AERCO BMS 168 User Manual

Boiler Management
System
Installation
Instructions
Boiler Management
System
Operation &
Troubleshooting
DISPLAY MODE
HDR
TEMP
AIR
TEMP
%
LOAD
FOR USE W/ INDOOR TEMP. SENS.
SET
POINT
OFF SET
PROP BAND
CONFG
SYS
Hold Key for
Display Header
Header Set
Temp., oF
Display Outside Air Temp., oF
Display % Load & No. of Units Operating
Display/Change Indoor Sensor Reference Temp.,
Display/Change Setpoint Temp when Activated
Display/Change Hdr. Temp. / Indoor Ref. Temp.
System Configuration
o
F
FIELD ADJUSTMENT MODE
FIELD
L.E.D. "On" Enables Field Adjustment
ADJ
Select System Start Option
SYS
Display/Change Outside Air
START
Temp. for System Start
TEMP
Display/Change Bldg Ref Temp — Indoor/Outdoor
REF
TEMP
Hdr Set Temp — Constant Set
HDR
Display/Change
TEMP
Minimum Or Maximum
LIMIT
Header Temp. Display/Change
RESET
Header Temp. / Outside Air Temp.
RATIO
(Alarm Cancel) Reset Alarm Contact
%
Set Date
LOAD
And Time
Set Up
OFF
Set Back
SET
Clock Select Fault
CONFG
Alarm Relay
SYS
Options
Enable BMS
ON
Disable BMS
OFF
Reset Mode Point Mode
Raise/Lower
To Change
HEADER SET INDOOR AIR
DISPLAY
ADJ
HDR
TEMP
TEMP
SYS
REF
START
TEMP
LEVEL
PROP
SET
BAND
POINT
OFF SET
ON OFF
CONFIG
AERCO INTERNATIONAL INC., NORTHVALE, N.J.
AIR
SYS
HDR TEMP LIMIT
RESET RATIO
%
LOAD
FIELD
ADJ
Applicable to Serial Numbers 329985 and above (EPROM Rev. K and above)
AERCO International, Inc.
AERCO International, Inc.
159 Paris Avenue
159 Paris Avenue Northvale, NJ 07647-0128
Northvale, NJ 07647-0128
GF-108M
Telephone Support
Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday):
1-800-526-0288
AERCO International, Inc. 159 Paris Avenue Northvale, NJ 07647-0128
www.aerco,com
© AERCO International, Inc., 2008
The information contained in this installation, operation and mainte­nance manual is subject to change without notice from AERCO International, Inc.
AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.

Table of Contents

Page
SECTION 1 ABOUT YOUR NEW BOILER MANAGEMENT SYSTEM (BMS) 1-1
SECTION 2 FEATURES OF THE BMS 2-1
SECTION 3 INSTALLING THE BMS 3-1
3.1 MOUNTING THE BMS 3-1
3.2 GENERAL WIRING 3-1
3.3 PULSE WIDTH MODULATION WIRING 3=2
3.3.1 PWM Wiring at BMS 3-2
3.3.2 PWM Wiring at Boilers 3-2
3.4 RS485 (MODBUS) WIRING 3-2
3.4.1 RS485 Wiring at BMS 3-2
3.4.2 RS485 Wiring at Boilers 3-3
3.5 SENSOR INSTALLATION AND WIRING 3-3
3.5.1 Header Sensor 3-3
3.5.2 Outside Air Sensor 3-3
3.6 INTERLOCK WIRING 3-4
3.6.1 Interlock 1 Wiring 3-4
3.6.2 Interlock 2 Wiring 3-4
3.7 RELAY WIRING 3-4
3.7.1 System Start Relay 3-4
3.7.2 Fault Alarm Relay 3-4
3.7.3 Auxiliary Relay 3-4
3.8 SET BACK 3-4
SECTION 4 FAMILIARIZING YOURSELF WITH THE BMS 4-1
4.1 ABOUT BMS MODES 4-1
4.1.1 Selecting and Viewing Functions 4-1
4.1.2 Changing Function Settings 4-1
4.2 NORMAL MODE FUNCTIONS 4-4
4.2.1 HDR TEMP 4-4
4.2.2 AIR TEMP 4-4
4.2.3 % LOAD 4-4
4.2.4 SYS START TEMP 4-4
4.2.5 REF TEMP 4-4
4.2.6 HDR TEMP LIMIT 4-4
4.2.7 FIELD ADJ 4-4
4.2.8 SET POINT 4-4
4.2.9 PROP BAND 4-4
4.2.10 OFF SET 4-4
4.2.11 RESET RATIO 4-4
4.2.12 and Arrow Keys 4-5
i
Table of Contents
(Continued)
4.2.13 ON and OFF Keys 4-5
4.2.14 CONFIG SYS 4-5
4.3 FIELD ADJUST MODE FUNCTIONS 4-5
4.3.1 HDR TEMP 4-5
4.3.2 AIR TEMP 4-6
4.3.3 % LOAD 4-6
4.3.4 Setting the Internal Clock With the % LOAD Key 4-6
4.3.5 SYS START TEMP 4-7
4.3.6 REF TEMP 4-7
4.3.7 HDR TEMP LIMIT 4-7
4.3.8 FIELD ADJ 4-8
4.3.9 SET POINT 4-8
4.3.10 PROP BAND 4-8
4.3.11 OFFSET 4-8
4.3.12 Setting Up a Reset Schedule 4-8
4.3.13 Manual Set Back 4-9
4.3.14 RESET RATIO 4-9
4.3.15 and Arrow Keys 4-9
4.3.16 ON and OFF Keys 4-9
4.3.17 CONFIG SYS 4-9
4.4 SYSTEM CONFIGURATION MODE FUNCTIONS 4-10
4.4.1 TEMP FAIL MODE 4-10
4.4.2 SYS ENABLE 4-11
4.4.3 MAX PWR INPUT 4-11
4.4.4 START AND STOP LEVEL Keys 4-12
4.4.5 BLR OP MODE 4-12
4.4.5.1 Sequential Mode 4-12
4.4.5.2 Parallel Mode 4-13
4.4.5.3 Combination Mode 4-13
4.4.5.4 Designating the Number of Combination Boilers 4-13
4.4.6 HDR SET MODE 4-13
4.4.7 INTGL RATE GAIN and DERIV GAIN Keys 4-13
4.4.7.1 TEMP BANDWIDTH 4-14
4.4.7.2 INTGL RATE GAIN 4-14
4.4.7.3 DERIV GAIN 4-14
4.4.8 AUX RELAY 4-15
4.4.9 ▲ and ▼ Arrow Keys 4-15
4.4.10 ON and OFF Keys 4-15
4.4.11 CONFIG SYS 4-15
ii
Table of Contents
(Continued)
SECTION 5 PROGRAMMING THE BMS MODE OF OPERAT
5.1 INDOOR/OUTDOOR RESET MODE 5-1
5.1.1 Selecting Indoor/Outdoor Reset Mode 5-1
5.1.2 Entering System Start Temperature 5-1
5.1.3 Determining the Reset Schedule 5-1
5.1.4 Entering the Building Reference Temperature 5-2
5.1.5 Entering the Reset Ratio 5-2
5.2 SETUP FOR REMOTE SETPOINT MODE 5-2
5.2.1 Entering Header Set and Boiler Operating Modes 5-2
5.2.2 Entering Remote Signal Type and Header Temperature Limits 5-2
5.3 SETUP FOR CONSTANT SETPOINT MODE 5-3
5.3.1 Entering Header Set and Boiler Operating Mode 5-3
5.3.2 Entering Header Reference Temperature 5-3
5.4 CONFIGURING BOILERS FOR PULSE WIDTH MODULATION (PWM) 5-3
5.4.1 C-More Control System PWM Setup 5-4
5.4.2 Configuring the Temperature Controller 5-4
5.5 SYSTEM INITIALIZATION AND POLLING 5-4
5.6 TESTING THE SYSTEM 5-5
ION
APPENDICES
Appendix A Specifications A-1 Appendix B Methods for Determining Reset Schedule and Indoor/Outdoor Reset Ratio Charts B-1 Appendix C Normal (Read-Only) Mode Display Messages and Defaults C-1 Appendix D Field Adjust Mode Display Messages and Defaults D-1 Appendix E Config Sys Mode Display Messages and Defaults E-1 Appendix F Sensor Resistance Data Sheet F-1 Appendix G Parts List G-1 Appendix H Troubleshooting H-1 Appendix I General BMS Wiring I-1 Appendix J Programming the BMS Using RS-232 Communication J-1
iii
List of Figures
Figure 1 Typical BMS Installation 3-5 Figure 2 BMS Mounting 3-6 Figure 3 Wire Routing Locations at the BMS 3-7 Figure 4 PWM Communication Outputs at the BMS 3-8 Figure 5 Pulse Width Modulation Connections at KC Series Boiler Boiler With Modular Control Box 3-9 Figure 6 PWM & RS485 Connections at KC Series Boiler With C-More Control Box 3-10 Figure 7 Pulse Width Modulation Connections at the Benchmark Boiler With Modular Control Box 3-11 Figure 8 PWM & RS485 Connections at the Benchmark Boiler With C-More Control Box 3-12 Figure 9 BMS RS485 & RS232 Connector Locations 3-13 Figure 10 BMS RS485 & RS232 Connector Pin Assignments 3-14 Figure 11 Header Sensor Installation With Well 3-15 Figure 12 Outside Air Sensor Mounting and Connections 3-16 Figure 13 Normal and Field Adjust Mode Overlay 4-2 Figure 14 System Configuration Mode Overlay 4-3
iv
Section 1 ______________________________
SIMPLE INSTALLATION AND
About Your New Boiler Management System (BMS)
AERCO’s Boiler Management System (BMS), stages and modulates AERCO KC Series and Benchmark Boilers, allowing them to operate efficiently as a system. It provides a broad array of operating modes, so that the nuances of specific applications can be easily accommodated. The BMS can control up to 40 boilers; 8 via pulse width modulation (PWM) and up to 32 via Modbus (RS485) communication. For Modbus control, the AERCO Boilers must be equipped with C-More Control Systems.
PRECISE CONTROL
Utilizing PWM or Modbus control, the BMS fully exploits the condensing and modulating ability and efficiency of each boiler and regulates the output of the boiler plant with water supply temperature variation of no more than ±2°F
Staging can be performed sequentially or in parallel. The BMS can sample building reference temperatures to modulate boiler plant output, and will perform water supply temperature night setback automatically referenced to its internal clock.
OPERATION
Installation of the BMS is simple, and low­voltage wiring is employed between the BMS panel and boiler modules. There are no complex design steps to be performed, since a keypad in conjunction with the LCD allows the operator to acquire, change, and program settings through easy-to-use labeled buttons. Each BMS function consists only of selecting the function and toggling values, which generally requires no more than pressing four keys.
The instant a parameter is programmed, it is automatically entered into the BMS memory, avoiding multiple programming steps to store information. In the event of power loss, most factory default settings remain in nonvolatile memory for up to 10 years and need not be reprogrammed. However, date and time remain in memory for about 30 days.
BMS PROGRAMMING VIA RS232 PORT
If desired, the BMS can be programmed by connecting a Laptop Computer, or other type of terminal emulation device, to the RS232 connector on the left side of the BMS. See Appendix J for programming using RS232 communication.
1-1
Section 2 ______________________________
SEQUENTIAL OR PARALLEL
Features of
OPERATION
the BMS____
APPLICATION FLEXIBILITY
Three different system or control options can be selected at setup to match the needs of any closed-loop system - Indoor/Outdoor Reset, 4-to-20 mA Remote Setpoint, and Constant Setpoint.
CONTINUOUS COMMUNICATIONS
The BMS continually sends information to the boilers and receives information from them, providing total control of boiler plant dynamics.
EXCEPTIONAL ACCURACY
The BMS control system uses a PID (Proportional Integral Derivative) control algorithm to respond dynamically to system changes. Water temperatures are precisely controlled by modulating energy in put. A supply water temperature of ±2°F is assured.
BUILDING INDOOR AIR TEMPERATURE INPUTS
The BMS accepts building indoor air temperatures directly from a thermistor sensor or from a 4-to-20 mA signal. Adjustments can be made to the header setpoint temperature to compensate for varying building temperatures and conditions.
Modules can be either sequenced on, or run in parallel, by selection from the front panel. In sequential mode, boilers are brought on one at a time, so turn-down ratio is 14 multiplied by the number of KC Series boilers, or 20 multiplied by the number of Benchmark boilers. This provides higher energy savings and seasonal efficiency. In parallel mode, all of the boilers are modulated together at the same firing rate. The turn-down ratio of the system is fixed at 14:1 for the KC Series boilers and 20:1 for the Benchmark boilers.
BUMPLESS TRANSFER
When in sequential mode, the BMS stages boilers on and off, one at a time, at selectable percentages of firing rate. The result is a seamless transition and undetectable room temperature changes. Sequential mode has several other unique features:
Run-Time Equalization: The BMS se-
quences boilers on a first on-first off basis, which automatically equalizes the run time of all boilers in the plant.
Automatic Load Distribution: The BMS
continuously monitors the number of modules that are available for operation. In the event of a boiler malfunction or when service is performed, the BMS automatically compensates for a lack of response from any unit and brings on the next available boiler to satisfy demand. This feature operates in both parallel and sequential modes.
2-1
Time Delay Between Boiler Starts:
A fixed, 30-second time delay between boiler starts ensures smooth energy input without spikes in electrical, gas, or venting conditions.
AUTOMATIC SYSTEM START
Automatic system start contacts for controlling auxiliary equipment such as pumps and dampers can be selected to close between 32°F and 100°F outside air temperature, eliminating the need for the plant operator to turn auxiliary equipment on and off.
MINIMUM AND MAXIMUM HEADER SET CLAMPING
The supply water temperature can be clamped at a maximum high temperature or minimum low temperature, to ensure that the building temperature is optimal for the greatest comfort.
Two Interlock Circuits (Enable/Disable Contacts)
The BMS contains two normally-open interlock circuits that require only a set of dry contacts to enable or disable the boiler plant. They can be used to monitor pumps, combustion air dampers, or other equip­ment. Out-of-limit conditions trip the interlocks, shutting down the boiler plant, and providing a high level of protection.
ADJUSTABLE OFFSET
The Offset feature can allow the temperature of the supply water to be offset in 1° increments over a range of -50°F below to +50°F above its current temperature. This feature is employed for night setback or morning warmup. The BMS lets you select, over a 7-day period, the time when the offset begins and ends.
CONTROL OF AUXILIARY EQUIPMENT
The auxiliary relay uses a dry set of contacts to operate auxiliary equipment. For example, when the boiler plant is at 100% load, these contacts close and can start an auxiliary boiler, or notify an energy manage­ment system of a full-load condition.
FAULT ALARM SURVEILLANCE
The BMS continually monitors its sensors for opens and shorts and the interlock circuits for opens. However, the BMS fault alarm relay does not close or indicate a fault when a boiler has failed. The fault alarm circuit consists of a dry set of 120 VAC contacts rated at 5 A.
SIMPLE INSTALLATION
The BMS operates from 120 VAC, 50 to 60 Hz, and uses Belden 9841 or equivalent wiring between modules for control and monitoring. The lightweight panel can be mounted up to 200 feet from the boilers when using pulse width modulation communication.
RUGGED AND RELIABLE
The BMS is housed in a NEMA 13-grade enclosure and operates in ambient tempera­tures as high as 131°F (55°C).
POWER-OFF MEMORY
Most system configuration values are retained in nonvolatile memory for up to 10 years. Date and time remain in memory for approximately 30 days.
MODBUS COMMUNICATION
The BMS can monitor or control C-More Boilers using Modbus communication via its RS485 port. It can also be monitored or controlled by a Building Automation System (BAS) or a PC connected to its RS232 port.
2-2
Section 3 ______________________________
3.2 GENERAL WIRING
Installing the BMS________
Please follow the installation procedure in the order presented. Incorrect wiring may damage the unit and void the AERCO warranty Do not omit steps, and do not substitute other types of wiring for those specified. Figure 1 shows a typical BMS installation.
3.1 MOUNTING THE BMS
Use the mounting plate (Figure 2) supplied with the BMS to securely mount the unit away from moisture, and at an appropriate height for easy reading of the display. To reduce the possibility of electrical noise entering the system, mount the BMS at least 6 feet away from electrical devices such as power panels, high voltage transformers and transmission lines, motors, and fluorescent lights.
All wiring and fusing must be in compliance with the National Electrical Code and with local electrical codes. Control wiring for the sensors and communications links must run in separate conduit and not in the conduit providing line voltage in order to ensure immunity from electrical noise.
All wiring should be installed in conduit leading up to the bottom of the BMS panel. There are five knock-outs in the bottom of the panel by which wiring must enter the BMS.
Shielded, twisted-pair cable should be used for sensor and communication wiring. This wiring should be 18 to 24 AWG. Examples of suitable sensor and communication wire are: Belden 9841, 8761, 3105A or equiv­alent. AC power wiring should be 16 to 18 AWG. A BMS wiring diagram is included in Appendix I. Once mounting is complete and the BMS is secured in place, loosen the two captive screws on the wiring cover plate with a Phillips screwdriver. Feed all wiring through the knock-outs provided on the bottom of the panel. All pulse width modulation (PWM) and RS485 control wires should be fed through the two knock-outs furthest to the left.
Shock Hazard!
Extreme caution must be exercised when connecting power wiring to the BMS. The external circuit breaker supplying Line voltage to the the BMS must be turned off to avoid electrical shock
Power wiring should be fed through the right-most knock-out in the bottom of the panel (Figure 3). The remaining knockouts are for control wiring located on the middle terminal block. The terminal blocks can be detached from the BMS headers to simplify field wiring.
Once power wiring is completed, apply line voltage to the BMS, and press the ON key on the BMS keypad to verify proper connection. The display should show INITIALIZING EPROM REV. n where n is the current EPROM version.
3-1
WARNING!
Turn off AC input power to the BMS to avoid electrical shock.
3.3 PULSE WIDTH MODULATION WIRING
Pulse width modulation (PWM) wiring connections are made between the BMS JP2 terminal block and the Relay or I/O Box terminals at each AERCO Boiler. Shielded twisted-pair wire is recommended.
3.3.1 PWM Wiring At BMS
To wire boilers for pulse width modulation (PWM), connect the boiler control wires in ascending order according to the numbers on the BMS (Figure 4). For example, the control wiring for boiler 1 at the BMS would be connected as follows:
Positive control wire connects to JP 2, terminal 1 (+).
Negative control wire connects to JP 2, terminal 2 (-).
Shield wiring connects to the negative (-) control wire at Section BLR 1, terminal 2. The shield is not terminated at the boiler. All shields must be terminated on the BMS end. The wiring terminals labeled SHIELD at terminal block JP3 of the BMS are not internally connected to ground and are only used as a place to terminate the sensor shields. The pulse width modulation shield can be connected to any minus (-) terminal of the PWM terminal strip (JP2).
3.3.2 PWM Wiring At The Boilers
The pulse-width modulation (PWM) control wiring from the BMS to each boiler is connected at each boiler’s relay box or input/output (I/O) box, depending on the type of control system used. Modular control systems utilize a relay box as shown in Figure 5 (KC1000) and Figure 7 (Benchmark). The newer C-More control system utilizes an I/O box as shown in Figure 6 and Figure 8.
Regardless of the type of control system used, the PWM wiring is connected to the BMS + and – terminals as shown in the respective illustrations. It is imperative that positive (+) and negative (-) polarity be observed when making these connections. All boilers follow the same control wiring scheme.
When using pulse width modulation, the BMS may be mounted up to 200 feet from the boilers.
3.4 RS485 (MODBUS) WIRING
All Modbus Networks are implemented using a “Master - Slave” technique. The BMS can function as either a “Master” controlling C-More Slaves or a “Slave” controlled by a “Master” Energy Management System (EMS) or Building Automation System (BAS). Therefore, the following paragraphs provide only an over­view of the required wiring connections. Detailed information and setup procedures for RS485 Modbus networks are provided in Modbus Communication Manual GF-114. Refer to GF-114 prior to implementing any RS485 networks using Modbus.
RS485 wiring connections are made using a “Daisy-Chain” configuration. Shielded twisted-pair wire from 18 to 24 AWG is required for all RS485 wiring.
3.4.1 RS485 Wiring At BMS
RS485 wiring connections are made at the BMS at connector JP11 which is labeled RS485 TO BLRS. The location of this RS485 connector is shown in Figure 9. In addition, Figure 9 also shows the locations of the external and internal RS232 connectors which are used to interface the BMS to an EMS Master if required. The pin assignments for the RS485 and RS232 connectors are shown in Figure 10.
3-2
Connect the RS485 wiring at the BMS as follows:
Connect the positive (+) lead to the +(B) terminal of JP11.
Connect the negative (-) lead to the -(A) terminal of JP11.
Connect the shield to the SHLD terminal of JP11.
3.4.2 RS485 Wiring At Boilers
RS485 wiring connections are made at the RS485 COMM terminals of each boiler’s I/O Box as shown in Figures 6 (KC1000) and Figure 8 (Benchmark). Connect the wiring as follows:
Connect the positive lead to the + terminal
Connect the negative lead to the ­terminal
DO NOT terminate the shields to the Ground (G) terminal at the Boiler end of the RS485 loop. Connect the shields of the incoming and outgoing leads together. The RS485 loop should only be terminated at the BMS.
RS485 loops should not exceed 4000 feet.
Detailed wiring diagrams for RS485 Modbus communication networks are provided in the Modbus Communication Manual GF-114.
3.5 SENSOR INSTALLATION
AND
There are two types of sensors that may be installed -- header sensors and outside air sensors. While an outside air sensor is required for Indoor/Outdoor Reset mode, it is not required for Constant Setpoint or 4-to­20-mA modes of operation. However, it is recommended to take full advantage of all BMS features. The header sensor is required for all modes of operation.
Sensor wiring and power wiring should be run separately to reduce the chance of electrical noise entering the sensor wiring.
WIRING
3.5.1 Header Sensor
The header sensor to be used with the BMS is a sensor that requires a well as shown in Figure 11. When installing the sensor, use a 1/2 inch NPT tapped coupling or a 4 x 4 x 1/2 Tee fitting. Use heat-conductive grease when installing to aid in its response. The sensor probe must be inserted at least 2 inches into the flow of water for proper response. The header sensor must be installed between 2 and 10 feet downstream of the LAST boiler in the plant’s supply water header.
The header sensor is a thermistor type sensor. The Resistance vs. Temperature Chart for the sensor is provided in Appendix F. See Figure 11 for installation details.
Shielded pair 18 AWG cable (Belden # 8760 or equiv.) is recommended for header sensor wiring. There is no polarity to be observed. Connect the wires from the sensor to BMS terminals 4 and 5 on JP3. The ground for the shield is at BMS end of the link, not the header sensor. Connect the ground to JP3, terminal 8 (SHIELD). The header sensor can be installed up to 600 feet from the BMS.
3.5.2 Outside Air Sensor
The Outside Air Sensor, AERCO part no. 122662, must be mounted on the North side of the building, shielded from direct sunlight, and away from air intakes or outlets from the building. See Figure 12 for a typical installation. The sensor includes a plate for wall mounting. Shielded pair 18 AWG cable (Belden # 8760 or equiv.) is recommended for sensor wiring. There is no polarity to be observed. Connect the sensor wires to BMS terminals 1 and 2 on JP3. Connect the shield to JP3, terminal 3 (SHIELD) at the BMS. The shield must not be grounded on the sensor end. The sensor can be mounted up to 600 feet from the BMS.
3-3
3.6 INTERLOCK WIRING
The BMS is equipped with two interlocks designated Interlock 1 (INT 1) and Interlock 2 (INT 2). Since both interlocks must be closed for the BMS to operate the boiler plant, the associated wiring terminals are jumpered, prior to shipment. If desired, proving device switches can be connected to either used, interlock wiring connections are made as described in the following paragraphs.
3.6.1 Interlock 1 Wiring
Interlock 1 is often used with auxiliary equipment, such as air dampers or flow switches. If used, connect the end proving switch to INT 1 terminals 11 and 12 as shown in the wiring diagram in Appendix I.
3.6.2 Interlock 2 Wiring
Interlock 2 is a general purpose interlock which can be used with a variety of devices or equipment or conditions that must be proved prior to enabling the boiler plant. If used, connect the end proving switch to INT 2 terminals 13 and 14 as shown in the wiring diagram in Appendix I.
interlock in place of the jumper. If
NOTE
If necessary, Interlock 1 can be programmed to operate the boilers only when the outside air temperature falls below the system start temperature. See para. 4.4.2 for details. Interlock 2 cannot programmed with this feature.
be
3.7 RELAY WIRING
The BMS contains a System Start Relay, a Fault Alarm Relay and an Auxiliary Relay which can be connected to external monitoring or control devices. The contacts for each of these relays are rated at 120 VAC, 5A and are fused internally at 5A with replaceable fuses. The contact terminals for these relays are shown in the wiring diagram in Appendix I.
3.7 1 System Start Relay
The state of the System Start (SYS START) relay contacts are controlled by the value set for the SYS START TEMP function in the Field Adjust Mode (para. 4.3.5). The contacts are closed only when the outside air temperature is less than the System Start Temperature (SYS START TEMP) which is set in the Field Adjust Mode. The default for this temperature setting is 70°F.
3.7.2 Fault Alarm Relay
The state of the Fault Alarm (FLT ALARM) relay contacts are controlled by the option selected by pressing the CONFIG SYS key when in the Field Adjust mode (para.
4.3.16). Contact closure can be set to ALL FAULTS, INTERLOCK 1, INTERLOCK 2, or NO INTERLOCK.
3.7.3 Auxiliary Relay
The state of the Auxiliary (AUX) relay contacts are controlled by the AUX RELAY CLOSE option selected when in the System Configuration mode (para. 4.4.8). Contact closure can be set to occur either when all available boilers are at the maximum power input or no boilers are available (all boilers faulted or turned off).
NOTE
The SET BACK function is used only if the header supply temperature will be offset manually as described in para. 4.3.13. Disregard para. 3.8 if an automatic header temperature reset schedule is used as described in para. 4.3.12.
3.8 SET BACK
The SET BACK terminals shown in the wiring diagram in Appendix I are used only when implementing a manually-controlled header temperature offset. If used, connect a dry contact switch across SET BACK terminals 15 and 16 on JP3.
3-4 3-5
Figure 2
BMS MOUNTING
3-6
Figure 3
RECOMMENDED WIRE ROUTING LOCATIONS AT THE BMS
3-7
Figure 4
PWM COMMUNICATION OUTPUTS AT THE BMS
3-8
Figure 5
PULSE WIDTH MODULATION CONNECTIONS AT
KC SERIES BOILER WITH MODULAR CONTROL BOX
3-9
Remove sheet metal cover to access I/O Box
OUTDOOR SENSOR IN
SENSOR COMMON
AUX SENSOR IN
NOT USED
ANALOG IN
B.M.S. (PWM) IN
SHIELD
mA OUT
RS-485 COMM.
NOT USED
REMOTE INTL'K IN
EXHAUST SWITCH IN
DELAYED INTL'K IN
NOT USED
NC
FAULT RELAY
COM
120 VAC, 5A, RES
+
­+
-
+
-
+
G
-
NO
NC
AUX RELAY
COM NO
120 VAC, 5A, RES
NOT USED
PWM Connections
RS485 COMM Connections
Figure 6
PWM & RS485 CONNECTIONS AT
KC SERIES BOILER WITH C-MORE CONTROL BOX
3-10
Figure 7
PWM CONNECTIONS AT
BENCHMARK BOILER WITH MODULAR CONTROL BOX
3-11
Open Door To Access I/O Box
OUTDOOR SENSOR IN
SENSOR COMMON
AUX SENSOR IN
NOT USED
ANALOG IN
B.M.S. (PWM) IN
SHIELD
mA OUT
RS-485 COMM.
NOT USED
REMOTE INTL'K IN
EXHAUST SWITCH IN
DELAYED INTL'K IN
NOT USED
NC
FAULT RELAY
COM
120 VAC, 5A, RES
+
­+
-
+
­+
G
-
NO
NC
AUX RELAY
COM NO
120 VAC, 5A, RES
NOT USED
PWM Connections
RS485 COMM Connections
Figure 8
PWM & RS485 CONNECTIONS AT
BENCHMARK BOILER WITH C-MORE CONTROL BOX
3-12
Figure 9
BMS RS485 & RS232 CONNECTOR LOCATIONS
3-13
Figure 10
BMS RS485 & RS232 CONNECTOR PIN ASSIGNMENTS
3-14
1/2 “ NPT
Figure 11
HEADER SENSOR INSTALLATION WITH WELL
3-15
Figure 12
OUTSIDE AIR SENSOR MOUNTING AND CONNECTIONS
3-16
Loading...
+ 60 hidden pages