH LIMIT and HDR LOW LIMIT settings.
5. Select the desired header high temperature limit setting using the and arrow keys. The selected temperature will be equal to a 20 mA Remote Signal.
6. Press and release the HDR TEMP LIMIT key again. HDR LOW LIMIT is displayed with the present low temperature limit setting.
7. Select the desired header low temperature limit setting using the and arrow keys. The selected temperature will be equal to a 4 mA Remote Signal.
5.3 S
ETUP FOR CONSTANT
SETPOINT MODE
In this mode of operation, only a header sensor is required. Entries in this mode are required for Header Set Mode, Boiler Operating Mode and Header Reference Temperature.
5.3.1 Entering Header Set and Boiler
Operating Modes
These selections are made with the BMS in the System Configuration mode. Proceed as follows:
1. Press the CONFIG SYS key to enter the System Configuration mode. The CONFIG SYS key LED will illuminate.
2. Place SYSTEM CONFIGURATION OVERLAY on the BMS front panel.
3. Press the HDR SET MODE key once. HEADER SET MODE is displayed with the presently stored mode selection.
4. While observing the display, toggle the
HDR SET MODE to CONSTANT SETTEMP using the or arrow key.
5. Press the BLR OP MODE key. BOILER OP MODE is displayed with the
presently stored mode selection.
6. Select the PARALLEL, SEQUENTIAL or
COMBINATION MODE using the ▲ or arrow key.
7. Press the CONFIG SYS key to exit the System Configuration mode. The CONFIG SYS LED will go off.
8. Remove the SYSTEM CONFIG- URATION overlay from the BMS front panel.
5.3.2 Entering Header Reference
Temperature (Setpoint)
The Header Reference Temperature (Set­point) is entered as follows:
1. Enter Field Adjust mode by pressing the FIELD ADJ key. Verify that the key LED illuminates.
2. Press the REF TEMP key. The display will show the present HEADER REF. TEMP stored in memory.
3. Set the desired setpoint temperature using the and arrow keys. The set­point temperature can be adjusted from 40°F to 220°F.
4. Initialize the BMS using the procedures in paragraph 5.5.
5.4 CONFIGURING BOILERS
FOR PULSE WIDTH MODULATION (PWM)
Configuring each boiler for BMS control using Pulse Width Modulation (PWM) differs, depending on the Control System used by each AERCO boiler. Refer to the appropriate Operation and Maintenance Manuals provided with the boilers being used. If the KC1000 or Benchmark boilers are equipped with the newer C-More Control Systems, proceed to paragraph
5.4.1. However, if the boilers are equipped
with the older Modular Control Systems, proceed to paragraph 5.4.2.
5-3
5.4.1 C-More Control System PWM Setup
For PWM communication, each boiler’s C­More Control System must have the Configuration Menu items properly set up as follows:
1. Boiler Mode – This option must be set for Direct Drive.
2. Remote Signal – This option must be set for BMS (PWM Input).
Refer to Operation and Maintenance Manual GF-109 (KC1000 Boiler) or GF-110 (Benchmark Boiler) for instructions on changing menu items.
NOTE
AERCO Modular Control Systems are equipped with Honeywell (Blue) or Fire-Eye (Red) Temperature Controllers.
5.4.2 Modular Control System PWM
Setup
For proper PWM communication, each boiler’s Modular Control System Temp­erature Controller must be properly addressed and configured as follows:
5.4.2.1 Temperature Controller
Addressing
For proper PWM communication, each boiler’s Temperature Controller must be set to a comm. Address of 32. This is true whether the boilers are space heating or Combination (CCP) types.
If the individual boiler’s temperature controller is not correctly addressed, the secure menu of the temperature controller must be entered in order to change the address. Refer to Operation and Maintenance Manual GF-106 (KC1000 Boiler) or GF-107 (Benchmark Boiler) for detailed procedures.
5.4.2.2 Configuring the Temperature
Controller
Once addressing has been completed, it is necessary to perform two more configuration steps to each boiler’s temperature controller. Each temperature controller must be in the Remote and Auto/Off (Manual) modes for proper communication and operation with the BMS.
Refer to Operation and Maintenance Manual GF-106 (KC1000 Boiler) or GF-107 (Benchmark Boiler) for detailed procedures to set each boiler to the Remote and Auto/Off (Manual) modes.
5.5 SYSTEM INITIALIZATION
AND POLLING
In order for the BMS to recognize each boiler, a closed signal loop must exist between the BMS and the boiler. Initialization and polling is accomplished by performing the following simple steps:
1. Set the ON/OFF switch on each boiler control panel to ON.
2. Turn on the BMS by pressing the ON key. The BMS will automatically poll (recognize) each boiler at prescribed intervals.
3. Check the yellow REMOTE (REM) LED on each boiler control panel to ensure it is ON. This indicates that the boiler is now being controlled by the BMS.
4. If any of the boiler REMOTE LEDs are off, check to ensure that:
(a) Boiler AC power is not turned off.
(b) Boiler is not shut down due to a
fault.
(c) The BMS-to-boiler signal loop is not
broken.
The BMS will continuously poll the boilers at prescribed intervals. Therefore, if a boiler is placed off-line and then placed back on-line, it will again be recognized by the BMS during the next polling cycle.
5-4
5.6 TESTING THE SYSTEM
The following procedure places a load on the system and will begin firing the boilers. At this point it is very important to make sure the system pumps are running.
After system has been initialized as described in paragraph 5.5, proceed as follows:
IMPORTANT
Prior to performing these tests, view and record the PRESENT settings stored in the BMS for HDR SET MODE and REF TEMP. These settings MUST be restored to these values upon completion of the following tests.
1. Turn off the BMS by pressing the OFF key. The OFF LED will illuminate..
2. Place the SYSTEM CONFIGURATION OVERLAY on the BMS front panel.
3. Press the CONFIG SYS key. The CONFIG SYS LED will illuminate.
4. Press the HDR SET MODE key. HEADER SET MODE will be displayed, followed by the mode setting stored in memory (IN/OUTDOOR RESET,
REMOTE (4-20ma.), or CONSTANT SETTEMP).
10. Set the HEADER REF. TEMP (setpoint) to 220°F using the and arrow keys.
11. Press the FIELD ADJ key. The LED will turn off.
12. Press the %LOAD key and monitor the display for the firing rate (PERCENT OF LOAD) and the number of boilers firing (Units).
13. When all boilers have reached at least a 55% firing rate, any boilers that have not started have not been identified by the BMS.
14. Remember that in the Sequential or Combination modes, the BMS turns boilers on in 30-second intervals. Therefore, in a 6-boiler plant, with five boilers operating at 55% capacity, a boiler that has not started after 3 minutes has not been recognized. In parallel mode, all boilers will start at the same time.
15. This completes the System Test. Return the HDR SET MODE and REF TEMP settings to their previously stored values.
16. If the System Test is not completed successfully, contact AERCO at 1-800-526-0288.
5. Select CONSTANT SETTEMP using the or arrow key.
6. Press the CONFIG SYS key The LED will turn off.
7. Remove the SYSTEM CONFIG­URATION OVERLAY.
8. Press the FIELD ADJ key. The LED will illuminate.
9. Press the REF TEMP key.
5-5
Appendix A ____________________________
SPECIFICATIONS
INPUTS
POWER
Input voltage 120 VAC, 60Hz, 1 phase, ± 10%, fused at 1 A
OUTSIDE AIR SENSOR (NTC thermistor)
Acceptable types AERCO GP-122662 (Sensor Only) or
Range -60°F to +80°F
Short sensor protection Invoked at +200°F
HEADER SENSOR (NTC thermistor)
Acceptable types AERCO 64038 (Sensor Only) or
Range 40°F to +220°F
GM-122781 (Sensor & Mounting Plate)
GM-122790 (Sensor and Thermowell)
Short sensor protection Invoked at +300°F
INDOOR TEMPERATURE SENSOR (NTC thermistor)
Acceptable types AERCO GP-122882 (Sensor Only)
Range 40°F to 140°F
Short sensor protection Invoked at 300°F
A-1
Appendix A (cont.) ________________________
CURRENT LOOP
Input resistance
Protection Isolated from AC line potential, fuse-protected at
Operational current range 4 mA to 20 mA
SET BACK
Input 12 VDC at 15 mA. External short activates circuit;
OUTPUTS
SYSTEM START RELAY
Contact Rating 120 VAC at 5 A, fuse protected at 5 A
Operation Relay closes when outside air temperature is less
FAULT ALARM RELAY
Contact Rating 120 VAC at 5 A, fuse protected at 5 A
250 Ohms
62 mA, open loop detected at <1 mA
Open deactivates it
than the system start temperature setting
Operation Relay closes when valid error condition occurs
AUXILIARY RELAY
Contact Rating 120 VAC at 5 A, fuse protected at 5 A
Operation
Relay closes when all available boilers are operating at maximum power input (fire rate). Relay can be programmed to close when all available boilers are at maximum power input or no boilers are available (all boilers faulted or turned off).
A-2
Appendix A (cont.) ________________________
BOILER DRIVE
Drive Type (PWM) Signal (with 12 msec time base)
Valve drive 100% fire rate at 95% pulse width, 0% fire rate at
Current Loop Determination Optically isolated detection
MEMORY
Non-Volatile Memory
ALARMS
Error Handling
Error Messages Refer to Appendix H for displayed error messages
Optically-isolated, pulse width modulated
5% pulse width
EPROM storage of system input. Variables changed in Field Adjust or Configure System mode. EPROM storage of on/off state. All other variables stored in volatile memory which is not retained after power interruption.
If a valid error condition occurs, the display will show the error condition for 2 seconds, then return to the previous display. If multiple error conditions are present, the display will show all error modes. The alarm relay contacts will close upon detection of the error. The alarm can be canceled by pressing the RESET RATIO key or correcting the error.
and troubleshooting information.
A-3
Appendix A (cont.) ________________________
DEFAULT VALUES
System State Halted (stop mode) Header Set Mode
Indoor Air Input
Boiler Op Mode
Start Level 45%
Stop Level 18%
Auxiliary Relay Open 45% Fire Rate
Auxiliary Relay Close 100% and Off
Header Temperature Bandwidth 70°F
Integral Gain .15 repeats/min.
Derivative Gain .15
Indoor/Outdoor Reset
Thermistor
Sequential
System Start Relay 70°F
Building Reference Temperature 70°F
Header Reference Temperature 160°F
Header High Limit 220°F
Header Low Limit 40°F
Reset Ratio 1.2
Indoor Setpoint 70°F
All Offset Temperatures 0
All Offset Times 0
Indoor Prop Band 0
Maximum Power Input 100%
Interlock 1 Start Enabled
Number of Combo Units 1
Real-Time Clock Set to Present Date and Time
A-4
Appendix B _____________________________
Methods for Determining Reset Schedule and Indoor/Outdoor Reset Ratio Charts
Using the Charts to Determine Reset Schedule
Each table in this appendix provides data for a specific building reference temperature. On the vertical axis of each table are degree day temperatures. These are the average lowest temperatures likely to be encountered. The engineer of your system should have this number for your area. The reset ratio is shown across the top. The data in the tables is header temperature. To determine the reset ratio for your installation, follow these steps:
On the vertical axis, find the degree
day for your area.
Select the temperature that should be
maintained in the header to maintain the building at the desired temperature. The system engineer should have this information.
The proper reset ratio is the value
found above the two selected points. For example, for a degree day of 15°F and a header temperature of 125°F, the reset ratio is 1.4.
Determining Reset Schedule By Formula
There are two steps required to determine reset schedule with this method. The first is to determine the reset ratio by dividing the range of outside temperatures by the range of header temperatures:
T
header/Toutside
= Reset Ratio.
for example, If T
varies from -10 to
outside
+95°F (105° range), and
T
varies from 125 to 200°F (75°
header
range), then the reset ratio equals
75°/105° = 0.714.
Once the reset ratio is determined, this number and the lowest or highest header temperature and corresponding lowest or highest air temperature, are input to the following equation to yield the building reference temperature:
T
- RR (TR-TO)+TR, where:
header
RR is the reset ratio TR is the building reference temperature TO is the minimum outside temperature, and
T
is the maximum heating system
header
Temperature desired at the minimum outside air temperature.
So in this example:
T
header
= 200°F
200°F = 0.714 [TR-(-10°F)] +TR 200°F = 1.714TR + 7.14°F
Solving for TR:
TR = (200°F-7.14°F)/1.714 TR = 192.86°F/1.714 TR = 112.5°F
Therefore, use a reset ratio of 0.7 (closest to 0.714) and a building reference temperature of 113 (closest to
112.5).
B-1
Appendix B (cont.) _________________________
Header Temperature for a Building Reference
Temperature of 50°F
Reset Ratio
Air Temp (°F) 0.6
50 50
45 53
40 56
35 59
30 62
25 65
25 65
20 68
15
10 74
5 77
0 80
-5 83
-10 86
-15 89 102 116 128 141 154 167 180 193
71 78 85 92 99
0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
50 50 50 50 50 50 50 50 50
54 55 56 57 58 59 60 60 62
58 60 62 64 66 68 70 72 74
62 65 68 71 74 77 80 83 86
66 70 74 78 82 86 90 94 98
70 75 80 85 90 95 100 105 110
70 75 80 85 90 95
74 80 86 92 98 104
106 113 120 127
82 90 98
86 95 104
90 100 110
94 105 116
98 110 122
106 114 122 130 138
113 122 131 140 149
120 130 140 150 160
127 138 149 160 171
134 146 158 170 182
100 105
110
111
110
122
134
146
158
170
182
194
206
-20 92 106 120 134 148 162 176 190 204
B-2
218
Appendix B (cont.) _________________________
Header Temperature for a Building Reference
Temperature of 65°F
Air Temp (0F)
65 60 55 71 73 75 77 79 81 83 85 87 89 50 74 77 80 83 86 89 92 95 98 101 45 77 81 85 89 93 97 101 105 109 113 40 80 85 90 95 100 105 110 115 120 125 35 30 25 89 97 105 113 121 129 137 145 153 161 20 92 101 110 119 128 137 146 155 164 173 15 10
5 101 113 125 137 149 161 173 185 197 209 0 104 117 130 143 156 169 182 195 208
-5 107 121 135 149 163 177 191 205 219
-10 110 125 140 155 170 185 200 215
-15 113 129 145 161 177 193 209
-20 116 133 150 167 201 218
0.6 0.8
65 65 65 65 65 65 65 65 65 65 68 69 70 71 72 73
83 89 95 86 93
95 98
105 115 126 135 145 109 120 131 142 153
1.0 1.2 1.4 1.6
100 107 114 121
Reset Ratio
101 107 113
1.8 2.0 2.2
74
119 128
155 164
75 76
125 131 135 142
165 175 175 186
2.4
77
137 149
185 197
B-3
Appendix B (cont.) __________________________
Header Temperature for a Building Reference
Temperature of 70°F
Air Temp (0F) 0.6
70 70 65 73 60 76 55 79 50 82 45 40 35 30 94 102 110 118 126 134 142 150 158 166 25 97 106 115 124 133 142 151 160 169 178 20 100 110 120 130 140 150 160 170 180 190 15 103 114 125 136 147 158 169 180 191 202 10 106 118 130 142 154 166 178 190 202 214
5 109 122 135 148 161 174 187 200 213 0 112 126 140 154 168 182 196 210
-5 115 130 145 160 175 190 205
-10 118 134 150 166 182 198 214
-15 121 138 155 172 189 206
-20 124 142 160 178 196 214
85 90 88 94 91 98
0.8
70 74 78 82 86
1.0 1.2
70 70 75 76 80 82 85 88 90 94
95 100 105 110 115 120 125 130 100 106 112 118 124 130 136 142 105 112 119 126 133 140 147 154
Reset Ratio
1.4 1.6 1.8 2.0 2.2 2.4
70 70 70 70 70 70 77 78 79 80 81 82 64 86 88 90 92 94 91 94 97 98 102 106
100 103 106 110 114 118
B-4
Appendix B (cont.) __________________________
Header Temperature for a Building Reference
Temperature of 75°F
Air Temp (°F)
75 75 75 75 75 75 75 75 75 75 75 70 78 79 80 81 82 83 84 85 88 75 65 81 83 85 87 89 91 93 95 97 87 60
55 87 91 96 99 103 107 111 115 119 111 50 90 95 100 105 110 115 120 125 130 123 45 93 99 105 111 117 123 129 135 141 135 40 96 103 110 117 124 131 138 145 156 147 35 99 107 115 123 131 139 147 155 163 159 30 102 111 120 129 138 147 156 165 174 171
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
84 87 90 93 96 99
25 105 115 125 135 145 155 165 175 185 183 20 108 119 130 141 152 163 174 185 196 195
15 111 123 135 147 159 171 183 195 207 207 10 114 127 140 153 166 179 192 205 218 219
5 117 131 145 159 173 187 201 215 0 120 135 150 165 180 195 210
-5 123 139 155 171 187 203 219
-10 126 143 160 177 194 211
-15 129 147 165 183 201 219
Reset Ratio
102 105 108
99
B-5
Appendix B (cont.) _________________________
Header Temperature for a Building Reference
Temperature of 80°F
Air Temp (°F)
80 75 83 84 85 86 87 88 89 90 91 92 70 86 88 90 92 94 96 98 100 102 104 65 60 55 50 45 101 108 115 122 129 136 143 150 157 164 40 104 112 120 128 136 144 152 160 168 176 35 107 116 125 134 143 152 30 110 120 130 140 150 160 170 180 190 200 25 113 124 135 146 157 168 174 190 201 212 20 116 128 140 152 164 176 188 200 212 15 119 132 145 158 171 184 197 210 10 122 136 150 164 178 192 206
5 125 140 155 170 185 200 215 0 128 144 160 176 192 208
-5 131 148 165 187 199 216
-10 134 152 170 188 206
0.6
80 80 80 80 80 80 80 80 80 80
89 92 95 98 92 96 95 100
98
0.8
104 110 116 122 128 134 140 148 152
1.0 1.2
100 104 108 112 116 120 124 128 105 110 115 120 125 130 135 140
Reset Ratio
1.4 1.6 1.8 2.0 2.2 2.4
101 104 107 110 113 116
161
170 179 188
B-6
Appendix B (cont.) _________________________
Header Temperature for a Building Reference
Temperature of 90°F
Air Temp (°F)
90 85 80 75 70 102 106 65 105 110 60 108 114 55 111 118 50 114 122 45 117 126 40 120 130 35 123 134 30 126 138 150 162 174 186 198 210 25 129 142 155 168 181 194 207 20 132 146 160 174 188 202 218 15 135 150 10 138 154 170 186 202 218
5 141 158 0 144 162 180 198 216
0.6
0.8 1.0
90 90 90 90 90 90 90 90 90 90 93 94 95 96 97 98 99 96 98 100 99
102
105 110 115 120 125 130 135 140 145
165
175
102 104 106 108 110 112 114 108 111 114 117 120 123 126 114 118 122 126 130 134 138 120 125 130 135 140 145 150 126 132 138 144 150 156 162 132 139 146 153 160 167 174 138 146 154 162 170 178 186 144 153 162 171 180 189 198 150 160 170 180 190 200 210 156 174 186 198 210
180 195 210
192 209
Reset Ratio
1.2 1.4 1.6
1.8 2.0 2.2
100 101 102
2.4
B-7
Appendix C _____________________________
Normal (Read-Only) Mode
Display Messages and Defaults
Key Display Message Default Range
HDR
TEMP
(Press and Hold) HEADER SET TEMP
AIR
TEMP
(Press and Hold) INDOOR AIR TEMP
% LOAD
SYS
START TEMP
(Press and Hold)
REF
TEMP
(Press and Hold)
HEADER REF. TEMP
BLDG REF TEMP
HDR
TEMP
LIMIT
(Press and Hold)
SET
POINT
(Press and Hold)
PROP BAND
(Press and Hold)
RESET
RATIO
(Press and Hold)
OFF SET
(Press and Hold)
HEADER TEMP 160°F (Default Display)
160°F OUTSIDE AIR TEMP 70°F
70°F (If Connected) PERCENT OF LOAD 100% 8 Units SYS. START RELAY 70°F
BLDG REF TEMP (Indoor/Outdoor Reset Mode)
(Constant Setpoint Mode)
(Remote Setpoint Mode) HDR HIGH LIMIT 220°F
INDOOOR SET POINT 70°F
INDOOR PROP BAND
00.0°F/°F
RESET RATIO
1.2°F/°F (Indoor/Outdoor Reset Mode Only) FUNCTION NOT VALID (All Other Modes) OFFSET TEMP 0°F
160°F 40 to 220°F
100 % 0 to 100 %
0 to 40 Units
70°F 32 to 120°F
70°F 40 to 220°F
120°F 40 to 220°F
70°F 40 to 220°F
220°F 40 to 220°F
70°F 50 to 150°F
00.0°F/°F 0 to 20°F/°F in 0.5°F/°F
increments
1.2°F/°F 0.3 to 3.0°F/°F in 0.1 increments
0°F -50 to +50°F
C-1
D-1
Appendix D _____________________________
Field Adjust Mode
Display Messages and Defaults
Key Display Message Default Range
HDR
TEMP
(Press Once)
(Press 2nd Time) MIN SLAVE ADDR
(Press 3rd Time) MAX SLAVE ADDR
(Press 4th Time) NUMBER NETW BLRS
(Press 5th Time) MODBUS CNTL TYPE
(Press 6th Time) NETW BOILER 1
AIR
TEMP
(Press Once)
(Press 2nd Time) RS232 BAUDRATE
(Press 3rd Time) MODBUS ADDRESS
(Press 4th Time) NETWORK TIMEOUT
(Press 5th Time) REMOTE SIGNAL
(Press 6th Time) MODBUS PASS THRU
% LOAD
(Press & Hold)
% LOAD
(Press & Release)
(Press 2nd Time) SET TIME CLOCK
(Press 3rd Time) SET TIME CLOCK
(Press 4th Time) SET TIME CLOCK
(Press 5th Time) SET TIME CLOCK
(Press 5th Time) SET TIME CLOCK
(Press 6th Time) SET TIME CLOCK
RS485 BAUDRATE 9600
0
0
0
Round Robin
ADDRESS=0 (Repeat for Each Netw Boiler) RS232 MODE MODBUS SLAVE
9600
128
60
4-20MA
DISABLED PERCENTAGE OF LOAD 100% 8 Units SET TIME CLOCK MONTH: 06
DATE: 21
YEAR: 03
DAY: 1
HOURS: 14
HOURS: 14
MINS: 30
9600 2400, 4800, 9600,
14400, 19200
0 0 to 127
0 0 to 127
0 0 to 32
Round Robin Round Robin or
Broadcast
0 0 to 127
MODBUS SLAVE NORMAL or
MODBUS SLAVE
9600 2400, 4800, 9600,
14400, 19200
128 0, 128 to 247
60 sec. 5 to 240 sec.
4-20MA 4-20MA or
MODBUS
DISABLED ENABLED or
DISABLED
100 % 0 to 100 %
0 to 8 Units
Present month 01 to 12
Present day of
month
Present year 00 to 99
Day one is
Sunday
Present time 00 to 23
Present time 00 to 23
Present time 00 to 59
1 to 31
1 to 7
Appendix D (cont.)__________________________
Field Adjust Mode
Display Messages and Defaults (cont.)
Key Display Message Default Range
SYS
START
TEMP
(Press 2nd Time) SYS START OPTION
REF
TEMP
HEADER REF TEMP
HDR TEMP LIMIT
(Press 2nd Time) HDR LOW LIMIT
(Press 3rd Time) HEADER OFFSET
SET
POINT
PROP BAND
RESET
RATIO
OFFSET
CONFIG
SYS
(Press 2nd Time) FAULT ALARM CLEAR
SYS START RELAY 70°F
TEMP ONLY BLDG REF TEMP (When in Indoor/Outdoor Reset Mode or Remote Setpoint Mode)
(When in Constant Setpoint Mode) HDR HIGH LIMIT 220°F
40°F
0°F INDOOOR SET POINT 70°F INDOOR PROP BAND
00.0°F/°F
RESET RATIO
1.2°F/°F (Indoor/Outdoor Reset Mode Only) FUNCTION NOT VALID (All Other Modes) OFFSET ENABLE OFF OFFSET TEMP DAY 1: OFFSET ON TIME DAY 1 OFFSET OFF TIME DAY 1 FAULT ALARM RELAY ALL FAULTS
MANUAL RESET
70°F 32 to 120°F
TEMP ONLY TEMP ONLY, or
TEMP AND LOAD
70°F 40 to 220°F
120°F 40 to 220°F
220°F 40 to 220°F
40°F 40 to 220°F
0°F -5°F to 5°F
70°F 50 to 150°F
00.0°F/°F 0 to 20°F/°F in 0.5°F/°F
increments
1.2°F/°F 0.3 to 3.0°F/°F in 0.1 increments
OFF ON or OFF
0 -50 to +50°F
00:00 00 to 23 Hours
00 to 59 Mins.
00:00 00 to 23 Hours
00 to 59 Mins.
ALL FAULTS ALL FAULTS,
NO INTERLOCK,
INTERLOCK 2 INTERLOCK 1
MANUAL
RESET
MANUAL RESET
or AUTOMATIC
D-2
Appendix E _____________________________
Config Sys Mode
Display Messages and Defaults
Key
TEMP FAIL
MODE
SYS
ENABLE
MAX PWR INPUT
(Press 2nd Time)
START LEVEL
STOP
LEVEL
BLR OP
MODE
(Press 2nd Time)
If COMBINATION
MODE is selected
HDR SET
MODE
(Press 2nd Time)
INTGL RATE
GAIN
TEMP
BANDWIDTH
AUX
RELAY
(Press 2nd Time)
DERIV
GAIN
Display Message Defaults Range
TEMP FAIL MODE SHUTDOWN INTERLOCK 1 START ENABLED MAX POWER INPUT 100% PWM TIMEBASE CAL 0
BLR. START LEVEL 45% BLR STOP LEVEL 18% BOILER OP MODE
SEQUENTIAL MODE
COMBINATION MODE 1 OF CCP BOILERS
HEADER SET MODE IN/OUTDOOR RESET
INDOOR TEMP INP. THERMISTOR INPUT INTEGRAL GAIN
0.15 REP/MIN HDR TEMP B.W. 70°F AUX RELAY OPEN 45% AUX RELAY CLOSE 100% AND OFF DERIVATIVE GAIN
0.15 MIN.
SHUTDOWN SHUTDOWN or
SWITCH INPUTS
START ENABLED
100% 50 to 100%
0 -30 to 30
45%
18% 10 to 45%
SEQUENTIAL SEQUENTIAL,
1 1 to 4
IN/OUTDOOR RESET
THERMISTOR THERMISTOR or
0.15 REP/MIN 0.00 to 9.99
70°F 5 to 100°F
45% 0 to 99%
100% AND OFF 100% AND OFF or
0.15 MIN. -2.00 to 2.00 MIN.
START ENABLED or ALWAYS ENABLED
25 to 100%
PARALLEL or COMBINATION
IN/OUTDOOR RESET, CONSTANT SETTEMP, REMOTE SET TEMP
4-20 mA
REP/MIN
100% FIRE RATE
E-1
Appendix F _____________________________
Temperature Sensor Resistance Data
Temperature
(°F)
-40 239,571 180 1,362
-30 173,530 190 1,155
-20 127,088 200 984
-10 94,059 210 842
0 70,314 220 723
Resistance
(ohms)
Temperature
(°F)
Resistance
(ohms)
10 53,068 230 623
20 40,418 240 539
30 31,053 250 468
40 24,057 260 408
50 18,787 270 357
60 14,783 280 313
70 11,717 290 276
80 9,353 300 243
90 7,516 310
100 6,078 320
110 4,946 330
120 4,049 340
130 3,333 350 140 2,759 360
150 2,296 370
160 1,920 380 170 1,613 390
F-1
Appendix G _____________________________
Parts List
Part Number
GP-122783 Boiler Management System (BMS) Complete BMS
124376 Electronics
GP-6-217 #10-32 x 3/8 inch Mounting Screws GP-6-218 #10-32 x 1/2 inch Mounting Screw GP-161228 Mounting Plate GP-181108 Field Adjust Overlay GP-181109 System Configuration Overlay
18949 Machined Front Panel
122784 Control Panel
GP-123042
GP-123043
GP-122662 Outside Air Temperature Sensor
GM-122781 Outside Air Temperature Sensor Kit
64038 Header Temperature Sensor Sensor Only
GP-122758
GM-122790
GM-122791 Outdoor Reset Kit
GP-122882 Indoor Temperature Sensor 65020 Low Voltage Terminal Block (16 pin) 65021 High Voltage Terminal Block (9 pin)
120 VAC, 1A, 2AG subminiature, fast­acting fuse (Littlefuse 225001) 12 VAC, 5A, 2AG Subminiature, Fast­Acting Fuse (Littlefuse 225005)
Thermowell for Header Temperature Sensor
Header Temperature Sensor Kit
Description
BMS Controls per Spec. 5C5-380
Supplied with Control Panel (122784) Includes Machined Front Panel (18949)
For BMS Electronics
For System-Start, Fault Alarm, and Auxiliary Relays
Includes Sensor (122662) and Mounting Bracket
Thermowell Only
Includes 64038 and GP-122758 Includes GM-122781 and GM-122790
Comment
G-1
Appendix H _____________________________
TROUBLESHOOTING
When a fault occurs in the boiler plant, the BMS flashes error messages at 2-second intervals and the alarm contacts close. To cancel alarms (open contacts but message still displays), press the RESET RATIO key The fault messages shown in Table H1 can occur in any mode of operation, Constant Setpoint, Indoor/Outdoor Reset, or Remote Setpoint. Some of the most common problems encountered in BMS operation are contained in Table H2.
Table H1 Error Messages
Fault Message
Description & Possible cause
OUTSIDE AIR TEMP NOT CONNECTED
OUTSIDE AIR TEMP SENSOR ERROR
HEADER TEMP SENSOR ERROR
INDOOR AIR TEMP SENSOR ERROR
Open outside air temp. sensor: resistance greater than 240K ohms (less than -40°F) Shorted outside air temp. sensor: resistance less than 1K ohms (greater than 200°F) No sensor connected
Note: Displays only in 4-to-20 mA and Constant
Setpoint modes. It does not display as an error message, and will display only after pressing the AIR TEMP key.
When in Indoor/Outdoor Reset Mode, the outside air temperature sensor is either open, shorted, or not connected.
Open header sensor: resistance greater than 240K ohms (less than
-40°F) Shorted header sensor: resistance less than 240 ohms (over 300°F) Sensor not installed
Open indoor air temp. sensor: resistance greater than 240K ohms (less than -40°F) . Shorted sensor: resistance less than 240 ohms (over 300°F) No sensor installed and Prop Band is adjusted to > 0°F/°F
SYSTEM ERROR, INTERLOCK 1
Interlock 1 is open
H-1
Appendix H _____________________________
Table H1 Error Messages - Continued
Fault Message
Description & Possible cause
SYSTEM ERROR, INTERLOCK 2 OPEN
(4-20 MA) INPUT OPEN LOOP ERROR
FAIL SAFE MODE ACTIVATED
NETWORK COMM FLT TIMEOUT ERROR
NETWORK DISABLED MODBUS LISTEN
Interlock 2 is open
The 4-to-20-mA remote input signal has dropped below 3 mA, or the signal is not present at the BMS.
This message can be displayed when the BMS is controlling the boilers via Modbus or PWM communication. It indicates that the BMS is operating in the Fail Safe (Constant Setpoint) mode.
Displayed during Modbus Remote Setpoint operation when the BMS is functioning as a Slave to an EMS Master. Error indicates that the Network Timeout has expired.
Displayed during Modbus operation when the “FORCE LISTEN ONLY” Modbus diagnostic command is sent to the BMS Slave by the controlling Master, thereby disabling normal Modbus Network communication. It indicates that the Master is listening for the “RESTART COMMUNICATIONS OPTIONS” diagnostic command required to restart normal Modbus communication. The BMS will operate in the Fail Safe mode during this period.
H-2
Appendix H ____________________________
Table H2 Common Problems
Problem
Possible Causes
Solution
Boiler plant not started by BMS
Boiler not being recognized by BMS with Modular Control Box
Outside air temperature higher than system’s start temperature
System must be initialized
Wiring between boilers and
BMS not correct
Temperature controller is
not in Manual/Remote mode
Temperature controller’s secure menu is not locked
Boilers are not correctly
addressed
Wiring between the BMS
and boilers is incorrect Indoor sensor not installed but value has been entered under PROP BAND
Check outside air temperature and system start temperature. System start temperature should be higher than outside air temperature for boilers to run. See para. 4.3.3 and
4.3.5. Initialize and test system (para. 5.5 and 5.6).
Check wiring (Section 3)
Check temperature controller. The
REM and MAN lights should be illuminated. If not, shut off AC power to the boiler, wait 30 sec., and reapply power. The boiler will automatically return to remote/manual mode.
Go to Secure menu in temperature controller. It should display Secure
3. If the display shows Secure 4, relock to Secure 4.
See para. 5.4
See Section 3 for correct wiring
connections
If value has been entered under PROP BAND, change value to 00/00° F
Boiler not being recognized by BMS with
C-More Control Box
C-More Box not configured correctly.
C-More Box not enabled. Front panel switch is off.
Incorrect wiring between BMS and Boiler.
H-3
Ensure that the C-More Boiler is configured for Direct Drive and PWM (see para. 5.5 of GF-109 (KC1000) or GF-110 (Benchmark) for required menu settings.
Check ON/OFF switch.
See Section 3 for correct wiring
connections
Appendix H _____________________________
Table H2 Common Problems - Continued
Problem
Possible Causes
Solution
Boilers overshooting setpoint or tripping aquastat
Modbus Network faults encountered. Boiler plant not operating
Header sensor not installed correctly
PID setting require adjustment
Adjustable aquastat set too low
System pumps are shut
down and not controlled by or interlocked with the BMS
BMS is set to ALWAYS ENABLE
BMS or boilers not properly configured for Modbus communication
Check header sensor connections and installation.
Adjust PID settings. See para. 4.4.7
If aquastat is set lower than 200°F,
reset it to 220°F.
If system pumps are shut down,
check start and stop temperatures on energy management system. They should correspond to those set in the BMS. In addition, interlock wiring can be run between the BMS and energy management system to disable the BMS pumps when pumps are not running.
If BMS is set to ALWAYS
ENABLED, change it to START ENABLED
Refer to Modbus Communication Manual GF-114. Check all wiring connections and software menu settings.
H-4
Appendix I _____________________________
GENERAL WIRING
I-1
Appendix J _____________________________
PROGRAMMING THE BMS USING RS-232 COMMUNICATION
Introduction
The RS-232 port on the left side of the BMS can be used to program the BMS using a laptop computer or other suitable terminal. Connection to a laptop or other terminal device is made using a 9-pin RS-232 adapter cable. Communication can be accomplished using any “Dumb Terminal” emulation, such as Hyper Terminal which is included with Microsoft Windows. The RS-232 communication feature allows the BMS to be easily programmed to your installation requirements using a listing of entry commands.
Set-Up
Regardless of the terminal emulation utilized, the following guidelines must be adhered to when interfacing the BMS to the Terminal device:
1. Connect a 9-pin serial cable to the RS-232 connector near the lower left corner of the BMS front panel.
2. Connect the free end of the cable to the COM 1 or COM 2 port on your laptop, or other suitable terminal device.
3. Set up the emulator communication link as follows:
(a) Set the baud rate to 9600.
(b) Set the data format to 8 bits, 1 stop bit, no parity and either Xon/Xoff or No Flow Control.
4. Turn on the BMS by pressing the ON key. Verify that the ON LED lights.
5. Press the FIELD ADJ key on the BMS to enter the Field Adjust Mode. Verify that the FIELD
ADJ LED lights.
IMPORTANT
The RS232 MODE setting MUST be set to NORMAL to permit the
6. Press the AIR TEMP key until RS232 MODE is shown in the top line of the display. If necessary, press the or arrow key until NORMAL appears in the second line of the display.
7. Press the FIELD ADJ key to exit the Field Adjust Mode. Verify that the FIELD ADJ LED goes off.
8. Start the emulator software program.
BMS functions to be programmed via the RS232 port.
9. At the command prompt, enter the password EXACTLY as follows (case-sensitive):
P=gobms
10. Press Return (<Rtn>) on your terminal.
11. The setup is now complete. You are ready to begin viewing or changing BMS functions.
-1
J
Appendix J (cont.) __________________________
Programming Procedure
BMS functions which can be viewed or changed are listed in Table J-1 along with their corresponding command numbers. Functions which can only be viewed (such as actual sensor readings) are marked “Read Only”. Viewing or changing function values is accomplished as follows:
1. Select the number of the desired command from Table J-1.
2. To view a parameter, type ?, followed by the command number and then press return (<Rtn>). For example, to view command no. 00 (HEADER TEMPERATURE), enter:
?00<Rtn>
The header temperature reading will be displayed. All temperature readings are in °F.
3. To program (set) a BMS parameter, type @, followed by the command number, an equal sign, the parameter value and a trailing zero. For example, to set command 05 (SYSTEM OUTSIDE AIR START TEMPERATURE) to 65°F, enter:
@05=650<Rtn>
Use the above steps to view and/or program the desired BMS functions listed in Table J-1.
-2
J
Appendix J (cont.) __________________________
Table J-1. BMS COMMANDS
No.
00 Header Temperature (°F) 40 to 220 Read Only
01 Outside Air Temperature (°F) -60 to 80 Read Only
02 Indoor Air Temperature (°F) 40 to 160 Read Only
03 Fire Rate (%) 0 to 100 Read Only
04 Header Set Temperature (°F) 40 to 220 Read Only
COMMAND
ENTRY RANGE
FACTORY DEFAULT
05 System Outside Air Start Temperature
(°F)
06 System Start Mode 0 = Temp Only
1 = Temp and Load
07 Manual Header Set Temperature (°F) 40 to 220 160
08 Reference Temperature (°F) 40 to 220 70°F
09 Indoor Prop Band 0.0 to 20.0
10 Setpoint Temperature(°F) 40 to 220 160
11 Reset Ratio 0.3 to 3.0
12 Maximum Header Temperature (°F) 40 to 220 220
13 Minimum Header Temperature (°F) 40 to 220 40
14 Boiler Start Percent 25 to 100 45
15 Boiler Stop Percent 10 to 45 18
16 Integral Gain (Rep./Min) 0.00 to 9.99
17 Header Set Mode 0 = Constant Settemp
1 = Indr/Outdr Reset
2 = Remote Settemp
32 to 120 70
0 = Temp Only
0.0
(0.1 increments)
1.2
(0.1 increments)
0.15
(0.01 increments)
1 = Indr/Outdr Reset
18 Derivative Gain -2.00 to 2.00
(0.01 increments)
19 Header Bandwidth (°F) 5 to 100 70
20 Aux Relay Off Level (%) 0 to 99 45
-3
J
0.15
Appendix J (cont.) __________________________
No.
Table J-1. BMS COMMANDS
COMMAND
ENTRY RANGE
FACTORY DEFAULT
21 Aux Relay Mode 0 = 100% Fire Rate
1 = 100% and OFF
22 Temperature Sensor Fail Mode 0 = Shutdown
1 = Switch Inputs
23 Fault Relay Mode 0 = All Faults
1 = No Interlock
2 = Interlock 2
3 = Interlock 1
24 Alarm Clear Method 0 = Automatic
1 = Manual
25 Boiler Operation Mode 0 = Parallel
1 = Sequential
2 = Combination
26 Number Of PWM Combo Units 0 to 4 1
27 28 29
30 Maximum PWM Percent Level 50 to 100 100
Reserved
1 = 100% AND OFF
0 = Shutdown
0 = All Faults
0 = Automatic
1 = Sequential
31 Interlock 1 Method Of Operation 0 = Always Enabled
1 = Start Enabled
32 Real Time Clock - Minutes 00 to 59 Present Time
33 Real Time Clock - Hours 00 to 23 Present Time
34 Real Time Clock - Day Of Week 1 to 7 Present Day
35 Real Time Clock - Year 00 to 99 Present Year
36 Real Time Clock - Day Of Month 00 to 31 Present Day
37 Real Time Clock - Month 00 to 12 Present Month
38 (Day 1)
Thru Offset Temperatures (Day 1-7) -50 to +50°F All Set To 0°F
44 (Day 7)
1 = Start Enabled
-4
J
Appendix J (cont.) __________________________
Table J-1. BMS COMMANDS – (Continued)
No.
45 (Day 1)
Thru Offset ON Time – Minutes (Day 1-7) 00 to 59 All Set to Zero
51 (Day 7)
52 (Day 1)
Thru Offset ON Time – Hours (Day 1-7) 00 to 23 All Set To Zero
58 (Day 7)
COMMAND
ENTRY RANGE
FACTORY DEFAULT
59 Offset Enable 0 = Disabled
1 = Enabled
60 Header Offset (°F) 0 to 5 0
61 System Start Relay Contact Operation
With Interlocks
70 (Day 1)
Thru Offset OFF Time – Minutes (Day 1-7) 00 to 59 All Set To Zero
76 (Day 7)
77 (Day 1)
Thru Offset OFF Time – Hours (Day 1-7) 0 to 23 All Set To Zero
83 (Day 7)
84 (Reserved)
85 Indoor Air Input 0 or 1
0 = No Action
1 = Either Intlk Opens Start Relay
2 = Intlk 1 Opens Start Relay
3 = Intlk 2 Opens Start Relay
0 = 4 - 20 mA
1 = Thermistor
0 = Disabled
0 = No Action
1 = Thermistor
Command Nos. 86 and Up Apply Only to BMS Units Equipped With Modbus Capability
86 Remote Signal 0 or 1
0 = 4 - 20 mA
1 = Modbus
0 = 4 - 20 mA
-5
J
Appendix J (cont.) __________________________
Table J-1. BMS COMMANDS – (Continued)
No.
COMMAND
ENTRY RANGE
FACTORY DEFAULT
87 RS232 Mode 0 or 1
0 = Normal
1 = Modbus
88 RS232 Baud Rate 2400, 4800, 9600,
14400, 19200
89 Number Of Network Boilers 0 to 32 0
90 Min Slave Address 0 to 127 0
91 Max Slave Address 0 to 127 0
92 Net Boiler 1 Address Address for Network
Boiler 1 (same as Boiler #9)
93 Net Boiler 2 Address Address for Network
Boiler 2 (same as Boiler #10)
94 Net Boiler 3 Address Address for Network
Boiler 3 (same as Boiler #11)
95 Net Boiler 4 Address Address for Network
Boiler 4 (same as Boiler #12)
1 = Modbus
9600
96 Net Boiler 5 Address Address for Network
Boiler 5 (same as Boiler #13)
97 Net Boiler 6 Address Address for Network
Boiler 6 (same as Boiler #14)
98 Net Boiler 7 Address Address for Network
Boiler 7 (same as Boiler #15)
99 Net Boiler 8 Address Address for Network
Boiler 8 (same as Boiler #16)
100 Net Boiler 9 Address Address for Network
Boiler 9 (same as Boiler #17)
-6
J
Appendix J (cont.) __________________________
Table J-1. BMS COMMANDS – (Continued)
No.
COMMAND
ENTRY RANGE
FACTORY DEFAULT
101 Net Boiler 10 Address Address for Network
Boiler 10 (same as Boiler #18)
102 Net Boiler 11address Address for Network
Boiler 11 (same as Boiler #19)
103 Net Boiler 12 Address Address for Network
Boiler 12 (same as Boiler #20)
104 Net Boiler 13 Address Address for Network
Boiler 13 (same as Boiler #21)
105 Net Boiler 14 Address Address for Network
Boiler 14 (same as Boiler #22)
106 Net Boiler 15 Address Address for Network
Boiler 15 (same as Boiler #23)
107 Net Boiler 16 Address Address for Network
Boiler 16 (same as Boiler #24)
108 Net Boiler 17 Address Address for Network
Boiler 17 (same as Boiler #25)
109 Net Boiler 18 Address Address for Network
Boiler 18 (same as Boiler #26)
110 Net Boiler 19 Address Address for Network
Boiler 19 (same as Boiler #27)
111 Net Boiler 20 Address Address for Network
Boiler 20 (same as Boiler #28)
112 Net Boiler 21 Address
Address for Network Boiler 21 (same as Boiler #29)
-7
J
Appendix J (cont.) __________________________
Table J-1. BMS COMMANDS – (Continued)
No.
COMMAND
ENTRY RANGE
FACTORY DEFAULT
113 Net Boiler 22 Address Address for Network
Boiler 22 same as Boiler #30)
114 Net Boiler 23 Address Address for Network
Boiler 23 (same as Boiler #31)
115 Net Boiler 24 Address Address for Network
Boiler 24 (same as Boiler #32)
116 Net Boiler 25 Address Address for Network
Boiler 25 (same as Boiler #33)
117 Net Boiler 26 Address Address for Network
Boiler 26 (same as Boiler #34)
118 Net Boiler 27 Address Address for Network
Boiler 27 (same as Boiler #35)
119 Net Boiler 28 Address Address for Network
Boiler 28 (same as Boiler #36)
120 Net Boiler 29 Address Address for Network
Boiler 29 (same as Boiler #37)
121 Net Boiler 30 Address Address for Network
Boiler 30 (same as Boiler #38)
122 Net Boiler 31 Address Address for Network
Boiler 31 (same as Boiler #39)
123 Net Boiler 32 Address
Address for Network Boiler 32 (same as Boiler #40)
-8
J
Appendix J (cont.) __________________________
Table J-1. BMS COMMANDS – (Continued)
No.
COMMAND
ENTRY RANGE
FACTORY DEFAULT
124 Network Baud 2400, 4800, 9600,
14400, 19200
125 Network Timeout 5 to 240 sec 60 sec.
126 Password Lo 0 to 255 0
127 Password Hi 0 to 255 0
128 Modbus Control Type 0 = Round-Robin
1 = Broadcast
129 Modbus Pass-Thru 0 = Disabled
1 = Enabled
130
Up
(Reserved For Future Expansion) Undefined
&
9600
0 = Round Robin
0 = Disabled
-9
J
Loading...