The information contained in this
installation, operation and maintenance manual is subject to
change without notice from
AERCO International, Inc.
AERCO makes no warranty of any
kind with respect to this material,
including but not limited to implied
warranties of merchantability and
fitness for a particular application.
AERCO International is not liable
for errors appearing in this
manual. Nor for incidental or
consequential damages occurring
in connection with the furnishing,
performance, or use of this
material.
Page 3
FOREWORD
Foreword
The AERCO Benchmark 2.0LN Boiler is a modulating unit. It represents a true industry advance
that meets the needs of today's energy and environmental concerns. Designed for application
in any closed loop hydronic system, the Benchmark's modulating capability relates energy input
directly to fluctuating system loads. The Benchmark 2.0LN, with its 20:1 turn down ratio and
condensing capability, provides extremely high efficiencies and makes it ideally suited for
modern low temperature, as well as, conventional heating systems.
The boiler operates at inputs ranging from 100,000 BTU/hr. to 2,000,000 BTU/hr. The output of
the boiler is a function of the unit’s firing rate and return water temperature. Output ranges from
99,000 BTU/hr. to 1,933,000 BTU/hr., depending on operating conditions.
When installed and operated in accordance with this Instruction Manual, the Benchmark 2.0LN
Boiler complies with the NOx emission standards outlined in:
• South Coast Air Quality Management District (SCAQMD), Rule 1146.2
Whether used in singular or modular arrangements, the Benchmark 2.0LN offers the maximum
flexibility in venting with minimum installation space requirements. The Benchmark's advanced
electronics are available in several selectable modes of operation offering the most efficient
operating methods and energy management system integration.
For service or parts, contact your local sales representative or AERCO INTERNATIONAL.
Chapter 3 – CONTROL PANEL COMPONENTS AND
OPERATING PROCEDURES 3-1
Para. Subject Page
3.1 Introduction 3-1
3.2 Control Panel Description 3-1
3.3 Control Panel Menus 3-4
3.4 Operating Menu 3-5
3.5 Setup Menu 3-5
Para. Subject Page
3.6 Configuration Menu 3-6
3.7 Tuning Menu 3-7
3.8 Start Sequence 3-7
3.9 Start/Stop Levels 3-9
Chapter 4 – INITIAL START-UP 4-1
Para. Subject Page
4.1 Initial Startup Requirements 4-1
4.2 Tools and Instruments for
Combustion Calibration
4.3 Natural Gas Combustion
Calibration
4-1
4-2
Para. Subject Page
4.4 Unit Reassembly 4-5
4.5 Over-Temperature Limit
Switches
4-5
i
Page 6
CONTENTS
Chapter 5 – MODE OF OPERATION 5-1
Para. Subject Page
5.1 Introduction 5-1
5.2 Indoor/Outdoor Reset Mode 5-1
5.3 Constant Setpoint Mode 5-2
5.4 Remote Setpoint Mode 5-2
5.5 Direct Drive Modes 5-3
Para. Subject Page
5.6 Boiler Management System
(BMS)
5.7 Combination Control System
(CCS)
5-4
5-5
Chapter 6 – SAFETY DEVICE TESTING PROCEDURES 6-1
Para. Subject Page
6.1 Testing of Safety Devices 6-1
6.2 Low Gas Pressure Fault Test 6-1
6.3 High Gas Pressure Test 6-2
6.4 Low Water Level Fault Test 6-2
6.5 Water Temperature Fault Test 6-2
6.6 Interlock Tests 6-3
6.7 Flame Fault Test 6-4
Para. Subject Page
6.8 Air Flow Fault Test 6-4
6.9 SSOV Proof of Closure Switch 6-4
6.10 Purge Switch Open During
Purge
6.11 Ignition Switch Open During
Ignition
6.12 Safety Pressure Relief Valve
Test
6-5
6-5
6-6
Chapter 7 – MAINTENANCE REQUIREMENTS 7-1
Para. Subject Page
7.1 Maintenance Schedule 7-1
7.2 Spark Ignitor 7-1
7.3 Flame Detector 7-2
7.4 Combustion Calibration 7-2
7.5 Safety Device Testing 7-3
7.6 Burner Assembly 7-3
Para. Subject Page
7.7 Condensate Drain Trap 7-4
7.8 Shutting the Boiler Down For An
Extended Period of Time
7.9 Placing The Boiler Back In
Service After A Prolonged
Shutdown
7-4
7-4
Chapter 8 – TROUBLESHOOTING GUIDE 8-1
Para. Subject Page
8.1 Introduction 8-1
Para. Subject Page
ii
Page 7
CONTENTS
APPENDICES
App Subject Page
A Boiler Menu Item Descriptions A-1
B Startup, Status and Fault
Messages
C Temperature Sensor Resistance
Chart
D Indoor/Outdoor Reset Ratio
Charts
B-1
C-1
D-1
WARRANTIES W-1
App Subject Page
E Boiler Default Settings E-1
F Dimensional and Part Drawings F-1
G Piping Drawings G-1
H Wiring Schematics H-1
I Recommended Periodic Testing
Checklist
J Benchmark Control Panel Views J-1
I-1
iii
Page 8
Page 9
SAFETY PRECAUTIONS
CHAPTER 1 SAFETY PRECAUTIONS
1.1 WARNINGS & CAUTIONS
Installers and operat ing personnel MUST, at all
times, observe all safety regulations. The
following warnings an d cautions are gener al and
must be given the same attention as specific
precautions included in these instructions. In
addition to all the requirements included in this
AERCO Instruction Manual, the installation of
units MUST conform with local building codes,
or, in the absence of local codes, ANSI Z223.1
(National Fuel Gas Code Publ ication No. NFPA-
54). Where ASME CSD-1 is required by local
jurisdiction, the installation must conform to
CSD-1.
Where applicable, the equipment shall be
installed in accordance with the current
Installation Code for Gas Burning Appliances
and Equipment, CGA B149, and applicable
Provincial regulat io ns f or th e c las s; which should
be carefully followed in all cases. Authorities
having jurisdiction should be consulted before
installations are made.
IMPORTANT
This Instruction Manual is an integral
part of the product and must be
maintained in legible condition. It must
be given to the user by the installer
and kept in a safe place for future
reference.
WARNINGS!
MUST BE OBSERVED TO PREVENT
SERIOUS INJURY.
WARNING!
BEFORE ATTEMPTING TO PERFORM ANY MAINTENANCE ON THE
UNIT, SHUT OFF ALL GAS AND
ELECTRICAL INPUTS TO THE UNIT.
WARNING
DO NOT USE MATCHES, CANDLES,
FLAMES, OR OTHER SOURCES OF
IGNITION TO CHECK FOR GAS
LEAKS.
WARNING!
FLUIDS UNDER PRESSURE MAY
CAUSE INJURY TO PERSONNEL
OR DAMAGE TO EQUIPMENT
WHEN RELEASED. BE SURE TO
SHUT OFF ALL INCOMING AND
OUTGOING WATER SHUTOFF
VALVES. CAREFULLY DECREASE
ALL TRAPPED PRESSURES TO
ZERO BEFORE PERFORMING
MAINTENANCE.
WARNING!
ELECTRICAL VOLTAGES UP TO
120 VAC ARE USED IN THIS
EQUIPMENT. THEREFORE THE
COVER ON THE UNIT’S POWER
BOX (LOCATED BEHIND THE
FRONT PANEL DOOR) MUST BE
INSTALLED AT ALL TIMES, EXCEPT
DURING MAINTENANCE AND SERVICING.
CAUTIONS!
Must be observed to prevent equipment damage or loss of operating
effectiveness.
CAUTION!
Many soaps used for gas pipe leak
testing are corrosive to metals. The
piping must
clean water after leak checks have
been completed.
be rinsed thoroughly with
WARNING!
THE EXHAUST VENT PIPE OF THE
UNIT OPERATES UNDER A
POSITIVE PRESSURE AND THEREFORE MUST BE COMPLETELY
SEALED TO PREVENT LEAKAGE
OF COMBUSTION PRODUCTS INTO
LIVING SPACES.
CAUTION!
DO NOT use this boiler if any part has
been under water. Call a qualified
service technician to inspect and
replace any part that has been under
water.
1-1
Page 10
SAFETY PRECAUTIONS
1.2 EMERGENCY SHUTDOWN
If overheating occurs or the gas supply fails to
shut off, close the manual gas shutoff valve
(Figure 1-1) located external to the unit.
IMPORTANT
The Installer must identify and indicate
the location of the emergency shutdown
manual gas valve to operating personnel.
MANUAL GAS SHUTOFF VALVE
VALVE OPEN
VALVE CLOSED
1.3 PROLONGED SHUTDOWN
After prolonged shutdown, it is recommended
that the startup proce dures in Chapter 4 and the
safety device test procedures in Chapter 6 of
this manual be performed, to verify all systemoperating param eters. If ther e is an em ergenc y,
turn off the electrical power supply to the
AERCO boiler and close the manual gas valve
located upstream the unit. The installer must
identify the emergency shut-off device.
Figure 1-1
Manual Gas Shutoff Valve
IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS
Boiler Installations within the Commonwealth of Massachusetts must conform to the following
requirements:
• Boiler must be installed by a plumber or a gas f itter who is licens ed within the Commonwealth of
Massachusetts.
• Prior to unit operation, the complete gas train and all connections must be leak tested using a
non-corrosive soap.
• If a glycol solution is used as anti-freeze protection, a backflow preventer must be installed
upstream of the Fill/Makeup Valve.
• The vent termination must be located a minimum of 4 feet above grade le vel.
• If side-wall venting is used, the installation m us t conform to the following r equirem ents ext racted
from 248 CMR 5.08 (2):
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or
structure used in whole or in part for residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
finished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satisfied:
1-2
1. INSTALLATION OF CARBON MONOXIDE DETECTORS
side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe
that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the
floor level where the gas equipment is to be installed. In addition, the installing plumber or
gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to
secure the services of qualified licensed professionals for the installation of hard wired carbon
monoxide detectors.
. At the time of installation of the
Page 11
Extracted Information From 248 CMR 5.08 (2) – Continued
a. In the event that the side wall horizontally vented g as fueled equ ipment is installed in
a crawl space or an attic, the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on t he next adj ac ent floor le ve l.
b. In the event that the requirements of this subdivision can not be met at the time of
completion of installation, the owner shall have a period of thirty (30) days to comply with
the above requirements; provided, however, that during said thirty (30) day period, a
battery operated carbon monoxide detector with an alarm shall be installed.
SAFETY PRECAUTIONS
2. APPROVED CARBON MONOXIDE DETECTORS.
required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL
2034 listed and IAS certified.
3. SIGNAGE
of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust
vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign
shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION
equipment shall not approve the installation unless, upon inspection, the inspector observes
carbon monoxide detectors and signage ins ta l led in acc or dance with the pr ov isi on s of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the
most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or
structure separate from the dwelling, building or structure used in whole or in part for residential
purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED.
the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting
system design or venting system components with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system
components; and
2. A complete parts list for the venting system design or venting system.
. A metal or plastic identification plate shall be permanently mounted to the exterior
. The state or local gas inspector of the side wall horizontally vented gas fueled
: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
Each carbon monoxide detector as
When
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does
not provide the parts for venting the flue gases, but identifies "special venting systems", the following
requirements shall be satisfied by the manufacturer:
1. The identification of each "special venting system" shall include the listing of either the
website, phone number or manufacturer’s address where the venting system installation
instructions can be obtained, and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions
for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for the Product Approved side wall horizontally vented gas fueled
equipment and all the venting instructions, parts lists and/or design instructions for the venting system
shall remain with the appliance or equipment at the completion of the installation.
_______________________________ [End of Extracted Information From 248 CMR 5.08 (2)]
1-3
Page 12
Page 13
INSTALLATION
CHAPTER 2 INSTALLATION
2.1 INTRODUCTION
This Chapter provides the descriptions and
procedures necessary to unpack, inspect and
install the AERCO Benchmark 2.0 Low NOx
(LN) Boiler. Brief descr iptions are also provid ed
for each available mode of operation. Detailed
procedures for implementing these modes are
provided in Chapter 5.
2.2 RECEIVING THE UNIT
Each Benchmark 2.0LN S ystem is shipped as a
single crated unit. The shipping weight is
approximately 1600 pounds. The unit must be
moved with the proper rigging equipment for
safety and to avoid equipment dam age. The unit
should be complete ly inspected for evidence of
shipping damage and ship ment com pleteness at
the time of receipt from the carrier and before
the bill of lading is signed.
NOTE
AERCO is not responsible for lost or
damaged freight.
Each unit has a Tip-N-Tell indicator on the
outside of the crate. T his indic ates if the un it has
been turned on its side during shipment. If the
Tip-N-Tell indicat or is trip ped, do not s ign for the
shipment. Note the information on the carrier’s
paperwork and request a freight claim and
inspection by a claims adjuster before
proceeding. Any other visual damage to the
packaging materials s hould also be made clear
to the delivering carrier.
2.3 UNPACKING
Carefully unpack the unit taking care not to
damage the unit enclosure when cutting away
packaging materials
A close inspection of the unit s hould be made to
ensure that there is no evidence of dam age not
indicated by the T ip-N-Tell indicator. The f reight
carrier should be notified immediately if any
damage is detected.
The following accessories come standard with
each unit and are either packed separately
within the unit’s pack ing container or are fac tory
installed on the boiler:
• Pressure/Temperature Gauge
• Spare Spark Igniter
• Spare Flame Detector
• ASME Pressure Relief Valve
• Condensate Drain Trap
• 2” Gas Supply Shutoff Valve
When ordered, optional accessories may be
packed separately, packed within the boiler
shipping container, or may be installed on the
boiler. Any standard or optional accessories
shipped loose should b e identified and s tored in
a safe place until ready for installation or use.
2.4 SITE PREPARATION.
Ensure that the site selected for installation of
the Benchmark 2.0LN Boiler includes:
• Access to AC Input Power at 120 VAC,
Single-Phase, 60 Hz @ 20 A mps
• Access to Natural Gas line at a minimum
pressure of 4 inches W.C. at 2,000 CFH
2.4.1 Installation Clearances
The unit must be installed with the prescribed
clearances for service as shown in Figure 2-1.
The minimum
AERCO, are listed below. However, if Local
Building Codes require additional clearances,
these codes shall supersede AERCO’s
requirements. Minimum acceptable clearances
required are:
• Sides: 24 inches
• Front : 24 inches
• Rear: 30 inches
• Top: 18 inches
All gas piping, water piping and el ec tric al c on du it
or cable must be arranged so that they do not
interfere with the removal of any panels, or
inhibit service or maintenance of the unit.
clearance dimens ions , requir ed by
2-1
Page 14
INSTALLATION
44.5"
4" HIGH PAD
18"
79"
101"
Figure 2-1 Benchmark 2.0LN Boiler Clearances
WARNING
KEEP THE UNIT AREA CLEAR AND
FREE FROM ALL COMBUSTIBLE
MATERIALS AND FLAMMABLE
VAPORS OR LIQUIDS
.
CAUTION
While packaged in the shipping
container, the boiler must be moved
by pallet jack or forklift from the
FRONT ONLY.
24"
30"
REAR
USE THE TABS SHOWN IN FIGURE 2-2 TO
LIFT AND MOVE THE UNIT. Remove the top
panel from the unit to provide access to the
lifting tabs. Remove the four (4) lag screws
securing the unit to the shipping skid. Lift the
unit off the shipping sk id and position it on the 4
inch to 6 inch housekeeping concrete pad
(required) in the desired location.
24"
FRONT
24"
IMPORTANT
The boiler installation must be
installed by a plumber or gas fitter
who is licensed within the Commonwealth of Massachusetts. In addition,
the installation must comply with all
requirements specified in Chapter 1
(Safety Precautions), pages 1-2 & 1-3.
2.4.2 Setting the Unit
The unit must be installed on a 4 inch to 6 inch
housekeeping pad to e nsure proper conde nsate
drainage. If anchoring the unit, refer to the
dimensional drawings in Appendix F for anchor
locations. Two lifting t abs ar e provided a t the top
of the heat exchanger as shown in Figure 2-2.
2-2
Figure 2-2
Partial Top View Showing Lifting Tab
Locations
Page 15
INSTALLATION
Y
In multiple unit installations, it is important to
plan the position of each unit in advance.
Sufficient space for piping connections and
future service/maintenance requirements must
also be taken into cons ider ation. All pipin g m ust
include ample provisions for expansion.
If installing a Combina tion Control Panel (CCP)
system, it is important to identify the
Combination Mode B oilers in adv ance and plac e
them in the proper physical location. Refer to
Chapter 5 for inform ation on Combination Mode
Boilers.
2.5 SUPPLY AND RETURN PIPING
The Benchmark 2.0LN Boiler utilizes 4” 150#
flanges for the water system supply and return
piping connectio ns. The physical location of the
supply and return p iping connections are on the
rear of the unit as shown in Figure 2-3. Ref er to
Appendix F, Drawing AP-A-841 for additional
dimensional data.
BOILER SUPPL
4" – 150# FLANGE
CONNECTION
2" GAS INLET
CONNECTION
provided on the exhaust manifold as shown in
Figure 2-4.
BOILER
RETURN
EXHAUST
MANIFOLD
1/2” NPT
CONDENSATE
DRAIN
CONNECTION
HOUSE-
KEEPING
PAD
Figure 2-4
Condensate Drain Connection Location
A separate condensate drain trap (part no.
24060) is shipped loose and must be installed
on the floor
the exhaust manifold as follows:
behind the unit. Connect th e trap to
SHELL
DRAIN
VALVE
EXHAUST
MANIFOLD
REAR VIEW
BOILER RETURN
4" – 150# FLANGE
CONNECTION
Figure 2-3
Supply and Return Locations
2.6 CONDENSATE DRAIN AND PIPING
The Boiler is designe d to condense water va por
from the flue produc ts. Therefore, the ins t al lat ion
must have provisions for suitable drainage or
collection. A 1/2” NPT drain connection is
1. First, install a 1/2” NPT nipple in the
condensate drain port shown in Figure 2.4.
2. Next, connect a 3/4-to-1/2” reducer to the
1/2” nipple.
3. Refer to Figure 2-5 and connect the
condensate drain trap to the exhaust
manifold as described in steps 4 through 7.
4. On the condensate drain trap, install 3/4”
NPT nipples in the tapped inlet and outlet of
the trap.
5. Attach a length of 1” I.D. po l ypropylene hose
between the exhaust m anifold drain and the
inlet side of the condensate trap (Fig 2.5).
Secure both ends of the hose with clamps.
6. Connect a second length of 1” I.D. hose to
the outlet side of the condensate trap and
route it to a nearby floor drain.
7. Drainage from the condensate drain trap
outlet must be by gravity to a nearby floor
drain.
If a floor drain is not available, a condensate
pump can be used to remove the condens ate to
drain. The max imum condensate f low rate is 20
GPH. The condensate drain trap, associated
fittings and drain line must be removable for
routine maintenance.
DO NOT
hard pipe.
2-3
Page 16
INSTALLATION
Figure 2.5
Condensate Trap Installation
2.7 GAS SUPPLY PIPING
The AERCO Benchmark 2.0LN Gas
Components and Supply Design Guide, GF2030LN must be consu lted prior to designing or
installing any gas supply piping.
fittings. Piping must be s upported from the floor,
ceiling or walls onl y and must not be supported
by the unit.
A suitable piping compound, approved for use
with natural gas, should be used. Any excess
must be wiped off to prevent clogging of
components.
To avoid unit damage whe n pres sur e tes ting gas
piping, isolate the unit from the gas supply
piping. At no time should the gas pressure
applied to the unit exceed 2 psi. Leak test all
external piping thoroughly using a soap and
water solution or suitable equivalent. The gas
piping used must meet all applicable codes.
2.7.1 Gas Supply Specifications.
The gas supply input specifications to the unit
for Natural Gas are as follows:
The maximum static pressure to the unit must
not exceed 2 psi. The minimum operating gas
pressure for natural gas is 4 inches W.C. for
both FM and IRI gas trains when the unit is firing
at maximum input. The gas supply pressure to
the unit must be of suff icient capacity to provide
2000 cfh while maintain ing the gas press ure at 4
inches W.C. for FM or IRI gas trains.
WARNING
NEVER USE MATCHES, CANDLES,
FLAMES OR OTHER SOURCES OF
IGNITION TO CHECK FOR GAS
LEAKS
Many soaps used for gas pipe leak
testing are corrosive to metals. Therefore, piping must be rinsed thoroughly
with clean water after leak checks
have been completed.
All gas piping m ust be arranged so that it
does not interfere with removal of any
covers, inhibit service/maintenance, or
restrict access between the unit and
walls, or another unit.
A 2 inch gas inlet connection is located on the
rear of the unit as shown in Figure 2-3.
Prior to installation, all pipes should be deburred and internally clear ed of any scale, m etal
chips or other foreign particles. Do Not install
any flexible connectors or unapproved gas
2-4
.
CAUTION
NOTE
2.7.2 Manual Gas Shutoff Valve
A manual shut-off valve must be installed in th e
gas supply line upstream of the Boiler as shown
in Figure 2-6. M aximum allowable gas pressure
to the Boiler is 2 psi
MANDATORY
GAS PRESSURE
REGULATOR
NATURAL
GAS
SUPPLY
2" MANUAL
SHUTOFF
VALVE
DIRT
TRAP
Figure 2-6
Manual Gas Shut-Off Valve Location
Page 17
INSTALLATION
2.7.3 IRI Gas Train Kit
The IRI gas train is an optional gas train
configuration which is r e qui red i n s ome areas for
code compliance or for insurance purposes.
The IRI gas train is factor y pre-piped and wired.
See Appendix F, Drawing AP- A-843for details.
2.8 AC ELECTRICAL POWER WIRING
The AERCO Benchm ark 2.0LN Electr ical Power
Wiring Guide, GF-2060LN, must be consulted
prior to connecting an y AC power wiring to the
unit. External AC power connections ar e made
to the unit inside the Power Box on the front
panel of the unit. Rem ove the front door of the
unit to access the Power Box mounted directly
above the Control Box. Loosen the four Power
Box cover screws and remove cover to access
the AC terminal connections inside the Power
Box (Figure 2-7).
NOTE
All electrical conduit and hardware must
be installed so that it does not interfere
with the removal of any un it cover s, inh ibit
service/maintenance, or prevent access
between the unit and walls or another
unit.
Each Boiler must be connected to a dedicated
electrical circuit. NO OTHER DEVICE
SHOULD BE ON THE SAME ELECTRICAL
CIRCUIT AS THE BOILER. A means for
disconnecting AC po wer f rom the unit (such as a
service switch) must be installed near the unit
for normal operation and maintenance. All
electrical connections should be made in
accordance with the National Electrical Code
and/or with any applicable local codes.
For electrical power wiring diagrams, see the
AERCO Benchmark 2.0LN Electrica
Wiring Guide, (GF-2060LN).
l Power
S
Figure 2-7
AC Input Terminal Block Location
2.8.1 Electrical Power Requirements
The AERCO Benchmark 2.0LN Boiler accepts
120 VAC, single-phase, 60 Hz @ 20A. The
Power Box contains a ter minal block as shown
in Figure 2-8. In addition, a wiring diagram
showing the required AC power connections is
provided on the front cover of the Power Box.
Figure 2-8
AC Terminal Block Configurations
MODES OF OPERATION A ND
2.9
FIELD CONTROL WI
The Benchmark 2.0LN Boiler is availa
several different modes of o
each unit is fac tory configured and wired f or its
intended mode, som e additional field wiring may
be required to complete the installation. This
wiring is typicall y connected to the Input/Output
(I/O) Box located on the lower por tion of the unit
front panel (Figure 2-9) behind the removable
front door.
To access the I/O Box terminal strips shown in
Figure 2-10,
remove the cover. All field wiring is installed
from the rear of the panel by routing the wires
through one of the four bushings provided.
Refer to the wiring diagram provided on the
cover of the I/O Box (Figur e 2-10) when mak
all wiring connections.
loosen the four cover screws and
RING
ble in
peration. While
ing
2-5
Page 18
INSTALLATION
addition to the term inal strips s hown in Figure
In
2-9, the I/O Box also contains a pre-wired
temperature transmitter which receives inlet air
temperature sensor readings and transmits this
signal to the variable frequency drive (VFD)
contained in the Boiler. The VFD utilizes this
input signal to adjust the rotation speed of the
blower.
Brief de
scriptions of each mode of operation,
and their wiring requirements, are provided in
the following paragr aphs. Additional information
concerning field wiring is prov ided in paragr aphs
2.10.1 through 2.10.10. Refer to Chapter 5 for
detailed information on the available modes of
operation.
2.9.1 Con
The Constant Setpoi nt Mode is use
stant Setpoint Mode
d when it is
d to have a fixed setpoint thdesireat does not
deviate. No wiring connections, other than AC
electrical power connections, are required for
this mode. However, if desired, fault monitor ing
or enable/disable in terlock wiring c an be utilized
(see paragraphs 2.10.9.1 and 2.10.10).
OUTDOOR SENSOR IN
SENSOR COMMON
AUX SENSOR IN
Figure 2-9.
Input/Output (I/O) Box Location
REMOTE INTL'K IN
EXHAUST SWITCH IN
DELAYED INTL'K IN
NOT USED
ANALOG IN
B.M.S. (PWM) IN
SHIELD
mA OUT
RS-485
COMM.
+
+
-
+
+
G
-
RELAY CONTACTS:
120 VAC, 30 VDC
5 AMPS RESISTIVE
DANGER
NOT USED
NC
FAULT RELAY
COM
120 VAC, 5A, RES
NO
NC
AUX RELAY
COM
NO
120 VAC, 5A, RES
NOT USED
120 VAC USED
NOT USED
IN THIS BOX
Figure 2-10. I/O Box Terminal Strip
2-6
Page 19
INSTALLATION
2.9.2 Indoor/Outdoor Reset Mode
This mode of operation increases supply water
temperature as outdoor te mperatures decrease.
An outside air temperatur e sensor (AERCO Part
No. 122790) is requ ired. The sensor MUST BE
wired to the I/O Box wiring term inals (see Figure
2-10). Refer to paragraph 2.10.1 for additional
information on outside air temperature sensor
installation.
2.9.3 Boiler Management System Mode
NOTE
BMS Model 168 can utilize either pulse
width modulation (PWM) or RS485
Modbus signaling to the Boiler. BMS II
Model 5R5-384 can utilize only RS485
signaling to the Boiler.
When using an AERCO Boiler Management
System (BMS), the field wiring is connected
between the BMS Panel and each Boiler’s I/O
Box terminal strip (Figure 2-10). Twisted
shielded pair wire f rom 18 to 22 AWG must be
utilized for the connections. The BMS Mode can
utilize either pulse width modulation (PWM)
signaling, or RS485 Modbu s s ignaling. F or PWM
signaling, connections are made from the
AERCO Boiler Management System to the
B.M.S. (PWM) IN terminals on the I/O Box
terminal strip. For RS485 Modus signaling,
connections are made from the BMS to the
RS485 COMM term inals on the I/O Box ter minal
strip. Polarity m ust be maintain ed and the shie ld
must be connected only at the AERCO BMS.
The boiler end of the shi eld m ust be left f loating.
For additional instructions, refer to Chapter 5,
paragraph 5.6 in t his manual. Also, ref er to GF108M (BMS Model 168) and GF-124 (BMS II
Model 5R5-384), BMS -Operations Guides.
operation, it ma y not be the method best suited
for the application. Prior to selecting one of
these modes of operation, it is recommended
that you consult with your local AERCO
representative or the factory for the mode of
operation that will work best with your
application. For m ore information on wir ing the
4 to 20 mA / 1 to 5VDC or the 0 to 20 mA / 0 to 5
VDC, see paragraph 2.9.3.
2.9.5 Combination Mode
NOTE
Only BMS Model 168 can be utilized for
the Combination Mode, not the BMS II
(Model 5R5-384).
With a Combination Mode unit, field wiring is
between the unit’s I/O Box wiring terminals, the
CCP (Combination Contr ol Panel), an d the BMS
(Boiler Management System). The wiring must
be accomplished using twisted-shielded pair
wire from 18 to 22 AWG. Polarity must be
maintained. For further instructions and wiring
diagrams, refer to the GF-108M Boiler
Management System Operations Guide and the
CCP-1 data sheet.
2.10 I/O BOX CONNECTIONS
The types of input and output signals and
devices to be connecte d to the I/O Box terminals
shown in Figure 2-10 are described in the
following paragraphs.
CAUTION
DO NOT make any connections to the
I/O Box terminals labeled “NOT
USED”. Attempting to do so may
cause equipment damage.
2.9.4 Remote Setpoint and Direct Drive
Modes
The boiler can accept several types of signal
formats from an Energy Management System
(EMS), Building Automation System (BAS) or
other source, to control either the setpoint
(Remote Setpoint Mode) or firing rate (Direct
Drive Mode) of the Boiler. These formats are:
• 4 to 20 mA/1 to 5 VDC
• 0 to 20 mA/0 to 5 VDC
• PW M – (Pulse Width Modulate d signal. See
para. 2.10.4)
• Network (RS485 Modbus. See para. 2.10.7)
While it is possible to c ontrol a boiler or boilers
using one of the previously described m odes of
2.10.1 OUTDOOR SENSOR IN
An outdoor air temperature sensor (AERCO Part
No. 122790) will be required primarily for the
Indoor/Outdoor reset m ode of operation. It can
also be used with anoth er m ode if it is desired to
use the outdoor sensor enable/disable feature.
This feature allows the boiler to be enabled or
disabled based on the outdoor air temperature.
The factory default for the outdoor sensor is
DISABLED. To enable the sensor and/or select
an enable/disable o utdoor temperature, see the
Configuration menu in Chapter 3.
The outdoor sensor m ay be wired up t o 200 feet
from the boiler. It is connected to the
OUTDOOR SENSOR IN and SENSOR
COMMON terminals in the I/O Box (see Figures
2-7
Page 20
INSTALLATION
2-9 and 2-10). Wire the sensor using a twisted
shielded pair wire fr om 18 to 22 AWG. There is
no polarity to observe when terminating these
wires. The shield is to be c onnected only to the
terminals labeled SHIELD in the I/O Box. The
sensor end of the shield must be left free and
ungrounded.
When mounting the sensor, it must be located
on the North side of the building where an
average outside air temperature is expected.
The sensor must be shield ed f r om dir ect sunli ght
as well as impingement by the elements. If a
shield is used, it must allow for free air
circulation.
2.10.2 AUX SENSOR IN
The AUX SENSOR IN terminals can b e used to
add an additional temperature sensor for
monitoring purposes. This input is always
enabled and is a view-only input that can be
seen in the Operating Menu. The sensor must
be wired to the AUX S ENSOR IN and SENSOR
COMMON terminals and must be similar to
AERCO BALCO wire se nsor Part No. 124 49. A
resistance chart for this sensor is provided in
Appendix C.
2.10.3 ANALOG IN
The ANALOG IN + and – terminals are used
when an external signal is used to drive the
firing rate (Direct Drive Mode) or change the
setpoint (Remote Setpoint Mode) of the Boiler.
Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA/
0 to 5 VDC signal may be used to vary the
setpoint or firing rate. T he factory def ault setting
is for 4 to 20 mA / 1 to 5 VDC, howev er this m a y
be changed to 0 to 20 mA / 0 to 5 VDC usi ng the
Configuration Menu described in Chapter 3. If
voltage rather than current is selected as the
drive signal, a DIP switch must be set on the
PMC Board located inside the Control Box.
Contact the AERCO factory for information on
setting DIP switches.
a 40°F to 240°F setpoint or a 0% to 100% f iring
rate. No scaling for these signals is provided
2.10.4 B.M.S. (PWM) IN
NOTE
Only BMS Model 168 can utilize Pulse
Width Modulation (PW M), not the BMS II
(Model 5R5-384).
These terminals are used to connect the
AERCO Boiler Management System (BMS) to
the unit. The BMS utilizes a 12 millisecond,
ON/OFF duty cycle. This duty cycle is Pulse
Width Modulated (PW M) to control f iring rate. A
0% firing rate = a 5% ON pulse and a 100%
firing rate = a 95% ON pulse.
2.10.5 SHIELD
The SHIELD terminals are us ed to terminate any
shields used on sensor wires connected to the
unit. Only shields m ust be connected to these
terminals.
2.10.6 mA OUT
These terminals provide a 4 to 20 mA output to
the VFD to control the rotational speed of the
blower. This function is enabled in the
Configuration Menu (Chapter 3, Table 3.4).
2.10.7 RS-485 COMM
These terminals are used for RS-485 MODBUS
serial communication between the unit and an
external “Master” suc h as a Boiler Management
System (BMS), Energy Management System
(EMS), Building Automation System (BAS) or
other suitable device.
2.10.8 EXHAUST SWITCH IN
These terminals permit an external exhaust
switch to be connected to the exhaust manifold
of the boiler. The exhaust switch should be a
normally open t ype s witc h (such as AERCO Par t
No. 123463) that closes (trips) at 500°F.
All of the supplied signals must be floating
(ungrounded) signals . Connectio ns bet ween the
signal source and the Boiler’s I/O Box must be
made using twiste d shiel ded pa ir wire fr om 18 to
22 AWG, such as Belden 9841 (see Figure
2-10). Polarity mu st be maintained. The shi eld
must be connected only at the source end and
must be left floating (not connected) at the
Boiler’s I/O Box.
Regardless of whether volt age or curr ent is used
for the drive signal, the y are linearly mapped to
2-8
2.10.9 INTERLOCKS
The unit offers two interlock circuits for
interfacing with Energy Management Systems
and auxiliary equipment such as pumps or
louvers. These interlock s are called the Rem ote
Interlock and Delayed Interlock (Figure 2-10).
The wiring terminals for these interlocks are
located inside the I/O Box on the unit front
panel. The I/O Box cover contains a wiring
diagram which s hows th e ter m inal str ip locat ions
for these interlocks (REMOTE INTL’K IN and
DELAYED INTL’K IN). Both interlocks,
Page 21
INSTALLATION
described below, are fac tory wired in the closed
position.
NOTE
Both the Delayed Interlock and Remote
Interlock MUST be in the closed position
to allow the unit to fire.
2.10.9.1
The remote interlock circuit is provided to
remotely start (enable) and stop (disable) the
Boiler, if desired. The circuit is labeled
REMOTE INTL’K IN and is loc ate d i nsid e th e I/O
Box on the front panel. The circuit is 24 VAC
and is factory pre-wired in the c losed (jum pered)
position.
2.10.9.2
The delayed interlock is typically used in
conjunction with the aux iliary relay described in
paragraph 2.10. This interlock circuit is located
in the purge section of the start string. It can be
connected to the proving device (end switch,
flow switch etc.) of an auxiliary piece of
equipment started b y the Boiler’s a uxiliary rela y.
The delayed interlock must be closed for the
boiler to fire.
If the delayed interl ock is connec ted t o a pr oving
device that requir es tim e to clos e (mak e), a tim e
delay (Aux Start On Dly) that holds the start
sequence of the boiler lon g enoug h for a proving
switch to make can be progr amm ed. Should the
proving switch not prove within the programm ed
time frame, the boiler will shut down. The Aux
Start On Dly can be progr ammed from 0 to 120
seconds. This option is locate in the
Configuration Menu (Chapter 3, Table 3-4).
REMOTE INTERLOCK IN
DELAYED INTERLOCK IN
2.10.10 FAULT RELAY
The fault relay is a single pole double throw
(SPDT) relay having a normally open and
normally closed set of relay contacts that are
rated for 5 amps at 12 0 VAC and 5 amps at 30
VDC. The relay energizes when any fault
condition occurs and remains energized until the
fault is cleared and the CLEAR button is
depressed. The fault relay connections are
shown in Figure 2-10.
2.11 AUXILIARY RELAY CONTACTS
Each Boiler is equipped with a single pole
double throw (SPDT) relay that is energized
when there is a demand for heat and deenergized after the dem and for heat is satisf ied.
The relay is prov ided for the control of auxiliary
equipment, such as pumps and louvers, or can
be used as a Boiler status indictor (firing or n ot
firing). Its contacts are r ated for 120 VAC @ 5
amps. Refer to Figure 2- 10 to locate the AUX
RELAY terminals for wiring connections.
2.12 FLUE GAS VENT INSTALLATION
The minimum allowable vent diameter for a
single Benchmark 2.0LN Boiler is 8 inches.
The AERCO Benchmark Venting and
Combustion Air Guide, GF-2050, must be
consulted before any flue gas vent or inlet air
venting is designed or installed. U/L listed,
positive pressure, watertight vent materials as
specified in AERCO’s GF-2050, must be used
for safety and code com pliance. S ince the u nit is
capable of dischar ging low temperature ex haust
gases, horizontal sections of the flue vent
system must be pitched back to the unit a
minimum of 1/4 inch per foot to avoid
condensate pooling and allow for proper
drainage.
The combined pressure drop of vent and
combustion air systems must not exceed 140
equivalent feet of 8 inc h ducting. Fittings as we ll
as pipe lengths must be calculate d as part of the
equivalent length.
For a natural draf t installation the draf t must not
exceed ±0.25 inch W .C. These factors must be
planned into the vent installation. If the
maximum allowabl e equivalent lengt hs of piping
are exceeded, the unit will not operate properly
or reliably.
The Heatfab Division of the Selk irk Corporation
provides vent systems which conform to all
applicable requirements for installations within
the Commonwealth of Massachusetts. Contact
information for this supplier are as follows:
Selkirk Corporation
Heatfab Division
130 Industrial Blvd.
Turners Falls, MA 01376
Phone: 1-800-772-0739
www.heat-fab.com
2.13 COMBUSTION AIR
The AERCO Benchmark Venting and
Combustion Air Guide, GF-2050MUST be
consulted before any flue or combustion supply
air venting is designed or implemented.
Combustion air supp ly is a direct r equirem ent of
ANSI 223.1, NFPA-54, and local codes. These
codes should be consulted before a permanent
design is determined.
The combustion air must be free of chlorine,
halogenated hydrocarbons, or other chemicals
that can become ha zardous when used in gas-
2-9
Page 22
INSTALLATION
fired equipment. Common sources of these
compounds are swimming pools, degreasing
compounds, plastic proc essing and refrigerants.
Whenever the env ironment c ontains thes e t ypes
of chemicals, combustion air must be supplied
from a clean area outdoors for the protection
and longevity of the equipment.
The AERCO Benchmark 2.0LN Boiler is UL
listed for 100% sealed combustion. It can also
be installed us ing room air, provid ed there is an
adequate supply. (See para. 2.13.3 for more
information concerning sealed combustion air).
If the sealed com bustion air option is not be ing
used, an inlet screen will be attached at the air
inlet on the top of the unit
The more common methods of supplying
combustion air are outlined below. For more
information concerning combustion air, refer to
the AERCO Benchmark Venting and Combustion Air Guide, GF-2050.
2.13.1 Combustion Air From Outside the
Building
Air supplied from outside the building must be
provided through two perm anent openings. Each
opening must have a free area of not less than
one square inch for each 4000 BTU/H boiler
input. The free area must take into account
restrictions such as louvers and bird screens.
2.13.2 Combustion Air From Inside the
Building
When combustion air is provided f rom within the
building, it must be supplied through two
permanent openings in an interior wall. Each
opening must have a free area of not less than
one square inch per 1000 BTU/H of total boiler
input. The free area must take into ac count any
restrictions such as louvers.
2.13.3 Sealed Combustion
The AERCO Benchmark 2.0LN Boiler is UL
listed for 100%-sealed combustion. For sealed
combustion installations, the screen on the air
inlet duct of the unit m ust be removed. T he inlet
air ductwork must then be attached directly to
the unit’s air inlet.
In a sealed combustion air application, the
combustion air ducting pre ssure losses must be
taken into account when calculating the total
maximum allowable venting run. See the
AERCO Benchmark Venting and Combustion
Air Guide, GF-20 50. When using the bo iler in a
sealed combustion air configuration, each unit
must have a minimum 8 inch diameter
connection at the unit.
2-10
Page 23
CONTROL PANEL OPERATING PROCEDURES
CHAPTER 3 CONTROL PANEL OPERATING PROCEDURES
3.1 INTRODUCTION
The information in this Chapter provides a guide
to the operation of the Benchmark 2.0 Low NOx
Boiler using the Control Panel mounted on the
front of the unit. It is imperative that the initial
startup of this unit be performed by factory
trained personnel. Operation prior to initial
startup by factory trained personnel will void the
equipment warranty. In addition, the following
WARNINGS and CAUTIONS must be observed
at all times.
CAUTION
2
1
3
All of the installation procedures in
Chapter 2 must be completed before
attempting to start the unit.
WARNING
ELECTRICAL VOLTAGES IN THIS
SYSTEM MAY INCLUDE 460, 208
AND 24 VOLTS AC. IT MUST BE
SERVICED ONLY BY FACTORY
CERTIFIED SERVICE TECHNICIANS
WARNING
DO NOT ATTEMPT TO DRY FIRE
THE BOILER. STARTING THE UNIT
WITHOUT A FULL WATER LEVEL
CAN SERIOUSLY DAMAGE THE
UNIT AND MAY RESULT IN INJURY
TO PERSONNEL OR PROPERTY
DAMAGE. THIS SITUATION WILL
VOID ANY WARRANTY.
3.2 CONTROL PANEL DESCRIPTIO N
The Benchmark 2.0 Control Panel shown in
Figure 3-1 contains all of the controls, indicators
and displays necessary to operate, adjust and
troubleshoot the Benchmark 2.0 Boiler. These
operating controls, indicators and displays are
listed and described in Table 3-1. Additional
information on these items are provided in the
individual operating procedures provided in this
Chapter.
4
12
11
10
9
5
6
7
8
Figure 3-1.
Control Panel Front View
3-1
Page 24
CONTROL PANEL OPERATING PROCEDURES
Table 3-1 Operating Controls, Indicators and Displays
ITEM
NO.
CONTROL, INDICATOR
OR DISPLAY
1 LED Status Indicators Four Status LEDs indicate the current operating status as
follows:
COMM
MANUAL
REMOTE
DEMAND
OUTLET
2
TEMPERATURE
Display
3 VFD Display Vacuum Fluorescent Display (VFD) consists of 2 lines each
Lights when RS-232 communication is occurring
Lights when the unit is being controlled using the front panel
keypad.
Lights when the unit is being controlled by an external signal
from an Energy Management System
Lights when there is a demand for heat.
3–Digit, 7–Segment LED display continuously displays the
outlet water temperature. The °F or °C LED next to the
display lights to indicate whether the displayed temperature is
in degrees Fahrenheit or degrees Celsius.
capable of displaying up to 16 alphanumeric characters. The
information displayed includes:
Startup Messages
Fault Messages
Operating Status Messages
FUNCTION
Menu Selection
RS-232 Port
4
FAULT Indicator Red FAULT LED indicator lights when a boiler alarm
5
CLEAR Key Turns off the FAULT indicator and clears the alarm message
6
READY Indicator
7
ON/OFF Switch
8
LOW WATER LEVEL
9
TEST/RESET Switches
Port permits a Laptop Computer or External Modem to be
connected to the unit’s Control Panel.
condition occurs. An alarm message will appear in the VFD.
if the alarm is no longer valid. Lockout type alarms will be
latched and cannot be cleared by simply pressing this key.
Troubleshooting may be required to clear these types of
alarms.
Lights ON/OFF switch is set to ON and all Pre-Purge
conditions have been satisfied.
Enables and disables boiler operation.
Allows operator to test operation of the water level monitor.
Pressing TEST opens the water level probe circuit and
simulates a Low Water Level alarm.
Pressing RESET resets the water level monitor circuit.
Pressing the CLEAR key (item 6) resets the display.
3-2
Page 25
CONTROL PANEL OPERATING PROCEDURES
Table 3-1 Operating Controls, Indicators and Displays – Continued
ITEM
NO.
10 MENU Keypad Consists of 6 keys which provide the following functions for
CONTROL, INDICATOR
OR DISPLAY
the Control Panel Menus:
MENU
BACK
▲ (UP) Arrow When in one of the main menu categories (Figure 3-2),
▼ (DOWN) Arrow When in one of the main menu categories (Figure 3-2),
CHANGE
Steps through the main menu categories shown in Figure 3-
2. The Menu categories wrap around in the order shown.
Allows you to go back to the previous menu level without
changing any information. Continuously pressing this key
will bring you back to the default status display in the VFD.
Also, this key allows you to go back to the top of a main
menu category.
pressing the ▲ arrow key will select the displayed menu
category. If the CHANGE key was pressed and the menu
item is flashing, pressing the ▲ arrow key will increment the
selected setting.
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is
flashing, pressing the ▼ arrow key will decrement the
selected setting.
Permits a setting to be changed (edited). When the
CHANGE key is pressed, the displayed menu item will begin
to flash. Pressing the ▲ or ▼ arrow key when the item is
flashing will increment or decrement the displayed setting.
FUNCTION
11
12
ENTER
AUTO/MAN Switch
FIRE RATE Bargraph
Saves the modified menu settings in memory. The display
will stop flashing.
This switch toggles the boiler between the Automatic and
Manual modes of operation. When in the Manual (MAN)
mode, the front panel controls are enabled and the
MANUAL status LED lights.
When in the Automatic (AUTO) mode, the MANUAL status
LED will be off and the front panel controls disabled.
20 segment red LED bargraph continuously shows the Fire
Rate in 5% increments from 0 to 100%
3-3
Page 26
CONTROL PANEL OPERATING PROCEDURES
3.3 CONTROL PANEL MENUS
The Control Panel incorporates an extensive
menu structure which permits the operator to set
up, and configure the unit. The menu structure
consists of four major menu categories as
shown in Figure 3-2. Each of the menus shown,
contain options which permit operating
parameters to be viewed or changed. The
menus are protected by a password to prevent
unauthorized use.
Prior to entering the correct password, the
options contained in the Operating, Setup,
Configuration and Tuning Menu categories can
be viewed. However, with the exception of
Internal Setpoint Temperature (Configuration
Menu), none of the viewable menu options can
be changed.
Once the valid password (159) is entered, the
options listed in the Setup. Configuration and
Tuning Menus can be viewed and changed, if
desired.
3.3.1 Menu Processing Procedure
Accessing and initiating each menu and option
is accomplished using the Menu Keys shown in
Figure 3-1. Therefore, it is imperative that you
be thoroughly familiar with the following basic
steps before attempting to perform specific
menu procedures.
around after the first or last available option
is reached.
6. To change the value or setting of a
displayed menu option, press the CHANGE
key. The displayed option will begin to flash.
Press the ▲ or ▼ arrow key to scroll
through the available menu option choices
for the option to be changed. The menu
option choices do not wrap around.
7. To select and store a changed menu item,
press the ENTER key.
OPERATION
PASSWORD
SETUP
CONFIGURATION
1. The Control Panel will normally be in the
Operating Menu and the VFD will display the
current unit status. Pressing the ▲ or ▼
arrow key will display the other available
data items in the Operating Menu.
2. Press the MENU key. The display will show
the Setup Menu, which is the next menu
category shown in Figure 3-2. This menu
contains the Password option which must be
entered if other menu options will be
changed.
3. Continue pressing the MENU key until the
desired menu is displayed.
4. With the desired menu displayed, press the
▲ or ▼ arrow key. The first option in the
selected menu will be displayed.
5. Continue to press the ▲ or ▼ arrow key
until the desired menu option is displayed.
Pressing the ▲ arrow key will display the
available menu options in the Top-Down
sequence. Pressing the ▼ arrow key will
display the options in the Bottom-Up
sequence. The menu options will wrap-
TUNING
Figure 3-2. Menu Structure
NOTE
The following paragraphs provide brief
descriptions of the options contained in each
menu. Refer to Appendix A for detailed
descriptions of each menu option. Refer to
Appendix B for listings and descriptions of
displayed startup, status and error
messages.
3-4
Page 27
CONTROL PANEL OPERATING PROCEDURES
3.4 OPERATING M ENU
The Operating Menu displays a number of key
operating parameters for the unit as listed in
Table 3-2. This menu is “Read-Only” and does
not allow personnel to change or adjust any
displayed items. Since this menu is “Read-Only”,
it can be viewed at any time without entering a
password. Pressing the ▲ arrow key to display
the menu items in the order listed (Top-Down).
Pressing the ▼ arrow key will display the menu
items in reverse order (Bottom-Up).
3.5 SETUP MENU
The Setup Menu (Table 3-3) permits the
operator to enter the unit password (159) which
is required to change the menu options. To
prevent unauthorized use, the password will
Table 3-2. Operating Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Status Message
time-out after 1 hour. Therefore, the correct
password must be reentered when required. In
addition to permitting password entries, the
Setup Menu is also used to enter date and time,
units of temperature measurements and entries
required for external communication and control
of the unit via the RS-232 port. A view-only
software version display is also provided to
indicate the current Control Box software
version.
NOTE
The Outdoor Temp display item shown with
an asterisk in Table 3-2 will not be displayed
unless the Outdoor Sensor function has
been enabled in the Configuration Menu
(Table 3-4).
Active Setpoint 40°F 240°F
Aux Temp 30°F 245°F
Outdoor Temp* -70°F 130°F
Fire Rate In 0% Max Fire Rate
Flame Strength 0% 100%
Run Cycles 0 999,999
Run Hours 0 999,999
Fault Log 0 9 0
Table 3-3. Setup Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Passsword 0 9999 0
Language English English
Time 12:00 am 11:59 pm
Date 01/01/00 12/31/99
Unit of Temp Fahrenheit or Celsius Fahrenheit
Comm Address 0 127 0
Baud Rate 2400, 4800, 9600, 19.2K 9600
Software Ver 0.00 Ver 9.99
3-5
Page 28
CONTROL PANEL OPERATING PROCEDURES
3.6 CONFIGURATION MENU
The Configuration Menu shown in Table 3-4
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
may or may not be displayed, depending on the
current operating mode setting.
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Internal Setpt Lo Temp Limit Hi Temp Limit 130°F
Unit Type Boiler or Water Heater Boiler
Unit Size 0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
2.5 MBTU, 3.0 MBTU
Boiler Mode Constant Setpoint,
Remote Setpoint,
Combination
Outdoor Reset
NOTE
The Configuration Menu settings shown in
Table 3-4 are Factory-Set in accordance
with the requirements specified for each
individual order. Therefore, under normal
operating conditions, no changes will be
required.
1.0 MBTU
Constant
Setpoint
Direct Drive
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
Bldg Ref Temp
(If Mode = Outdoor
Reset)
Reset Ratio
(If Mode = Outdoor
Reset)
Outdoor Sensor Enabled or Disabled Disabled
System Start Tmp
(If Outdoor Sensor =
Enabled)
Setpt Lo Limit 40°F Setpt Hi Limit 60°F
Setpt Hi Limit Setpt Lo Limit 220°F 200°F
Temp Hi Limit 40°F 240°F 210°F
Max Fire Rate 40% 100% 100%
Pump Delay Timer 0 min. 30 min. 0 min.
Aux Start On Dly 0 sec. 120 sec. 0 sec.
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
40°F 230°F 70°F
0.1 9.9 1.2
30°F 100°F 60°F
4 – 20 mA,
1-5V
3-6
Page 29
CONTROL PANEL OPERATING PROCEDURES
Table 3-4. Configuration Menu - Continued
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Failsafe Mode Shutdown or Constant Setpt Shutdown
*mA Output
(See CAUTION)
Low Fire Timer 2 sec. 120 sec. 2 sec.
Setpt Limiting Enabled or Disabled Disabled
Setpt Limit Band 0°F 10°F 5°F
*CAUTION: DO NOT CHANGE mA Output Menu Item from its Default setting.
Setpoint, Outlet Temp,
Fire Rate Out, Off
*Fire Rate
Out
3.7 TUNING MENU
The Tuning Menu items in Table 3-5 are Factory
set for each individual unit. Do not change
these menu entries unless specifically requested
to do so by Factory-Trained personnel.
Table 3-5. Tuning Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Prop Band 1°F 120°F 70°F
Integral Gain 0.00 2.00 1.00
Derivative Time 0.0 min 2.00 min 0.00 min
Reset Defaults? Yes
No
Are You Sure?
No
3.8 START SEQUENCE
When the Control Box ON/OFF switch is set to
the ON position, it checks all pre-purge safety
switches to ensure they are closed. These
switches include:
• Safety Shut-Off Valve Proof of Closure
(POC) switch
• Low Water Level switch
• High Water Temperature switch
• High Gas Pressure switch
• Low Gas Pressure switch
• Blower Proof switch
If all of the above switches are closed, the
READY light above the ON/OFF switch will light
and the unit will be in the Standby mode.
When there is a demand for heat, the following
events will occur:
NOTE
If any of the Pre-Purge safety device
switches are open, the appropriate fault
message will be displayed. Also, the
appropriate fault messages will be displayed
throughout the start sequence, if the
required conditions are not observed.
1. The DEMAND LED status indicator will light.
2. The unit checks to ensure that the Proof of
Closure (POC) switch in the Safety Shut-Off
Valve (SSOV) is closed. See Figure 3-3 for
SSOV location.
3-7
Page 30
CONTROL PANEL OPERATING PROCEDURES
S
GA
INLET
SSOV
MANUAL
SHUT-OFF
VALVE
TO AIR/FUEL
VALVE
Figure 3-3.
SSOV Location
3. With all required safety device switches
closed, a purge cycle will be initiated and the
following events will occur:
(a) The Blower Relay energizes and turns
on Blower.
(b) The Air/Fuel Valve rotates to the full-
open purge position and closes purge
position switch. The dial on the Air/Fuel
Valve (Figure 3-4) will read 100 to
indicate that it is full-open (100%).
(c) The VFD sends a signal and turns on
the Blower.
DIAL
(DETAIL “A”)
TO BLOWER
STEPPER
MOTOR
100
DETAIL “A”
Figure 3-4.
Air/Fuel Valve In Purge Position
AIR IN
(d) The FIRE RATE bargraph will show
100%.
4. Next, the Blower Proof Switch on the
Air/Fuel Valve (Figure 3-5) closes. The
display will show Purging and indicate the
elapsed time of the purge cycle in seconds.
The normal (default) time for the purge cycle
is 7 seconds.
Figure 3-5.
Blower Proof Switch
3-8
Page 31
CONTROL PANEL OPERATING PROCEDURES
5. Upon completion of the purge cycle, the
Control Box initiates an ignition cycle and
the following events occur:
(a) The Air/Fuel Valve rotates to the low-
fire ignition position and closes the
ignition switch. The dial on the Air/Fuel
Valve (Figure 3-6) will read between 25
and 35 to indicate that the valve is in
the low-fire position.
(b) The igniter relay is activated and
provides ignition spark.
(c) The gas Safety Shut-Off Valve (SSOV)
is energized (opened) allowing gas to
flow into the Air/Fuel Valve.
TO BLOWER
STEPPER
MOTOR
DIAL
(DETAIL “A”)
AIR IN
6. Up to 7 seconds will be allowed for ignition
to be detected. The igniter relay will be
turned off one second after flame is
detected.
7. After 2 seconds of continuous flame, Flame Proven will be displayed and the flame
strength will be indicated. After 5 seconds,
the current date and time will be displayed in
place of the flame strength.
8. With the unit firing properly, it will be
controlled by the temperature controller
circuitry. The boiler’s FIRE RATE will be
continuously displayed on the front panel
bargraph.
Once the demand for heat has been satisfied,
the Control Box will turn off the SSOV gas valve.
The blower relay will be deactivated and the
Air/Fuel Valve will be closed. Standby will be
displayed.
5
2
DETAIL “A”
Figure 3-6.
Air/Fuel Valve In Ignition
3.9 START/STOP LEVELS
The start and stop levels are the fire rate
percentages that start and stop the unit, based
on load. These levels are Factory preset as
follows:
Start Level: 24%
Stop Level: 18%
Normally, these settings should not require
adjustment.
Note that the energy input of the boiler is not
linearly related to the fire rate percentage
(Air/Fuel Valve position). Refer to Table 3-6 on
the following page for the relationship between
the energy input and fire rate percentage for a
unit running on natural gas.
3-9
Page 32
CONTROL PANEL OPERATING PROCEDURES
Table 3-6.
Relationship Between Air/Fuel Valve Position and Energy Input For Unit Running On Natural Gas
Fire Rate,
Air/Fuel Valve
Position
(% Open)
0 0 0
10% 0 0
18%
(Stop Level)
20%
30%
40%
50%
60%
70%
80%
90%
100%
Energy Input
(BTU/Hr)
Boiler Energy Input
(% of Full Capacity)
5.0%
100,000
134,000 7%
349,000 17%
631,000 32%
893,000 45%
1,150,000 58%
1,410,000 71%
1,610,000 81%
1,830,000 92%
2,000,000 100%
3-10
Page 33
CHAPTER 4 INITIAL START-UP
INITIAL START-UP
4.1 INITIAL START-UP REQUIREMENTS
The requirements for the initial start-up of the
Benchmark 2.0 Low NOx (LN) Boiler consist of
the following:
• Complete installation
• Perform combustion calibration
• Set proper controls and limits
• Set up mode of operation (see Chapter 5)
• Test safety devices (see Chapter 6)
Installation should be fully completed before
performing initial start-up. The start-up must be
complete prior to putting the unit into service.
Starting a unit without the proper piping, venting,
or electrical systems can be dangerous and may
void the product warranty. The following start-up
instructions should be followed precisely in order
to operate the unit safely and at a high thermal
efficiency, with low flue gas emissions.
Initial unit start-up is to be performed ONLY by
AERCO factory trained start-up and service
personnel. After following the steps in this
chapter, it will be necessary to perform the Mode
of Operation settings in Chapter 5, and the
Safety Device Testing procedures in Chapter 6
to complete the initial unit start-up.
AERCO Gas Fired Startup Sheets, included with
each Benchmark Boiler, must be completed for
each unit for warranty validation and a copy
must be returned promptly to AERCO at:
AERCO International, Inc.
159 Paris Ave.
Northvale, NJ 07647
WARNING
DO NOT ATTEMPT TO DRY FIRE
THE BOILER. STARTING THE UNIT
WITHOUT A FULL WATER LEVEL
CAN SERIOUSLY DAMAGE THE
UNIT AND MAY RESULT IN INJURY
TO PERSONNEL OR PROPERTY
DAMAGE. THIS SITUATION WILL
VOID ANY WARRANTY.
CAUTION
All applicable installation procedures
in Chapter 2 must be completed
before attempting to start the unit.
4.2 TOOLS AND INSTRUMENTATION
FOR COMBUSTION CALIBRATION
To properly perform combustion calibration, the
proper instruments and tools must be used and
correctly attached to the unit. The following
paragraphs outline the necessary tools and
instrumentation as well as their installation.
4.2.1 Required Tools & Instrumentation
The following tools and instrumentation are
necessary to perform combustion calibration of
the unit:
• Digital Combustion Analyzer: Oxygen
accuracy to ± 0.4%; Carbon Monoxide
(CO) and Nitrogen Oxide (NOx) resolution
to 1PPM.
• 16 inch W.C. manometer or equivalent
gauge and plastic tubing.
• 1/8 inch NPT-to-barbed fittings for use with
gas supply manometer or gauge.
• Small and large flat blade screwdrivers.
• Tube of silicone adhesive
4.2.2 Installing Gas Supply Manometer
The gas supply manometer is installed in the
gas train as follows:
1. Close the main manual gas supply shut-off
valve upstream of the unit.
2. Remove the top panel and left or right side
panel from the boiler to access the gas train
components.
3. Remove the 1/8 inch NPT pipe plug from the
leak detection ball valve on the downstream
side of the Safety Shut Off Valve (SSOV) as
shown in Figure 4-1.
4. Install a NPT-to-barbed fitting into the
tapped plug port.
4-1
Page 34
INITIAL START-UP
5. Attach one end of the plastic tubing to the
barbed fitting and the other end to the 16
inch W.C. manometer.
GAS
INLET
LOW GAS
PRESSURE
SWITCH
SSOV
HIGH GAS
PRESSURE
SWITCH
MANUAL
SHUT-OFF
VALVE
1/8" NPT PLUG
(INSTALL
MANOMETER
HERE)
TO AIR/
FUEL
VALVE
Figure 4-1.
1/8 Inch NPT Gas Plug Location
4.2.3 Accessing the Analyzer Probe Port
The unit contains NPT plugs on the left and right
side of the exhaust manifold at the rear of the
unit as shown in Figure 4-2. Prepare the port for
the combustion analyzer probe as follows:
1. Remove the plug from the probe port on the
right side of the exhaust manifold.
left or
2. If necessary, adjust the stop on the
combustion analyzer probe so that it will
extend mid-way into the flue gas flow. DO
NOT install the probe at this time.
4.3 NATURAL GAS COMBUSTION
CALIBRATION
The Benchmark 2.0LN Boiler is combustion
calibrated at the factory prior to shipping.
However, recalibration as part of initial start-up
is necessary due to changes in the local altitude,
gas BTU content, gas supply piping and supply
regulators. Factory Test Data sheets are
shipped with each unit. These sheets must be
filled out and returned to AERCO for proper
Warranty Validation.
It is important to perform the following procedure
as outlined. This will keep readjustments to a
minimum and provide optimum performance.
1. Open the water supply and return valves to
the unit and ensure that the system pumps
are running.
2. Open the natural gas supply valve(s) to the
unit.
3. Set the control panel ON/OFF switch to the
OFF position.
4. Turn on external AC power to the unit. The
display will show LOSS OF POWER and the
time and date.
5. Set the unit to the Manual Mode by pressing
the AUTO/MAN key. A flashing Manual Fire Rate message will be displayed with the
present rate in %. Also, the MANUAL LED
will light.
6. Adjust the fire rate to 0% by pressing the ▼
arrow key.
EXHAUST
MANIFOLD
ANALYZER
PROBE PORT
CONDENSATE
CONNECTION
Analyzer Probe Port Location
4-2
BOILER
RETURN
1/2” NPT
DRAIN
Figure 4-2
7. Ensure that the leak detection ball valve
down-stream of the SSOV is open.
8. Set the ON/OFF switch to the ON position.
9. Change the fire rate to 29% using the ▲
arrow key. The unit should begin its start
sequence and fire.
10. Next, verify that the gas pressure
downstream of the SSOV is 2.8” W.C. for
both FM and IRI gas trains. If gas pressure
adjustment is required, remove the brass
hex nut on the SSOV actuator (IRI gas train)
containing the droop eliminator (Figure 4-3).
Make droop eliminator adjustments using a
flat-tip screwdriver to obtain 2.8” W.C.
Page 35
INITIAL START-UP
R
R
BRASS HEX
HEAD CAP
(REMOVE TO
ACCESS DROOP
ELIMINATOR
ADJUSTMENT)
TYPICAL SSOV ACTUATOR WITH DROOP
ELIMINATO
Figure 4-3
Regulator Adjustment Screw Location
11. Raise the firing rate to 100% and verify that
the gas pressure downstream of the SSOV
remains at 2.8” W.C. Readjust pressure if
necessary.
12. With the firing rate at 100%, insert the
combustion analyzer probe into the flue
probe opening and allow enough time for the
combustion analyzer to settle.
13. Compare the measured oxygen level to the
oxygen range for the inlet air temperature
shown in Table 4-1. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide
(NOx) readings do not exceed the values
shown.
14. If necessary, adjust the iris air damper
shown in Figure 4-4 until the oxygen level is
within the range specified in Table 4-1.
15. Once the oxygen level is within the specified
range at 100%, lower the firing rate to 80%.
Oxygen %
± 0.2
Carbon
Monoxide NOx
AI
INLET
IRIS AIR
DAMPER
(SEE VIEW “A”)
USE 1/2"
WRENCH TO
INCREASE (CW)
OR DECREASE
(CCW) INLET AIR
IRIS ADJUSTMENT
VIEW A - A
Figure 4-4
Iris Air Damper Location/Adjustment
NOTE
The remaining combustion calibration
steps utilize the Variable Frequency Drive
(VFD) located behind the front door of the
unit. The VFD up (Λ) and down (V) arrow
keys will be used to adjust the oxygen
level (%) at firing rates of 80%, 60%,
45%, 30% and 18% as described in the
following steps.
16. Locate the Variable Frequency Drive (VFD)
behind the front door of the unit. Refer to the
VFD operating controls shown in Figure 4-5.
4-3
Page 36
INITIAL START-UP
Figure 4-5
VFD Controls and Displays
IMPORTANT
In the following steps, the values
appearing in the right part of the VFD
display for parameters 65, 64, 63, 62, 61
represent the base frequency (Hz) x 10.
For example: a displayed value of 326
corresponds to a frequency of 32.6 Hz.
17. Press the M (Menu) programming key on
the VFD.
18. Using the up (Λ) arrow key, select VFD
parameter 65. The selected parameter will
appear in the left part of the display and the
voltage frequency (Hz) will appear in the
right part of the display (see IMPORTANT
note above). This is the frequency of the AC
voltage sent to the blower.
19. With the selected VFD parameter display
flashing, press the M key. Code will be
displayed, requesting the valid code to be
entered. Enter code 59 using the arrow
keys. Press M again to store the valid code.
21. If the oxygen level is not within the specified
range, adjust the level using the up (Λ) and
down (V) arrow keys on the VFD. Using the
up (Λ) arrow key will increase oxygen level
and the down (V) arrow key will decrease
the oxygen level.
22. Once the oxygen level is within the specified
range at 80%, lower the firing rate to 60%
and select VFD parameter 64. The oxygen
level at the 60% firing rate should be as
shown below.
Combustion Oxygen Level at
60% Firing Rate
Oxygen %
± 0.2
5.7 % <50 ppm <30 ppm
23. Adjust the oxygen level as necessary using
the up (Λ) and down (V) arrow keys on the
VFD to obtain the required reading at the
60% firing rate.
24. Next, set the firing rate to 45% and select
VFD parameter 63. The oxygen level at the
45% firing rate should be as shown below.
Carbon
Monoxide
NOx
Combustion Oxygen Level at
45% Firing Rate
Oxygen %
± 0.2
7.2 % <50 ppm <30 ppm
25. Adjust the oxygen level as necessary to
obtain the required reading at the 45% firing
rate.
26. Next, set the firing rate to 30% and select
VFD parameter 62. The oxygen level at the
30% firing rate should be as follows:
Carbon
Monoxide
NOx
20. With parameter 65 displayed in the left part
of the VFD display, observe the oxygen level
(%) on the Combustion Analyzer. The
oxygen level at the 80% firing rate should be
as shown in the following tabular listing.
Also, ensure that the carbon monoxide (CO)
and nitrogen oxide (NOx) readings do not
exceed the values shown.
Combustion Oxygen Level at
80% Firing Rate
Oxygen %
± 0.2
5.0 % <100 ppm <30 ppm
4-4
Carbon
Monoxide
NOx
Combustion Oxygen Level at
30% Firing Rate
Oxygen %
± 0.2
8.0 % <50 ppm <30 ppm
27. Adjust the oxygen level as necessary to
obtain the required reading at the 30% firing
rate.
28. Finally, reduce the firing rate to 18% and
select VFD parameter 61. The oxygen level
at the 18% firing rate should be as shown in
the following tabular listing:
Carbon
Monoxide
NOx
Page 37
INITIAL START-UP
Combustion Oxygen Level at
18% Firing Rate
Oxygen %
± 0.2
8.0 % <50 ppm <30 ppm
29. Adjust the oxygen level as necessary to
obtain the required reading at the 18% firing
rate.
30. This completes the Natural Gas combustion
calibration procedures.
Carbon
Monoxide
NOx
4.4 UNIT REASSEMBLY
Once the combustion calibration adjustments
are properly set, the unit can be reassembled for
service operation.
1. Set the ON/OFF switch in the OFF position.
2. Disconnect AC power from the unit.
3. Shut off the gas supply to the unit.
SEE
DETAIL “A”
FRONT VIEW
4. Remove the manometer and barbed fittings
and reinstall the NPT plug using a suitable
pipe thread compound.
5. Remove the combustion analyzer probe
from the vent hole. Replace the NPT plug in
the vent hole using a suitable pipe joint
compound.
6. Replace the unit’s side panels and front
door.
4.5 OVER-TEMPERATURE LIMIT
SWITCHES
The unit contains both automatic and manual
reset over-temperature limit switches. These
switches are mounted on a plate next to the
VFD as shown in Figure 4-6. The switches can
be accessed by opening the front panel door of
the unit. The manual reset switch is not
adjustable and is permanently fixed at 210°F.
This switch will shut down and lock out the boiler
if the water temperature exceeds 210°F.
Following an over-temperature condition, it must
be manually reset by pressing the RESET
button before the boiler can be restarted. The
automatic reset over-temperature switch is
adjustable and allows the boiler to restart, once
the temperature drops below its temperature
setting. Set the automatic over-temperature
switch to the desired setting.
RESET BUTTON FOR
MANUAL RESET
TEMPERATURE
LIMIT SWITCH
MOUNTING
PLATE
DETAIL “A”
Figure 4-6
Over Temperature Limit Switch
Locations
ADJUSTABLE
TEMPERATURE
LIMIT SW ITCH
VFD
LOGICSTICK
SLOT
4-5
Page 38
Page 39
MODE OF OPERATION
CHAPTER 5 MODE OF OPERATION
5.1 INTRODUCTION
The Benchmark 2.0 Low NOx (LN) Boiler is
capable of being operated in any one of six
different modes. The following paragraphs in this
Chapter provide descriptions of each of these
operating modes. Each Benchmark 2.0LN Boiler
is shipped from the factory tested and
configured for the ordered mode of operation.
All temperature related parameters are at their
factory default values which work well in most
applications. However, it may be necessary to
change certain parameters to customize the unit
to the system environment. A complete listing
and descriptions of the temperature related
parameters are included in Appendix A. Factory
defaults are listed in Appendix E. After reading
this chapter, parameters can be customized to
suit the needs of the specific application.
5.2 INDOOR/OUTDOOR RESET MODE
This mode of operation is based on outside air
temperatures. As the outside air temperature
decreases, the supply header temperature will
increase and vice versa. For this mode, it is
necessary to install an outside air sensor as well
as select a building reference temperature and a
reset ratio.
5.2.1 Reset Ratio
Reset ratio is an adjustable number from 0.1 to
9.9. Once adjusted, the supply header
temperature will increase by that number for
each degree that the outside air temperature
decreases. For instance, if a reset ratio of 1.6 is
used, for each degree that outside air
temperature decreases, the supply header
temperature will increase by 1.6 degrees.
5.2.3 Outdoor Air Temperature Sensor
Installation
The outdoor air temperature sensor must be
mounted on the North side of the building in an
area where the average outside air temperature
is expected. The sensor must be shielded from
the sun's direct rays, as well as direct
impingement by the elements. If a cover or
shield is used, it must allow free air circulation.
The sensor may be mounted up to 200 feet from
the unit. Sensor connections are made at the
Input/Output (I/O) Box on the front of the
Benchmark 2.0LN Boiler. Connections are
made at the terminals labeled OUTDOOR
SENSOR IN and SENSOR COMMON inside the
I/O Box. Use shielded 18 to 22 AWG wire for
connections. A wiring diagram is provided on
the cover of the I/O Box. Refer to Chapter 2,
paragraph 2.9 for additional wiring information.
5.2.4 Indoor/ Outdoor Startup
Startup in the Indoor/Outdoor Reset Mode is
accomplished as follows:
1. Refer to the Indoor/Outdoor reset ratio
charts in Appendix D.
2. Choose the chart corresponding to the
desired Building Reference Temperature.
3. Go down the left column of the chart to the
coldest design outdoor air temperature
expected in your area.
NOTE
A design engineer typically provides
design outdoor air temperature and
header temperature data
supply
5.2.2 Building Reference Temperature
This is a temperature from 40°F to 230°F. Once
selected, it is the temperature that the system
references to begin increasing its temperature.
For instance, if a reset ratio of 1.6 is used, and
we select a building reference temperature of
70°F, then at an outside temperature of 69°F,
the supply header temperature will increase by
1.6° to 71.6°F.
4. Once the design outdoor air temperature is
chosen, go across the chart to the desired
supply header temperature for the design
temperature chosen in step 3.
5. Next, go up that column to the Reset Ratio
row to find the corresponding reset ratio.
6. Access the Configuration Menu and scroll
through it until the display shows Bldg Ref Temp. (Building Reference Temperature).
5-1
Page 40
MODE OF OPERATION
7. Press the CHANGE key. The display will
begin to flash.
8. Use the ▲ and ▼ arrow keys to select the
desired Building Reference Temperature.
9. Press ENTER to save any changes.
10. Next, scroll through the Configuration Menu
until the display shows Reset Ratio.
11. Press the CHANGE key. The display will
begin to flash.
12. Use the ▲ and ▼ arrow keys to select the
Reset Ratio determined in step 5.
13. Press ENTER to save the change.
Refer to paragraph 3.3 for detailed instructions
on menu changing.
5.3 CONSTANT SETPOINT MODE
The Constant Setpoint mode is used when a
fixed header temperature is desired. Common
uses of this mode of operation include water
source heat pump loops, and indirect heat
exchangers for potable hot water systems or
processes.
5.4 REMOTE SETPOINT MODES
The unit’s setpoint can be remotely controlled by
an Energy Management System (EMS) or
Building Automation System (BAS). The Remote
Setpoint can be driven by a current or voltage
signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Remote
Setpoint mode is 4 - 20 mA/1 - 5 Vdc. With this
setting, a 4 to 20 mA/1 to 5 Vdc signal, sent by
an EMS or BAS, is used to change the unit's
setpoint. The 4 mA/1V signal is equal to a 40°F
setpoint while a 20 mA /5V signal is equal to a
240°F setpoint. When a 0 to 20 mA/0 to 5 Vdc
signal is used, 0 mA is equal to a 40°F setpoint.
In addition to the current and voltage signals
described above, the Remote Setpoint mode
can also be driven by a RS485 Modbus Network
signal from an EMS or BAS.
The Remote Setpoint modes of operation can be
used to drive single as well as multiple units.
No external sensors are required to operate in
this mode. While it is necessary to set the
desired setpoint temperature, it is not necessary
to change any other temperature-related
functions. The unit is factory preset with settings
that work well in most applications. Prior to
changing any temperature-related parameters,
other than the setpoint, it is suggested that an
AERCO representative be contacted. For
descriptions of temperature-related functions
and their factory defaults, refer to Appendix A
and Appendix E, respectively.
5.3.1 Setting the Setpoint
The setpoint temperature of the unit is
adjustable from 40°F to 240°F. To set the unit
for operation in the Constant Setpoint Mode, the
following menu settings must be made in the
Configuration Menu:
MENU OPTION SETTING
Boiler Mode Constant Setpoint
Internal Setpt Select desired setpoint
using ▲ and ▼ arrow
keys (40°F to 240°F)
NOTE
If a voltage, rather than current signal is
used to control the remote setpoint, a DIP
switch adjustment must be made on the
PMC Board located in the Control Panel
Assembly. Refer to GF-112, Appendix F
for instructions on changing Control Panel
DIP switch settings.
In order to enable the Remote Setpoint Mode,
the following menu setting must be made in the
Configuration Menu:
MENU OPTION SETTING
Boiler Mode Remote Setpoint
Remote Signal 4-20mA/1-5V,
0-20mA/0-5V, or
Network
Refer to paragraph 3.3 for detailed instructions
on changing menu options.
Refer to paragraph 3.3 for detailed instructions
on changing menu options.
5-2
Page 41
If the Network setting is selected for RS485
Modbus operation, a valid Comm Address must
be entered in the Setup Menu. Refer to Modbus
Communication Manual GF-114 for additional
information.
While it is possible to change the settings of
temperature related functions, the unit is factory
preset with settings that work well in most
applications. It is suggested that an AERCO
representative be contacted, prior to changing
any temperature related function settings. For
descriptions of temperature-related functions
and their factory defaults, refer to Appendices A
and E.
5.4.1 Remote Setpoint Field Wiring
The only wiring connections necessary for the
Remote Setpoint mode are connection of the
remote signal leads from the source to the unit’s
I/O Box. The I/O Box is located on the front
panel of the Benchmark 2.0LN Boiler. For either
a 4-20mA/0-5V or a 0-20mA/0-5V setting, the
connections are made at the ANALOG IN
terminals in the I/O Box. For a Network setting,
the connections are made at the RS-485 COMM
terminals in the I/O Box. The signal must be
floating, (ungrounded) at the I/O Box and the
wire used must be a two wire shielded pair from
18 to 22 AWG. Polarity must be observed. The
source end of the shield must be connected at
the source. When driving multiple units, each
unit’s wiring must conform to the above.
5.4.2 Remote Setpoint Startup
Since this mode of operation is factory preset
and the setpoint is being externally controlled,
no startup instructions are necessary. In this
mode, the REMOTE LED will light when the
external signal is present.
To operate the unit in the Manual mode, press
the AUTO/MAN switch. The REMOTE LED will
go off and the MANUAL LED will light.
To change back to the Remote Setpoint mode,
simply press the AUTO/MAN switch. The
REMOTE LED will again light and the MANUAL
LED will go off.
MODE OF OPERATION
5.5 DIRECT DRIVE MODES
The unit’s fire rate can be changed by a remote
signal which is typically sent from an Energy
Management System (EMS) or from a Building
Automation System (BAS). The Direct Drive
mode can be driven by a current or voltage
signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Direct Drive
mode is 4-20 mA/1-5 Vdc. With this setting, a 4
to 20 mA signal, sent by an EMS or BAS is used
to change the unit’s fire rate from 0% to 100%. A
4 mA/1V signal is equal to a 0% fire rate, while a
20 mA /5V signal is equal to a 100% fire rate.
When a 0-20 mA/0-5 Vdc signal is used, zero is
equal to a 0% fire rate.
In addition to the current and voltage signals
described above, the Direct Drive mode can also
driven by a RS485 Modbus Network signal from
an EMS or BAS.
When in a Direct Drive mode, the unit is a slave
to the EMS or BAS and does not have a role in
temperature control. Direct Drive can be used to
drive single, or multiple units.
NOTE
If a voltage, rather than current signal is
used to control the remote setpoint, a DIP
switch adjustment must be made on the
PMC Board located in the Control Box
Assembly. Refer to GF-112, Appendix F
for instructions on changing Control Panel
DIP switch settings.
To enable the Direct Drive Mode, the following
menu setting must be made in the Configuration
Menu:
MENU OPTION SETTING
Boiler Mode Direct Drive
Remote Signal 4-20mA/1-5V,
0-20mA/0-5V, or
Network
Refer to paragraph 3.3 for instructions on
changing menu options.
5-3
Page 42
MODE OF OPERATION
If the Network setting is selected for RS485
Modbus operation, a valid Comm Address must
be entered in the Setup Menu. Refer to Modbus
Communication Manual GF-114 for additional
information.
5.5.1 Direct Drive Field Wiring
The only wiring connections necessary for Direct
Drive mode are connection of the remote signal
leads from the source to the unit’s I/O Box. For
either a 4-20mA/0-5V or a 0-20mA/0-5V setting,
the connections are made at the ANALOG IN
terminals in the I/O Box. For a Network setting,
the connections are made at the RS-485 COMM
terminals in the I/O Box. The signal must be
floating, (ungrounded) at the I/O Box and the
wire used must be a two wire shielded pair from
18 to 22 AWG. Polarity must be observed. The
source end of the shield must be connected at
the source. When driving multiple units, each
unit’s wiring must conform to the above.
5.5.2 Direct Drive Startup
Since this mode of operation is factory preset
and the fire rate is being externally controlled, no
startup instructions are necessary. In this mode,
the REMOTE LED will light when the signal is
present.
To operate the unit in manual mode, press the
AUTO/MAN switch. The REMOTE LED will go
off and the MANUAL LED will light.
To change back to the Direct Drive mode, simply
press the AUTO/MAN switch. The REMOTE
LED will again light and the MANUAL LED will
go off.
5.6 BOILER MANAGEMENT SYSTEM
(BMS)
NOTE
BMS Model 168 can utilize either pulse
width modulation (PWM) or RS485
Modbus signaling to the Boiler. BMS II
Model 5R5-384 can utilize only RS485
signaling to the Boiler.
and operation, see GF-108M (BMS Model 168)
and GF-124 (BMS II Model 5R5-384), BMS
Operations Guides. For operation via an RS485
Modbus network, refer to Modbus Communication Manual GF-114.
To enable the BMS Mode, the following menu
settings must be made in the Configuration
Menu:
MENU OPTION SETTING
Boiler Mode Direct Drive
Remote Signal BMS (PWM Input)
or
Network (RS485)
Refer to paragraph 3.3 for instructions on
changing menu options.
5.6.1 BMS External Field Wiring
Wiring connections for BMS (Model 168) control
using PWM signaling are made between
connector JP2 on the BMS (boilers 1 through 8),
and the B.M.S. (PWM) IN terminals in the I/O
Box on the front of the Benchmark 2.0LN
Boilers. Refer to the wiring diagram provided on
the cover of the I/O Box.
For the BMS (Model 168), RS485 Modbus
control wiring connections are made between
BMS connector JP11 (boilers 9 – 40) and the
RS485 COMM terminals in the I/O Box on the
front of the Benchmark 2.0LN Boilers.
For the BMS II (Model 5R5-384), RS485
Modbus control wiring connections are made
between the BMS II 485 B+/485 A- terminals
and the RS485 COMM terminals in the I/O Box
on the front of the Benchmark 2.0LN Boilers.
Wire the units using shielded twisted pair wire
between 18 and 22 AWG. Observe the proper
polarity for the B.M.S. (PWM) IN and/or RS485
COMM wiring connections. Shields should be
terminated only at the BMS and the boiler end
must be left floating. Each unit’s wiring must
conform to the above.
The BMS mode of operation is used in
conjunction with an AERCO Boiler Management
System. The BMS mode is used when it is
desired to operate multiple units in the most
efficient manner possible. The BMS can control
up to 40 boilers; 8 via pulse width modulation
(PWM) and up to 32 via Modbus (RS485)
network communication. For BMS programming
5-4
5.6.2 BMS Setup and Startup
This mode of operation is factory preset and the
AERCO BMS controls the firing rate. There are
no setup instructions for each individual unit.
To operate the unit in manual mode, press the
AUTO/MAN switch. The REMOTE LED will go
off and the MANUAL LED will light
Page 43
MODE OF OPERATION
To change back to the BMS mode, simply press
the AUTO/MAN switch. The REMOTE LED will
again light and the MANUAL LED will go off.
5.7 COMBINATION CONTROL SYSTEM
(CCS)
NOTE
Only BMS Model 168 can be utilized for
the Combination Mode, not the BMS II
(Model 5R5-384).
A Combination Control System (CCS) is one
that uses multiple boilers to cover both spaceheating and domestic hot water needs. An
AERCO Boiler Management System (BMS)
Model 168 and a Combination Control Panel
(CCP) are necessary to configure this system.
Typically, an adequate number of boilers are
installed to cover the space-heating load on the
design day, however one or more units are used
for the domestic hot water load.
The theory behind this type of system is that the
maximum space-heating load and the maximum
domestic hot water load do not occur simultaneously.+ Therefore, boilers used for the
domestic hot water are capable of switching
between constant setpoint and BMS modes of
operation. These boilers are the combination
units and are referred to as the combo boilers.
The combo boilers heat water to a constant
setpoint temperature. That water is then
circulated through a heat exchanger in a
domestic hot water storage tank.
When the space-heating load is such that all the
space-heating boilers are at 100% firing rate, the
BMS will then ask the Combination Control
Panel for the domestic boilers to become spaceheating boilers. Provided the domestic hot
water load is satisfied, the combo (hot water)
boilers will then become space-heating boilers.
If the domestic hot water load is not satisfied,
the combo boiler(s) remain on the domestic hot
water load. If the combo boilers switch over to
space heating, but there is a call for domestic
hot water, the CCP switches the combo units
back to the domestic load.
When the combo units are satisfying the
domestic load they are in constant setpoint
mode of operation. When the combo units
switch over to space heating, their mode of
operation changes to the BMS mode. For more
information concerning the operation of the
Combination Control Panel see the AERCO
CCP-1 literature.
5.7.1 Combination Control System Field
Wiring
Wiring for this system is between the BMS
Model 168 panel, the CCP and the B.M.S.
(PWM) IN terminals in the I/O Box. Wire the
units using a shielded twisted pair of 18 to 22
AWG wire. When wiring multiple units, each
unit’s wiring must conform to the above. For a
complete CCP system-wiring diagram see the
AERCO CCP-1 literature.
5.7.2 Combination Control System Setup
and Startup
Setup for the Combination Mode requires entries
to be made in the Configuration Menu for boiler
mode, remote signal type and setpoint. The
setpoint is adjustable from 40°F to 240°F.
Enter the following settings in the Configuration
Menu:
MENU OPTION SETTING
Boiler Mode Combination
Remote Signal BMS (PWM Input)
Internal Setpt 40°F to 240°F
Refer to paragraph 3.3 for instructions on
changing menu options.
While it is possible to change other temperaturerelated functions for combination mode, thes
functions are preset to their factory default
values. These default settings work well in most
applications. It is suggested that AERCO be
contacted prior to changing settings other than
the unit’s setpoint. For a complete listing of
temperature related function defaults, see
Appendix E.
To set the unit to the manual mode, press the
AUTO/MAN switch. The MANUAL LED will
light.
To set the unit back to the auto mode, press the
AUTO/MAN switch. The MANUAL LED will go
off and the REMOTE LED will light.
When the boiler is switched to BMS mode, the
AERCO BMS controls the firing rate. There are
no setup requirements to the boiler(s) in this
mode.
5-5
Page 44
Page 45
SAFETY DEVICE TESTING
CHAPTER 6 SAFETY DEVICE TESTING
6.1 TESTING OF SAFETY DEVICES
Periodic safety device testing is required to
ensure that the control system and safety
devices are operatin g properly. The Benchmark
2.0LN control system comprehensively monitors
all combustion-related safety devices before,
during and after the start sequence. The
following tests chec k to ensure that the system
is operating as designed.
Operating controls and saf ety devices s hould be
tested on a regu lar basis or f ollowing service or
replacement. All testing must conform to local
codes such as ASME CSD-1.
NOTE
MANUAL and AUTO modes of operation
are required to perform the following
tests. Refer to Chapter 3.
NOTE
It will be necessary to remove the front
door, top panel and side panels from the
unit to perform the following tests.
5. While the unit is firing, slowly close the
external
6. The unit should shut down and display a
LOW GAS PRESSURE fault message at
approximately 2.6” W.C. The FAULT indicator should also start flashing.
7. Fully open the extern al manual gas shut-off
valve and press the CLEAR button on the
Control Box.
8. The fault message should clear and the
FAULT indicator should go off. The unit
should restart.
9. Upon test completion, close the ball val ve at
the low gas pressure switc h and remove the
manometer. Replace the 1/8“ plug removed
in step 1.
manual gas shut-off valve.
WARNING
ELECTRICAL VOLTAGES IN THIS
SYSTEM INCLUDE 120 AND 24
VOLTS AC. POWER MUST BE REMOVED PRIOR TO PERFORMING
WIRE REMOVAL OR OTHER TEST
PROCEDURES THAT CAN RESULT
IN ELECTRICAL SHOCK.
6.2 LOW GAS PRESSURE FAULT TEST
Refer to Figure 6-1 and ensure that the ball
valve located at the low gas pressure switch is
closed.
1. Remove the 1/8“ plug from the ball valve at
the low gas pressur e s witch sho wn in F igure
6-1.
2. Instal l a 0 – 16“ W.C. manom eter or a W.C.
gauge where the 1/8" plug was removed.
3. Slowly open the ball valve at the low gas
pressure switch.
4. Start the unit in Manual Mode an d adjust t he
firing rate to between 25 and 30%.
Figure 6-1
Low & High Gas Pressure Testing
6.3 HIGH GAS PRESSURE TEST
To simulate a high gas pressure fault, the gas
pressure will be gradually increased using the
adjustment screw on the SSOV regulator. This
adjustment is locate d be hi n d the bras s hex hea d
cap shown in Figure 4-3. Perform the test as
follows:
1. Refer to Figure 6-1 and remove the 1/8“ plug
from the ball valve at the high gas pressur e
switch.
2. Install a 0 – 16” W.C. manometer or W.C.
gauge where the 1/8” plug was removed.
6-1
Page 46
SAFETY DEVICE TESTING
3. Slowly open the ball valve at the high gas
pressure switch.
4. Start the unit in Manua l mode a t a firing rate
between 25 and 30%.
5. Using a flat-tip screwdriver, slowl y increase
the gas pressure by turning the SSOV
regulator adjustment screw clockwise.
6. The unit should shut down and display a
HIGH GAS PRESSURE fault message
when the gas pressure exceeds 4.7” W.C.
The FAULT indicator should also start
flashing.
7. Reduce the gas press ure back to 2.7” W.C.
and replace the hex head cap on th e SSOV
regulator.
8. Press the CLEAR button on the Contro l Box
to clear the fault.
9. The fault message should clear and the
FAULT indicator should go off. The unit
should restart.
8. Open the water shut-off valve in the return
piping to the unit.
9. Open the water supply shut- off valve to the
unit to refill.
10. After the shell is full, press the LOW WATER LEVEL RESET button to reset the
low water cutoff.
11. Press the CLEAR button to reset the
FAULT LED and clear the displayed error
message.
12. Set the ON/OFF switch to the ON position.
The unit is now ready for operation.
6.5 HIGH WATER TEMPERATURE
FAULT TES T
A high water temperature fault is simulated by
adjusting the automatic ov e r- tem per ature switch.
This switch is accessible from the front of the
unit as shown in Figure 6-2.
10. Upon test completion, close the ball valve
and remove the manometer. Replace the
1/8“ plug removed in step 1.
6.4 LOW WATER LEVEL FAU LT TEST
To simulate a low water level fault:
1. Set the ON/OFF switch on the Control Box
to the OFF position.
2. Close the water shut-off val ves in the su pply
and return piping to the unit.
3. Slowly open the drain valve on the rear of
the unit. If necessar y, the unit’s relief v alve
may be opened to aid in draining.
4. Continue draining the unit until a LOW WATER LEVEL fault message is displayed
and the FAULT indicator flashes.
5. Place the unit in the Man ual M ode and ra ise
the firing rate above 30%.
6. Set the ON/OFF switch to the ON position.
The READY light should r emain off and the
unit should not start. If the unit does
shut the unit off imm ediately and refer fault
to qualified service personnel.
start,
1. Start the un it in the normal operating m ode.
Allow the unit to stabilize at its setpoint.
2. Lower the adjustable temperature limit
switch setting to match the displayed
OUTLET TEMPERATURE.
3. Once the adjustable over-temperature
switch setting is approximately at, or just
below, the actual outlet water temperature,
the unit should shut down. The FAULT
indicator should start flashing and a HIGH WATER TEMP SWITCH OPEN fault
message should be d isplayed. It s hould not
be possible to restart the unit.
4. Reset the adjustable temperature limit
switch to its original setting.
5. The unit should start once the adjustable
temperature limit s witch setting is above t he
actual outlet water temperature.
7. Close the drain and pressure relief valve
used in draining the unit.
6-2
Page 47
SAFETY DEVICE TESTING
SEE
DETAIL “A”
RESET BUTTON FOR
MANUAL RESET
TEMPERATURE
LIMIT SWITC H
FRONT VIEW
ADJUSTABLE
TEMPERATURE
LIMIT SWITCH
VFD
6.6.1 REMOTE INTERLOCK
1. Remove the cover from the I/O Box and
locate the REMOTE INTL’K IN terminals.
2. Start the unit in the Manual Mode and set
the firing rate between 25% and 30%.
3. If there is a jumper across the REMOTE
INTL’K IN terminals, rem ove one side of the
jumper. If the interlock is being controlled by
an external device, either open th e interlock
via the external device or disconnect one of
the wires leading to the external device.
4. The unit should shut down and display
INTERLOCK OPEN.
5. Once the interlock connection is
reconnected, the INTERLOCK OPEN
message should autom atically clear and the
unit should restart.
6.6.2 DELAYED INTERLOCK
1. Remove the cover from the I/O Box and
locate the DELAYED INTL’K IN terminals.
2. Start the unit in the Manual Mode at a firing
rate between 25% and 30%.
3. If there is a jumper across the DELAYED
INTL’K IN terminals, rem ove one side of the
jumper. If the interlock is connected to a
proving switch of an external device,
disconnect one of the wires leading to the
proving switch.
MOUNTING
PLATE
DETAIL “A”
Figure 6-2
Temperature Limit Switch Setting
6.6 INTERLOCK TESTS
The unit is equipped with two interlock circuits
called the Remote Interlock and Delayed
Interlock. Term inal connections for thes e circuits
are located in the I/O Box ( F igures 2-9 and 2- 10)
and are labeled REMOTE INTL’K IN and
DELAYED INTL’K IN. These circuits can shut
down the unit in the event that an interlock is
opened. These int erlocks are shipped f rom the
factory jumpered (closed). However, each of
these interlocks m ay be utilized in the field as a
remote stop and start, a n emergency cut-off, or
to prove that a device such as a pump, gas
booster, or louver is operational.
4. The unit should shut down and display a
DELAYED INTERLOCK OPEN fault
message. The FAULT LED should be
flashing.
5. Reconnect the wire or jumper removed in
step 3 to restore the interlock.
6. Press the CLEAR button to reset the fault.
7. The unit should start.
6.7 FLAME FAULT TES TS
Flame faults can occur during ignition or while
the unit is already running. To simulate each of
these fault conditions, proceed as follows:
1. Set the ON/OFF switch to the OFF position.
2. Place the unit in the Manual Mode and set
the firing rate between 25% and 30%.
3. Close the manual gas shutoff valve located
between the Safety Shut-Off Valve (SSOV)
and the Air/Fuel Valve (see Figure 6-3).
6-3
Page 48
SAFETY DEVICE TESTING
4. Set the ON/OFF switch to the ON position to
start the unit.
5. The unit should shut d o wn af ter reac hing t he
Ignition cycle and display FLAME LOSS
DURING IGN.
6. Open the valve previously closed in step 3
and press the CLEAR button.
7. Restart the unit and allow it to prove flame.
8. Once flame is proven, clos e the manual gas
valve located between the SSOV and the
Air/Fuel Valve.
9. The unit should shut down and display
FLAME LOSS DURING RUN.
10. Open the valve previously closed in step 8.
11. Press the CLEAR button. The unit should
restart and fire.
5. Press the CLEAR button. The unit should
restart.
6. Next, check the Blocked Inlet Switch by
closing the Iris Air Damper (Figure 4-4) to
position 8.
7. .The unit should shut down and again
display AIRFLOW FAULT DURING RUN.
8. Return the Iris Air Damper to its previous
setting.
9. Press the CLEAR button. The unit should
restart.
6.9 SSOV PROOF OF CLOSURE SWITCH
The SSOV shown in Figure 6-1 contains the
proof of closure switch. The proof of closure
switch circuit is checked as follows:
1. Set the unit’s ON/OFF switch to the OFF
position.
2. Place the unit in Manual Mode and set the
firing rate between 25% and 30%
Figure 6-3
Manual Gas Shut-Off Valve Location
6.8 AIR FLOW FAULT TESTS
These tests check the operation of the Blower
Proof Switch and Blocked Inlet Switch s hown in
Figure 6-3.
1. Start the unit in the Manual Mode at a firing
rate between 25% and 30%.
2. Once the unit has proved fl ame, rem ove the
memory stick from the Variable Frequency
Drive (VFD) shown in Figure 6-2.
3. Refer to Figure 6-1 and locate the SSOV.
4. Remove the cover from the SSOV by
loosening the screw shown in Figure 6-4. Lift
off the cover to access the terminal wiring
connections.
5. Disconnect wire #148 from the SSOV to
“open” the proof of closure switch circuit.
6. The unit should fault and display SSOV SWITCH OPEN.
7. Replace wire #148 and press the CLEAR
button.
8. Set the ON/OFF switch to ON to start the
unit.
9. Remove the wire again when the unit
reaches the purge cycle and PURGING is
displayed.
10. The unit should shut down and display
SSOV FAULT DURING PURGE.
11. Replace the wire on the SSOV and press
the CLEAR button. The unit should restart.
3. The Blower Proof Switch will open and the
blower should stop. The unit should shut
down and display AIRFLOW FAULT DURING RUN.
4. Replace the memory stick in the VFD.
6-4
Page 49
Figure 6-4
SSOV Actuator Cover Location
6.10 PURGE SWITCH OPEN DURING
PURGE
The Purge Switch (and Ignition Switch) is
located on the Air/Fuel Valve. To check the
switch, proceed as follows:
SAFETY DEVICE TESTING
3. Remove the Air/Fuel Valve cover (Figure
6-5) by rotating the cover counterclockwise
to unlock and lift up to remove.
4. Remove one of the two wires (#169 or # 170)
from the Ignition Switch (Figure 6-6).
5. Initiate a unit start sequence.
6. The unit should begin it’s start sequence
and then shut down and display IGN SWITCH OPEN DURING IGNITION.
7. Replace the wire on the Ig nition Switch and
press the CLEAR button. The unit should
restart.
1. Set the unit’s ON/OFF switch to the OFF
position. Place the un it in manual m ode and
set the fire rate between 25% and 30%.
2. Remove the Air/Fuel V alve cover b y rotating
the cover counterclockwise to unlock it and
then lift up (see Figure 6-5).
3. Remove one of the two wires (#171 or # 172)
from the Purge Switch (Figure 6-6).
4. Initiate a unit start sequence.
5. The unit should begin it’s start sequence,
then shut down and display PRG SWITCH OPEN DURING PURGE.
6. Replace the wire on the Purge Switch and
depress the CLEAR button. The unit s hould
restart.
6.11 IGNITION SWITCH OPEN DURING
IGNITION
The Ignition Switch (and the Purge Switch) is
located on the Air/Fuel Valve. To check the
switch, proceed as follows:
1. Set the unit’s ON/OFF switch to the OFF
position.
Figure 6-5
Air/Fuel Valve Cover Location
2. Place the unit in Manual Mode and set the
firing rate between 25% and 30%.
6-5
Page 50
SAFETY DEVICE TESTING
9
6
1
1
7
2
Figure 6-6
Air/Fuel Valve Purge and Ignition Switch
Locations
6.12 SAFETY PRESSURE RELIEF
VALVE TEST
Test the safety Pressure Relief Valve in
accordance with ASME Boiler and Pressure
Vessel Code, Section VI.
6-6
Page 51
MAINTENANCE
CHAPTER 7 MAINTENANCE
7.1 MAINTENANCE SCHEDULE
The unit requires regular routine maintena nce to
keep up efficiency and reliability. For best
operation and life of the unit, the following
routine maintenance procedures should be
carried out in the tim e periods spec ified in T able
7-1. See Appendix I for a complete CSD-1
inspection check list.
WARNING
TO AVOID PERSONAL INJURY,
PRIOR TO SERV ICING:
• DISCONNECT THE AC SUPPLY BY
TURNING OFF THE SERVICE
SWITCH AND AC SUPPLY CIRCUIT
BREAKER.
• SHUT OFF THE GAS SUPPLY AT
THE MANUAL SHUT-OFF VALVE
PROVIDED WITH THE UNIT
• ALLOW THE UNIT TO COOL TO A
SAFE WATER TEMPERATURE TO
PREVENT BURNING OR SCALDING
7.2 SPARK IGNITER
The spark igniter (part no. GP-122435-S) is
located on the burner plate (s ee Figur e 7-1) . The
igniter may be HOT . Care should be exercised.
It is easier to remove the igniter from the unit
after the unit has cooled to room temperature.
To inspect/replace the Igniter:
5. The igniter is gapped at 1/8-inch. If there is a
substantial erosion of the spark gap or
ground electrode, the igniter should be
replaced. If carbon buil d-up is pres ent, clean
the igniter using fine emery cloth. Repeate d
carbon build-up on the igniter is an
indication that a check of the combustion
settings is required (see Chapter 4 for
combustion calibration.
6. Prior to reinstalling the igniter, a high
temperature anti-seize compound must
be
applied to the igniter threads.
7. Reinstall the ig niter. Do not over tighten the
igniter. A slight snugging up is sufficient.
Reconnect the igniter cable.
8. Reinstall the side and top panels on the unit.
SEE
DETAIL “A”
TOP VIEW
FLAME
DETECTOR
SPARK
IGNITER
BURNER
PLATE
1. Set the ON/OFF switch on the control pa nel,
to the OFF position. Disconnect AC power
from the unit
2. Remove the side and top panels from the
unit.
3. Disconnect the igniter cable from the igniter.
4. Using a 15/16” wrench, unscrew the igniter
from the burner head. Remove the igniter
from the burner shell, by grasping the
contact end of the igniter.
TOP VIEW
Figure 7-1
Spark Igniter and Flame Detector
Location – Top View
STAGED
IGNITION
ASSEMBLY
7-1
Page 52
MAINTENANCE
Table 7-1 - Maintenance Schedule
PARAGRAPH ITEM 6 Mos. 12 Mos. 24 Mos.
7.2
7.3
7.4
7.5
7.6 Burner Inspect 2 hrs.
7.7
* Only performed after initial 6 month period after initial startup.
7.3 FLAME DETECTOR
The flame detector (part no. 66006) is located
on the burner plate (see Figur e 7-1). The flame
detector may be HOT. Allow the unit to cool
sufficiently before removing the flame detector.
1. Set the ON/OFF switch on the con trol pa nel,
to the OFF position. Disconnect AC power
from the unit.
2. Remove the top panels from the unit.
3. Disconnect the flame detector lead wire.
Unscrew the flame detector and remove it.
(See Figure 7-2).
4. Inspect the detector thoroughly. If eroded,
the detector should be replac ed. Otherwise
clean the detector with a fine emery cloth.
5. Reinstall the flame detector and flame
detector gasket, if removed.
6. Reconnect the flame detector lead wire.
7. Reinstall the side and top panels on the unit.
7.4 COMBUSTION CALIBRATION
Combustion settings must be checked at the
intervals shown in Table 1 as part of the
maintenance requirem ents. Refer to Chapter 4
for combustion calibration instructions.
BURNER
PLATE
FLAME
SPARK
IGNITOR
BURNER
DETECTOR
Figure 7-2
Burner Assembly Spark Igniter and
Flame Detector Location
7.5 SAFETY DEVICE TESTING
Systematic and thorough tests of the operating
and safety devices should be performed to
ensure that they are operating as designed.
Certain code requirements, such as ASME
CSD-1, require that t hese tests be perform ed on
a scheduled basis. Test schedules must
conform to local jurisdictions. The results of the
tests should be recorded in a log book. See
Chapter 6-Safety Device Testing Procedures.
7-2
Page 53
7.6 BURNER ASSEMBLY
6
The burner assembl y is located at the top of the
unit. The burner assembly may be HOT. Allow
the unit to cool sufficiently before removing the
burner assembly.
It should be noted that the complete burner
assembly also includes the blower and air/fuel
valve in addition to the B enchm ark 2.0 Low NOx
burner. It can be removed as one complete
assembly.
MAINTENANCE
NOTE
The burner assembly is heavy, weighing
approximately 30 pounds.
9. Remove the burner assembly from burner
flange by pulling straight up.
10. Remove the grounding screw.
11. Remove and replace the burner gaskets.
The following parts will be necessary for
reassembly after inspection :
1. Set the ON/OFF switch on the con trol pa nel,
to the OFF position. Disconnect AC power
from the unit and turn off the gas supply.
2. Remove the side and top panels from the
unit to provide access to the burner
assembly (Figure 7-3).
3. Disconnect the lead wire from the flame
detector. Unscrew and remove the flame
detector.
4. Disconnect the igniter cable from the igniter
contactor. Unscrew and remove the igniter.
5. Remove the two (2) 10-3 2 screws securing
the gas injector to the burner plate. Separate
the gas injector and gask et from the burner
plate.
12. Beginning with the burner assembly
removed in step 9, reinstall all the
components in the reverse order that they
were removed.
13. Make sure to align the staged ignition
assembly, igniter and flame detector holes in
the burner plate with the h eat exchanger top
head.
14. Check to ensure that the ground ing screw is
reinstalled.
SPARK
IGNITER
GAS
INJECTOR
STAGED
IGNITION
ASSEMBLY
FLAME
DETECTOR
3/8-1
NUTS
(8)
BLOWER
BURNER
PLATE
AIR/FUEL
VALVE
6. Disconnect the gas train from the air/fuel
valve flange b y removing the four 1/2” bo lts
and nuts (Figure 7-3).
7. Disconnect the inlet air flex hose from the
air/fuel valve by loosening the hose clamp.
8. Remove the eight (8) 3/8-16 nuts from the
burner flange (Figure 7-3) using a 9/16”
1/2” BOLTS & NUTS
(4 PLACES) CONNECT AIR/
FUEL VALVE TO GAS TRAIN
(NOT SHOWN)
Figure 7-3
Burner Disassembly Diagram
wrench.
7-3
Page 54
7.7 CONDENSATE DRAIN TRAP
The Benchmark 2.0LN Boiler contains a
condensate trap as shown in Figure 2-5. The
trap is located external to t he unit and attached
to the drain pipe fr om the exhaus t m anifold. T his
traps should be inspected and, if necessary,
cleaned to ensure proper operation. To inspect
and clean the trap, proceed as follows:
1. Disconnect the external c ondensate trap by
loosening the hose c lam ps between the trap
and the connecting manifold drain pipe.
2. Remove the connections on the inlet and
outlet sides of the condensate tr ap shown in
Figure 7-4.
3. Loosen the four (4) thumbscrews securing
the cover on the condensate trap. Remove
the cover.
4. Remove the float from the condensate trap.
5. Remove the orifice gasket from the trap.
6. Thoroughly clean the tr ap and gasket. Also
inspect the drain piping for blockage. If the
trap cannot be thoroughly cleaned, replace
the trap.
7. After the above items have bee n inspected
and thoroughly cleaned, replace the orifice
gasket and float in the condensat e trap and
replace the trap cover.
8. Reassemble all piping and hose connections
to the condensate trap inlet and outlet.
Reconnect trap to conn ecting manif old drain
pipe.
7.8 SHUTTING THE BOILER DOWN FOR
AN EXTENDED PERIOD OF TIME
If the boiler is to be taken out of s ervice for an
extended period of tim e (one year or more), the
following instructions must be followed.
1. Set ON/OFF sw itch on the f ront panel to the OFF position to shut down the boiler’s
operating controls.
2. Disconnect AC power from the unit.
3. Close the water supp ly and return valves to
isolate boiler.
4. Close external gas supply valve.
5. Open relief valve to vent water pressure.
7.9 PLACING THE BOILER BACK IN
SERVICE AFTER A PROLONGED
SHUTDOWN
After a prolonged shutdo wn (one year or more),
the following procedures must be followed:
1. Review ins tallation require ments included in
Chapter 2.
2. Inspect all piping and connections to the
unit.
3. Inspect exhaust vent, air duct (if applicable).
4. Perform initial startup per Chapter 4.
5. Perform safety device testing and the
scheduled maintenance procedures per
Chapters 6 and 7 of this manual.
7-4
Figure 7-4
External Condensate Trap
Page 55
TROUBLESHOOTING
Chapter 8- TROUBLESHOOTING GUIDE
8.1 INTRODUCTION
This troubleshooting guide is intended to aid
service/maintenance personnel in isolating the
cause of a fault in a Benchm ark 2.0 Boiler. The
troubleshooting procedures contained her ein are
presented in tabular form on the f ollowing pages.
These tables are comprised of three columns
labeled: Fault Indication, Probable Cause and
Corrective Action. The numbered items in the
Probable Cause and Corrective Ac tion columns
correspond to each other. For example,
Probable Cause No. 1 corresponds to Corrective
Action No. 1, etc.
When a fault occurs in the Benchmark Boiler,
proceed as follows to isolate and correct the
fault:
1. Observe the fault messages displayed in the
Control Box display.
2. Refer to the Fault Indication column in
Troubleshooting Table 8-1 which f ollows and
locate the Fault that best describes the
existing conditions.
3. Proceed to the Probable Cause c olumn and
start with the first item (1) lis ted for the Fault
Indication.
4. Per form the chec ks and procedures listed in
the Corrective Action column for the first
Probable Cause candidate.
5. Continue checking each additional Probable
Cause for the existing fault until the fault is
corrected.
6. Paragraph 8.2 and Table 8-2 contain
additional troubleshooting information which
may apply when no fault message is
displayed.
7. If the fault cannot be corrected using the
information provided in the Troubleshooting
Tables, contact your local AERCO
Representative.
1. Blower stopped running due to thermal
or current overload
2. Blocked Blower inlet or inlet ductwork
3. Blocked Blower proof switch
4. Defective Blower proof switch
5. Defective blocked-air inlet switch
6. Loose temperature transmitter to
VFD’s analog input wire connection
7. Loose temperature sensor to
temperature transmitter wire
connection.
8. Defective temperature transmitter
9. Defective temperature sensor
10. Loose wire connection between the 420 mA signal from I/O box to VFD
analog input
11. Defective I/O box
12. Wrong 4-20 mA output selection on
the control box
13. Defective air-fuel valve potentiometer
14. Missing VFD logic stick
15. Incorrect or missing analog output
from VFD to blower.
1. Check combustion blower for signs of excessive heat or high
current drain that may trip thermal or current overload devices.
2. Inspect the inlet to the combustion blower including any ductwork
leading up to the combustion blower for signs of blockage.
3. Remove the Blower proof switch and inspect for signs of
blockage, clean or replace as necessary.
4. Measure the Blower proof switch for continuity with the
combustion blower running. If there is an erratic resistance
reading or the resistance reading is greater than zero ohms,
replace the switch.
5. Measure the blocked-air inlet switch for continuity with the
combustion blower running. If there is an erratic resistance
reading or the resistance reading is greater than zero ohms,
replace the switch.
6. Check the actual inlet air temperature and measure voltage at
temperature transmitter and VFD analog input. Verify that the
voltage conforms to Table 8-3 for the inlet air temperature.
7. Refer to CORRECTIVE ACTION 7 and verify that the resistance
conforms to Table 8-3.
8. See CORRECTIVE ACTION 7.
9. See CORRECTIVE ACTION 8.
10. Measure amperage at the I/O box output and VFD analog input,
4mA equates to 0% fire rate and 20 mA equates to 100% fire
rate
11. See CORRECTIVE ACTION 11.
12. Check C-More configuration menu, mA OUT – Fire Rate should
be selected
13. Check air fuel valve position at 0%, 50% and 100% fire rates,
the position on the c-more barograph should match the valve
14. Confirm that the logic stick is securely inserted in the VFD
15. Measure DC voltage between VFD terminals B1 and T1 (see
Figure 8-4). Voltage should be between 2.0 and 5.0 VDC.
1. Delayed Interlock Jumper not
installed or removed.
2. Device proving switch hooked to
interlocks is not closed
1. Direct drive signal is not present:
Not yet installed.
Wrong polarity.
Signal defective at source.
Broken or loose wiring.
2. Signal is not isolated (floating).
3. Control Box signal type selection
switches not set for correct signal
type (voltage or current).
1. Burner Ground Screw not installed
or loose.
2. Worn flame detector
3. No spark from Spark Plug
4. Defective Ignition Transformer
5. Defective Ignition/Stepper (IGST)
Board
6. Defective SSOV
7. Closed manual valve in staged
ignition line.
1. Check for a jumper properly installed across the delayed
interlock terminals in the I/O box.
2. If there are 2 external wires on these terminals, check to see if
an end switch for a device such as a pump, louver, etc. is tied
these interlocks. Ensure that the device and or its end switch
are functional. (jumper may be temporarily installed to test
interlock)
1. Check I/O Box to ensure signal is hooked up.
Hook up if not installed.
If installed, check polarity.
Measure signal level.
Check continuity of wiring between source and boiler.
2. Check signal at source to ensure it is isolated.
3. Check DIP switch on PMC board to ensure it is set correctly for
the type of signal being sent. Check control signal type set in
Configuration Menu.
1. Inspect and install/retighten Burner Ground Screw.
2. Remove and inspect the flame detector for signs of wear.
Replace if necessary.
3. Close the internal gas valve in the boiler. Install and arc a spark
ignitor outside the unit.
4. If there is no spark, check for 120VAC at the primary side to the
ignition transformer during the ignition cycle.
5. If 120VAC is not present, the IGST Board in the Control Box
may be defective. Refer fault to qualified service personnel.
6. While externally arcing the spark ignitor, observe the
open/close indicator in the Safety Shut-Off Valve to ensure it is
opening. If the valve does not open, check for 120VAC at the
valves input terminals. If 120VAC is not present, the IGST
board in the Control Box may be defective. Refer fault to
qualified service personnel.
7. Check position of staged ignition manual ball valve (Fig. 8-1)
1. The Heat Demand Relays on the
Ignition/Stepper board failed to
activate when commanded
2. Relay is activated when not in
Demand
1. Incorrect supply gas pressure.
2. Defective SSOV Droop Elimimator.
3. Defective High Gas P ressure Switch
4. Gas pressure snubber not installed.
5. Fluctuating supply gas pressure.
8. When boiler goes to ignition, listen to solenoid valve to ensure it
is opening.
9. Remove and inspect staged ignition piece for blockage.
10. Remove the burner and inspect for any carbon or debris. Clean
and reinstall
1. Remove and inspect the Flame Detector for signs of wear or
cracked ceramic. Replace if necessary.
2. Check combustion calibration. Adjust as necessary.
3. Remove the burner and inspect for any carbon or debris. Clean
and reinstall.
4. Remove blockage in condensate drain.
5. See Table 8-4 for VFD settings and faults.
1. Press CLEAR button and restart the unit. If the f ault persists,
replace Ignition/Stepper (IGST) Board.
2. Defective relay. Replace IGST Board.
1. Check to ensure gas pressure at inlet of SSOV is 2 psig
maximum.
2. If gas supply pressure downstream of SSOV cannot be lowered,
to 2.8” W.C. (see para. 4.3, step 10), the SSOV Droop
Eliminator may be defective.
3. Remove the leads from the high gas pressure switch and
measure continuity across the common and normally closed
terminals with the unit not firing. Replace the switch if it does not
show continuity.
4. See Figure 8-1. Ensure that the gas pressure snubber is
installed at the high gas pressure switch.
5. Measure gas pressure upstream of SSOV and monitor for
sudden changes (see Fig. 8-1).
5. Unit setpoint is greater than Over
Temperature Switch setpoint.
6. Boiler Management System PID or
other settings not correctly setup.
7. No interlock to boiler or BMS to
disable boiler(s) in event that system
pumps have failed.
8. System flow rate changes are
occurring faster than boilers can
respond.
1. See HIGH WATER TEMPERATURE
SWITCH OPEN.
2. Temp HI Limit setting is too low.
1. Communication fault has occurred
between the PMC board and
Ignition/Stepper (IGST) board
1. Test the temperature switch to insure it trips at its actual water
temperature setting.
2. Check PID settings against Menu Default settings in the
Appendix. If the settings have been changed, record the current
readings then reset them to the default values.
3. Using the resistance charts in the Appendix C, Measure the
resistance of Shell sensor and BTU sensor at a known water
temperature.
4. If unit is in Manual Mode switch to Auto Mode.
5. Check setpoint of unit and setpoint of Temperature Switch;
Ensure that the temperature switch is set higher than the unit’s
setpoint.
6. Check the BMS for changes to PID default values, correct as
necessary.
7. If system pump is controlled by Energy Management System
other than BMS or pumps are individually controlled by boiler,
check to see if there are flow switches interlocked to the BMS or
boiler.
8. If the system is a variable flow system, monitor system flow
changes to ensure that the rate of flow change is not faster than
what the boilers can respond to.
1. See HIGH WATER TEMPERATURE SWITCH OPEN.
2. Check Temp HI Limit setting.
1. Press CLEAR button and restart unit. If fault persists, contact
qualified Service Personnel.
1. Air/Fuel Valve not rotating to ignition
position.
2. Defective ignition switch
3. Defective Power Supply Board or
fuse
4. Defective IGST Board
1. Interlock jumper not installed or
removed
2. Energy Management System does
not have boiler enabled.
1. Start the unit. The Air/Fuel Valve should rotate to the purge
(open) position. If the valve does not rotate at all or does not
rotate fully open, check the Air/Fuel Valve calibration. If
calibration is okay, the problem may be in the Air-Fuel Valve or
the Control Box. Refer to qualified service personnel
2. . If the Air/Fuel Valve does rotate to purge, check the ignition
switch for continuity between the N.O. and COM terminals. If the
switch shows continuity when not in contact with the cam replace
the switch.
3. Check to ensure that the switch is wired correctly (correct wire
numbers on the normally open terminals). If the switch is wired
correctly, replace the switch
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF
every second. If not, replace IGST Board
1. Start the unit. The Air/Fuel Valve should rotate to the purge
(open) position, then back to ignition position (towards closed)
during the ignition cycle. If the valve does not rotate back to the
ignition position, check the Air/Fuel Valve calibration. If
calibration is okay, the problem m ay be in the Air/Fuel Valve or
the Control Box. Refer fault to qualified service personnel.
2. If the Air/Fuel Valve does rotate to the ignition position, check the
ignition position switch for continuity between the N.O. and COM
terminals when in contact with the cam.
3. Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
4. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF
every second. If not, replace IGST Board.
1. Check for a jumper properly installed across the interlock
terminals in the I/O box
2. If there are two external wires on these terminals check any
Energy Management system to see if they have the units
disabled (a jumper may be temporarily installed to see if the
interlock circuit is functioning).
3. Check that proving switch for any device hooked to the interlock
interlocks is not closed.
1. Line and Neutral switched in AC
Power Box.
2. Incorrect power supply transformer
wiring.
1. Incorrect supply gas pressure.
2. Defective Low Pressure Gas Switch
1. Insufficient water level in system
2. Defective water level circuitry.
3. Defective water level probe.
1. Boiler not seeing information from
modbus network
1. A/F Valve rotated open to purge and
did not rotate to ignition position
2. Defective or shorted switch.
3. Switch wired incorrectly.
4. Defective Power Supply Board or
fuse
5. Defective IGST Board
circuit is closing and that the device is operational.
1. Check hot and neutral in AC Power Box to ensure they are not
reversed
2. Check transformer wiring, in AC Power Box, against the power
box transformer wiring diagram to ensure it is wired correctly
1. Measure gas pressure upstream of the supply gas regulator with
the unit firing. Ensure it is between 4” W.C. and 2 psig (see para.
2.7.1).
2. Measure gas pressure at the low gas pressure switch. If it is
greater than 2.6” W.C., measure continuity across the switch and
replace if necessary.
1. Check system for sufficient water level.
2. Test water level circuitry using the Control Box front panel LOW
WATER TEST and RESET buttons. Replace water level
circuitry if it does not respond.
3. Check continuity of probe end to the shell, change probe if there
is no continuity.
1. Check network connections. If fault persists, contact qualified
Service Personnel.
1. Start the unit. The Air/Fuel Valve should rotate to the purge
(open) position, then back to ignition position (towards closed)
during the ignition cycle. If the valve does not rotate back to the
ignition position, check the Air/Fuel Valve calibration. If
calibration is okay, the problem m ay be in the Air/Fuel Valve or
the Control Box. Refer fault to qualified service personnel.
2. If the Air/Fuel Valve does rotate to the ignition position, check the
purge switch for continuity between the N.O. and COM terminals.
If the switch shows c ontinuity when not in contact with the cam,
check to ensure that the switch is wired correctly (correct wire
numbers on the normally open terminals).
3. If the switch is wired correctly, replace the switch.
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and ver ify it is blinking ON & OFF
every second. If not, replace IGST Board.
1. Remote setpoint signal not present:
Not yet installed.
Wrong polarity.
Signal defective at source.
Broken or loose wiring.
2. Signal is not isolated (floating) if 4 to
20 mA.
3. Control Box signal type selection
switches not set for correct signal
type (voltage or current).
1. SSOV not fully closed. 1. Check open/close indicator window of Safety Shut-Off Valve
1. If the air-fuel valve does rotate, check the purge switch for
continuity when closing. Replace switch if continuity does not
exist.
2. Measure for 24 VAC f rom each side of the switch to ground. If
24VAC is not present, refer fault to qualified service personnel.
3. Check to ensure that the switch is wired correctly (correct wire
numbers on the normally open terminals).
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and ver ify it is blinking ON & OFF
every second. If not, replace IGST Board.
1. Inspect Outdoor Temperature sensor for loose or broken wiring.
2. Check resistance of sensor to determine if it is within
specification.
3. Ensure that the correct sensor is installed.
1. Check I/O Box to ensure signal is hooked up.
Hook up if not installed.
If installed, check polarity.
Measure signal level.
Check continuity of wiring between source and boiler.
2. Check signal at source to ensure it is isolated.
3. Check DIP switch on PMC board to ensure it is set correctly for
the type of signal being sent. Check control signal type set in
Configuration Menu.
(SSOV) and ensure that the SSOV is fully closed. If not fully
closed, replace the valve and or actuator.
Close gas shut-off valve downstream of SSOV. Install a
manometer or gauge in a gas test port between the SSOV and
the gas shut off valve. If a gas pressure reading is observed
replace the SSOV valve and or actuator.
1. SSOV relay failed on board. 1. Press CLEAR button and restart unit. If fault persists, replace
1. Actuator not allowing for full closure
of gas valve
2. SSOV powered when it should not be
3. Defective Switch or Actuator
4. Incorrectly wired switch.
1. Air/Fuel Valve out of calibration.
2. Air/Fuel Valve unplugged.
3. Loose wiring connection to the
stepper motor.
4. Defective Air/Fuel Valve stepper
motor.
5. Defective Power Supply Board or
fuse
6. Defective IGST Board
2. Replace Flame Detector.
1. Replace or adjust microswitch in SSOV actuator. If fault
persists, replace actuator.
Ignition/Stepper (IGST) Board.
1. Observe operation of the Safety Shut-Off Valve (SSOV) through
indicator on the Valve actuator and ensure that the valve is fully
and not partially closing.
2. If the SSOV never closes, it may be powered continuously. Close
the gas supply and remove power from the unit. Refer fault to
qualified service personnel.
3. Remove the electrical cover from the SSOV and check switch
continuity. If the switch does not show continuity with the gas
valve closed, either adjust or replace the switch or actuator.
4. Ensure that the SSOV Proof of Closure switch is correctly wired.
1. Refer to GF-112 and perform Stepper Test (para. 6.3.5) to
ensure stepper motor rotates properly between the 0% (fully
closed) and 100% (fully open) positions. Verify that the FIRE
RATE bargraph and the dial on the Air/Fuel Valve track each
other to indicate proper operation. If operation is not correct,
perform the Stepper Feedback Calibration (GF-112, para. 6.2.1).
2. Check that the Air/Fuel Valve is connected to the Control Box.
3. .Inspect for loose connections between the Air/Fuel Valve motor
and the wiring harness.
4. Replace stepper motor.
5. Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
6. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF
every second. If not, replace IGST Board.
8-10
Page 65
TROUBLESHOOTING
8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES
Refer to Table 8-2 to troubleshoot faults which may occur without a specific fault message being displayed.
TABLE 8-2. BOILER TROUBLESHOOTING WITH NO FAULT MESSAGE DISPLAYED
Fluctuating Gas Pressure 1. Gas pressure going into unit is
fluctuating.
2. Damping Orifice not installed.
Air/Fuel Valve “hunting” at 80%
Firing Rate
1. IGST and Power Supply Boards in
Control Box are outdated.
1. Open the 1/4” Ball Valve downstream of the SSOV (Fig. 8-1).
2. Remove and inspect Gas Injector to ensure it is not clogged or
damaged.
3. Close the 2” and the 1/4” Ball Valve downstream of the SSOV
(Fig. 8-1). Start the unit and listen for a “clicking” sound that the
Staged Ignition Solenoid makes during Ignition Trial. If “clicking”
sound is not heard after 2 or 3 attempts, replace the Staged
Ignition Solenoid.
1. Stabilize gas pressure going into unit. If necessary, troubleshoot
Building Supply Regulator.
2. Check to ensure that the Damping Orifice is installed in the
SSOV Droop Eliminator (Figure 8-3).
1. Check to ensure that the IGST and Power Supply Boards are
Rev. E or higher.
8-11
Page 66
TROUBLESHOOTING
TO AIR/FUEL
VALVE
HIGH GAS
PRESSURE
SWITCH
SSOV
LOW GAS
PRESSURE
SWITCH
MANUAL
SHUT-OFF
GAS
INLET
STAGED
IGNITION LINE
BALL VALVE
Figure 8-1
High Pressure Gas Switch & Snubber Locations
SNUBBER
VALVE
Damping Orifice Location
Figure 8-3
8-12
Figure 8-2
Staged Ignition Solenoid Location
Figure 8-4
VFD Terminal Locations
Page 67
TROUBLESHOOTING
Table 8-3
BMK 2.0 LN (3.3 KΩ) Temperature Sensor and Temperature
5
10 L3
19 Between -70.0 & 100.0
59 1
61 Between -150 & 250
62 Between 200 & 500
63 Between 250 & 600
64 Between 250 & 700
65 Between 400 & 850
71 18.20
72 18.21
73 18.22
74 18.23
75 18.24
• If a parameter value differ s from the one shown in Table 8- 4, reset the param eter to the value
shown in the Table.
• If a parameter value differ s from the one shown in Table 8- 4, reset the param eter to the value
shown in the Table
• If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in Table 8-4, reset the parameter to the value shown in the Table.
AI.AV
• If parameters 61, 62, 63, 64, and 65 are skipped and do not appear, perform the following
procedure:
1. Set Pr. 28 to USA
2. Set Pr. 1 to 0.0
3. Set Pr. 2 to 100.0
4. Set Pr. 10 to L3
5. Set Pr. 19 to 82.0
6. Set Pr. 71 to 18.20
7. Set Pr. 72 to 18.21
8. Set Pr. 73 to 18.22
9. Set Pr. 74 to 18.23
10. Set Pr. 75 to 18.24
11. Set Pr. 61 to 50
12. Set Pr. 62 to 300
13. Set Pr. 63 to 400
14. Set Pr. 64 to 450
15. Set Pr. 65 to 600
8-14
Page 69
TROUBLESHOOTING
16. Shut down VFD power.
17. Turn On VFD power.
18. Set Pr. 59 to 1
19. Recalibrate the boiler using the combustion calibration procedures in Chapter 4.
Table 8-5. VFD Faults
NOTE
Check parameters 55, 56, 57, & 58 for the last 4 Trips.
VFD Fault Possible Cause
U U Low AC supply voltage
OU High AC supply voltage
O.ht2 High ambient temperature
CL1 Analog input loss
(4-20 mA Air/Fuel Valve position signal)
EEF Possible loss of parameters values
C.dAt Empty SmartStick has been read
C.Err Bad connection or faulty SmartStick
C.Acc Bad connection or faulty SmartStick
8-15
Page 70
Page 71
APPENDIX A - BOILER MENU ITEM DESCRIPTIONS
MENU LEVEL & OPTION DESCRIPTION
OPERATING MENU
Active Setpoint This is the setpoint temperature to which the
control is set when operating in the Constant
Setpoint, Remote Setpoint or Outdoor Reset
Mode. When in the Constant Setpoint Mode, this
value is equal to the Internal Setpoint setting in the
Configuration Menu. When in the Remote
Setpoint Mode, this value is the setpoint equivalent
to the remote analog signal supplied to the unit.
When in the Outdoor Reset Mode, this is the
derived value from the charts in Appendix D.
Aux Temp For monitoring purposes only
APPENDIX A
Outdoor Temp Displayed only if outdoor sensor is installed and
enabled.
Fire Rate In Desired input fire rate. This would normally be the
same as the fire rate shown on the bar-graph (fire
rate out) when the boiler is operating.
Flame Strength Displays flame strength from 0% to 100%.
Run Cycles Displays the total number of run cycles from 0 to
999,999.
Run Hours Displays total run time of unit in hours from 0 to
9,999,999.
Fault Log Displays information on the last 9 faults.
A-1
Page 72
APPENDIX A
APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
SETUP MENU
Password Allows password to be entered.
Once the valid password (159) is entered, options in
the Setup, Configuration and Tuning Menus can be
modified.
Language Permits selection of English, Spanish or French for
displayed messages. Default is English.
Time Displays time from 12:00 am to 11:59 pm.
Date Displays dates from 01/01/00 to 12/31/99
Unit of Temp Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). Default is
°F.
Comm Address For RS-485 communications (0 to 127). Default
address is 0. RS-232 should have its own
(programmable) password.
Baud Rate Allows communications Baud Rate to be set (2400
to 19.2K). Default is 9600.
Software Version Identifies the current software version of the control
box (Ver 0.0 to Ver 9.9).
CONFIGURATION MENU
Internal Setpoint Allows internal setpoint to be set . Default is 130°F.
Unit Type Allows selection of Boiler or Water Heater.
Unit Size Sets unit size from 0.5 to 3.0 MBTUs. Default is 1.0
MBTU.
Boiler Mode It allows selection of: Constant Setpoint, Remote
Setpoint, Direct Drive, Combination, or Outdoor
Reset Mode. Default is Constant Setpoint Mode.
Remote Signal Used to set the type of external signal which will be
used when operating in the Remote Setpoint, Direct
Drive or Combination Mode. The factory default is
4-20 mA/1-5V.
Bldg Ref Temp
Allows the building reference temperature to be set
when operating a boiler in the Outdoor Reset Mode.
Default is 70°F.
A-2
Page 73
APPENDIX A
APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
Reset Ratio Permits setting of Reset Ratio when operating boiler
in the Outdoor Reset Mode. Reset Ratio is
adjustable from 0.1 to 9.9. Default is 1.2.
Outdoor Sensor Allows outdoor sensor function to be enabled or
disabled. Default is disabled.
System Start Tmp If outdoor sensor is enabled, this menu item allows
the system start temperature to be set from 30 to
100°F. Default is 60°F.
Setpoint Lo Limit Used to set the minimum allowable setpoint (40°F to
Setpoint Hi Limit). Default is 60°F
Setpoint Hi Limit Used to set the maximum allowable setpoint
(Setpoint Lo Limit to 240°F). Default is 200°F.
Temp Hi Limit This is the maximum allowable outlet temperature
(40 to 240°F). Any temperature above this setting
will turn off the unit. The temperature must then drop
5° below this setting to allow the unit to run. Default
Hi Limit is 210°F.
Max Fire Rate Sets the maximum allowable fire rate for the unit
(40% to 100%). Default is 100%.
Pump Delay Timer Specifies the amount of time (0 to 30 min.) to keep
the pump running after the unit turns off. Default is
zero.
Aux Start On Dly Specifies the amount of time to wait (0 to 120 sec.)
between activating the Aux Relay (due to a demand)
and checking the pre-purge string to start the boiler.
Default is 0 sec.
Failsafe Mode Allows the Failsafe mode to be set to either
Constant Setpoint or Shutdown. Default is
Shutdown.
mA Output Must be set to Fire Rate Out for Benchmark 3.0LN.
Lo Fire Timer Specifies how long (2 to 600 sec.) to remain in the
low fire position after ignition, before going to the
desired output. Default is 2 sec.
A-3
Page 74
APPENDIX A
APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
TUNING MENU
Prop Band Generates a fire rate based on the error that exists
between the setpoint temperature and the actual
outlet temperature. If the actual error is less than
the proportional band setting (1 to 120°F), the fire
rate will be less than 100%. If the error is equal to
or greater than the proportional band setting, the fire
rate will be 100%.
Integral Gain This sets the fraction of the output, due to setpoint
error, to add or subtract from the output each minute
to move towards the setpoint. Gain is adjustable
from 0.00 to 1.00 (Default is 0.10).
Derivative Time This value (0.0 to 20.0 min.) responds to the rate of
change of the setpoint error. This is the time that
this action advances the output.
Reset Defaults? Allows Tuning Menu options to be reset to their
Factory Default values.
A-4
Page 75
APPENDIX B - STARTUP, STATUS AND FAULT MESSAGES
MESSAGE DESCRIPTION
DISABLED
HH:MM pm MM/DD/YY
STANDBY Displayed when ON/OFF switch is in the ON position, but
DEMAND DELAY
XX sec
PURGING
XX sec
IGNITION TRIAL
XX sec
FLAME PROVEN
WARMUP
XX sec
WAIT Prompts the operator to wait.
APPENDIX B
TABLE B-1. STARTUP AND STATUS MESSAGES
Displayed if ON/OFF switch is set to OFF. The display also
shows the time and date that the unit was disabled.
there is no demand for heat. The time and date are also
displayed.
Displayed if Demand Delay is active.
Displayed during the purge cycle during startup. The
duration of the purge cycle counts up in seconds.
Displayed during ignition trial of startup sequence. The
duration of cycle counts up in seconds.
Displayed after flame has been detected for a period of 2
seconds. Initially, the flame strength is shown in %. After 5
seconds has elapsed, the time and date are shown in place
of flame strength.
Displayed for 2 minutes during the initial warmup only.
B-1
Page 76
APPENDIX B
FAULT MESSAGE FAULT DESCRIPTION
HIGH WATER TEMP
SWITCH OPEN
LOW WATER
LEVEL
LOW GAS
PRESSURE
HIGH GAS
PRESSURE
INTERLOCK
OPEN
DELAYED
INTERLOCK OPEN
AIRFLOW FAULT
DURING PURGE
PRG SWTCH OPEN
DURING PURGE
IGN SWTCH OPEN
DURING IGNITION
IGN SWTCH CLOSED
DURING PURGE
PRG SWTCH CLOSED
DURING IGNITION
AIRFLOW FAULT
DURING IGN
AIRFLOW FAULT
DURING RUN
SSOV
SWITCH OPEN
SSOV FAULT
DURING PURGE
SSOV FAULT
DURING IGN
SSOV FAULT
DURING RUN
SSOV RELAY
FAILURE
FLAME LOSS
DURING IGN
FLAME LOSS
DURING RUN
HIGH EXHAUST
TEMPERATURE
LOSS OF POWER
TABLE B-2. FAULT MESSAGES
The High Water Temperature Limit Switch is open.
The Water Level Control board is indicating low water level.
The Low Gas Pressure Limit Switch is open.
The High Gas Pressure Limit Switch is open.
The Remote Interlock is open.
The Delayed Interlock is open.
The Blower Proof Switch opened during purge,
or air inlet is blocked.
The Purge Position Limit switch on the air/fuel valve opened
during purge.
The Ignition Position Limit switch on the air/fuel valve opened
during ignition.
The Ignition Position Limit switch on the air/fuel valve closed
during purge.
The Purge Position Limit switch on the air/fuel valve closed
during ignition.
The Blower Proof Switch opened during ignition.
The Blower Proof Switch opened during run.
The SSOV switch opened during standby.
The SSOV switch opened during purge.
The SSOV switch closed or failed to open during ignition.
The SSOV switch closed for more than 15 seconds during
run.
A failure has been detected in one of the relays that control
the SSOV.
The Flame signal was not seen during ignition or lost within 5
seconds after ignition.
The Flame signal was lost during run.
The High Exhaust Temperature Limit Switch is closed.
A power loss had occurred. The time and date when power
was restored is displayed.
B-2
Page 77
APPENDIX B
TABLE B-2. FAULT MESSAGES - Continued
FAULT MESSAGE FAULT DESCRIPTION
RESIDUAL
FLAME
HEAT DEMAND
FAILURE
IGN BOARD
COMM FAULT
DIRECT DRIVE
SIGNAL FAULT
REMOTE SETPT
SIGNAL FAULT
OUTDOOR TEMP
SENSOR FAULT
OUTLET TEMP
SENSOR FAULT
FFWD TEMP
SENSOR FAULT
HIGH WATER
TEMPERATURE
LINE VOLTAGE
OUT OF PHASE
STEPPER MOTOR
FAILURE
NETWORK COMM
FAULT
The Flame signal was seen for more than 60 seconds during
standby.
The Heat Demand Relays on the Ignition board failed to
activate when commanded.
A communication fault has occurred between the CPU board
and Ignition board.
The direct drive signal is not present or is out of range.
The remote setpoint signal is not present or is out of range.
The temperature measured by the Outdoor Air Sensor is out
of range.
The temperature measured by the Outlet Sensor is out of
range.
The temperature measured by the FFWD Sensor is out of
range.
The temperature measured by the Outlet Sensor exceeded
the Temp Hi Limit setting.
The High AC voltage is out of phase from the low AC voltage.
The stepper motor failed to move the valve to the desired
position.
The RS-485 network information is not present or is
corrupted.