AERCO BMK 2.0 LN Dual Fuel Serial G-11-2402 and UP User Manual

Page 1
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
USER MANUAL
Revised: 04/22/2013
Benchmark 2.0LN Low NOx Boiler
Installation, Operation, and Maintenance
Benchmark
Modulating, Condensing, Forced Draft, Hot Water Boiler 2,000,000 BTU/H Input
Applicable for Serial N umb er s: G-11-2402 and above.
2.0LN Dual-Fuel
Low NOx Boiler
PR2: 04/22/13 Page 1 of 160
Page 2
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
Technical Support:
1-800-526-0288
www.aerco.com
(Mon–Fri, 8am-5pm EST)
Disclaimer
The information containe d in this manual is subject to c hange without notice from AERCO Inter national, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness f or a particular application. AE RCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
Page 2 of 160 PR2: 04/22/13
Page 3
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Table of Contents
CHAPTER 1: SAFETY PRECAUTIONS .................................................................................. 9
1.1 WARNINGS & CAUTIONS .................................................................................... 9
1.2 EMERGENCY SHUTDOWN ............................................................................... 10
1.3 PROLONGED SHUTDOWN ................................................................................ 10
CHAPTER 2: INSTALLATION .............................................................................................. 11
2.1 INTRODUCTION ................................................................................................. 11
2.2 RECEIVING THE UNIT ....................................................................................... 11
2.3 UNPACKING ....................................................................................................... 11
2.4 SITE PREPARATION .......................................................................................... 11
Installation Clearances ............................................................................................. 12 2.4.1
Setting the Unit ........................................................................................................ 12 2.4.2
2.5 SUPPLY AND RETURN PIPING ......................................................................... 13
2.6 CONDENSATE DRAIN AND PIPING .................................................................. 14
Exhaust Manifold Condensate Drain ....................................................................... 15 2.6.1
2.7 GAS SUPPLY PIPING ......................................................................................... 16
Gas Supply Specifications. ...................................................................................... 17 2.7.1
Manual Gas Shutoff Valve....................................................................................... 17 2.7.2
IRI Gas Train Kit ..................................................................................................... 17 2.7.3
2.8 AC ELECTRICAL POWER WIRING .................................................................... 18
Electrical Power Requirements ................................................................................ 18 2.8.1
2.9 MODES OF OPERATION AND FIELD CONTROL WIRING ............................... 19
Constant Setpoint Mode ........................................................................................... 19 2.9.1
Indoor/Outdoor Reset Mode .................................................................................... 20 2.9.2
Boiler Management System Mode........................................................................... 20
Remote Setpoint and Direct Drive Modes ............................................................... 20
Combination Mode .................................................................................................. 20 2.9.5
2.10 I/O BOX CONNECTIONS .................................................................................. 21
Outdoor Sensor In (1) .......................................................................................... 21 2.10.1
Air Temp. Sensor (2) ........................................................................................... 22 2.10.2
Analog In (3) ........................................................................................................ 22 2.10.3
2.9.3
2.9.4
B.M.S. (PWM) In (4) .......................................................................................... 22 2.10.4
Shield (5).............................................................................................................. 23 2.10.5
mA Out (6) ........................................................................................................... 23 2.10.6
RS-485 Comm (7) ................................................................................................ 23 2.10.7
TxD, RxD (8) ....................................................................................................... 23 2.10.8
VFD/Blower (9)................................................................................................... 23 2.10.9
Exhaust Switch In (11) ...................................................................................... 23 2.10.10
PR2: 04/22/13 Page 3 of 160
Page 4
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
Interlocks (10, 12) ........................................................................................... 23 2.10.11
Fault Relay (13).................................................................................................. 24 2.10.12
Auxiliary Relay Contacts (14) ........................................................................... 24 2.10.13
2.11 FLUE GAS VENT INSTALLATION .................................................................... 24
2.12 COMBUSTION AIR ........................................................................................... 24
Combustion Air From Outside the Building .......................................................... 25 2.12.1
Combustion Air From Inside The Building ........................................................... 25 2.12.2
Sealed Combustion ................................................................................................ 25 2.12.3
Temporary Combustion Air Filtering During Construction .................................. 25 2.12.4
2.13 BENCHMARK PUMP RELAY OPTION ............................................................. 25
CHAPTER 3: CONTROL PANEL OPERATION ................................................................. 27
3.1 INTRODUCTION ................................................................................................. 27
3.2 CONTROL PANEL DESCRIPTION ..................................................................... 27
3.3 CONTROL PANEL MENUS ................................................................................ 31
Menu Processing Procedure ..................................................................................... 31 3.3.1
3.4 OPERATING MENU ............................................................................................ 32
3.5 SETUP MENU ..................................................................................................... 33
3.6 CONFIGURATION MENU ................................................................................... 34
3.7 TUNING MENU ................................................................................................... 35
3.8 COMBUSTION CAL MENU ................................................................................. 35
3.9 START SEQUENCE ............................................................................................ 36
3.10 START/STOP LEVELS ...................................................................................... 39
CHAPTER 4: INITIAL START-UP ........................................................................................ 41
4.1 INITIAL START-UP REQUIREMENTS ................................................................ 41
4.2 TOOLS AND INSTRUMENTATION FOR COMBUSTION CALIBRATION .......... 41
Required Tools & Instrumentation .......................................................................... 42 4.2.1
Installing Gas Supply Manometer ........................................................................... 42
Accessing the Analyzer Probe Port.......................................................................... 43 4.2.3
4.3 NATURAL GAS COMBUSTION CALIBRATION ................................................. 44
4.4 PROPANE COMBUSTION CALI BRATION ......................................................... 49
4.5 UNIT REASSEMBLY ........................................................................................... 53
4.6 OVER-TEMPERATURE LIMIT SWITCHES ........................................................ 53
4.2.2
Digital Alarm Switch Checks and Adjustments ...................................................... 54 4.6.1
CHAPTER 5: MODE OF OPERATION ................................................................................ 56
5.1 INTRODUCTION ................................................................................................. 56
5.2 INDOOR/OUTDOOR RESET MODE .................................................................. 56
Reset Ratio ............................................................................................................... 56 5.2.1
Building Reference Temperature ............................................................................. 56 5.2.2
Outdoor Air Temperature Sensor Installation .......................................................... 56 5.2.3
Indoor/ Outdoor Startup ........................................................................................... 56 5.2.4
Page 4 of 160 PR2: 04/22/13
Page 5
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
5.3 CONSTANT SETPOINT MODE .......................................................................... 57
Setting the Setpoint .................................................................................................. 57 5.3.1
5.4 REMOTE SETPOINT MOD ES ............................................................................ 58
Remote Setpoint Field Wiring ................................................................................. 58 5.4.1
Remote Setpoint Startup .......................................................................................... 59 5.4.2
5.5 DIRECT DRIVE MODES ..................................................................................... 59
Direct Drive Field Wiring ........................................................................................ 60 5.5.1
Direct Drive Startup ................................................................................................. 60 5.5.2
5.6 BOILER MANAGEMENT SYSTEM (BMS) .......................................................... 60
BMS External Field Wiring ..................................................................................... 60 5.6.1
BMS Setup and Startup ............................................................................................ 61 5.6.2
5.7 COMBINATION CONTROL SYSTEM (CCS) ...................................................... 61
Combination Control System Field Wiring ............................................................. 61 5.7.1
Combination Control System Setup and Startup ..................................................... 62 5.7.2
CHAPTER 6: SAFETY DEVICE TESTING ......................................................................... 63
6.1 TESTING OF SAFETY DEVICES........................................................................ 63
6.2 NATURAL GAS LOW GAS PRESSURE FAULT TEST ....................................... 63
6.3 PROPANE LOW GAS PRESSURE FAULT TEST .............................................. 64
6.4 NATURAL GAS HIGH GAS PRESSURE TEST .................................................. 65
6.5 PROPANE HIGH GAS PRESSURE TEST .......................................................... 65
6.6 LOW WATER LEVEL FAULT TES T .................................................................... 66
6.7 WATER TEMPERATURE FAULT TEST ............................................................. 66
6.8 INTERLOCK TESTS............................................................................................ 67
REMOTE INTERLOCK ......................................................................................... 67 6.8.1
DELAYED INTERLOCK ....................................................................................... 68 6.8.2
6.9 FLAME FAULT TESTS ........................................................................................ 68
6.10 AIR FLOW FAULT TESTS ................................................................................ 69
6.11 SSOV PROOF OF CLOSURE SWITCH ............................................................ 70
6.12 IGNITION SWITCH OPEN DURING IGNITION ................................................ 71
6.13 PURGE SWITCH OPEN DURING PURGE ....................................................... 71
6.14 SAFETY PRESSURE RELIEF VALVE TEST .................................................... 72
CHAPTER 7: MAINTENANCE .............................................................................................. 73
7.1 MAINTENANCE SCHEDULE .............................................................................. 73
7.2 IGNITER-INJECTOR ........................................................................................... 74
7.3 FLAME DETECTOR ............................................................................................ 76
7.4 COMBUSTION CALIBRATION ........................................................................... 77
7.5 SAFETY DEVICE TESTING ................................................................................ 77
7.6 BURNER ASSEMBLY INSPECTION .................................................................. 77
7.7 CONDENSATE DRAIN TRAP ............................................................................. 80
PR2: 04/22/13 Page 5 of 160
Page 6
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
7.8 SHUTTING THE BOILER DOWN FOR AN EXTENDED P ERIOD OF TIME ....... 81
7.9 PLACING THE BOILER BACK IN SERVICE AFTER A PROLONGED
SHUTDOWN ............................................................................................................. 81
CHAPTER 8: TROUBLESHOOTING GUIDE ..................................................................... 83
8.1 INTRODUCTION .............................................................................................. 83
8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES ................ 93
CHAPTER 9: RS232 COMMUNICATION ............................................................................ 97
9.1 INTRODUCTION ................................................................................................. 97
Aquiring the PuTTY Application ............................................................................ 97 9.1.1
Logging on to a Remote Machine Using PuTTY .................................................... 97 9.1.2
Running a Command on a Remote Machine Using PuTTY.................................... 98 9.1.3
9.2 RS232 COMMUNICATION SETUP ..................................................................... 99
9.3 MENU PROCESSING UTILIZING RS232 COMMUNICATION ........................... 99
9.4 DATA LOGGING ............................................................................................... 100
Fault Log ................................................................................................................ 100 9.4.1
Operation Time Log ............................................................................................... 100
Sensor Log ............................................................................................................. 101
APPENDIX A: MENU ITEM DESCRIPTIONS ................................................................ 103
APPENDIX B: STARTUP, STATUS AND FAULT MESSAGES ..................................... 109
APPENDIX C: SENSOR TEMPERATURE RESISTANCE ............................................. 113
APPENDIX D: INDOOR/OUTDOOR RESET RATIO CHARTS................................... 115
APPENDIX E: BOILER DEFAULT SETTINGS .............................................................. 119
APPENDIX F: PART AND DIMENSIONAL DRAWINGS .............................................. 121
APPENDIX G: PIPING DRAWINGS ................................................................................. 137
APPENDIX H: WIRING SCHEMATICS........................................................................... 143
APPENDIX I: RECOMMENDED PERIODIC TESTING CHECK LIST ....................... 149
APPENDIX J: BENCHMARK CONTROL PANEL FEATURES..................................... 151
APPENDIX K: BMK 2.0 DUAL-FUEL SWITCHOVER INSTRUCTIONS .................... 153
SWITCHOVER FROM NATURAL GAS TO PROP ANE .......................................... 153
SWITCHOVER FROM PROPANE TO NATURA L GAS .......................................... 156
APPENDIX L: RECOMMENDED SPARE PARTS LISTS .............................................. 157
STANDARD WARRANTY: Benchmark Gas-Fired Hydronic Boiler .............................. 159
9.4.2
9.4.3
Page 6 of 160 PR2: 04/22/13
Page 7
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Foreword
The AERCO Benchmark 2.0LN Dual-Fuel Low NOx (LN) Boiler is a modulating unit. It represents a true industry advance that meets the needs of today's energy and environmental concerns. Designed for application in any closed loop hydronic system, the Benchmark's modulating capability relates energy input directly to fluctuating system loads. The Benchmark
2.0LN, with its 20:1 turn down ratio and condensing capability, provides extremely high efficiencies and makes it ideally suited for modern low temperature, as well as, conventional heating systems.
The boiler operates at inputs ranging from 100,000 BTU/hr. to 2,000,000 BTU/hr. The output of the boiler is a function of the unit’s firing rate and return water temperature. Output ranges from 99,000 BTU/hr. to 1,933,000 BTU/hr., depending on operating conditions.
When installed and operated on natural gas in accordance with this Instruction Manual, the Benchmark 2.0LN Boiler complies with the NOx emission standards outlined in:
South Coast Air Quality Management District (SCAQMD), Rule 1146.2
Whether used in singular or modular arrangements, the Benchmark 2.0LN offers the maximum flexibility in venting with minimum installation space requirements. The Benchmark's advanced electronics are available in several selectable modes of operation offering the most efficient operating methods and energy management system integration.
For service or parts, contact your local sales representative or AERCO INTERNATIONAL.
NAME: ORGANIZATION: ADDRESS: TELEPHONE: INSTALLATION DATE: _____________________________________________
PR2: 04/22/13 Page 7 of 160
Page 8
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
(This page left intentionally blank)
Page 8 of 160 PR2: 04/22/13
Page 9
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 1: SAFETY PRECAUTIONS

CHAPTER 1: SAFETY PRECAUTIONS

1.1 WARNINGS & CAUTIONS

Installers and operating personnel MUST, at all times, observe all safety regulations. The following warnings and cautions are general and must be given the same attention as specific precautions included in these instructions. In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54). Where ASME CSD-1 is required by local jurisdiction, the installation must conform to CSD-1. Where applicable, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CSA B149.1, and applicable Provincial regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
IMPORTANT
This Instruction Manual is an integral part of the product and must be maintained in legible condition. It must be given to the user by the installer and kept in a safe place for future reference.
WARNING
WARNINGS MUST BE OBSERVED TO PREVENT SERIOUS INJURY.
WARNING
BEFORE ATTEMPTING TO PER-FORM ANY MAINTENANCE ON THE UNIT, SHUT OFF ALL GAS AND ELECTRICAL INPUTS TO THE UNIT.
WARNING
THE EXHAUST VENT PIPE OF THE UNIT OPERATES UNDER A POSITIVE PRESSURE AND THERE-FORE MUST BE COMPLETELY SEALED TO PREVENT LEAKAGE OF COMBUSTION PRODUCTS INTO LIVING SPACES.
WARNING
A DOUBLE-POLE SWITCH MUST BE INSTALLED ON THE ELECTRICAL SUPPLY LINE OF THE UNIT. THE SWIT CH MUST BE INSTALLED IN AN EASILY ACCESSIBLE POSITION TO QUICKLY AND SAFELY DISCONNECT ELECTRICAL SERVICE. DO NOT AFFIX SWITCH TO UNIT SHEET METAL ENCLOSURES.
WARNING
DO NOT USE MATCHES, CANDLES, FLAMES, OR OTHER SOURCES OF IGNITION TO CHECK FO R GAS LEAKS.
WARNING
FLUIDS UNDER PRESSURE MAY CAUSE INJURY TO PERSONNEL OR DAMAGE TO EQUIPMENT WHEN RELEASED. BE SURE TO SHUT OFF ALL INCOMING AND OUTGOING WATER SHUTOFF VALVES. CAREFULLY DECREASE ALL TRAPPED PRESSURES TO ZERO BEFORE PERFORMING MAINTENANCE.
PR2: 04/22/13 Page 9 of 160
Page 10
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
MANUAL GAS SHUTOFF VALVE
VALVE OPEN
VALVE CLOSED
CHAPTER 1: SAFETY PRECAUTIONS
electrical voltages up to 120 vac may be used in this equipment. Therefore the cover on the unit’s power box (located behind the front panel door) must be installed at all times, except during maintenance and servicing.
Must be observed to prevent equipment damage or loss of operating effectiveness.
WARNING
CAUTIONS
CAUTION
Many soaps used for gas pipe leak testing are corrosive to metals. The piping must be rinsed thoroughly with clean water after leak checks have been completed.
CAUTION!
DO NOT use this boiler if any part has been under water. Call a qualified service technician to inspect and replace any part that has been under water.

1.2 EMERGENCY SHUTDOWN

If overheating occurs or the gas suppl y fails to shut off, c lose the manual gas shutoff valve (Figure 1-1) located external to the unit.
IMPORTANT
The Installer must identify and indicate the location of the emergency shutdown manual gas valve to operating personnel.

1.3 PROLONGED SHUTDOWN

After prolonged shutdo wn, it is recommended that the startup procedures in Chapt er 4 and the safet y device test procedures in Chapter 6 of this manual be performed, to verify all system-operating parameters. If there is an em ergenc y, turn off the ele ctrical power supply to the AERCO boi ler and close the manual gas valve located upstream the unit. The installer must identify the emergency shut-off device.
Figure 1-1: Manual Gas Shutoff Valve
Page 10 of 160 PR2: 04/22/13
Page 11
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 2: INSTALLATION

CHAPTER 2: INSTALLATION

2.1 INTRODUCTION

This Chapter provides the descriptions and procedures necessary to unpack, inspect and install the AERCO Benchmark 2.0LN Dual-Fuel Boiler. Brief descriptions are also provided for each available mode of operation. Detailed procedures for implementing these modes are provided in Chapter 5.

2.2 RECEIVING THE UNIT

Each Benchmark 2.0LN System is shipped as a single crated unit. The shipping weight is approximately 1600 pounds. The unit must be moved with the proper rigging equipment for safety and to avoid equipment damage. The unit should be completely inspected for evidence of shipping damage and shipment completeness at the time of receipt fr om the carrier and before the bill of lading is signed.
NOTE
AERCO is not responsible for lost or damaged freight.
Each unit has a Tip-N-Tell indicator on the outside of the crate. This indicates if the unit has been turned on its side during shipment. If the Tip-N-Tell indicator is tripped, do not sign for the shipment. Note the information on the carrier’s paperwork and request a freight claim and inspection by a claims adjuster before proceeding. Any other visual damag e to the packaging materials should also be made clear to the delivering carrier.

2.3 UNPACKING

Carefully unpack the unit taking care not to damage the unit enclosure when cutting away packaging materials
A close inspection of the unit should be made to ensure that there is no evidence of damage not indicated by the Tip-N-Tell indicator. The freight carrier should be notified immediately if any damage is detected.
IMPORTANT
After unpacking, take off the unit top panel and remove the strap and packing material at the top of the heat exchanger. The packing material is located in the area of the igniter-injector and staged ignition solenoid on the burner assembly.
The following accessories come standard with each unit and are either packed separately within the unit’s packing container or are factory installed on the boiler:
Pressure/Temperature Gauge
ASME Pressure Relief Valve
Condensate Drain Trap
2” Gas Supply Shutoff Valve
When ordered, optional accessories may be packed separately, packed within the boiler shipping container, or may be installed on the boiler. Any standard or optional accessories shipped loose should be identified and stored in a safe place until ready for installation or use.

2.4 SITE PREPARATION

Ensure that the site selected for installation of the Benchmark 2.0LN Boiler includes:
PR2: 04/22/13 Page 11 of 160
Page 12
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
44.5"
18"
79"
101"
4" HIGH PAD
24"
24"
30"
24"
REAR
FRONT
CHAPTER 2: INSTALLATION
Access to AC Input Power at 120 VAC, Single-Phase, 60 Hz @ 20 Amps
Access to Natural Gas line at a minimum supply gas pressure of 8.5" W.C.
Access to Propane line at a minimum supply gas pressure of 8.5” W .C.

Installation Clearances 2.4.1

The unit must be installed with the prescribed clearances for service as shown in Figure 2-1. The minimum clearance dimensions, required by AERCO, are listed below. However, if Local Building Codes require additional clearances, these codes shall supersede AERCO’s requirements. Minimum acceptable clearances required are:
Sides: 24 inches
Front : 24 inches
Rear: 30 inches
Top: 18 inches
All gas piping, water piping and electrical conduit or cable must be arranged so that t hey do not interfere with the removal of any panels, or inhibit service or maintenance of the unit.
Figure 2-1: Benchmark 2.0LN Boiler Clearances
WARNING
KEEP THE UNIT AREA CLEAR AND FREE FROM ALL COMBUSTIBLE MATERIALS AND FLAMMABLE VAPORS OR LIQUIDS.
While packaged in the shipping container, the boiler must be
CAUTION
moved by pallet jack or forklift from the FRONT ONLY.

Setting the Unit 2.4.2

The unit must be installed on a 4 inch to 6 inch housekeeping pad to ensure proper condensate drainage. If anchoring the unit, refer to the dimensional drawings in Appendix F for anchor
Page 12 of 160 PR2: 04/22/13
Page 13
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
LIFTING
TABS (2)
locations. Two lifting tabs are provided at the top of the heat exchanger. Figure 2-2 shows the location of the tab on the top-left side. The second tab is located on the top-right side of the heat exchanger. USE THESE TWO TABS TO LIFT AND MOVE THE UNIT. Remove the top panel from the unit to provide access to the lifting tabs. Remove the four (4) lag screws securing the unit to the shipping skid. Lift the unit off the shipping skid and position it on the 4 inch to 6 inch housekeeping concrete pad (required) in the desired location.
CHAPTER 2: INSTALLATION
WARNING
WHEN LIFTING OR MOVING THE BOILER:
DO NOT MANIPULATE THE BOILER USING THE GAS TRAIN OR BLOWER
WHEN USING THE LIFTING TABS, ENSURE THERE IS NO LOAD PLACED ON THE GAS TRAIN OR BLOWER
Figure 2-2: Partial Top View Showing Lifting Tab Location
In multiple unit installations, it is important to plan the position of each unit in advance. Sufficient space for piping connections and future service/maintenance requirements must also be taken into consideration. All piping must include ample provisions for expansion.
If installing a Combination Control Panel (CCP) system, it is important to identify the Combination Mode Boilers in advance and place them in the proper physical location. Refer to Chapter 5 for information on Combination Mode Boilers.

2.5 SUPPLY AND RETURN PIPI NG

The Benchmark 2.0LN Boiler utilizes 4” 150# flanges for the water system supply and return piping connections. The physica l location of the suppl y and return piping c onnections are on the r ear of the unit as shown in Figure 2-3. Refer to Appendix F, Drawing AP-A-798 for additional dimensional data.
PR2: 04/22/13 Page 13 of 160
Page 14
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
2" PROPANE INLET CONNECTION
2" NATURAL GAS INLET CONNECTION
BOILER RETURN
EXHAUST
MANIFOLD
BOILER SUPPLY
4" – 150# FLANGE
CONNECTION
SHELL DRAIN VALVE
REAR VIEW
CHAPTER 2: INSTALLAT ION

2.6 CONDENSATE DRAIN AND PIPING

The Benchmark 2.0LN Boiler is designed to condense water vapor from the flue products. Therefore, the installation must have provisions for suitable condensate drainage or collection.
The condensate drain pipe located on the exhaust manifold (Figure 2-4) must be connected to a condensate trap which is packed separately within the unit’s shipping container.
The procedure to install and connect the condensate drain is provided in paragraph 2.6.1.
Figure 2-3: Supply and Return Locations
Page 14 of 160 PR2: 04/22/13
Page 15
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
EXHAUST
MANIFOLD
1/2” NPT
CONDENSATE
DRAIN
CONNECTION
HOUSE-
KEEPING
PAD
BOILER
RETURN
CHAPTER 2: INSTALLATION
Figure 2-4: Condensate Drain Connection Location
2.6.1

Exhaust Manifold Condensate Drain

NOTE
There are two slightly different types of condensate traps that may be used in your configuration; an older style without built-in adapter, and a newer style with a built-in adapter (see Figure 2-5). Installation is the same (1/4” threads are inside built-in adapter on newer style).
A condensate drain trap (part no. 24060) is shipped loose and must be installed at the rear of the unit. The trap inlet and outlet contain tapped 3/4” NPT ports. The actual installation details for the condensate trap will depend on the available clearances, housekeeping pad height/dimensions and other prevailing conditions at the site. However, the following guidelines must be observed to ensure proper condensate trap operation:
The condensate trap inlet (Figure 2-5) must be level with, or lower than the exhaust manifold drain port.
The condensate trap must be supported to ensure that its base is level (horizontal).
The trap must be removable for routine maintenance. AERCO recommends that a union be
utilized between the exhaust manifold condensate drain port and the trap inlet port.
1. While observing the above guidelines, connect the condensate trap inlet to the exhaust
manifold drain connection using the appropriate piping components (nipples, reducers, elbows, etc.) for the boiler installation site.
2. At the condensate trap outlet, install a 3/4” NPT nipple.
3. Connect a length of 1” I.D polypropylene hose to the trap outlet and secure with a hose
clamp.
4. Route the hose on the trap outlet to a nearby floor drain.
If a floor drain is not available, a condensate pump can be used to remove the condensate to drain. The maximum condensate flow rate is 20 GPH. The condensate drain trap, associated fittings and drain line must be removable for routine maintenance.
PR2: 04/22/13 Page 15 of 160
Page 16
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 2: INSTALLATION
Figure 2-5: Condensate Trap Installation: Older (l eft) and Newer (right) Style

2.7 GAS SUPPLY PIPING

The AERCO Benchmark 2.0LN Gas Components and Supply Design Guide, GF-2030 must be consulted prior to designing or installing any gas supply piping.
WARNING
NEVER USE MATCHES, CANDLES, FLAMES OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS.
WARNING
Many soaps used for gas pipe leak testing are corrosive to metals. There-fore, piping must be rinsed thoroughly with clean water after leak checks have been completed.
NOTE
All gas piping must be arranged so that it does not interfere with removal of any covers, inhibit service/maintenance, or restrict access between the unit and walls, or another unit.
Benchmark 2.0LN Dual-Fuel units contain two 2 inch gas inlet connections on the rear of the unit as shown in Figure 2-3.
Prior to installation, all pipes should be de-burred and internally cleared of any scale, metal chips or other foreign particles. Do Not install any flexible connectors or unapproved gas fittings. Piping must be supported from the floor, ceiling or walls only and must not be supported by the unit.
A suitable piping compound, approved for use with natural gas, should be used. Any excess must be wiped off to prevent clogging of components.
To avoid unit damage when pressure testing gas piping, isolate the unit from the gas supply piping. At no time should the gas pressure applied to the unit exceed 14” W.C. Leak test all external piping thoroughly using a soap and water solution or suitable equivalent. The gas piping used must meet all applicable codes.
Page 16 of 160 PR2: 04/22/13
Page 17
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
2" MANUAL
SHUTOFF
VALVES
NATURAL GAS SUPPLY
PROPANE
SUPPLY
DIRT
TRAPS
CHAPTER 2: INSTALLATION

Gas Supply Specifications. 2.7.1

The maximum static pressure to the unit must not exceed 14” W.C. The specifications for natural gas and propane are as follows:
Natural Gas:
The gas supply pressure to the unit must be of sufficient capacity to provide 2000 cfh while maintaining the gas pressure at 4.0" W.C. for FM or 5.0" W.C. for IRI gas trains.
Propane:
The gas supply pressure to the unit must be of sufficient capacity to provide 800 cfh while maintaining the gas pressure at 4.0" W.C. for FM or 5.0" W.C. for IRI gas trains.
The maximum static pressure to the unit must not exceed 14” W.C.. The minimum operating gas pressure for natural gas and propane is 8.5 inches W.C. for both FM and IRI gas trains when the unit is firing at maximum input.

Manual Gas Shutoff Valve 2.7.2

A manual shut-off valve must be installed in the gas supply line upstream of the Boiler as shown in Figure 2-6. Maximum allowable gas pressure to the Boiler is 14” W.C.
Figure 2-6: Manual Gas Shut-Off Valve Location

IRI Gas Train Kit 2.7.3

The IRI gas train is an optional gas train configuration which is required in some areas for code
PR2: 04/22/13 Page 17 of 160
Page 18
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
UPPER RIGHT CORNER OF FRONT PANEL
TERMINAL BLOCK
CHAPTER 2: INSTALLATION
compliance or for insurance purposes. The IRI gas train is factory pre-piped and wired. See Appendix F, Drawing AP-A-843 for details.

2.8 AC ELECTRICAL POWER WIRING

The AERCO Benchmark 2.0LN Electrical Power Wiring Guide, GF-2060LN, must be consulted prior to connecting any AC power wiring to the unit. External AC power connections are made to the unit inside the Power Box on the front panel of the unit. Remove the front door of the unit to access the Power Box mounted directly above the Control Box. Loos en the four Power Box cover screws and remove cover to access the AC terminal connections inside the Power Box (Figure 2-7).
NOTE
All electrical conduit and hardware must be installed so that it does not interfere with the removal of any unit covers, inhibit service/maintenance, or prevent access between the unit and walls or another unit.
Figure 2-7: AC Input Terminal Block Location

Electrical Power Req u irem ent s 2.8.1

The AERCO Benchmark 2.0LN Boiler accepts 120 VAC, single-phase, 60 Hz @ 20A. The Power Box contains a terminal block as shown in Figure 2-8. In addition, a wiring diagram showing the required AC power connections is provided on the front cover of the Power Box.
Each Boiler must be connected to a dedicated electrical circuit. NO OTHER DEVICES SHOULD BE ON THE SAME ELECTRICAL CIRCUIT AS THE BOILER.
A double-pole switch must be installed on the electrical supply line in an easily accessible location to quickly and safely disconnect electrical service. DO NOT attach the switch to sheet metal enclosures of the unit.
After placing the boiler in service, the ignition safety shutoff device must be test ed. If an exter nal electrical power source is used, the installed boiler must be electrically bonded to ground in accordance with the requirements of the authority having jurisdiction. In the absence of such requirements, the installation shall conform to National Electrical Code ( NEC), ANSI/NFPA 70 and/or the Canadian Electrical Code (CEC) Part I, CSA C22.1 Electrical Code.
For electrical power wiring diagrams, see the AERCO Benchmark 2.0LN Electrical Power Wiring Guide, (GF-2060LN).
Page 18 of 160 PR2: 04/22/13
Page 19
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
GND
NEU
L1
120 VAC, 1 PHASE
CHAPTER 2: INSTALLATION
Figure 2-8: AC Terminal Block Configurations

2.9 MODES OF OPERATION AND FIELD CONTROL WIRING

The Benchmark 2.0 Boiler is available in several different modes of operation. W hile each unit is factory configured and wired for its intended mode, some additional field wiring may be required to complete the installation. This wiring is typically connected to the Input/Output (I/O) Box located on the lower portion of the unit front panel (Figure 2-9) behind the removable front door.
To access the I/O Box terminal strips shown in Figur e 2-9, loosen the four cover screws and remove the cover. All field wiring is installed from the rear of the panel by routing the wires through one of the four bushings provided.
Refer to the wiring diagram provided on the cover of the I/O Box when making all wiring connections.
Brief descriptions of each mode of operation, and their wiring requirements, are provided in the following paragraphs. Additional information concerning field wiring is provided in paragraphs
2.10.1 through 2.10.13. Refer to Chapter 5 for detailed information on the available modes of
operation.
Figure 2-9: Input/Output (I/O) Box Location

Constant Setpoint Mode 2.9.1

The Constant Setpoint Mode is used when it is desired to have a fixed setpoint that does not deviate. No wiring connections, other than AC electrical power connections, are required for this mode. However, if desired, fault monitoring or enable/disable interlock wiring can be utilized (see paragraphs 2.10.11.1 and 2.10.11.2).
PR2: 04/22/13 Page 19 of 160
Page 20
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 2: INSTALLATION

Indoor/Outdoor Reset Mode 2.9.2

This mode of oper ation increases supply water temperature as outdoor temperatures decrease. An outside air temperature sensor (AERCO Part No. 122790) is required. T he sensor MUST BE wired to the I/O Box wiring terminals (see Figure 2-10). Refer to paragraph 2.10.1 for additional information on outside air temperature sensor installation.

Boiler Management System Mode 2.9.3

NOTE
BMS Model 168 can utilize either pulse width modulation (PWM) or RS485 Modbus signaling to the Boiler. BMS II Model 5R5-384 and the AERCO Control System (ACS) can utilize only RS485 signaling to the Boiler.
When using an AERCO BMS, BMS II, or ACS (AERCO Control System), the field wiring is connected between the BMS/BMS II/ACS Panel and each Boiler’s I/O Box terminal strip (Figure 2-10). Twisted shielded pair wire from 18 to 22 AWG must be utilized for the connections. The BMS Mode can utilize either pulse width modulation (PWM) signaling, or RS485 Modbus signaling. For PWM signaling, connections are made from the AERCO Boiler Management System to the B.M.S. (PWM) IN terminals on the I/O Box terminal strip. For RS485 Modus signaling, connections are made from the BMS/BMS II/ACS to the RS485 COMM terminals on the I/O Box terminal strip. Polarity must be maintained and the shield must be connected only at the AERCO BMS/BMS II/ACS. The boiler end of the shield must be left floating.
For additional instructions, refer to Chapter 5, paragraph 5.6 in this manual. Also, refer to GF­108M (BMS), GF-124 (BMS II Model 5R5-384), and GF-131 (ACS) operation manuals.

Remote Setpoint and Direct Drive Modes 2.9.4

The boiler can accept several types of signal formats from an Energy Management System (EMS), Building Automation System (BAS) or other source, to control either the setpoint (Remote Setpoint Mode) or air/fuel valve position (Direct Drive Mode) of the Boiler. These formats are:
4 to 20 mA/1 to 5 VDC
0 to 20 mA/0 to 5 VDC
PWM – (Pulse Width Modulated signal. See para. 2.10.4)
Network (RS485 Modbus. See para. 2.10.7)
While it is possible to control a boiler or boilers using one of the previously described modes of operation, it may not be the method best suited for the application. Prior to selecting one of these modes of operation, it is recommended that you consult with your local AERCO representative or the factory for the mode of operation that will work best with your application. For more information on wiring the 4 to 20 mA / 1to 5VDC or t he 0 to 20 mA / 0 to 5 VDC, see paragraph 2.10.3.

Combination Mode 2.9.5

NOTE
Only BMS Model 168 and ACS can be utilized for the Combination Mode, not the BMS II (Model 5R5-384).
With a Combination Mode unit, field wiring is between the unit’s I/O Box wiring terminals, the CCP (Combination Control Panel), and the BMS (Boiler Management System). For ACS applications, the wiring is between the ACS panel, the ACS Relay panel (optional, depending on
Page 20 of 160 PR2: 04/22/13
Page 21
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
applications), and the RS485 comm terminals in the I/O box. The wiring must be accomplished using twisted-shielded pair wire from 18 to 22 AWG. Polarity must be maintained. For further instructions and wiring diagrams, refer to the GF-108 Boiler Management System Operations Guide and the CCP-1 data sheet (BMS 168 applications)/GF-131 and TAG-0050 (ACS applications).
CHAPTER 2: INSTALLATION
Figure 2-10. I/O Box Terminal Locations and Functions

2.10 I/O BOX CONNECTIONS

The types of input and output signals and devices to be connected to the I/O Box terminals shown in Figure 2-10 are described in the following paragraphs.
NOTE
Older I/O PCBs are wired the same as new ones, even if silk­screen designations differ.
NOTE
DO NOT make any connections to the I/O Box terminals labeled “NOT USED”. Attempting to do so may cause equipment damage.
Outdoor Sensor In (1) 2.10.1
An outdoor air temperature sensor (AERCO Part No. 122790) will be req uir ed pr im ar ily for the Indoor/Outdoor reset mode of operation. It can also be used with another mode if it is desired to use the outdoor sensor enable/disable feature. This feature allows the boiler to be enabled or disabled based on the outdoor air temperature.
The factory default for the outdoor sensor is DISABLED. To enable the sensor and/or select an
PR2: 04/22/13 Page 21 of 160
Page 22
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 2: INSTALLATION
enable/disable outdoor temperature, see the Configuration menu in Chapter 3. The outdoor sensor may be wired up to 200 feet from the boiler. It is connected to the
OUTDOOR SENSOR IN and SENSOR COMMON terminals in the I/O Box (see Figures 2-9 and 2-10). Wire the sensor using a twisted shielded pair wire from 18 to 22 AWG. There is no polarity to observe when terminating these wires. The shield is to be connected only to the terminals labeled SHIELD in the I/O Box. The sensor end of the shield must be left free and ungrounded.
When mounting the sensor, it must be located on the North side of the building where an average outside air temperature is expected. The sensor must be shielded from direct sunlight as well as impingement by the elements. If a shield is used, it must allow for free air circulation.
Air Temp. Sensor (2) 2.10.2
The Air Temperature Sensor is connected to the positive (+) and negative (-) term inals of the AIR TEMP. SENSOR on the I/O board. This sensor measures the temperature of the air input to the Air/Fuel Valve. This temperature reading is one of the components used to calculate the rotational speed of the blower used in the combustion Calibration process (Chapter 4).
The AIR TEMP. SENSOR terminals can be used to add an additional temperature sensor for monitoring purposes. This input is always enabled and is a view-onl y input that can be seen in the Operating Menu. The sensor must be wired to the positive (+) and negative (-) terminals of the AIR TEMP. SENSOR and must be similar to AERCO BALCO wire sens or Part No. 12449. A resistance chart for this sensor is provided in Appendix C.
Analog In (3) 2.10.3
The ANALOG IN + and – terminals are used when an external signal is used to drive the air/fuel valve position (Direct Drive Mode) or change the setpoint (Remote Setpoint Mode) of the Boiler.
Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA / 0 to 5 VDC signal may be used to vary the setpoint or valve position. The factory default setting is for 4 to 20 mA / 1 to 5 VDC, however this may be changed to 0 to 20 mA / 0 to 5 VDC using the Configuration Menu described in Chapter
3. If voltage rather than current is selected as the drive signal, a DIP switch must be set on the
PMC Board located inside the Control Box. Contact the AERCO factory for information on setting DIP switches.
All of the supplied signals must be floating (ungrounded) signals. Connections between the signal source and the Boiler’s I/O Box must be made using twisted shielded pair wire fr om 18 to 22 AWG, such as Belden 9841 (see Figure 2-10). Polarity must be maintained. The shield must be connected only at the source end and must be left floating (not connected) at the Boiler’s I/O Box.
Regardless of whether voltage or current is used for the drive signal, they are linearly mapped to a 40°F to 240°F setpoint or a 0% to 100% valve position. No scaling for these signals is provided.
B.M.S. (PWM) In (4) 2.10.4
NOTE
Only BMS Model 168 can utilize Pulse Width Modulation (PWM), not the BMS II or ACS (AERCO Control System).
These terminals are used to connect the AERCO Boiler Management System (BMS) to the unit. The BMS utilizes a 12 millisecond, ON/OFF duty cycle. This duty cycle is Pulse Width Modulated (PWM) to control valve position. A 0% valve position = a 5% ON pulse and a 100% valve position = a 95% ON pulse.
Page 22 of 160 PR2: 04/22/13
Page 23
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 2: INSTALLATION
Shield (5) 2.10.5
The SHIELD terminals are used to terminate any shields used on sensor wires connected to the unit. Only shields must be connected to these terminals.
IMPORTANT
DO NOT USE the mA OUT output to remotely monitor Setpoint, Outlet Temp or Fire Rate Out.
mA Out (6) 2.10.6
These terminals provide a 4 to 20 mA output to the VFD ( if so equipped) to control the rotational speed of the blower. This function is enabled in the Configuration Menu (Chapter 3, Table 3-4).
RS-485 Comm (7) 2.10.7
These terminals are used for RS-485 MODBUS serial communication between the unit and an external “Master” such as a Boiler Management System (BMS), AERCO Cont ro l System (ACS) , Energy Management System (EMS), Building Automation System (BAS) or other suitable device.
TxD, RxD (8) 2.10.8
These terminals provide a parallel connection to the connector on the C -More Controller front panel, for connecting a computer or laptop.
VFD/Blower (9) 2.10.9
These terminals provide a 0 to 10 volt output to control t he rotational speed of the blower. This function is enabled in the Configuration Menu (Chapter 3, Table 3-4).
Exhaust Switch In (11) 2.10.10
These terminals permit an external exhaust switch to be connected to the exhaust manifold of the boiler. The exhaust switch should be a normally open type switch (such as AERCO Part No.
123463) that closes (trips) at 500°F.
Interlocks (10, 12) 2.10.11
The unit offers two interlock circuits for interfacing with Energy Management Systems and auxiliary equipment such as pumps or louvers. These interlocks are called the Remote Interlock and Delayed Interlock (Figure 2-10). The wiring terminals for these interlocks are located inside the I/O Box on the unit front panel. The I/O Box cover contains a wiring diag ram which shows the terminal strip locations for these interlocks (REMOTE INTL’K IN and DELAYED INTL’K I N). Both interlocks, described below, are factory wired in the closed position.
NOTE
Both the Delayed Interlock and Remote Interlock MUST be in the closed position to allow the unit to fire.
Remote Interlock In (10) 2.10.11.1
The remote interlock circuit is provided to remotely start (enable) and stop (disable) t he Boiler, if desired. The circuit is labeled REMOTE INTL’K IN and is located inside the I/O Box on the front panel. The circuit is 24 VAC and is factory pre-wired in the closed (jumpered) position.
Delayed Interlock In
The delayed interlock is typically used in conjunction with the auxiliary relay described in paragraph 2.11. This interlock circuit is located in the purge section of the start string. It can be connected to the proving device (end switch, flow switch etc.) of an auxiliary piece of equipm ent started by the Boiler’s auxiliary relay. The delayed interlock must be closed for the boiler to fire.
PR2: 04/22/13 Page 23 of 160
(12)
2.10.11.2
Page 24
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 2: INSTALLATION
If the delayed interlock is connected to a proving device that r equires time to close (m ake), a time delay (Aux Start On Dly) that holds the start sequence of the boiler long enough for a proving switch to make can be programmed. Should the proving switch not prove within the programmed time frame, the boiler will shut down. T he Aux Start On Dly can be programmed from 0 to 120 seconds. This option is locate in the Configuration Menu (Chapter 3, Table 3-4).
Fault Relay (13) 2.10.12
The fault relay is a single pole double throw (SPDT) relay having a normally open and normally closed set of relay contacts that are rat ed for 5 amps at 120 VAC and 5 am ps at 30 VDC. The relay energizes when any fault condition occurs and remains energized until the fault is cleared and the CLEAR button is depressed. The fault relay connections are shown in Figure 2-10.
Auxiliary Relay Contacts (14) 2.10.13
Each Boiler is equipped with a single pole double throw (SPDT) relay that is energized when there is a demand for heat and de-energized after the demand for heat is satisf ied. The relay is provided for the control of auxiliary equipment, such as pumps and louvers, or can be used as a Boiler status indictor (firing or not firing). Its contacts are rated for 120 VAC @ 5 amps. Refer to Figure 2-10 to locate the AUX RELAY terminals for wiring connections.

2.11 FLUE GAS VENT INSTALLATION

The minimum allowable vent diameter for a single Benchmark 2.0LN Boiler is 8 inches. The AERCO Benchmark Venting and Combustion Air Guide, GF-2050, must be consulted
before any flue gas vent or inlet air venting is designed or inst alled. U/L listed, posit ive pressur e, watertight vent materials as specified in AERCO’s GF-2050, must be used for safety and code compliance. Since the unit is capable of discharging low tem perature exhaust gases, horizontal sections of the flue vent system must be pitched back to the unit a minimum of 1/4 inch per foot to avoid condensate pooling and allow for proper drainage.
The combined pressure drop of vent and combustion air systems must not exceed 140 equivalent feet of 8 inch ducting. Fittings as well as pipe leng ths must be calculated as part of the equivalent length.
For a natural draft installation the draft must not exceed ±0.25 inch W.C. These fa ct ors mus t be planned into the vent installation. If the maximum allowable equivalent lengths of piping are exceeded, the unit will not operate properly or reliably.

2.12 COMBUSTION AIR

The AERCO Benchmark Venting and Combustion Air Guide, GF-2050 MUST be consulted before any flue or combustion supply air venting is designed or implemented. Combustion air supply is a direct requirement of ANSI 223.1, NFPA-54, CSA B149.1 and local codes. These codes should be consulted before a permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons, or other chemicals that can become hazardous when used in gas-fired equipment. Common sources of these compounds are swimming pools, degreasing compounds, plastic processing and refrigerants. Whenever the environment contains these types of chemicals, combustion air must be supplied from a clean area outdoors for the protection and longevity of the equipment.
The AERCO Benchmark 2.0LN Boiler is UL listed for 100% sealed combust ion. It can also be installed using room air, provided there is an adequate supply. (See para. 2.13.3 for more information concerning sealed combustion air). If the sealed combustion air option is not being used, an inlet screen will be attached at the air inlet on the top of the unit
The more common methods of supplying combustion air are outlined below. For more
Page 24 of 160 PR2: 04/22/13
Page 25
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
information concerning combustion air, refer to the AERCO Benchmark Venting and Combus­tion Air Guide, GF-2050.
CHAPTER 2: INSTALLATION

Combustion Air From Outside the Building 2.12.1

Air supplied from outside the building must be provided through two permanent openings. Each opening must have a free area of not less than one square inch for each 4000 BTU/H boiler input. The free area must take into account r estrictions such as louvers and bird screens. For Canada installations, refer to the requirements specified in CSA B149.1-10, 8.4.1 and 8.4.3.

Combustion Air From Inside The Building 2.12.2

When combustion air is provided from within the building, it must be supplied through two permanent openings in an interior wall. Each opening must have a free area of not less than one square inch per 1000 BTU/H of total boiler input . The free area must take into ac count any restrictions such as louvers.

Sealed Combustion 2.12.3

The AERCO Benchmark 2.0LN Boiler is UL listed for 100%-sealed combustion. For sealed combustion installations, the screen on the air inlet duct of the unit must be removed. The inlet air ductwork must then be attached directly to the unit’s air inlet.
In a sealed combustion air application, the combustion air ducting pressure losses must be taken into account when calculating the total maximum allowable venting run. See the AERCO Benchmark Venting and Combustion Air Guide, GF-2050. When using the boiler in a sealed combustion air configuration, each unit must have a minimum 8 inch diameter connection at the unit.

Temporary Combustion Air Filtering During Construction 2.12.4

When the Benchmark 2.0LN Boiler is used to provide heat tempor arily during ongoing building construction, accumulated drywall dust, sawdust and similar particles can accumulate in the unit’s combustion air intake filter and block combustion air flow. In these situations, AERCO recommends that a disposable air intake filter be installed, temporarily, above the boiler combustion air inlet.
AERCO recommends that the temporary air filter be cut from a McMaster-Carr part no. 2122K315 Polyester Air Filter Roll Tackfield, ½” thick, 16” wide, or equivalent. Cover the Benchmark 2.0LN air inlet with the blue side of the filter material facing outward to hold the dust on the outside surface. Maximize the surface area of the filter covering the 8" diameter opening by creating a dome out of the filter material.
Cover the flared duct opening with the blue side facing outward. During construction check the filter for dust accumulation and replace it when the accumulation becomes noticeable.

2.13 BENCHMARK PUMP RELAY OPTION

An optional Benchmark pump relay allows the user to turn a pump on/off and open/close a motorized valve as the boiler cycles on and off on demand. The Pump Delay Timer feature allows the user to keep the pump running and keep the motorized valve open for up to 30 minutes after the boiler has shut down and the demand is satisfied.
The Benchmark pump relay (SPDT) contact is rated for:
10 A Resistive @ 277 VAC/28 VDC
1/3 HP N/O @ 120/240 VAC
1/6 HP N/C @ 120/240 VAC
480 VA Pilot Duty @ 240-277 VAC
PR2: 04/22/13 Page 25 of 160
Page 26
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 2: INSTALLATION
If pump/valve load exceeds the above contact ratings, use a separate contact relay. See Diagrams 2-1a and 2-1b. To identify if the boiler is equipped with the BMK Pump Relay Option (part no. 69102), look for
the label and relay as shown in Figure 2-12.
Diagram 2-1a: Schematic – System Pump Start using Boiler Pump Relay
Diagram 2-1b: Schematic – System Pump Start using a Separate Contact Relay
Figure 2-11: Identifying the Presence of BMK Pump Relay Option 69102
Page 26 of 160 PR2: 04/22/13
Page 27
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 3: CONTROL PANEL OPERATION

3.1 INTRODUCTION

The information in this Chapter provides a guide to the operation of t he Benchmark 2.0LN Boiler using the Control Panel mounted on the front of the unit. It is imperative that the initial startup of this unit be performed by factory trained personnel. Oper ation prior to initial startup by factory trained personnel will void the equipment warranty. In addition, the following WARNINGS and CAUTIONS must be observed at all times.
IMPORTANT!
All of the installation procedures in Chapter 2 must be completed before attempting to start the unit.
WARNING
ELECTRICAL VOLTAGES IN THI S SYSTEM MAY INCLUDE 460, 208 AND 24 VOLTS AC. IT MUST BE SERVICED ONLY BY FACTORY CERTIFIED SERVICE TECHNICIANS
WARNING
DO NOT ATTEMPT TO DRY FIRE THE BOILER. STARTING THE UNIT WITHOUT A FULL WAT ER LEVEL CAN SERIOUSLY DAMAGE THE UNIT AND MAY RESULT IN INJURY TO PERSONNEL OR PROPERTY DA MAGE. THIS SITUATION WILL VOID ANY WARRANTY.

3.2 CONTROL PANEL DESCRIP TION

The Benchmark 2.0LN Control Panel shown in Figure 3-1 contains all of the controls, indicators and displays necessary to operate, adjust and troubleshoot the Benchmark 2.0LN Boiler. These operating controls, indicators and displays are listed and described in Table 3-1. Additional information on these items is provided in the individual operating procedures provided in this Chapter.
PR2: 04/22/13 Page 27 of 160
Page 28
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
1
2
3
4
5
6
7
8
9
10
11
12
CHAPTER 3: CONTROL PANEL OPERATION
Figure 3-1: Control Panel Front View
Page 28 of 160 PR2: 04/22/13
Page 29
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
DISPLAY
8
CHAPTER 3: CONTROL PANEL OPERATION
Table 3-1 Operating Controls, Indicators and Displays
ITEM
NO.
CONTROL,
INDICATOR OR
1 LED Status
Indicators COMM MANUAL
REMOTE DEMAND
2
OUTLET
TEMPERATURE
Display
3
VFD Display
FUNCTION
Four Status LEDs indicate the current operating status as follows:
Lights when RS-232 communication is occurring Lights when the unit is being controlled using the front panel
keypad. Lights when the unit is being controlled by an external signal
from an Energy Management System Lights when there is a demand for heat.
3–Digit, 7–Segment LED display continuously displays the outlet water temperature. The °F or °C LED next to the display lights to indicate whether the displayed temperature is in degrees Fahrenheit or degrees Celsius. The °F or °C blinks when operating in the Deadband Mode.
Vacuum Fluorescent Display (VFD) consists of 2 lines each capable of displaying up to 16 alphanumeric characters. The information displayed includes:
Startup Messages Fault Messages Operating Status Messages Menu Selection
4
RS-232 Port
5
FAULT Indicator
6
CLEAR Key
READY Indicator
7
ON/OFF Switch
9
LOW WATER
LEVEL
TEST/RESET
Switches
Port permits a Laptop Computer or External Modem to be connected to the unit’s Contr ol Panel.
Red FAULT LED indicator lights when a boiler alarm condition occurs. An alarm message will appear in the VFD.
Turns off the FAULT indicator and clears the alarm message if the alarm is no longer valid. Lockout type alarms will be latched and cannot be cleared by simply pressing this key. Troubleshooting may be required to clear these types of alarms.
Lights ON/OFF switch is set to ON and all Pre-Purge conditions have been satisfied.
Enables and disables boiler operation. Allows operator to test operation of the water level monitor.
Pressing TEST opens the water level probe circuit and simulates a Low Water Level alarm.
Pressing RESET resets the water level monitor circuit. Pressing the CLEAR key (item 6) resets the display.
PR2: 04/22/13 Page 29 of 160
Page 30
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
DISPLAY
10
Bargraph
CHAPTER 3: CONTROL PANEL OPERATION
Table 3-1 Operating Controls, Indicators and Displays (Continued)
ITEM
NO.
CONTROL,
INDICATOR OR
MENU Keypad
MENU
BACK
(UP) Arrow
FUNCTION
Consists of 6 keys which provide the following functions for the Control Panel Menus:
Steps through the main menu categories shown in Figure 3-2. The Menu categories wrap around in the order shown.
Allows you to go back to the previous menu level without changing any information. Continuously pressing this key will bring you back to the default status display in the VFD. Also, this key allows you to go back to the top of a main menu category.
When in one of the main menu categories (Figure 3-2), pressing the ▲ arrow key will select the displayed menu category. If the CHANGE key was pressed and the menu item is flashing, pressing the arrow key will increment the selected setting.
(DOWN) Arrow
CHANGE
ENTER
11 AUTO/MAN Switch
12
VALVE POSITION
When in one of the main menu categories (Figure 3-2), pressing this key will select the displayed menu category. If the CHANGE key was pressed and the menu item is flashing, pressing the arrow key will decrement the selected setting.
Permits a setting to be changed (edited). When the CHANGE key is pressed, the displayed menu item will begin to flash. Pressing the or arrow key when the item is flashing will increment or decrement the displayed setting.
Saves the modified menu settings in memory. The display will stop flashing.
This switch toggles the boiler between the Automatic and Manual modes of operation. When in the Manual (MAN) mode, the front panel controls are enabled and the MANUAL status LED lights.
When in the Automatic (AUTO) mode, the MANUAL status LED will be off and the front panel controls disabled.
20 segment red LED bargraph continuously shows the Air/Fuel Valve position in 5% increments from 0 to 100%
Page 30 of 160 PR2: 04/22/13
Page 31
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 3: CONTROL PANEL OPERATION

3.3 CONTROL PANEL MENUS

The Control Panel incorporates an extensive menu structure which permits the operator to set up, and configure the unit. The menu structure consists of five major menu categories which are applicable to this manual. These categories are shown in Figure 3-2. Each of the menus shown, contain options which permit operating parameters to be viewed or changed. The menus are protected by a password levels to prevent unauthorized use.
Prior to entering the correct password, the options contained in the Operation, Setup, Configuration and Tuning Menu categories can be viewed. However, with the exception of Internal Setpoint Temperature (Configuration Menu), none of the viewable menu options can be changed.
Once the valid level 1 password (159) is entered, the options list ed in the Setup. Configuration and Tuning Menus can be viewed and changed, if desired. The Combustion Cal Menu is protected by the level 2 password which is used in Chapter 4 to perform combustion calibration prior to service use.

Menu Processing Procedure 3.3.1

Accessing and initiating each menu and option is accomplished using the Menu Keys shown in Figure 3-1. Therefore, it is imperative that you be thoroughly familiar with the following basic steps before attempting to perform specific menu procedures.
1. The Control Panel will normally be in the Operating Menu and the VFD will display the current unit status. Pressing the ▲ or ▼ arrow key will display the other available data items in the Operating Menu.
2. Press the MENU key. The display will show the Setup Menu, which is the next menu category shown in Figure 3-2. This menu contains the Password option which must be entered if other menu options will be changed.
3. Continue pressing the MENU key until the desired menu is displayed.
4. With the desired menu displayed, press the or arrow key. The first option in the selected menu will be displayed.
5. Continue to press the or arrow key until the desired menu option is displayed. Pressing the arrow key will display the available menu options in the Top-Down sequence. Pressing the arrow key will display the options in the Bottom-Up sequence. The menu options will wrap-around after the first or last available option is reached.
6. To change the value or setting of a displayed menu option, press the CHANGE key. The displayed option will begin to flash. Press the or ▼ arrow key to scroll through the available menu option choices for the opt ion to be changed. T he menu option choices do not wrap around.
7. To select and store a changed menu item, press the ENTER key.
PR2: 04/22/13 Page 31 of 160
Page 32
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
OPERATING
SETUP
CONFIGURATION
TUNING
COMBUSTION CAL
CALIBRATION
(NOT USED IN THIS O & M)
LEVEL 2 PWD
LEVEL 1 PWD
DIAGNOSTICS
(NOT USED IN THIS O & M)
CHAPTER 3: CONTROL PANEL OPERATION
Figure 3-2: Control Panel Menu Structure
NOTE

3.4 OPERATING MENU

The Operating Menu displays a number of key operating parameters for the unit as listed in Table 3-2. This menu is “Read-Only” and does not allow personnel to change or adjust any displayed items. Since this menu is “Read-Only”, it can be viewed at any time without entering a password. Pressing the arrow key to display the menu items in the order listed (Top-Down).
Pressing the arrow key will display the menu items in reverse order (Bottom-Up).
The following paragraphs provide brief descriptions of the options contained in each menu. Refer to Appendix A for detailed descriptions of each menu option. Refer to Appendix B for listings and descriptions of displayed startup, status and error messages.
Page 32 of 160 PR2: 04/22/13
Page 33
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Available Choices or Limits
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
CHAPTER 3: CONTROL PANEL OPERATION

3.5 SETUP MENU

The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is required to change the menu options. To prevent unauthorized use, the password will time­out after 1 hour. Therefore, the correct password must be reentered when required. In addition to permitting password entries, the Setup Menu is also used to enter date and time, units of temperature measurements and entries required for external communication and control of the unit via the RS-232 port. A view-only software version display is also provided to indicate the current Control Box software version.
NOTE
The Outdoor Temp display item shown with an asterisk in Table 3-2 will not be displayed unless the Outdoor Sensor function has been enabled in the Configuration Menu (Table 3-4).
Table 3-2: Operating Menu
Menu Item Display Minimum Maximum Default
Status Message Active Setpoint 40°F 240°F AIR Temp -70°F 245°F Outdoor Temp* -70°F 130°F Valve Position In 0% 100% Valve Position Flame Strength 0% 100% Run Cycles 0 999,999,999 Run Hours 0 999,999,999 Fault Log 0 19 0
Table 3-3: Setup Menu
Passsword 0 9999 0 Language English English Time 12:00 am 11:59 pm Date 01/01/00 12/31/99 Unit of Temp Fahrenheit or Celsius Fahrenheit Comm Address 0 127 0 Baud Rate 2400, 4800, 9600, 19.2K 9600 Software Ver 0.00 Ver 9.99
PR2: 04/22/13 Page 33 of 160
Page 34
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
CHAPTER 3: CONTROL PANEL OPERATION

3.6 CONFIGURATION MENU

The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt) temperature regardless of whether the valid password has been entered. Setpt is required for operation in the Constant Setpoint mode. The remaining options in this menu require the valid password to be entered, prior to changing existing entries. This menu contains a number of other configuration settings which may or may not be displayed, depending on the current operating mode setting.
The Configuration Menu settings shown in Table 3-4 are Factory-Set in accordance with the requirements specified for each individual order. Therefore, under normal operating conditions, no changes will be required.
Table 3-4: Configuration Menu
NOTE
Internal Setpt Lo Temp Limit Hi Temp Limit 130°F
KC Boiler, KC Boiler LN,
BMK Boiler Std, BMK Bo ile r LN,
Unit Type
Unit Size
Fuel Type Natural Gas, Propane Natural Gas
Boiler Mode
Remote Signal (If Mode = Remote Setpoint, Direct Drive or Combination)
Bldg Ref Temp (If Mode = Outdoor Reset) Reset Ratio(If Mode = Outdoor Reset) Outdoor Sensor Enabled or Disabled Disabled System Start Tmp (If Outdoor Sensor-
Enabled) Setpt Lo Limit 40°F Setpt Hi Limit 60°F Setpt Hi Limit Setpt Lo Limit 195°F 195°F Temp Hi Limit 40°F 210°F 195°F Max Valve Position 40% 100% 100%
BMK Blr Std Dual, BMK Blr LN KC Water
Heater,
KC Wtr Heater LN,
Innovation WH
600 MBH, 750 MBH, 800 MBH 1000 MBH,
1060 MBH,
1500 MBH, 2000 MBH,
3000 MBH
Constant Setpoint, Remote Setpoint,
Direct Drive, Combination
Outdoor Reset
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
40°F 230°F 70°F
0.1 9.9 1.2
30°F 100°F 60°F
BMK Boiler Dual
Constant Setpoint
2000 MBH
4 – 20 mA,
1-5V
Page 34 of 160 PR2: 04/22/13
Page 35
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Available Choices or Limits
Minimum
Maximum
CHAPTER 3: CONTROL PANEL OPERATION
Table 3-4: Configuration Menu (Continued)
Aux Start On Dly 0 sec. 120 sec. 0 sec. Failsafe Mode Shutdown or Constant Setpt Shutdown *Analog Output
(See CAUTION at end of Table 3-4 )
Low Fire Timer 2 sec. 600 sec. 2 sec. Setpt Limiting Enabled or Disabled Disabled Setpt Limit Band 0°F 10°F 5°F Network Timeout 5 Sec 999 Sec 30 Sec HI DB Setpt EN 0% 100% 30% Demand Offsert 0 25 10 Deadband High 0 25 2 Deadband Low 0 25 2
Off, Setpoint, Outlet Temp,
Valve Position 4-20 mA,
Valve Position 0-10V
*Valve Position
0-10V
*CAUTION!
DO NOT CHANGE the Analog Output Menu Item from its Default setting (Valve Position 0-10V).

3.7 TUNING MENU

The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change these menu entries unless specifically requested to do so by Factory-Trained personnel.

3.8 COMBUSTION CAL MENU

The Combustion Cal (Calibration) Menu items in Table 3-6 are used to vary the speed of the unit’s blower motor based on air temperature and air density at prescribed Air/Fuel Valve positions (% open). This is accomplished by providing a DC drive voltage to the motor which adjusts the rotational speed of the blower to maximize combustion efficiency and ensure the unit conforms to the Nitrogen Oxide (NOx) and Carbon Monoxide (CO) emissions specified in Chapter 4. The valve positions (%) and default drive voltages are listed in Table 3-6.
Table 3-5: Tuning Menu
Menu Item Display
Prop Band 1°F 120°F 70°F Integral Gain 0.00 2.00 1.00 Derivative Time 0.0 min 2.00 min 0.00 min Reset Defaults? Yes, No, Are You Sure? No
PR2: 04/22/13 Page 35 of 160
Default
Page 36
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CAL Voltage 20%
.25 Vdc
10.0 Vdc
1.00 Vdc
CAL Voltage 30%
.25 Vdc
10.0 Vdc
2.30 Vdc
CAL Voltage 45%
.25 Vdc
10.0 Vdc
2.9 Vdc
CAL Voltage 60%
.25 Vdc
10.0 Vdc
3.60 Vdc
CAL Voltage 80%
.25 Vdc
10.0 Vdc
5.30 Vdc
CAL Voltage 100%
.25 Vdc
10.0 Vdc
9.10 Vdc
SET Valve Position
0%
100%
0%
Blower Output
Monitor Blower Output Voltage
.00
Available Choices or Limits
CAL Voltage 21%
.25 Vdc
10.0 Vdc
1.10 Vdc
CAL Voltage 30%
.25 Vdc
10.0 Vdc
1.95 Vdc
CAL Voltage 45%
.25 Vdc
10.0 Vdc
3.00 Vdc
CAL Voltage 60%
.25 Vdc
10.0 Vdc
3.00 Vdc
CAL Voltage 80%
.25 Vdc
10.0 Vdc
4.45 Vdc
CAL Voltage 91%
.25 Vdc
10.0 Vdc
8.20 Vdc
SET Valve Position
0%
91%
0%
Blower Output
Monitor Blower Output Voltage
.00
CHAPTER 3: CONTROL PANEL OPERATION
Table 3-6: Combustion Cal Menu – Natural Gas
Available Choices or Limits Menu Item Display Minimum Maximum Default
Table 3-7: Combustion Cal Menu – Propane
Menu Item Display Minimum Maximum Default

3.9 START SEQUENCE

When the Control Box ON/OFF switch is set to the ON position, it checks all pre-purge safety switches to ensure they are closed. These switches include:
Safety Shut-Off Valve Proof of Closure (POC) switch
Low Water Level switch
High Water Temperature switch
High Gas Pressure switch
Low Gas Pressure switch
Blowe r Proo f swit ch
Blocked Inlet switch
If all of the above switches are closed, the READY light above the ON/OFF switch will light and the unit will be in the Standby mode.
When there is a demand for heat, the following events will occur:
NOTE
If any of the Pre-Purge safety device switches are open, the appropriate fault message will be displayed. Also, the appropriate fault messages will be displayed throughout the start sequence, if the required conditions are not observed.
Page 36 of 160 PR2: 04/22/13
Page 37
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
MANUAL
VALVE
PROPANE
INLET
NATURAL
INLET
CHAPTER 3: CONTROL PANEL OPERATION
1. The DEMAND L ED s tatus indicator will light .
2. The unit checks to ensure that the Proof of Closure (POC) switch in the downstream Safety Shut-Off Valve (SSOV) is closed. Figure 3-3 shows the Natural Gas SSOV location for a Factory Mutual (FM) Gas Train.
3. With all required safety device switches closed, a purge cycle will be initiated and the following events will occur:
a) The Blower relay energizes and turns on blower. b) The Air/Fuel Valve rotates to the full-open purge position and closes purge position
switch. The dial on the Air/Fuel Valve (Figure 3-4) will read 100 to indicate that it is full-open (100%).
PROPANE
SSOV
TO AIR/FUEL
VALVE
SHUT-OFF
GAS
NATURAL
GAS SSOV
GAS
Figure 3-3: SSOV Locations
4. Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display will show Purging and indicate the elapsed time of the purge cycle in seconds.
5. Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the following events occur:
a) The Air/Fuel Valve rotates to the low-fire ignition position and closes the ignition
switch. The dial on the Air/Fuel Valve (Figure 3-6) will read between 25 and 35 to indicate that the valve is in the low-fire position.
b) The igniter relay is activated and provides ignition spark.
PR2: 04/22/13 Page 37 of 160
Page 38
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
100
DETAIL “A”
TO BLOWER
AIR IN
DIAL (DETAIL “A”)
STEPPER
MOTOR
CHAPTER 3: CONTROL PANEL OPERATION
c) The gas Safet y Shut-Off Valve (SSOV) is energized (opened) allowing gas to flow
into the Air/Fuel Valve.
Figure 3-4: Air/Fuel Valve In Purge Position
Page 38 of 160 PR2: 04/22/13
Figure 3-5: Blower Proof Switch
Page 39
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
25
TO BLOWER
AIR IN
DIAL (DETAIL “A”)
STEPPER
MOTOR
DETAIL “A”
Start Level:
25%
25%
Stop Level:
20%
21%
CHAPTER 3: CONTROL PANEL OPERATION
Figure 3-6: Air/Fuel Valve In Ignition Position
6. Up to 7 seconds will be allowed for ignition to be detected. The igniter relay will be turned off one second after flame is detected.
7. After 2 seconds of continuous flame, Flame Proven will be displayed and the flame strength will be indicated. After 5 seconds, the current date and time will be displa yed in place of the flame strength.
8. With the unit firing properly, it will be controlled by the temperature controller circuitry. The boiler’s VALVE POSITION will be continuously displayed on the front panel bargraph.
Once the demand for heat has been satisfied, the Control Box will turn off the dual SSOV gas valves. The blower relay will be deactivated and the Air/Fuel Valve will be closed. Standby will be displayed.

3.10 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit, based on load. These levels are Factory preset as follows:
Natural Gas
Propane
Normally, these settings should not require adjustment.
PR2: 04/22/13 Page 39 of 160
Page 40
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
0 0 0
10% 0 0
20%
(Stop Level)
5.0%
30%
325,000
16%
40%
590,000
30%
50%
830,000
42%
60%
1,030,000
52%
70%
1,210,000
61%
80%
1,440,000
72%
90%
1,750,000
88%
100%
2,000,000
100%
0 0 0
CHAPTER 3: CONTROL PANEL OPERATION
Note that the energy input of the boiler is not linearly related to the Air/ Fuel Valve position. Refer to Table 3-8 for the relationship between the energy input and Air/Fuel Valve position for a unit running on natural gas.
Relationship Between Air/Fuel Valve Position and Energy Input For Unit
Running On Natural Gas
Table 3-8:
Air/Fuel Valve Position
(% Open)
Energy Input
(BTU/Hr)
105,000
Boiler Energy Input (% of Full Capacity)
Page 40 of 160 PR2: 04/22/13
Page 41
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 4: INITIAL START-UP

4.1 INITIAL START-UP REQUIREMENTS

The requirements for the initial start-up of the Benchmark 2.0LN Dual-Fuel Boiler consists of the following:
Complete installation (Chapter 2)
Set proper controls and limits (Chapter 3)
Perform combustion calibration (Chapter 4)
Set up mode of operation (Chapter 5)
Test safety devices (see Chapter 6)
All applicable Installation procedures in Chapter 2 must be fully completed before performing initial sta rt-up. The initial start-up must be successfully completed prior to putting the unit into service. Starting a unit without the proper piping, venting, or electrical systems can be dangerous and may void the product warranty. The following start-up instructions should be followed precisely in order to operate the unit safely and at a high thermal efficiency, with low flue gas emissions.
Initial unit start-up is to be performed ONLY by AERCO factory trained start-up and service personnel. After performing the start-up procedures in this Chapter, it will be necessary to perform the Mode of Operation settings in Chapter 5, and the Safety Device Testing procedures in Chapter 6 to complete all initial start-up requirements.
AERCO Gas Fired Startup Sheets, included with each Benchmark Boiler, must be completed for each unit for warranty validation. A copy of these sheets must be returned promptly to AERCO at:
AERCO International, Inc.
100 Oritani Drive Blauvelt, NY 10913
WARNING
DO NOT ATTEMPT TO DRY FIRE THE BOILER. STARTING THE UNIT WITHOUT A FULL WAT ER LEVEL CAN SERIOUSLY DAMAGE THE UNIT AND MAY RESULT IN INJURY TO PERSONNEL OR PROPERTY DA MAGE. THIS SITUATION WILL VOID ANY WARRANTY.
CAUTION!
All applicable installation procedures in Chapter 2 must be completed before attempting to start the unit.
4.2 TOOLS AND INSTRUMENT ATION FOR COMBUSTION
CALIBRATION
To properly perform combustion calibration, the proper instr uments and tools must be used and correctly attached to the unit. The following paragraphs outline the necessary tools and instrumentation as well as their installation.
PR2: 04/22/13 Page 41 of 160
Page 42
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
MANUAL
VALVE
CHAPTER 4: INITIAL START-UP

Required Tools & Instrumentation 4.2.1

The following tools and instrumentation are necessary to perform combustion calibration of the unit:
Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and Nitrogen Oxide (NOx) resolution to 1PPM.
16 inch W.C. manometer or equivalent gauge and plastic tubing.
1/4" NPT-to-barbed fittings for use with gas supply manometer or gauge.
Small and large flat blade screwdrivers.
Tube of silicone adhesive

Installing Gas Supply Manometer 4.2.2

The gas supply manometer (or gauge) is used to permit the gas pressure to be monitored on the downstream side of the SSOV during the Combustion Calibration procedures described in paragraphs 4.5 (natural gas) or 4.6 (propane).
The gas supply manometer is installed at the upstream and/or downstream location(s) shown in Figure 4-1.
PROPANE
SSOV
1/4” PLUG & LEAK
DETECTION BALL VALVE
(Install manometer
here for Combustion
Calibration)
TO AIR/FUEL
VALVE
SHUT-OFF
NATURAL
GAS SSOV
Figure 4-1: Manometer Installation Locations
Page 42 of 160 PR2: 04/22/13
Page 43
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
EXHAUST
MANIFOLD
1/2” NPT
CONDENSATE
DRAIN
CONNECTION
BOILER
RETURN
ANALYZER
PROBE PORT
CHAPTER 4: INITIAL START-UP
NOTE
If a second 16” W.C. manometer is available, it can be installed in the SSOV downstream location to provide continuous monitoring at both the upstream and downstream ports of the SSOV.
]Install the 16” W.C. manometer(s) as described in the following steps:
1. Turn off the main gas supply upstream of the unit.
2. Remove the top panel and left or right side panel from the boiler to access the gas train
components.
3. To monitor the gas pressure on the downstream side of the SSOV during Combustion
Calibration (paragraph 4.5 and 4.6), remove the 1/4” NPT plug from the appropriate leak detection ball valve (natural gas or propane) on the downstream side of the SSOV as shown in Figure 4-1.
4. Install a NPT-to-barbed fitting into the tapped plug port.
5. Attach one end of the plastic tubing to the barbed fitting and the other end to the 16”
W.C. manometer.

Accessing the Analyzer Probe Port 4.2.3

The unit contains NPT plugs on the left and right side of the exhaust manifold at the rear of the unit as shown in Figure 4-2. Prepare the port for the combustion analyzer probe as follows:
1. Remove the plug from the probe port on the left or right side of the exhaust manifold.
2. If necessary, adjust the stop on the combustion analyzer probe so that it will extend mid­way into the flue gas flow. DO NOT install the probe at this time.
Figure 4.2: Analyzer Probe Hole Location
PR2: 04/22/13 Page 43 of 160
Page 44
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
AIR/FUEL
VALVE
STAGED
IGNITION
ASSEMBLY
FLAME DETECTOR
IGNITOR-
INJECTOR
BLOWER
BURNER
PLATE
BURNER
Port
CHAPTER 4: INITIAL START-UP
Flame
Observation
Figure 4-3: Flame Observation Port Location

4.3 NATURAL GAS COMBUSTIO N CALIBRATION

The Benchmark 2.0LN Dual-Fuel Boiler is combustion calibrated at the factory prior to shipping. However, recalibration as part of initial start-up is necessary due to changes in t he local a lt it ude, gas BTU content, gas supply piping and supply regulators. Factory Test Data sheets are shipped with each unit. These sheets must be filled out and returned to AERCO for proper Warranty Validation.
It is important to perform the following procedure as outlined. This will keep readjustments to a minimum and provide optimum performance.
1. Open the water supply and return valves to the unit and ensure that the system pumps are running.
2. Open the natural gas supply valve(s) to the unit.
3. Set the control panel ON/OFF switch to the OFF position.
4. Turn on external AC power to the unit. The display will show LOSS OF POWER and the time and date.
5. Set the unit to the Manual Mode by pressing the AUTO/MAN key. A flashing Manual Valve Position message will be displayed with the present rate in %. Also, the MANUAL LED will light.
6. Adjust the air/fuel valve position to 0% by pressing the arrow key.
7. Ensure that the leak detection ball valve down-stream of the SSOV is open (Figure 4-1).
8. Ensure that the Fuel Selector Switch (Figure 4-5) is in the NATURAL GAS position.
Page 44 of 160 PR2: 04/22/13
Page 45
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
BRASS HEX
HEAD CAP
(REMOVE TO
ACCESS GAS
PRESSURE
ADJUSTMENT
SCREW)
SSOV ACTUATOR
Oxygen %
± 0.2
>100°F
5.5 %
<100 ppm
<20 ppm
90°F
5.7 %
<100 ppm
<20 ppm
80°F
5.9 %
<100 ppm
<20 ppm
<70°F
6.0 %
<100 ppm
<20 ppm
CHAPTER 4: INITIAL START-UP
Figure 4-4: Gas Pressure Adjustment Screw Location
9. Set the ON/OFF switch to the ON position.
10. Change the valve position to 34% using the ▲ arrow key. The unit should begin its start sequence and fire.
11. Next , ver ify that the gas pressure downstream of the SSOV is 7.3” W.C. for both FM and DBB (IRI) gas trains. If gas pressure adjustment is required, remove the brass hex nut on the Natural Gas SSOV actuator containing the gas pressure adjustment (Figure 4-4). Make gas regulator adjustments using a flat-tip screwdriver to obtain 7.3” W.C.
12. Increase the valve position to 100% and verify that the gas pressure downstream of the SSOV remains at 7.2” W.C. Readjust pressure if necessary.
13. With the valve position at 100%, insert the combustion analyzer probe into the flue pr obe opening and allow enough time for the combustion analyzer to settle.
14. Compare the measured oxygen level to the oxyg en range for the inlet air temperature shown in Table 4-1. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-1: Combustion Oxygen Levels for a
Inlet Air Temp
Carbon Monoxide NOx
100%
Air/Fuel Valve Position
15. If necessary, adjust the iris air damper shown in Figure 4-5 until the oxygen level is within the range specified in Table 4-1.
16. Once the oxygen level is within the specif ied range at 100%, lower the valve position t o 80%.
PR2: 04/22/13 Page 45 of 160
Page 46
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Oxygen %
± 0.2
6.0 %
<100 ppm
<20 ppm
CHAPTER 4: INITIAL START-UP
Figure 4-5: Iris Air Damper Location/Adjustment
NOTE
The remaining combustion calibration steps are performed using the Combustion Cal Menu included in the C-More Control System. The combustion calibration control functions will be used to adjust the oxygen level (%) at valve positions of 80%, 60%, 45%, 30% and 20% as described in the following steps. These steps assume that the inlet air temperature is within the range of 50°F to 100°F.
17. Press the MENU key on the front panel of the C-MORE and access the Setup menu. Enter password 6817 and then press the ENTER key.
18. Press the MENU key on the front panel of the C-MORE until Combustion Cal Menu appears on the C-More display.
19. Press the ▲ arrow key until SET Valve Posit ion appears on the C-MORE display.
20. Press the CHANGE key. SET Valve Position will begin to flash.
21. Press the ▲ arrow key until the SET Valve Posit ion reads 80%. Press the ENTER key.
22. Next, press the down (▼) arrow key until CAL Voltage 80% is displayed.
23. Press the CHANGE key and observe that CAL Voltage 80% is flashing.
24. The oxygen level at the 80% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-2: Combustion Oxygen Levels for a
Carbon Monoxide NOx
Page 46 of 160 PR2: 04/22/13
80%
Air/Fuel Valve Position
Page 47
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Oxygen %
± 0.2
6.0 %
<100 ppm
<20 ppm
CHAPTER 4: INITIAL START-UP
25. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼
arrow key decreases the oxygen level.
26. Once the oxygen level is within the specified range at 80%, press the ENTER key to store the selected blower output voltage for the 80% valve position.
NOTE
The remaining steps basically repeat the procedures in steps 19 through 26 for valve positions of 60%, 45%, 30% and 20%. However, since oxygen levels vary, these steps are repeated in their entirety. When performing these steps, also ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown for each valve position.
27. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
28. Press the CHANGE key. SET Valve Position will begin to flash.
29. Press the ▼ arrow key until the SET Valve Position reads 60% and press the ENTER key.
30. Press the down ▼ arrow key until CAL Voltage 60% is displayed.
31. Press the CHANGE key. CAL Voltage 60% will begin to flash.
32. The oxygen level at the 60% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-3: Combustion Oxygen Levels for a
60%
Air/Fuel Valve Position
Carbon Monoxide NOx
33. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
34. Once the oxygen level is within the specified range at 60%, press the ENTER key to store the selected blower output voltage for the 60% valve position.
35. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
36. Press the CHANGE key. SET Valve Position will begin to flash.
37. Press the ▼ arrow key until the SET Valve Position reads 45%, then press the ENTER key.
38. Press the ▼ arrow key until CAL Voltage 45% is displayed.
39. Press the CHANGE key. CAL Voltage 45% will begin to flash.
40. The oxygen level at the 45% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
PR2: 04/22/13 Page 47 of 160
Page 48
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Oxygen %
± 0.2
6.4 %
<50 ppm
<20 ppm
Oxygen %
± 0.2
8.4 %
<50 ppm
<20 ppm
CHAPTER 4: INITIAL START-UP
Table 4-4: Combustion Oxygen Levels for a 45% Air/Fuel Valve Position
41. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
42. Once the oxygen level is within the specified range at 45%, press the ENTER key to store the selected blower output voltage for the 45% valve position.
43. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
44. Press the CHANGE key. SET Valve Position will begin to flash.
45. Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER key.
Carbon Monoxide NOx
46. Press the ▼ arrow key until CAL Voltage 30% is displayed.
47. Press the CHANGE key. CAL Voltage 30% will begin to flash.
48. The oxygen level at the 30% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-5: Combustion Oxygen Levels for a
Carbon Monoxide NOx
49. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
50. Once the oxygen level is within the specified range at 30%, press the ENTER key to store the selected blower output voltage for 30% valve position.
51. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
52. Press the CHANGE key. SET Valve Position will begin to flash.
53. Press the ▼ arrow key until the SET Valve Position reads 20%, then press the ENTER key.
30%
Air/Fuel Valve Position
54. Press the ▼ arrow key until CAL Voltage 18% is displayed.
55. Press the CHANGE key. CAL Voltage 20% will begin to flash.
56. The oxygen level at the 20% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-6: Combustion Oxygen Levels for a
Page 48 of 160 PR2: 04/22/13
20%
Air/Fuel Valve Position
Page 49
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Oxygen %
± 0.2
8.8 %
<50 ppm
<20 ppm
CHAPTER 4: INITIAL START-UP
Carbon Monoxide NOx
57. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
58. Once the oxygen level is within the specified range at 20%, press the ENTER key to store the selected blower output voltage for the 20% valve position.
59. This completes the natural gas combustion calibration procedure.
IMPORTANT!
Refer to Appendix K for switchover instructions when changing from Natural Gas to Propane or from Propane to Natural Gas.

4.4 PROPANE COMBUSTION C ALIBRATION

The Benchmark 2.0LN Dual-Fuel Boiler is combustion calibrated at the factory prior to shipping. However, recalibration as part of initial start-up is necessary due to changes in t he local a lt it ude, gas BTU content, gas supply piping and supply regulators. Factory Test Data sheets are shipped with each unit. These sheets must be filled out and returned to AERCO for proper Warranty Validation.
Prior to starting these procedures, ensure that the Benchmark 2.0LN Dual-Fuel Boiler has been set up as specified in paragraphs 4.2 through 4.2.3.
It is important to perform the following procedure as outlined. This will keep readjustments to a minimum and provide optimum performance.
1. Open the water supply and return valves to the unit and ensure that the system pumps are running.
2. Open the propane supply valve(s) to the unit.
3. Set the control panel ON/OFF switch to the OFF position.
4. Turn on external AC power to the unit. The display will show LOSS OF POWER and the time and date.
5. Set the unit to the Manual Mode by pressing the AUTO/MAN key. A flashing Manual Valve Position message will be displayed with the present rate in %. Also, the MANUAL LED will light.
6. Access the Control Panel Configuration Menu and ensure that the Fuel Type is set to Propane.
7. Adjust the valve position to 0% by pressing the ▼ arrow key.
8. Ensure that the leak detection ball valve (Figure 4-1) down-stream of the SSOV is open.
PR2: 04/22/13 Page 49 of 160
Page 50
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Oxygen %
± 0.2
NOx
5.3 %
<150 ppm
<100 ppm
CHAPTER 4: INITIAL START-UP
9. Set the Fuel Selector Switch (Figure 4-4) to the PROPANE position.
10. Set the ON/OFF switch to the ON position.
11. Change the valve position to 34% using the ▲ arrow key. The unit should begin its start sequence and fire.
12. Next, increase the valve position to 91%. Verify that the gas pressure downstream of the Propane SSOV is 2.8” W.C. for both FM and IRI gas trains. If gas pressure adjustment is required, remove the brass hex nut on the Propane SSOV actuator containing the gas pressure adjustment (see Figures 4-1 & 4-3). For IRI gas trains, t he gas pressure adjustment is on the downstream SSOV. Make gas pressure adjustments using a flat-tip screwdriver to obtain 2.8” W.C.
13. With the valve position at 91%, insert the combustion analyzer probe into the flue probe opening and allow enough time for the combustion analyzer to settle.
14. Compare the measured oxygen % level to the range shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-7: Combustion Oxygen Level for a
91%
Valve Position
Carbon Monoxide
15. If necessary, adjust the iris air damper shown in Figure 4-5 until the oxygen level is within the range specified above.
16. Once the oxygen level is within the specified range at 91%, lower the valve position to 80%.
NOTE
The remaining combustion calibration steps are performed using the Combustion Cal Menu included in the C-More Control System. The combustion calibration control functions will be used to adjust the oxygen level (%) at valve positions of 80%, 60%, 45%, 30% and 21% as described in the following steps. These steps assume that the inlet air temperature is within the range of 50°F to 100°F.
17. Press the MENU Key on the front panel of the C-MORE and access the Setup menu. Enter password 6817 and then press the ENTER key.
18. Press the MENU Key on the f ront panel of the C-MORE until Combustion Cal Menu appears on the C-More display.
19. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
20. Press the CHANGE key. SET Valve Position will begin to flash.
21. Press the ▲ arrow key until the SET Valve Posit ion reads 80%. Press the ENTER key.
22. Next, press the down (▼) arrow key until CAL Voltage 80% is displayed.
23. Press the CHANGE key and observe that CAL Voltage 80% is flashing.
24. The oxygen level at the 80% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Page 50 of 160 PR2: 04/22/13
Page 51
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Oxygen %
± 0.2
NOx
4.8 %
<150 ppm
<100 ppm
Oxygen %
± 0.2
NOx
5.0 %
<150 ppm
<100 ppm
CHAPTER 4: INITIAL START-UP
Table 4-8: Combustion Oxygen Level at
Carbon Monoxide
25. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼ arrow key
decreases the oxygen level.
26. Once the oxygen level is within the specified range at 80%, press the ENTER key to s tor e the selected blower output voltage for 80% valve position.
80%
Valve Position
NOTE
The remaining steps basically repeat the procedures in steps 19 through 26 for valve positions of 60%, 45%, 30% and 21%. However, since oxygen levels vary, these steps are repeated in their entirety. When performing these steps, also ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown for each valve position.
27. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
28. Press the CHANGE key. SET Valve Position will begin to flash.
29. Press the ▼ arrow key until the SET Valve Posit ion reads 60% and press the ENTER key.
30. Press the down ▼ arrow key until CAL Voltage 60% is displayed.
31. Press the CHANGE key. CAL Voltage 60% will begin to flash.
32. The oxygen level at the 60% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-9: Combustion Oxygen Level at
Carbon Monoxide
33. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
34. Once the oxygen level is within the specified range at 60%, press the ENTER k ey t o st ore t he selected blower output voltage for the 60% valve position.
35. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
36. Press the CHANGE key. SET Valve Position will begin to flash.
37. Press the ▼ arrow key until the SET Valve Posit ion reads 45%, then press the ENTER key.
38. Press the ▼ arrow key until CAL Voltage 45% is displayed.
60%
Valve Position
39. Press the CHANGE key. CAL Voltage 45% will begin to flash.
PR2: 04/22/13 Page 51 of 160
Page 52
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Oxygen %
± 0.2
NOx
7.0 %
<100 ppm
<100 ppm
Oxygen %
± 0.2
NOx
7.9 %
<100 ppm
<100 ppm
CHAPTER 4: INITIAL START-UP
40. The oxygen level at the 45% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-10: Combustion Oxygen Level at
45%
Valve Position
Carbon Monoxide
41. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key decreases the oxygen level.
42. Once the oxygen level is within the specified range at 45%, press the ENTER key to s tor e the selected blower output voltage for the 45% valve position.
43. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
44. Press the CHANGE key. SET Valve Position will begin to flash.
45. Press the ▼ arrow key until the SET Valve Posit ion reads 30%, then press the ENTER key.
46. Press the ▼ arrow key until CAL Voltage 30% is displayed.
47. Press the CHANGE key. CAL Voltage 30% will begin to flash.
48. The oxygen level at the 30% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-11: Combustion Oxygen Level at
30%
Valve Position
Carbon Monoxide
49. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
50. Once the oxygen level is within the specified range at 30%, press the ENTER key to s tor e the selected blower output voltage for the 30% valve position.
51. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
52. Press the CHANGE key. SET Valve Position will begin to flash.
53. Press the ▼ arrow key until the SET Valve Posit ion reads 21%, then press the ENTER key.
54. Press the ▼ arrow key until CAL Voltage 21% is displayed.
55. Press the CHANGE key. CAL Voltage 21% will begin to flash.
56. The oxygen level at the 21% valve position should be as shown below. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Page 52 of 160 PR2: 04/22/13
Page 53
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Oxygen %
± 0.2
NOx
8.9 %
<100 ppm
<100 ppm
CHAPTER 4: INITIAL START-UP
Table 4-12: Combustion Oxygen Level at
Carbon Monoxide
57. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
58. Once the oxygen level is within the specified range at 21%, press the ENTER key to s tor e the selected blower output voltage for the 21% valve position.
59. This completes the Propane Combustion Calibration procedure.
21%
Valve Position

4.5 UNIT REASSEMBLY

Once the combustion calibration adjustments are properly set, the unit can be reassem bled for service operation.
1. Set the ON/OFF switch in the OFF position.
2. Disconnect AC power from the unit.
3. Shut off the gas supply to the unit.
4. Remove the manometer and barbed fittings and reinstall the NPT plug using a suitable pipe
thread compound.
5. Remove the combustion analyzer probe from the vent hole. Replace the NPT plug in the vent
hole using a suitable pipe joint compound.
6. Replace the unit’s side panels and front door.

4.6 OVER-TEMPERATURE LIMIT SWITCHES

The unit contains three (3) types of over-temperature limit switches. These switches consist of a manual reset switch, a rotary dial adjustable switch and a digital alarm switch. These switches are mounted on a plate as shown in Figure 4-6. The switches can be accessed by opening the front panel door of the unit.
The manual reset switch is not adjustable and is permanently fixed at 210°F. This switch will shut down and lock out the boiler if the water temperature exceeds 210°F. Following an over­temperature condition, it must be manually reset by pressing the manual reset button shown in Figurer 4-6 before the boiler can be restarted.
The rotary dial over-temperature switch is manually adjustable from xxx to yyy ºF. This switch allows the boiler to restart, once the temperature drops below the selected temperature setting on the dial. Set the dial on this over-temperature switch to the desired setting.
The digital alarm switch shown in Figures 4-6 and 4-7 is preset at the factory to 210ºF and should not be changed. If an over-temperature condition is detected, this switch automatically shuts down the boiler and sounds an audible alarm. If desired, the over-temperature alarm switch settings can be checked or adjusted using the procedure in paragraph 4.6.1.
PR2: 04/22/13 Page 53 of 160
Page 54
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
F
Alarm
RST
SET
Limit Control
RESET BUTTON
LIMIT SWITCH
DIGITAL OVER-
ALARM SWIT CH
FUEL
ADJUSTABLE
CHAPTER 4: INITIAL START-UP
FOR MANUAL
TEMPERATURE
TEMPERATURE
TEMPERATURE
LIMIT SWITCH
SELECTOR
Figure 4-6: Over Temperature Limit Switch and Fuel Selector Locations

Digital Alarm Switch Checks and Adjustments 4.6.1

The digital alarm switch se ttings can be checked or adjusted usin g the controls and display on the fr ont panel of the switch illustrated and described in Figure 4-7 and Table 4-13.
Figure 4-7: Digital Alarm Switch Front Panel
SWITCH
Page 54 of 160 PR2: 04/22/13
Page 55
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 4: INITIAL START-UP
Table 4-13: Digital Alarm Switch Controls and Display
CONTROL or
Display
MEANING
LED Display TEMP status Displays current water temperature or setpoint.
RST RESET Button Resets the unit after an alarm condition.
UP Button Increases the displayed temperature.
DOWN Button Decreases the displayed temperature.
SET SET Button Used to access and store param eters in the unit.
FUNCTION
Perform the following steps to check or adjust the digital alarm switch settings:
1. Set the ON/OFF to the ON position.
2. Press the SET button on the Digital Alarm Switch. SP will appear in the display.
3. Press the SET button again. The current over-temperature limit value stored in memory will be
displayed. (default = 210°F).
4. If the display does not show the required over-temperature alarm setting, press the ▲ or ▼ arrow
button to change the display to the desired temperature setting.
5. Once the desired over-temperature alarm setting (210ºF) is displayed, press the SET button to store
the setting in memory.
6. To calibrate the offset (P1), press and hold the SET button for 8 seconds on the Digital Alarm Switch.
Access code value 0 should appear in the display. The switch comes from the factory with the code set at 0. AERCO recommends that you do not change this code.
7. Press the SET button again to enter the code. The first parameter label (SP) will appear in the display.
8. Using the ▲ and ▼ arrow keys, select parameter P1.
9. Press SET to view the value stored in memory.
10. If the desired value is not displayed, modify the setting using the ▲ and ▼ arrow keys. The value can
be changed from -10° to +10° offset. Press SET to enter the value and exit to the text parameter.
11. To exit the programming mode, press the SET and ▼ buttons simultaneously, or simply wait one
minute and the display will automatically exit the programming mode.
12. Once the programming mode has been exited, the display will show the current outlet water
temperature of the boiler.
PR2: 04/22/13 Page 55 of 160
Page 56
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 5: MODE OF OPERATION

5.1 INTRODUCTION

The boiler is capable of being operated in any one of six different modes. The following paragraphs in this Chapter provide descriptions of each of these operating modes. Each boiler is shipped from the factory tested and configured for the ordered mode of operation. All temperature related parameters are at their factory default values which work well in most applications. However, it may be necessary to change certain parameters to customize the unit to the system environment. A complete listing and descriptions of the temperature related parameters are included in Appendix A. Factory defaults are listed in Appendix E. After reading this chapter, parameters can be customized to suit the needs of the specific application.

5.2 INDOOR/OUTDOOR RESET MODE

This m ode of operation is based on outside air temperatures. As the outside air temperature decreases, the supply header temperature will increase and vice versa. For this mode, it is necessary to install an outside air sensor as well as select a building reference temperature and a reset ratio.

Reset Ratio 5.2.1

Reset ratio is an adjustable number from 0.1 to 9.9. Once adjusted, the supply header temperature will increase by that number for each degree that the outside air temperature decreases. For instance, if a reset ratio of 1.6 is used, for each degree that outside air temperature decreases the supply header temperature will increase by 1.6 degrees.

Building Reference Temperature 5.2.2

This is a temperature from 40°F to 230°F. Once selected, it is the temperature that the system references to begin increasing its temperature. For instance, if a reset ratio of 1.6 is used, and we select a building reference temperature of 70°F, then at an outside temperature of 69°F, the supply header temperature will increase by 1.6° to 71.6°F.

Outdoor Air Temperature Sensor Installation 5.2.3

The outdoor air temperature sensor must be mounted on the North side of the building in an area where the average outside air temperature is expected. The sensor must be shielded from the sun's direct rays, as well as direct impingement by the elements. If a cover or shield is used, it must allow free air circulation. The sensor may be mounted up to two hundred feet from the unit. Sensor connections are made at the Input/Output (I/O) Box on the front of the boiler. Connections are made at the terminals labeled OUTDOOR SENSOR IN and SENSOR COMMON inside the I/O Box. Use shielded 18 to 22 AWG wire for connections. A wiring diagram is provided on the cover of the I/O Box. Refer to Chapter 2, paragraph 2.9.1 for additional wiring information.

Indoor/ Outdoor Startup 5.2.4

Startup in the Indoor/Outdoor Reset Mode is accomplished as follows:
1. Refer to the Indoor/Outdoor reset ratio charts in Appendix D.
2. Choose the chart corresponding to the desired Building Reference Temperature.
3. Go down the left column of the chart to the coldest design outdoor air temperature
expected in your area.
PR2: 04/22/13 Page 56 of 160
Page 57
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
MENU OPTION
SETTING
CHAPTER 5: MODE OF OPERATION
NOTE
A design engineer typically provides design outdoor air temperature and supply header temperature data.
4. Once the desig n outdoor air temperature is chosen, go across the chart to the desired supply header temperature for the design temperature chosen in step 3.
5. Next, go up that column to the Reset Ratio row to find the corresponding reset ratio.
6. Access the Configuration Menu and scroll through it until the display shows Bldg Ref Temp. (Building Reference Temperature).
7. Press the CHANGE key. The display will begin to flash.
8. Use the and arrow keys to select the desired Building Reference Temperature.
9. Press ENTER to save any changes.
10. Next, scroll through the Configuration Menu until the display shows Reset Ratio.
11. Press the CHANGE key. The display will begin to flash.
12. Use the and arrow keys to select the Reset Ratio determined in step 5.
13. Press ENTER to save the change.
Refer to paragraph 3.3 for detailed instructions on menu changing.

5.3 CONSTANT SETPOINT MODE

The Constant Setpoint mode is used when a fixed header temperature is desired. Common uses of this mode of operation include water source heat pump loops, and indirect heat exchangers for potable hot water systems or processes. No external sensors are required to operate in this mode. While it is necessary to set the desired setpoint temperature, it is not necessary to change any other temperature-related functions. The unit is factory preset with settings that work well in most applications. Prior to changing any temperature-related parameters, other than the setpoint, it is suggested that an AERCO representative be contacted. For descriptions of temperature-related functions and their factory defaults, see Appendices A and E.

Setting the Setpoint 5.3.1

The setpoint temperature of the unit is adjustable from 40°F to 240°F. To set the unit for operation in the Constant Setpoint Mode, the following menu settings must be made in the Configuration Menu:
Boiler Mode Constant Setpoint Internal Setpt Select desired setpoint
using and arrow keys (40°F to 240°F)
Refer to paragraph 3.3 for detailed instructions on changing menu options.
PR2: 04/22/13 Page 57 of 160
Page 58
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
MENU OPTION
SETTING
CHAPTER 5: MODE OF OPERATION

5.4 REMOTE SETPOINT MODES

The unit’s setpoint can be remotely controlled by an Energy Management System (EMS) or Building Automation System (BAS). The Remote Setpoint can be driven by a current or voltage signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Remote Setpoint mode is 4 - 20 mA/1 - 5 Vdc. With this setting, a 4 to 20 mA/1 to 5 Vdc signal, sent by an EMS or BAS, is used to change the unit's setpoint. The 4 mA/1V signal is equal to a 40°F setpoint while a 20 mA /5V signal is equal to a 240°F setpoint. When a 0 to 20 mA/0 to 5 Vdc signal is used, 0 mA is equal to a 40°F setpoint.
In addition to the current and voltage signals described above, the Remote Setpoint mode can also driven by a RS485 Modbus Network signal from an EMS or BAS.
The Remote Setpoint modes of operation can be used to drive single as well as multiple units.
NOTE
If a voltage, rather than current signal is used to control the remote setpoint, a DIP switch adjustment must be made on the CPU Board located in the Control Panel Assembly. Contact your local AERCO representative for details.
In order to enable the Remote Setpoint Mode, the following menu setting must be made in the Configuration Menu:
Boiler Mode Remote Setpoint Remote Signal 4-20mA/1-5V,
0-20mA/0-5V, or Network
Refer to paragraph 3.3 for detailed instructions on changing menu options. If the Network setting is selected for RS485 Modbus operation, a valid C omm Address must be
entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional information.
While it is possible t o change the settings of temperature related functions, the unit is factory preset with settings that work well in most applications. It is suggested that an AERCO representative be contacted, prior to changing any temperature related function settings. For descriptions of temperature-related functions and their factory defaults, refer to Appendices A and E.

Remote Setpoint Field Wiring 5.4.1

The only wiring connections necessary for the Remote Setpoint mode are connection of the remote signal leads from the source to the unit’s I/O Box. The I/O Box is located on the front panel of the boiler. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the connections are made at the ANALOG IN terminals in the I/O Box. For a Network setting, the connections are made at the RS-485 COMM terminals in the I/O Box. The signal must be f loat ing, (ungr ounded) at the I/O Box and the wire used must be a two wire shielded pair from 18 to 22 AWG. Polarity must be observed. The source end of the shield must be connected at the source. When driving multiple units, each unit’s wiring must conform to the above.
Page 58 of 160 PR2: 04/22/13
Page 59
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 5: MODE OF OPERATION

Remote Setpoint Startup 5.4.2

Since this mode of operation is factory preset and the setpoint is being externally controlled, no startup instructions are necessary. In t his mode, the REMOTE LED will light when the exter nal signal is present.
To operate the unit in the Manual mode, press the AUTO/MAN switch. The REMOTE LED will go off and the MANUAL LED will lig h t.
To change back to the Remote Setpoint mode, simply press the AUTO/MAN switch. The
REMOTE LED will again light and the MANUAL LED will go off.

5.5 DIRECT DRIVE MODES

The unit’s air/fuel valve position (% open) can be changed by a remote signal which is typically sent from an Energy Management System (EMS) or from a Building Automation System (BAS). The Direct Drive mode can be driven by a current or voltage signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Direct Drive mode is 4-20 mA/1-5 Vdc. With this setting, a 4 to 20 mA signal, sent by an EMS or BAS is used to change the unit’s valve position from 0% to 100%. A 4 mA/1V signal is equal to a 0% valve position, while a 20 mA /5V signal is equal t o a 100% valve position. When a 0-20 mA/0-5 Vdc signal is used, zero is equal to a 0% valve position.
In addition to the current and voltage signals described above, the Direct Drive mode can also driven by a RS485 Modbus Network signal from an EMS or BAS.
When in a Direct Drive mode, the unit is a slave to the EMS or BAS and does not have a role in temperature control. Direct Drive can be used to drive single, or multiple units.
NOTE
If a voltage, rather than current signal is used to control the remote setpoint, a DIP switch adjustment must be made on the CPU Board located in the Control Box Assembly. Contact your local AERCO representative for details.
To enable the Direct Drive Mode, the following menu setting must be made in the Conf iguration Menu:
MENU OPTION SETTING
Boiler Mode Direct Drive Remote Signal 4-20mA/1-5V,
0-20mA/0-5V, or Network
Refer to paragraph 3.3 for instructions on changing menu options. If the Network setting is selected for RS485 Modbus operation, a valid C omm Address must be
entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional information.
PR2: 04/22/13 Page 59 of 160
Page 60
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 5: MODE OF OPERATION

Direct Drive Field Wiring 5.5.1

The only wiring connections necessary for Direct Drive mode are connection of the remote signal leads from the source to the unit’s I/O Box. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the connections are made at the ANALOG IN terminals in the I/O Box. For a Network setting, the connections are made at the RS-485 COMM terminals in the I/O Box. The signal must be floating, (ungrounded) at the I/O Box and the wire used must be a two wire shielded pair from 18 to 22 AWG. Polarity must be observed. The source end of the shield must be connected at the source. When driving multiple units, each unit’s wiring must conform to the above.

Direct Drive Startup 5.5.2

Since this mode of operation is factory preset and the valve position is being externally controlled, no startup instructions are necessary. In this mode, the REMOTE LED will light when the signal is present.
To operate the unit in manual mode, press the AUTO/MAN s witch. The REMOTE LED wi ll go off and the MANUAL LED will light.
To change back to the Direct Drive mode, simply press the AUTO/MAN switch. The REMOTE LED will again light and the MANUAL LED will go off.

5.6 BOILER MANAGEMENT SYSTEM (BMS)

NOTE
BMS Model 168 can utilize either pulse width modulation (PWM) or RS485 Modbus signaling to the Boiler. The BMS II and the ACS (AERCO Control System) can utilize only RS485 signaling to the Boiler.
The BMS mode of operation is used in conjunction with an AERCO Boiler Management System (BMS or BMS II) and the AERCO Control System (ACS). The BMS mode is used when it is desired to operate multiple units in the most efficient manner possible. For this mode of operation, a BMS Header Sensor must be installed between 2 and 10 feet downstream of the LAST boiler in the boiler plant's supply water header. The BMS can control up to 40 boilers; 8 via pulse width modulation (PWM) and up to 32 via Modbus (RS485) net work communication. For BMS/BMS II/ACS programming, operation, and Header Sensor installation details, see GF­108M (BMS Model 168), GF-124 (BMS II Model 5R5-384), and GF-131 (ACS) Operations Manuals. For operation via an RS485 Modbus network, refer to Modbus Communication Manual, GF-114.
To enable the BMS Mode, the following menu settings must be made in the Configuration Menu:
MENU OPTION SETTING
Boiler Mode Direct Drive Remote Signal BMS (PWM Input)
or Network (RS485)
Refer to paragraph 3.3 for instructions on changing menu options.

BMS External Field Wiring 5.6.1

Wiring connections for BMS control using PWM signaling are made between connector J P2 on the BMS panel (boilers 1 through 8), and the B.M.S. (PWM) IN terminals in the I/O Box on the
Page 60 of 160 PR2: 04/22/13
Page 61
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
front of the boilers. Refer to the wiring diagram provided on the cover of the I/O Box. Wiring connections for RS485 Modbus control are made between connector JP11 on the BMS
(boilers 9 through 40) or JP6 on BMS II/ACS (boilers 1-32) and the RS485 COMM terminals in the I/O Box on the front of the boilers.
Wire the units using shielded twisted pair wire between 18 and 22 AWG. Observe the proper polarity for the B.M.S. (PWM) IN and/or RS485 COMM wiring connections. Shields should be terminated only at the BMS/BMS II/ACS and the boiler end must be left floating. Each unit’s wiring must conform to the above.
CHAPTER 5: MODE OF OPERATION

BMS Setup and Startup 5.6.2

This mode of operation is factory preset and the AERCO BMS/BMS II/ACS controls the f iring rate (air/fuel valve % open position). There are no setup instructions for each individual unit.
To operate the unit in manual mode, press the AUTO/MAN s witch. The REMOTE LED will go off and the MANUAL LED will light
To change back to the BMS mode, simply press the AUTO/MAN switch. T he REMOTE LED will again light and the MANUAL LED will go off.

5.7 COMBINATION CONTROL SY S TEM (CCS)

NOTE
Only the BMS and ACS can be utilized for the Combination Mode, but not the BMS II.
A Combination Control System (CCS) is one that uses multiple boilers to cover both space­heating and domestic hot water needs. An AERCO Boiler Management System (BMS) Model 168 and a Combination Control Panel (CCP) or an ACS and an ACS Relay Panel (optional, depending on applications) are necessary to configure this system. Typically, an adequate number of boilers are installed to cover the space-heating load on the design day, however one or more units are used for the domestic hot water load.
The theory behind this type of system is that the maximum space-heating load and the maximum domestic hot water load do not occur simultaneously. T herefore, boilers used for the domestic hot water are capable of switching between constant setpoint and BMS modes of operation. These boilers are the combination units and are referred to as the combo boilers. The combo boilers heat water to a constant setpoint temperature. That water is then circulated through a heat exchanger in a domestic hot water storage tank.
When t he space-heating load is such that all the space-heating boilers are at the 100% valve position, the BMS/ACS will then operate the domestic boilers to become space-heating boilers, provided the domestic hot water load is satisfied. If the domestic hot water load is not satisfied, the combo boiler(s) remain on the domestic hot water load. If the combo boilers switch over to space heating, but there is a call for domestic hot water, the combo units will resu me heating water for domestic needs.
When the combo units are satisfying the domestic load they are in con stant setpoint mode of operation. When the combo units switch over to space heating, their mode of operation changes to the BMS mode. For more information concerning the operation of the Combination Control Panel see the AERCO CCP-1 literature (BMS 168 applications) and TAG-0050 (ACS).

Combination Control System Field Wiring 5.7.1

Wiring for this system is between the BMS Model 168 panel, the CCP and the B.M.S. (PWM) IN terminals in the I/O Box. For ACS applications, the wiring is between the ACS panel, the ACS
PR2: 04/22/13 Page 61 of 160
Page 62
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 5: MODE OF OPERATION
Replay Panel (optional, depending on application), and the RS485 Comm terminals in the I/O box. Wire the units using a shielded twisted pair of 18 to 22 AWG wire. When wiring multiple units, each unit’s wiring must conform to the above. For a complete CCP system-wiring diagram see the AERCO CCP-1 literature (BMS 168 applications) and TAG-0050 (ACS).

Combination Control System Setup and Startup 5.7.2

Setup for the Combination Mode requires entries to be made in the Configuration Menu for boiler mode, remote signal type and setpoint. The setpoint is adjustable from 40°F to 240°F.
Enter the following settings in the Configuration Menu:
MENU OPTION
BMS 168 Applications ACS Applications
Boiler Mode Combination Combination Remote Signal BMS (PWM Input) Network (RS485) Internal Setpt 40°F to 240°F 40°F to 240°F
Refer to paragraph 3.3 for instructions on changing menu options. While it is possible to change other temperature-related f unctions for combination mode, thes
functions are preset to their factory default values. These default settings work well in most applications. It is suggested that AERCO be contacted prior to chang ing set ting s o ther th an t he unit’s setpoint. For a complete listing of temperature related function defaults, see Appendix E.
To set the unit to the manual mode, press the AUTO/MAN switch. The MANUAL LED will light. To set the unit back to the auto mode, pr es s t he AUTO/MAN switch. The MANUAL LED will g o
off and the REMOTE LED will light. When the boiler is switched to BMS mode, the AERCO BMS/ACS controls the valve position.
There are no setup requirements to the boiler(s) in this mode.
SETTINGS
Page 62 of 160 PR2: 04/22/13
Page 63
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 6: SAFETY DEVICE TESTING

6.1 TESTING OF SAFETY DEVICES

Periodic safety device testing is required to ensure that the control system and safety devices are operating properly. The boiler control system comprehensively monitors all combustion­related safety devices before, during and after the start sequence. The following tests check to ensure that the system is operating as designed.
Operating controls and safety devices should be tested on a regular basis or following service or replacement. All testing must conform to local codes such as ASME CSD-1.
NOTE
MANUAL and AUTO modes of operation are required to perform the following tests. For a complete explanation of these modes, see Chapter
3.
NOTE
It will be necessary to remove the front door and side panels from the unit to perform the following tests.
WARNING!
ELECTRICAL VOLTAGES IN THIS SYSTEM MAY INCLUDE 1 20 AND 24 VOLTS AC. POWER MUST BE REMOVED PRIOR TO PERFORMING WIRE REMOVAL OR OTHER TEST PROCEDURES THAT CAN RESULT IN EL ECTRICAL SHOCK.

6.2 NATURAL GAS LOW GAS PRESSURE FAULT TEST

Refer to Figure 6-1 and ensure that the leak detection ball valve located at the high gas pressure switch is closed.
1. Ensure that the Fuel Selector Switch (Figure 6-2) is set to the NATURAL GAS position.
2. Remove the 1/4“ plug from the ball valve at the natural gas low gas pressure switch shown in Figure 6-1.
3. Install a 0 – 16“ W.C. manometer or a W.C. gauge where the 1/4" plug was removed.
4. Slowly open the ball valve near the natural gas low gas pressure switch.
5. Place the unit in Manual Mode and adjust the valve position to 34%.
6. While the unit is firing, slowly close the external manual gas shut-off valve.
7. The unit should shut down and display a LOW GAS PRESSURE fault message at approximately 8.5” W.C. The FAULT indicator should also start flashing.
8. Fully open the external manual gas shut-off valve and press the CLEAR button on the Control Box.
9. The fault message should clear and the FAULT indicator should go off. The unit should restart.
10. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4“ plug removed in step 2.
PR2: 04/22/13 Page 63 of 160
Page 64
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
GAS
NATURAL GAS HIGH
GAS PRESSURE SWITCH
PROPANE GAS HIGH
PROPANE
INLET
NATURAL GAS INLET
MANUAL GAS SHUT-OFF VALVE
CHAPTER 6: SAFETY DEVICE TESTING
PROPANE SSOV
PROPANE LOW
GAS PRESSURE
SWITCH
1/4” PLUG
(Install manometer
here for Propane Low
Gas Pressure Test)
NATURAL GAS LOW
GAS PRESSURE SWITCH
GAS PRESSURE SWITCH
1/4” PLUG & LEAK DETECTION BALL VALVE (Install manometer here for High Gas Pressure Tests)
1/4” PLUG (Install manometer here for Natural Gas Low Gas Pressure Test)
NATURAL
SSOV
Figure 6-1: Low & High Gas Pressure Testing

6.3 PROPANE LOW GAS PRESSURE FAULT TEST

Refer to Figure 6-1 and ensure that the leak detection ball valve located at the high gas pressure switch is closed.
1. Ensure that the Fuel Selector Switch (Figure 6-2) is set to the PROPANE position.
2. Remove the 1/4“ plug from the ball valve at the propane low gas pressure switch shown in the upper-left p ortion of Figure 6 -1.
3. Install a 0 – 16 “ W.C. manometer or a W.C. gauge where the 1/4" plug was removed.
4. Slowly open the ball valve near the propane low gas pressure switch.
5. Place the unit in Manual Mode and adjust the valve position to 34%.
6. While the unit is firing, slowly close the external manual gas shut-off valve.
7. The unit should shut down and display a LOW GAS PRESSURE fault message at approximately 8.5” W.C. The FAULT indicator should also start flashing.
8. Fully open the external manual gas shut-off valve and press the CLEAR button on the Control Box.
9. The fault message should clear and the FAULT indicator should go off. The unit should restart.
10. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4“ plug removed in step 2.
Page 64 of 160 PR2: 04/22/13
Page 65
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 6: SAFETY DEVICE TESTING

6.4 NATURAL GAS HIGH GAS PRESSURE TEST

To simulate a natural gas high gas pressure fault, refer to Figure 6-1 and proceed as follows:
1. Ensure that the Fuel Selector Switch (Figure 6-2) is set to the NATURAL GAS position.
2. Remove the 1/4“ plug from the leak detection ball valve shown in Figure 6-1.
3. Install a 0 – 16” W.C. manometer (or W.C. gauge) where the 1/4” plug was removed.
4. Slowly open the leak detection ball valve
5. Start the unit in Manual mode at a valve position of 34%.
6. Slowly increase the gas pressure using the regulator adjustment screw on the natural gas SSOV.
7. The unit should shut down and display a HIGH GAS PRESSURE fault message when the gas pressure exceeds 10.5” W.C. The FAULT indicator should also start flashing.
8. Reduce the gas pressure back to 7.3” W.C.
9. Press the CLEAR button on the Control Box to clear the fault.
10. The fault message should clear and the FAULT indicator should go off. The unit should restart.
11. Upon test completion, close the leak detect-ion ball valve and remove the manometer. Replace the 1/4“ plug removed in step 2.

6.5 PROPANE HIGH GAS PRESSURE TEST

To simulate a propane high gas pressure fault, refer to Figure 6-1 and proceed as follows:
1. Ensure that the Fuel Selector Switch (Figure 6-2) is set to the PROPANE position.
2. Remove the 1/4“ plug from the leak detection ball valve shown in the upper portion of Figure 6-1.
3. Install a 0 – 16” W.C. manometer (or W.C. gauge) where the 1/4” plug was removed.
4. Slowly open the leak detection ball valve.
5. Start the unit in Manual mode at a valve position of 34%.
6. Slowly increase the propane gas pressure using the regulator adjustment screw on the propane SSOV.
7. The unit should shut down and display a HIGH GAS PRESSURE fault message when the gas pressure exceeds 3.5” W.C. The FAULT indicator should also start flashing.
8. Reduce the gas pressure back to 2.8” W.C.
9. Press the CLEAR button on the Control Box to clear the fault.
10. The fault message should clear and the FAULT indicator should go off. The unit should restart.
11. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4“ plug removed in step 2.
PR2: 04/22/13 Page 65 of 160
Page 66
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 6: SAFETY DEVICE TESTING

6.6 LOW WATER LEVEL FAULT TEST

To simulate a low water level fault:
1. Set the ON/OFF switch to the OFF position
2. Close the water shut-off valves in the supply and return piping to the unit.
3. Slowly open the drain valve on the rear of the unit. If necessary the unit’s relief valve may be opened to aid in draining.
4. Continue draining the unit until a LOW WATER LEVEL fault message is displayed and the FAULT indicator flashes.
5. Place the unit in the Manual Mode and raise the valve position above 30%.
6. Set the ON/OFF switch to the ON position. The READY light should remain off and the unit should not start. If the unit does start, shut the unit off immediately and refer fault to qualified service personnel.
7. Close the drain and pressure relief valve used in draining the unit.
8. Open the water shut-off valve in the return piping to the unit.
9. Open the water supply shut-off valve to the unit to refill.
10. After the shell is full, press the LOW WATER LEVEL RESET button to reset the low water cutoff.
11. Press the CLEAR button to reset the FAULT LED and clear the displayed error message.
12. Set the ON/OFF switch to the ON position. The unit is now ready for operation.

6.7 WATER TEMPERATURE FAULT TEST

A high water temperature fault is simulated by adjusting the automatic over-temperature switch. This switch is accessible from the front of the unit as shown in Figure 6-2.
1. Start the unit in the normal operating mode. Allow the unit to stabilize at its setpoint.
2. Lower the adjustable over-temperature switch setting to match the displayed OUTLET
TEMPERATURE.
3. Once the adjustable over-temperature switch setting is approximately at, or just below, the
actual outlet water temperature, the unit should shut down. The FAULT indicator should start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should be displayed. It should not be possible to restart the unit.
4. Reset the adjustable over-temperature switch to its original setting.
5. The unit should st art once the adjustable t emperature limit switch sett ing is above the actual
outlet water temperature.
Page 66 of 160 PR2: 04/22/13
Page 67
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 6: SAFETY DEVICE TESTING
Figure 6-2: Temperature Limit Switch Setting

6.8 INTERLOCK TESTS

The unit is equipped with two interlock circuits called the Remote Interlock and Delayed Interlock. Terminal connections for these circuits are located in the I/O Box (Figure 2-9) and are labeled REMOTE INTL’K IN and DELAYED INTL’K IN. These circuits can shut down the unit in the event that an interlock is opened. These interlocks are shipped from the factory jumpered (closed). However, each of these interlocks may be utilized in the field as a remote stop and start, an emergency cut-off, or to prove that a device such as a pump, gas booster, or louver is operational.

REMOTE INTERLOCK 6.8.1

1. Remove the cover from the I/O Box and locate the REMOTE INTL’K IN terminals.
2. Start the unit in the Manual Mode and set the valve position to 34%.
3. If there is a jumper across the REMOTE INTL’K IN terminals, remove one side of the jumper. If the interlock is being controlled by an external device, either open the interlock via the external device or disconnect one of the wires leading to the external device.
4. The unit should shut down and display INTERLOCK OPEN.
5. Once the interlock connection is reconnected, the INTERLOCK OPEN message should automatically clear and the unit should restart.
PR2: 04/22/13 Page 67 of 160
Page 68
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 6: SAFETY DEVICE TESTING

DELAYED INTERLOCK 6.8.2

1. Remove the cover from the I/O Box and locate the DELAYED INTL’K IN terminals.
2. Start the unit in the Manual Mode at a valve position between 25% and 30%.
3. If there is a jumper across the DELAYED INTL’K IN terminals, remove one side of the jumper. If the interlock is connected to a proving switch of an external device, disconnect one of the wires leading to the proving switch.
4. The unit should shut down and display a DELAYED INTERLOCK OPEN fault message. The FAULT LED should be flashing.
5. Reconnect the wire or jumper removed in step 3 to restore the interlock.
6. Press the CLEAR button to reset the fault.
7. The unit should start.

6.9 FLAME FAULT TESTS

Flame faults can occur during ignition or while the unit is already running. To simulate each of these fault conditions, proceed as follows:
1. Set the ON/OFF switch to the OFF position.
2. Place the unit in the Manual Mode and set the valve position to 34%.
3. Close the manual gas shutoff valve located between the Safety Shut-Off Valves (SSOVs) and the Air/Fuel Valve (see Figure 6-3).
4. Set the ON/OFF switch to the ON position to start the unit.
5. The unit should shut down after reaching the Ignition cycle and display FLAME LOSS DURING IGN.
6. Open the valve previously closed in step 3 and press the CLEAR button.
7. Restart the unit and allow it to prove flame.
8. Once flame is proven, close the manual gas valve located between the SSOV and the Air/Fuel Valve.
9. The unit should shut down and execute an IGNITION RETRY cycle by performing the following steps:
a) The unit will execute a shutdown purge cycle for a period of 15 seconds and
display WAIT FAULT PURGE.
b) The unit will execute a 30 second re-ignition delay and display WAIT RETRY
PAUSE.
c) The unit will then execute a standard ignition sequence and display WAIT
IGNITION RETRY.
10. Since the manual gas shutoff valve is still closed, the unit will fail the ignition retry
sequence. Therefore, it will shut down and display FLAME LOSS DURING IGNITION following the failed IGNITION RETRY cycle.
11. Open the valve previously closed in step 8.
12. Press the CLEAR button. The unit should restart and fire.
Page 68 of 160 PR2: 04/22/13
Page 69
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
PROPANE
SSOV
SWITCH
BLOCKED
SWITCH
CHAPTER 6: SAFETY DEVICE TESTING
BLOWER
PROOF
AIR/FUEL
VALVE
INLET
MANUAL GAS SHUTOFF VALVE
NATURAL
GAS
SSOV
Figure 6-3: Manual Gas Shut-Off Valve Location (Partial Left-Side View)

6.10 AIR FLOW FAULT TESTS

These tests check the operation of the Blower Proof Switch and Block ed Inlet Switch shown in Figure 6-3.
1. Disable the blower output drive voltage as follows: (a) Press the MENU key until CONFIGUR-ATION MENU is displayed. (b) Press the ▲ arrow key until the ANA-LOG OUTPUT function is displayed, then
press the CHANGE key.
(c) Press the ▼ arrow key until OFF is displayed, then press the ENTER key.
2. Start the unit in the Manual Mode at a valve position of 34%.
3. T he unit should shut down and execute an IGNITION RETRY cycl e by perform ing the
following steps:
(a) The unit will execute a 30 second re-ignition delay and display W AIT RETRY
PAUSE.
PR2: 04/22/13 Page 69 of 160
Page 70
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 6: SAFETY DEVICE TESTING
(b) The unit will then execute a standard ignition sequence and display WAIT
IGNITION RETRY.
4. The unit should perform one IGNITION RETRY cycle and then shut down, since the
blower is disabled. The unit will then display AIRFLOW FAULT DURING PURGE.
5. Re-enable the blower output drive voltage by performing the following steps: (a) Press the MENU key until CONFIGUR-ATION MENU is displayed. (b) Press the ▲ arrow key until the ANA-LOG OUTPUT function is displayed, then
press the CHANGE key.
(c) Press the ▲ arrow key until VALVE POSITION 0-10V is displayed, t hen press
the ENTER key.
6. Onc e the unit has proved flame, turn off the blower by going to the Configuration Menu,
Analog Output menu item and select OFF.
7. The Blower Proof Switch will open and the blower should stop. The unit should shut
down and display AIRFLOW FAULT DURING RUN.
8. Go to the Configuration Menu, Analog Output item and select VALVE POSITION 0-10v.
9. Pr es s the CLEAR button. The unit should restart.
10. Next, check the Blocked Inlet Switch by first noting the current position of the Iris Air
Damper and then closing the Damper to position 8.
11. .The unit should shut down and again display AIRFLOW FAULT DURING RUN.
12. Return the Iris Air Damper to its previous setting.
13. Press the CLEAR button. The unit should restart.

6.11 SSOV PROOF OF CLOSURE SWITCH

This test can be performed when the unit is set up to run on either natural gas or propane fuel. Both the Natural Gas and Propane SSOVs contain proof of closure switches which are wired in series.
1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in Manual Mode and set the valve position to 34%.
3. Refer to Figure 6-1 and locate the Natural Gas SSOV.
4. Remove the cover from the SSOV by loosening the screw shown in Figure 6-4. Lift off
the cover to access the terminal wiring connections.
5. Disconnect wire #148 from the SSOV to “open” the proof of closure switch circuit.
6. The unit should fault and display SSOV SWITCH OPEN.
7. Replace wire #148 and press the CLEAR button.
8. Set the ON/OFF switch to ON to restart the unit.
9. Remove the wire again when the unit reaches the purge cycle and PURGING is
displayed.
10. The unit should shut down and display SSOV FAULT DURING PURGE.
11. Replace wire #148 on the SSOV and press the CLEAR button. The unit should restart.
Page 70 of 160 PR2: 04/22/13
Page 71
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
ACTUATOR
COVER
SCREW
SSOV
ACTUATOR
COVER
CHAPTER 6: SAFETY DEVICE TESTING
Figure 6-4: SSOV Actuator Cover Location

6.12 IGNITION SWITCH OPEN DURING IGNITION

The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the switch, proceed as follows:
1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in Manual Mode and set the valve position to 34%.
3. Remove t he Air/Fuel Valve cover (Figure 6-5) by rotating the cover counterclockwise to
unlock and lift up to remove.
4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-6).
5. I nit iate a unit start sequence.
6. T he unit should begin it’s start sequence and then shut down and display IGN SWITCH
OPEN DURING IGNITION.
7. Replace the wire on the Ignition Switch and press the CLEAR button. The unit should
restart.

6.13 PURGE SWITCH OPEN DURING P URGE

The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. T o check the switch, proceed as follows:
1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and set
the valve position to 34%.
2. Remove the Air/ Fuel Valve cover by rotating the cover counterclockwise to unlock it and
then remove the cover (see Figure 6-5).
3. Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 6-6).
4. I nit iate a unit start sequence.
5. The unit should begin it’s start sequence, then shut down and display PRG SWITCH
OPEN DURING PURGE.
6. Replace the wire on t he Purge Switch and depress the CLEAR button. The unit should
restart.
PR2: 04/22/13 Page 71 of 160
Page 72
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
AIR/FUEL VALVE COVER (ROTATE CCW TO REMOVE)
STEPPER
MOTOR
DIAL
172
171
169
170
IGNITION
POSITION
SWITCH
PURGE
POSITION
SWITCH
AIR
IN
TO
BLOWER
CHAPTER 6: SAFETY DEVICE TESTING
Figure 6-5: Air/Fuel Valve Cover Location
Figure 6-6: Air/Fuel Valve Purge and Ignition Switch Locations

6.14 SAFETY PRESSURE RELIEF VALVE TEST

Test the safety Pressure Relief Valve in accordance with ASME Boiler and Pressure Vessel Code, Section VI.
Page 72 of 160 PR2: 04/22/13
Page 73
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Labor
Time
Igniter-Injector
(58023)
Flame Detector
(66006)
7.4
Combustion Calibration
*Check
Check
-
1 hr.
7.6
Burner
- - Inspect
2 hrs.
Inspect &
Clean

CHAPTER 7: MAINTENANCE

7.1 MAINTENANCE SCHEDULE

The unit requires regular routine maintenance to keep up efficiency and reliability. For best operation and life of the unit, the following routine maintenance procedures should be performed in the time periods specified in Table 7-1. See Appendix I for a complete CSD-1 inspection check list.
In order to perform the maintenance tasks specified in Table 7-1, the following maintenance kits are available through your local AERCO Sales Representative:
Annual Maintenance Kit, Part No. 58025-01
24-Month Waterside/Fireside Inspection Kit, Part No. 58025-06 (See NOTE below)
NOTE
The 24-Month Waterside/Fireside Inspection Kit also includes the items contained in the Annual Maintenance Kit. Therefore, only Kit Part No. 58025-06 is required when performing the waterside/fireside inspections.
Appendix K contains recommended spare parts lists for maintenance of the boiler.
WARNING
TO AVOID PERSONAL INJURY, PRIOR TO SERVICING ENSURE THAT THE FOLLOWING GUIDELINES ARE STRICT L Y OBSERVED:
DISCONNECT THE AC SUPPLY BY TURNING OFF THE SERVICE SWITCH AND AC SUPPLY CIRCUIT BREAKER.
SHUT OFF THE GAS SUPPLY AT THE MANUAL SHUT- OFF VALVE PROVIDED WITH THE UNIT
ALLOW THE UNIT TO COOL TO A SAFE WATER TEMPERATURE TO PREVENT BURNING OR SCALDING
Table 7-1: Maintenance Schedule
Paragraph Item 6 M os. 12 Mos. 24 Mos.
7.2
7.3
7.5 Testing of Safety Devices -
*Inspect Inspect Replace 15 mins. *Inspect Inspect Replace 15 mins.
See CSD-1
Chart in
Appendix I
- 20 mins.
7.7 Condensate Drain Trap *Inspect
*Only performed after initial 6 month period after initial startup.
PR2: 04/22/13 Page 73 of 160
- 30 mins.
Page 74
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
AIR/FUEL
VALVE
STAGED
IGNITION
ASSEMBLY
FLAME DETECTOR
IGNITOR-
INJECTOR
BLOWER
BURNER
PLATE
BURNER
CHAPTER 7: MAINTENANCE

7.2 IGNITER-INJECTOR

The igniter-injector (part no. 58023) is located on the burner plate at the top of the boiler. In addition to providing the ignition spark required to light the burner, the igniter-injector also contains a gas injector tube which connects to the staged ignition assembly. Figure 7-1 shows the complete burner assembly removed from the boiler and indicates the location of the igniter­injector flame detector and other related components.
The igniter-injector may be hot, therefore, care should be exercised to avoid burns. It is easier to remove the igniter-injector from the unit after the unit has cooled to room temperature.
Figure 7-1: Benchmark 2.0LN Burner Assembly (Shown Removed from Boiler)
To inspect/replace the Igniter:
1. Set the ON/OFF switch on the contr ol panel, to the OFF position. Disconnect AC power from the unit
2. Remove the side and top panels from the unit.
3. Disconnect the cable from the igniter-injector (Figure 7-1).
4. Refer to the partial exploded view in Figure 7-2. Using a 7/16” open-end wrench, disconnect the compression nut securing the gas injector tube of the igniter-injector to the elbow of the staged ignition assembly. Disconnect the staged ignition assem bly from the igniter-injector.
Page 74 of 160 PR2: 04/22/13
Page 75
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
STAGED
IGNITION
ASSEMBLY
FLAME DETECTOR
IGNITOR-
INJECTOR
BURNER
PLATE
COMPRESSION
FITTING & ELBOW
FLAME DETECTOR GASKET
INDEXING
WASHERS
(QTY = 0-3
AS REQ’D)
CHAPTER 7: MAINTENANCE
IMPORTANT
Prior to removing the igniter-injector, note the position of the gas injector tube relative to the burner plate and blower. This is necessary to ensure that the igniter injector is reinstalled in the proper orientation when it is reconnected to the staged ignition assembly.
Figure 7-2: Igniter-Injector & Flame Detector Mounting Details
5. Next, loosen and remove the igniter -injector from the burner plate using a 1" open-end wrench.
6. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence of substantial erosion or carbon build-up, the ig niter-injector should be replaced. If carbon build-up is present, clean the component using f ine emery cloth. Repeated carbon build­up is an indication that the combustion settings of the unit should be checked. Refer to Chapter 4 for combustion calibration procedures.
7. Prior to reinstalling the igniter-injector, a high temperature, conductive, anti-seize com­pound must be applied to the threads.
If a replacement igniter-injector (part no. 58023) is being installed, a compression nut containing a built-in ferrule will be included with the replacement part. If needed, three indexing washers are also included These washers may be needed to properly position the gas injector tube of the igniter-injector within the 120° angle range shown in Figure 7-3.
NOTE
PR2: 04/22/13 Page 75 of 160
Page 76
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
120
IGNITOR-
INJECTOR
GAS
INJECTOR
TUBE
BLOWER
BURNER
PLATE
CHAPTER 7: MAINTENANCE
Figure 7-3: Igniter-Injector Orientation
8. Reinstall the igniter-injector in the burner plate. Torque to 15 ft-lbs. Do not over tighten.
9. Connect the staged ignition assembly to the gas injector tube of the igniter-injector by securing the compression nut to the elbow of the staged ignition assembly.
10. Reconnect the igniter-injector cable.
11. Reinstall the side and top panels on the unit.

7.3 FLAME DETECTOR

The flame detector (part no. 66006) is located on the burner plate at the top of the unit (see Figures 7-1 and 7-2). The flame detector may be hot. Allow the unit to cool sufficiently before removing the flame detector.
To inspect or replace the flame detector:
1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from the unit.
2. Remove the side and top panels from the unit.
3. Disconnect the flame detector lead wire.
4. Remove the two (2) screws securing the flame detector to the plate (Figure 7-2 on previous page). The flame detector is secured to the burner plate with one (1) #10-32 screw and one (1) #8-32 screw.
5. Remove the flame detector and gasket from the burner plate.
6. Thoroughly inspect the flame detector. If eroded, the detector should be replaced. Otherwise clean the detector with a fine emery cloth.
7. Reinstall the flame detector and flame detector gasket.
8. Reconnect the flame detector lead wire.
9. Reinstall the side and top panels on the unit.
Page 76 of 160 PR2: 04/22/13
Page 77
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Part No.
Description
81101
Burner Gaskets (2)
81048
Flame Detector Gasket
81068
Blower Gasket
CHAPTER 7: MAINTENANCE

7.4 COMBUSTION CALIBRATION

The Combustion Calibration settings must be checked at the intervals shown in Table 7-1 as part of the maintenance requirements. Refer to Chapter 4 for combustion calibration instructions.

7.5 SAFETY DEVICE TESTING

Systematic and thorough tests of the operating and safety devices should be performed to ensure that they are operating as designed. Certain code requirements, such as ASME CSD-1, require that these tests be performed on a scheduled basis. Test schedules must conform to local jurisdictions. The results of the tests should be recorded in a log book. See Chapter 6­Safety Device Testing Procedures.

7.6 BURNER ASSEMBLY INSPECTION

The burner assembly (part no. 24176) is located at the top of the unit's heat exchanger. The burner assembly may be hot. Therefore, allow the unit to cool sufficiently before removing the burner assembly. It should be noted that the complete burner assembly also includes the blower and air/fuel valve in addition to the Benchmark 2.0 Low NOx burner. The following par ts will be required for reassembly after burner inspection:
To inspect or replace the burner assembly:
1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from the unit and turn off the gas supply.
2. Remove the side and top panels from the unit.
3. Disconnect the lead wire fr om the flame detector installed on the burner plate. See Fig ure 7-5.
PR2: 04/22/13 Page 77 of 160
Page 78
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
IGNITOR-
INJECTOR
3/8-16
NUTS (8)
BLOWER
BURNER
PLATE
AIR/FUEL
VALVE
FLAME
DETECTOR
STAGED
IGNITION
ASSEMBLY
1/2” BOLTS & NUTS (4)
CONNECT AIR/FUEL VALVE
TO GAS TRAIN
GROUNDING
SCREW
(10-32 x 1/2" LG.)
CHAPTER 7: MAINTENANCE
Figure 7-5: Burner Assembly Mounting Details
4. Remove the two (2) screws securing the flame detector to the plate. The flame detector is secured to the burner plate with one (1) #10-32 screw and one (1) #8-32 screw.
5. Remove the flame detector and gasket from the burner plate.
6. Disconnect the cable from the igniter-injector.
7. Using a 7/16” open-end wrench, disconnect the compression nut securing the gas injector tube of the igniter-injector to the elbow of the staged ignition assembly (see Figure 7-2). Disconnect the staged ignition assembly from the igniter-injector.
IMPORTANT
Prior to removing the igniter-injector, note the position of the gas injector tube relative to the burner plate and blower. This is necessary to ensure that the igniter injector is reinstalled in the proper orientation when it is reconnected to the staged ignition assembly.
8. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end wrench.
9. Disconnect the unit wiring harness connectors from the air/fuel valve and blower motor.
10. Disconnect the wire leads connected to the blower proof switch and blocked inlet switch (Figures 7-6).
11. Remove the 10-32 x 1/2" long grounding screw from the burner plate (Figures 7-4).
12. Disconnect the gas train from the air/fuel valve by removing the four (4) 1/2” bolts and nuts (Figure 7-5).
Page 78 of 160 PR2: 04/22/13
Page 79
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
BLOWER
PROOF
SWITCH
BLOCKED
INLET
SWITCH
AIR/FUEL
VAVLE
STAGED
IGNITION
ASSEMBLY
FLAME DETECTOR
BURNER
PLATE
HEX NUTS &
WASHERS (6)
BLOWER
GASKET
IGNITOR-
INJECTOR
BURNER
BLOWER
BURNER
GASKET
BURNER
GASKET
CHAPTER 7: MAINTENANCE
13. Disconnect the inlet air flex hose from the air/fuel valve by loosening the hose clamp.
14. Remove the six (6) 1/4-20 hex nuts and flat washers securing the blower to the burner plate (Figure 7-6).
15. Remove the blower and air/fuel valve from the burner plate by lifting straight up. Also, remove the blower gasket, which will be replaced with a new gasket.
16. Remove the eight (8) 3/8-16 nuts from the burner flange (Figure 7-5) using a 9/16” wrench.
Figure 7-6: Burner Assembly Exploded View
NOTE
The burner assembly is heavy, weighing approximately 30 pounds.
17. Remove the burner assembly from burner flange by pulling straight up.
18. Remove and replace the two (2) burner gaskets.
During reassembly, apply high-temperature, anti-seize lubricant to the threads of the igniter-injector and grounding screw. Also, ensure that the igniter-injector is properly positioned as indicated in Figure 7-3. Torque the
NOTE
igniter-injector to 15 ft-lbs.
PR2: 04/22/13 Page 79 of 160
Page 80
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 7: MAINTENANCE
19. Beginning with the burner assembly removed in step 17, reinstall all the components in the reverse order that they were removed. During re-assembly, replace the gaskets for the blower and flame detector with new ones.
20. Be sure to align the igniter-injector and flame detector tapped holes in the burner plate with the heat exchanger top head.
21. Check to ensure that the grounding screw is installed.

7.7 CONDENSATE DRAIN TRAP

The Benchmark 2.0LN Boiler contains a condensate trap as shown in Chapter 2, Figure 2-5. The trap is located external to the unit and attached to the drain pipe from the exhaust manifold. This trap should be inspected and, if necessary, cleaned to ensure proper operation.
NOTE
There are two slightly different types of condensate tr aps that may be used in your configuration; an older style without an inlet adapter, and a newer style with a built-in inlet ad apter (see Figure
7.5). Maintenance is the same, except that the newer s tyle does not need an orifice gasket (Step 6).
To inspect and clean the trap, proceed as follows:
1. Disconnect the external condensate trap by loosening the union pipe connection between the trap and the exhaust manifold drain pipe.
2. Remove the connections on the inlet and outlet sides of the condensate trap shown in Figure 7-7.
3. Loosen the four (4) thumbscrews securing the cover on the condensate trap. Remove the cover.
4. Remove the float from the condensate trap.
5. Remove the orifice gasket from the trap.
6. Thoroughly clean the trap, float and gasket. Also inspect the drain piping for blockage. If the trap cannot be thoroughly cleaned, replace the trap.
7. After the above items have been inspected and thoroughly cleaned, replace the orifice gasket and float in the condensate trap and replace the trap cover.
8. Reassemble all piping and hose connections to the condensate trap inlet and outlet. Reconnect trap to exhaust manifold drain.
Page 80 of 160 PR2: 04/22/13
Page 81
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 7: MAINTENANCE
Figure 7-7: External Condensate Trap

7.8 SHUTTING THE BOILER DOWN FOR AN EXTENDED PERIOD OF TIME

If the boiler is to be taken out of s ervice for an extended period of time (one year or more) , the following instructions must be followed.
1. Set ON/OFF switch on the front panel to the OFF position to shut down the boiler’s operating controls.
2. Disconnect AC power from the unit.
3. Close the water supply and return valves to isolate boiler.
4. Close external gas supply valve.
5. Open relief valve to vent water pressure.

7.9 PLACING THE BOILER BACK IN SERVICE AFTER A PROLONGED SHUTDOWN

After a prolonged shutdown (one year or more), the following procedures must be followed:
1. Review installation requirements included in Chapter 2.
2. I nspec t all piping and connections to the unit.
3. I nspec t exhaust vent, air duct (if applicable).
4. Perf orm initial startup per Chapter 4.
5. Perform safety device testing and scheduled maintenance procedures per Chapters 6 and
7 of this manual.
PR2: 04/22/13 Page 81 of 160
Page 82
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 7: MAINTENANCE
(This page intentionally blank)
Page 82 of 160 PR2: 04/22/13
Page 83
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 8: TROUBLESHOOTING GUIDE

8.1 INTRODUCTION

This troubleshooting guide is intended to aid service/maintenance personnel in isolating the cause of a fault in a Benchmark 2.0LN Boiler. The tr oubleshoot ing proc edures cont ained her ein are presented in tabular form on the following pages. These tables are comprised of three columns labeled: Fault Indication, Probable Cause and Corrective Action. The numbered items in the Probable Cause and Corrective Action columns correspond to each other. For example, Probable Cause No. 1 corresponds to Corrective Action No. 1, etc.
NOTE
The front panel of the C-More Control Box contains an RS232 port which can be interfaced to a laptop computer or other suitable device. This RS232 communication feature permits service personnel to view menu items and data logs which can be useful in isolating faults. Refer to Chapter 9 of this manual for detailed RS232 communication set-up and procedures.
When a fault occurs in the Benchmark Boiler, proceed as follows to isolate and correct the fault:
1. Observe the fault messages displayed in the Control Box display.
2. Refer to the Fault Indication column in Troubleshooting Table 8-1 which follows and
locate the Fault that best describes the existing conditions.
3. Proceed to the Probable Cause column and start with the first item (1) listed for the Fault
Indication.
4. Perform the checks and procedures listed in the Corrective Action colum n for the first
Probable Cause candidate.
5. Continue checking each additional Probable Cause for the existing fault until the f ault is
corrected.
6. Paragraph 8.2 and Table 8-2 contain additional troubleshooting information which may
apply when no fault message is displayed.
7. If the fault cannot be corrected using the information provided in the Troubleshooting Tables, contact your local AERCO Representative.
PR2: 04/22/13 Page 83 of 160
Page 84
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
INDICATION
1. Blower stopped running due to thermal or
1. Check combustion blower for signs of excessive heat or high
FAULT
TABLE 8-1. BOILER TROUBLESHOOTING
PROBABLE CAUSES CORRECTIVE ACTION
current overload
2. Blocked Blower inlet or inlet ductwork
3. Blocked Blower proof switch
4. Blocked blocked-air inlet switch
AIRFLOW FAULT
DURING IGNITION
5. Defective Blower proof switch
6. Defective blocked-air inlet switch
7. Loose temperature to AUX connection in I/O Box
8. Defective temperature sensor
9. Loos e wire co nnec t ion bet ween the 0-10V
signal from I/O box to the Blower Motor input.
10. Defective I/O box
11. Wrong 0-10V output selection on the
control box
12. Defective Air-Fuel Valve potentiometer
current drain that may trip thermal or current overload devices.
2. Inspect the inlet to the combustion blower including any ductwork leading up to the combustion blower for signs of blockage.
3. Remove the Blower proof switch and inspect for signs of blockage, clean or replace as necessary.
4. Remove the blocked-air inlet switch and inspect for signs of blockage, clean or replace as necessary.
5. Measure the Blower proof switch for continuity with the combustion blower running. If there is an erratic resistance reading or the resistance reading is greater than zero ohms, replace the switch.
6. Measure the blocked-air inlet switch for continuity with the combustion blower running. If there is an erratic resistance reading or the resistance reading is greater than zero ohms, replace the switch.
7. Check the actual inlet air temperature and measure voltage at AUX input in the I/O Box. Verify that the voltage conforms to the values shown in the tabular listing provided in Appendix C.
8. Refer to CORRECTIVE ACTION 7 and verify that the voltage conforms to the values shown in Appendix C.
9. Check wire connection from I/O Box 0-10V signal to the Blower Motor.
10. Measure voltage at the I/O box 0-10V output. A voltage of 8.2V equates to a 100% open valve position.
11. Check the Analog Out optio n on the C-More Configuration Menu. Valve Position 0-10V should be selected.
12. Check Air/Fuel Valve position at 0%, 50% and 100% open positions. The positions on the VALVE POSITION bargraph should match the dial readings on the Air/Fuel Valve dial.
PR2: 04/22/13 Page 84 of 160
Page 85
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
stion blower including any
ductwork leading up to the combustion blower for signs of
including any
ductwork leading up to the combustion blower for signs of
CHAPTER 8: TROUBLESHOOTING GUIDE
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
1. Blower not running or running too slow
2. Defective Air Flow Switch
3. Blocked Air flow Switch
AIRFLOW FAULT
DURING PURGE
AIRFLOW FAULT
DURING RUN
4. Blocked Blower inlet or inlet ductwork.
5. No voltage to switch from control box.
6. PROBABLE CAUSES from 3 to 12 for AIRFLOW FAULT DURING IGNITION applies for this fault
1. Blower stopped running due to thermal or current overload
2. Blocked Blower inlet or inlet ductwork
3. Blocked airflow switch
4. Defective airflow switch
5. Combustion oscillations
6. PROBABLE CAUSES from 3 to 16 for AIRFLOW FAULT DURING IGNITION applies for this fault
1. Start the unit. If the blower does not r un check the blower solid state relay for input and output voltage. If the relay is okay, check the blower.
2. Start the unit. If the blower runs, check the airflow switch for continuity. Replace the switch if there is no continuity.
3. Remove the air flow switch and inspect for signs of blockage, clean or replace as necessary.
4. Inspect the inlet to the combu blockage.
5. Measure for 24 VAC during start sequenc e from eac h side of the switch to ground. If 24VAC is not present refer to qualified service personnel.
6. See CORRECTIVE ACTIONS from 3 to 12 for AIRFLOW FAULT DURING IGNITION.
1. Check combustion blower for signs of excessive heat or high current draw that may trip thermal or current overload devices.
2. Inspect the inlet to the combustion blower blockage.
3. Remove the airflow switch and inspect for signs of blockage, clean or replace as necessary.
4. Measure the airflow switch for continuity with the combustion blower running. If there is an erratic resistance reading or the resistance reading is greater than zero ohms, replace the switch.
5. Run unit to full fire. If the unit rumbles or runs rough, perform combustion calibration.
6. See CORRECTIVE ACTIONS from 3 to 16 for AIRFLOW FAULT DURING IGNITION.
PR2: 04/22/13 Page 85 of 160
Page 86
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
INDICATION
functional. (jumper ma y be temporar il y installed to test interlock)
(voltage or current).
Configuration Menu.
CHAPTER 8: TROUBLESHOOTING GUIDE
FAULT
PROBABLE CAUSES CORRECTIVE ACTION
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
DELAYED
INTERLOCK OPEN
DIRECT DRIVE SIGNAL FAULT
FLAME LOSS
DURING IGN
1. Delayed Interlock Jumper not installed or removed.
2. Device proving switch hooked to interlocks is not closed
1. Direct drive signal is not present: Not yet installed. Wrong polarity. Signal defective at source. Broken or loose wiring.
2. Signal is not isolated (floating).
3. Control Box signal type selection switches not set for correct signal type
1. Burner Ground Screw not installed or loose.
2. Worn flame detector
3. No spark from Spark Plug
4. Defective Ignition Transformer
5. Defective Ignition/Stepper (IGST) Board
6. Defective SSOV
1. Check for a jumper properly installed across the delayed interlock terminals in the I/O box.
2. If there are 2 external wires on these terminals, check to see if an end switch for a device such as a pump, louver, etc. is tied these interlocks. Ensure that the device and or its end switch are
1. Check I/O Box to ensure signal is hooked up. Hook up if not installed. If installed, check polarity. Measure signal level. Check continuity of wiring between source and boiler.
2. Check signal at source to ensure it is isolated.
3. Check DIP switch on PMC board to ensure it is set correctly for the type of signal being sent. Check control signal type set in
1. Inspect and install/retighten Burner Ground Screw.
2. Remove and inspect the flame detector for signs of wear. Replace if necessary.
3. Close the internal gas valve in the boiler. Install and arc a spark igniter outside the unit.
4. If there is no spark, check for 120VAC at the primary side to the ignition transformer during the ignition cycle.
5. If 120VAC is not present, the IGST Board in the Control Box may be defective. Refer fault to qualified service personnel.
6. While externally arcing the spark igniter, observe the open/close indicator in the Safety Shut-Off Valve to ensure it is opening. If the valve does not open, check for 120VAC at the valves input terminals. If 120VAC is not present, the IGST board in the Control Box may be defective. Refer fault to qualified service personnel.
Page 86 of 160 PR2: 04/22/13
Page 87
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
2030:
5. Remove blockage in condensate drain.
2. Relay is activated when not in Demand.
unit. If the fault
sudden changes (see Fig. 8-1).
CHAPTER 8: TROUBLESHOOTING GUIDE
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
FLAME LOSS
DURING IGN
(continued)
FLAME LOSS
DURING RUN
HEAT DEMAND
FAILURE
HIGH GAS
PRESSURE
7. Unstable gas pressure.
8. Carbon or other debris on Burner.
9. Staged ignition solenoid valves don’t open.
10. Clogged staged ignition piece.
1. Worn Flame Detector or cracked ceramic.
2. Defective Regulator.
3. Poor combustion calibration.
4. Debris on burner.
5. Blocked condensate drain.
1. The Heat Demand Relays on the Ignition/Stepper board failed to activate when commanded.
1. Incorrect supply gas pressure.
2. Defective gas pressure adjustment in SSOV Actuator.
3. Defective High Gas Pressure Switch
4. Gas pressure snubber not installed.
5. Fluctuating supply gas pressure.
7. Refer to “Gas Pressure Requirem ents” section of GF­BMK Gas Supply Design Guide.
8. Remove the burner and inspect for any carbon or debris.
Clean and reinstall.
9. When boiler goes to ignition, listen to th e solenoid valves
for a clicking sound to ensure they are opening.
10. Remove and inspect staged ignition piece for blockage.
1. Remove and inspect the Flame Detector for signs of wear or cracked ceramic. Replace if necessary.
2. Check gas pressure readings using a gauge or manometer into and out of the Air/Fuel Valve to ensure that the gas pressure into and out of the valve is correct.
3. Check combustion calibration. Adjust as necessary.
4. Remove the burner and inspect for any carbon or debris. Clean and reinstall.
1. Press CLEAR button and restart the persists, replace Ignition/Stepper (IGST) Board.
2. Defective relay. Replace IGST Board.
Check to ensure gas pressure at inlet of SSOV is 2 psig maximum.
1.
2. If gas supply pressure downstream of SSOV Actuator cannot be
lowered, to 2.8” W.C. (or 2.3” W.C. for propane), using the gas pressure adjustment screw (see para. 4.3, step 10), the SSOV Actuator gas pressure adjustment mechanism may be defective. See para. 4.3, Step 10 (nat. gas) or 4.4, Step 10 (propane).
3. Remove the leads from the high gas pressure switch and measure
continuity across the common and normally closed terminals with the unit not firing. Replace the switch if it does not show continuity.
4. See Figure 8-1. Ensure that the gas pressure snubber is installed at
the high gas pressure switch.
5. Measure gas pressure upstream of SSOV and monitor for
PR2: 04/22/13 Page 87 of 160
Page 88
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
INDICATION
board
CHAPTER 8: TROUBLESHOOTING GUIDE
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
FAULT
HIGH WATER
TEMP
SWITCH OPEN
PROBABLE CAUSES CORRECTIVE ACTION
1. Faulty Water temperature switch.
2. Incorrect PID settings.
3. Faulty shell temperature sensor.
4. Unit in Manual mode.
5. Unit setpoint is greater than Over Temperature Switch setpoint.
6. Boiler Management System/AERCO Control System PID or other settings not correctly setup.
7. No interlock to boiler or BMS/ACS to disable boiler(s) in event that system pumps have failed.
8. System flow rate changes are occurring faster than boilers can respond.
1. Test the temperature switch to insure it trips at its actual water temperature setting.
2. Check PID settings against Menu Default settings in the Appendix. If the settings have been changed, record the current readings then reset them to the default values.
3. Using the resistance charts in the Appendix C, Measure the resistance of Shell sensor and BTU sensor at a known water temperature.
4. If unit is in Manual Mode switch to Auto Mode.
5. Check setpoint of unit and setpoint of Temperature Switch; Ensure that the temperature switch is set higher than the unit’s setpoint.
6. Check the BMS/ACS for changes to PID default values, correct as necessary.
7. If system pump is controlled by Energy Management System other than BMS/ACS or pumps are individually controlled by boiler, check to see if there are flow switches interlocked to the BMS/ACS or boiler.
8. If the system is a variable flow system, monitor system flow changes to ensure that the rate of flow change is not faster than what the boilers can respond to.
1. See HIGH WATER TEMPERATURE SWITCH
HIGH WATER
TEMPERATURE
IGN BOARD
COMM FAULT
Page 88 of 160 PR2: 04/22/13
OPEN.
2. Temp HI Limit setting is too low.
1. Communication fault has occurred between the PMC board and Ignition/Stepper (IGST)
1. See HIGH WATER TEMPERATURE SWITCH OPEN.
2. Check Temp HI Limit setting.
1. Press CLEAR button and restart unit. If fault persists, contact qualified Service Personnel.
Page 89
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
the Air/Fuel Valve calibration. If
CHAPTER 8: TROUBLESHOOTING GUIDE
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
IGN SWTCH CLOSED
DURING PURGE
IGN SWTCH OPEN
DURING IGNITION
1. Air/Fuel Valve not rotating
2. Defective or shorted switch
3. Switch wired incorrectly
4. Defective Power Supply Board or fuse
5. Defective IGST Board
1. Air/Fuel Valve not rotating to ignition position.
2. Defective ignition switch
3. Defective Power Supply Board or fuse
4. Defective IGST Board
1. Start the unit. The Air/Fuel Valve should rotate to the purge (open) position. If the valve does not rotate at all or does not rotate fully open, check the Air/Fuel Valve calibration. If calibration is okay, the problem may be in the Air-Fuel Valve or the Control Box. Refer to qualified service personnel
2. . If the Air/Fuel Valve does rotate to purge, check the ignition switch for continuity between the N.O. and COM terminals. If the switch shows continuity when not in contact with the cam replace the switch.
3. Check to ensure that the switch is wired correctly (correct wire numbers on the normally open terminals). If the switch is wired correctly, replace the switch
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board.
1. Start the unit. The Air/Fuel Valve should rotate to the purge (open) position, then back to ignition position (towards closed) during the ignition c ycle. If the valve does not rotate b ack to the ignition position, check calibration is ok ay, the problem may be in the A ir/Fuel Valve or the Control Box. Refer fault to qualified service personnel.
2. If the Air/Fuel Valve does rotate to the ignit io n p ositi on , c hec k the ignition position switc h for continuity between the N.O. and COM terminals when in contact with the cam.
3. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
4. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board.
PR2: 04/22/13 Page 89 of 160
Page 90
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
INDICATION
1. Interlock jumper not installed or
wiring.
continuity.
FAULT
Boiler not seeing information from Valve or the Control Box. Refer fault to qualified service personnel.
CHAPTER 8: TROUBLESHOOTING GUIDE
FAULT
PROBABLE CAUSES CORRECTIVE ACTION
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
INTERLOCK
OPEN
LINE
VOLTAGE
OUT OF
PHASE
LOW GAS
PRESSURE
LOW WATE R
LEVEL
removed
2. Energy Management System does not have boiler enabled.
3. Device proving switch hooked to interlocks is not closed.
1. Line and Neutral switched in AC Power Box.
2. Incorrect power supply transformer
1. Incorrect supply gas pressure.
2. Defective Low Pressure Gas Switch
1. Insufficient water level in system
2. Defective water level circuitry.
3. Defective water level probe.
1. Check for a jumper properly installed across the interlock terminals in the I/O box
2. If there are two external wires on these terminals check any Energy Management system to see if they have the units disabled (a jumper may be temporarily installed to see if the interlock circuit is functioning).
3. Check that proving switch for any device hooked to the interlock circuit is closing and that the device is operational.
1. Check hot and neutral in AC Power Box to ensure they are not reversed
2. Check transformer wiring, in AC Power Box, against the power box transformer wiring diagram to ensure it is wired correctly
1. Measure gas pressure upstream of the supply gas regulator with the unit firing. Refer to paragraph 2.7.1 to ensure that the gas pressure is correct for the type of fuel and gas train being used.
2. Measure gas pressure at the low gas pressure switch. If it is greater than
2.6” W.C. (or 2.1"W.C. for propane), measure continuity across the switch and replace if necessary.
1. Check system for sufficient water level.
2. Test water level circuitry using the Control Box front panel LOW WATER TEST and RESET buttons. Replace water level circuitry if it does not respond.
3. Check continuity of probe end to the shell, change probe if there is no
MODBUS
COMM
PRG SWTCH
CLOSED
DURING
IGNITION
Page 90 of 160 PR2: 04/22/13
1. Modbus network
1. A/F Valve rotated open to purge and did not rotate to ignition position.
1. Check network connections. If fault persists, contact qualified Service Personnel.
1. Start the unit. The Air/Fuel Valve shoul d rotate to t he purge ( open) pos ition, then back to ignition p osition (towards closed) during the ign ition cycle. If the valve does not rotate back to the ignition position, check the Air/Fuel Valve calibration. If calibra tion is okay, the problem may be in the Air/Fuel
Page 91
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
second. If not, replace IGST Board.
5. Defective IGST Board
the switch is wired correctly (correct wire
3. Incorrect Sensor.
1. Remote setpoint signal not present:
(voltage or current).
CHAPTER 8: TROUBLESHOOTING GUIDE
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
PRG SWTCH
CLOSED
DURING IGNITION
(continued)
PRG SWTCH OPEN
DURING PURGE
OUTDOOR TEMP
SENSOR FAULT
2. Defective or shorted switch.
3. Switch wired incorrectly.
4. Defective Power Supply Board or fuse
5. Defective IGST Board
1. Defective purge switch.
2. No voltage present at switch.
3. Switch wired incorrectly.
4. Defective Power Supply Board or fuse
1. Loose or broken wiring.
2. Defective Sensor.
2. If the Air/Fuel Valve does rotate to the ignition position, check the purge switch for contin uity between the N.O. and COM terminals. If the switch shows cont inuity when not i n contact with the c am, check to ensure that the switc h is wired correctly (cor rect wire numbers on the normally open terminals).
3. If the switch is wired correctly, replace the switch.
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS 1 and ver if y it is blink ing O N & OF F e very
1. If the air-fuel valve does r otate, check the purge s witch for conti nuity when closing. Replace switch if continuity does not exist.
2. Measure for 24 VAC from each side of the switch to ground. If 24VAC is not present, refer fault to qualified service personnel.
3. Check to ensure that numbers on the normally open terminals).
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS 1 and ver if y it is blink ing ON & OFF e ver y second. If not, replace IGST Board.
1. Inspect Outdoor Temperature sensor for loose or broken wiring.
2. Check resistance of sensor to determine if it is within specification.
3. Ensure that the correct sensor is installed.
Not yet installed. Wrong polarity. Signal defective at source.
REMOTE SETPT
SIGNAL FAULT
PR2: 04/22/13 Page 91 of 160
Broken or loose wiring.
2. Signal is not isolated (floating) if 4 to 20 mA.
3. Control Box signal type selection switches not set for correct signal type
1. Check I/O Box to ensure signal is hooked up. Hook up if not installed. If installed, check polarity. Measure signal level. Check continuity of wiring between source and boiler.
2. Check signal at source to ensure it is isolated.
3. Check DIP switch on PMC board to ensure it is set correctly for the type of signal being sent. Check control signal type set in Configuration Menu.
Page 92
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
INDICATION
1. SSOV not fully closed.
2. Replace Flame Detector.
PURGE
DURING RUN
SSOV switch closed for 15
3. Hot and Neutral reversed at SSOV.
4. Ensure that the SSOV Proof of Closure switch is correctly wired.
Stepper Feedback Calibration (GF-112, paragraph 6.2.1).
CHAPTER 8: TROUBLESHOOTING GUIDE
FAULT
RESIDUAL
FLAME
PROBABLE CAUSES CORRECTIVE ACTION
2. Defective Flame Detector
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
1. Check open/close indicator window of Safety Shut-Off Valve (SSOV) and ensure that the SSOV is fully closed. If not fully closed, replace the valve and or actuator.
Close gas shut-off valve downstream of SSOV. Install a manometer or gauge in a gas test port between the SSOV and the gas shut off valve. If a gas pressure reading is observed replace the SSOV valve and or actuator.2.
SSOV FAULT
DURING
SSOV FAULT
SSOV RELAY
FAILURE
SSOV
SWITCH
OPEN
STEPPER
MOTOR
FAILURE
See SSOV SWIT CH OPEN
1. seconds during run.
1. SSOV relay failed on board.
2. Floating Neutral.
1. Actuator not allowing for full closure of gas valve
2. SSOV powered when it should not be
3. Defective Switch or Actuator
4. Incorrectly wired switch.
1. Air/Fuel Valve out of calibration.
1. Replace or adjust microswitch in SSOV actuator. If fault persists, replace actuator.
1. Press CLEAR button and restart unit. If fault persists, replace Ignition/Stepper (IGST) Board.
2. The Neutral and Earth Ground are not connected at the source and therefore there is a voltage measured between the two. Normally this measurement should be near zero or no more than a few millivolts.
3. Check SSOV power wiring.
1. Observe operation of the Safety Shut-Off Valve (SSOV) through indicator on the Valve actuator and ensure that the valve is fully and not partially closing.
2. If the SSOV never closes, it may be powered continuously. Close the gas supply and remove power from the unit. Refer fault to qualified service personnel.
3. Remove the electrical cover from the SSOV and check switch continuity. If the switch does not show continuity with the gas valve closed, either adjust or replace the switch or actuator.
1. Refer to GF-112 and perform Stepper Test (para. 6.3.5) to ensure stepper motor rotates properly between the 0% (fully closed) and 100% (fully open) positions. Verify that the VALV E PO S I T I ON bargraph and the dial on the Air/Fuel Valve track each other to indicate proper operation. If operation is not correct, perform the
Page 92 of 160 PR2: 04/22/13
Page 93
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
connection to the
Defective Air/Fuel Valve stepper
every second. If not, replace IGST Board.
OBSERVED INCIDENT
PROBABLE CAUSES
CORRECTIVE ACTION
CHAPTER 8: TROUBLESHOOTING GUIDE
TABLE 8-1. BOILER TROUBLESHOOTING (Continued)
STEPPER MOT OR
FAILURE
(continued)
2. Air/Fuel Valve unplugged.
3. Loose wiring stepper motor.
4. motor.
5. Defective Power Supply Board or fuse
6. Defective IGST Board
2. Check that the Air/Fuel Valve is connected to the Control Box.
3. .Inspect for loose connections between the Air/Fuel Valve motor and the wiring harness.
4. Replace stepper motor.
5. Check DS1 & DS2 LEDs o n Po wer Su ppl y Board. If the y are not steady ON, replace Power Supply Board.
6. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

8.2 ADDITIONAL FAULTS WITHO UT S PECI FIC FAULT MESSAGES

Refer to Table 8-2 to troubleshoot faults which may occur without a specific fault message being displayed.
TABLE 8-2. BOILER TROUBLESHOOTING WITH NO FAULT MESSAGE DISPLAYED
1. Open the 1/4” Ball Valve downstream of the SSOV (Fig. 8-1).
2. Remove and inspect Gas Injector to ensure it is not clogged or damaged.
3. Close the 2” and the 1/4” Ball Valve downstream of the SSOV (Fig. 8-
1). Start the unit and listen for a “clicking” sound that the Staged Ignition Solenoid makes during Ignition Trial. If “clicking” sound is not heard after 2 or 3 attempts, replace the Staged Ignition Solenoid.
Hard Light-Off
1. Staged Ignition Ball Valve closed.
2. Clogged/damaged Gas Injector (Figure 8-2).
3. Defective Staged Ignition Solenoid (Figure 8-2).
1. Gas pressure going into unit is fluctuating.
Fluctuating Gas Pressure
Air/Fuel Valve “hunting” at
the 80% Valve Position
PR2: 04/22/13 Page 93 of 160
2. Damping Orifice not installed.
1. IGST and Power Supply Boards in Control Box are outdated.
1. Stabilize gas pressure going into unit. If necessary, troubleshoot Building Supply Regulator.
2. Check to ensure that the Damping Orifice is installed in the SSOV Actuator shown in Figure 8-3. (For IRI Gas Trains, the Damping Orifice is installed in the downstream SSOV Actuator).
1. Check to ensure that the IGST and Power Supply Boards are Rev. E or higher.
Page 94
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
STAGED
IGNITION
ASSEMBLY
IGNITOR-
INJECTOR
BURNER
PLATE
BURNER
NATURAL GAS HIGH GAS PRESSURE SWITCH
GAS PRESSURE SWITCH
PROPANE
INLET
MANUAL GAS SHUT-OFF VALVE
PROPANE LOW GAS PRESSURE
SWITCH
PROPANE SSOV
PROPANE GAS HIGH
nd
To 2
SOLENOID VA LV E VIA
FLEX GAS LINE
SNUBBERS
NATURAL GAS

Figure 8-1: High Gas Pressure Switch & Snubber Locatio

LOW GAS PRESSURE SWITCH
NATURAL GAS INLET
Figure 8-3: High Pressure Gas Switch and Snubber Locations
NATURAL GAS SSOV
Figure 8-2: Staged Ignition Solenoid Location
PR2: 04/22/13 Page 94 of 160
Page 95
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
SSOV ACTUATOR WITH GAS
PRESSURE ADJUSTMENT
DAMPING
ORIFICE
CHAPTER 8: TROUBLESHOOTING GUIDE
Figure 8-3: Damping Orifice Location
PR2: 04/22/13 Page 95 of 160
Page 96
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 8: TROUBLESHOOTING GUIDE
(This page intentionally blank)
Page 96 of 160 PR2: 04/22/13
Page 97
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 9: RS232 COMMUNICATION

9.1 INTRODUCTION

The RS232 communication feature permits viewing or changing of Control Panel menu options and also provides access to data logs showing Event Time Line, Fault and Sensor log displays.
The RS232 port on the front panel of the C-More Control Box (Figure 3-1) can be interfaced to a laptop computer or other suitable terminal using a RS232 adapter cable. RS232 communication can be accomplished using any “Dumb Terminal” emulation, such as “PuTTY” which is not included with Microsoft Windows, but can be downloaded for free on the internet. Source and instructions for using Putty are provided here:

Aquiring the PuTTY Application 9.1.1

Download the putty.exe program to your desktop from:
www.chiark.greenend.org.uk/~sgtatham/putty/download.html
You can use PuTTY to logon to remote computers as well as run a single command on a remote server. PuTTY does not need to be installed, so just clicking the downloaded executable will start it.

Logging on to a Remote Machine Using PuTTY 9.1.2

To use PuTTY to logon to a rem ote machine, bring up the PuTTY application by double-clicking its icon. You will see the main window as shown in left image of Figure 9-1.
Figure 9-1: PuTTY GUI: Basic Serial Session (L) and Serial Options (R)
In Serial mode, text typed into the PuTTY window will be sent straight out of your computer's serial port, and data received through that port will be displayed in the PuTTY window.
To create a Serial connection, click the radio button labeled Serial. The Serial line and Speed fields will then be automatically filled in as shown in left image of Fig ure 9-1, but will allow you to specif y the serial line to use (if your computer has more than one) and what speed (baud rate) to use when transferring data. For further configuration options (data bits, stop bits, parity, flow control), you can use the Serial Configuration panel (right image in Figure 9-1) by selecting “Serial” in the left navigation pane.
PR2: 04/22/13 Page 97 of 160
Page 98
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 9: RS232 COMMUNICATION
Now, to connect to the remote server, simply click the Open button at the bottom of the dialog box. A new terminal window will pop up and ask you to log in.
So that you don't have to enter this information every time you wish to c onnect to your server, you can save this configuration by typing an appropriate name in the Saved Sessions text box in the PuTTY “Basic Options” window (left image of Figure 9-1) and then clicking the Save button. In the future, you can select the name you chose in the list box and click the Load button to initialize this particular configuration.

Running a Command on a Remote Machine Using PuTTY 9.1.3

PuTTY may also be used to run some command residing on the remote server. After specifying the command line you want to run, you will be asked for your account name and password, and then the command you specified will execute. When it completes, your session will terminate, and your window will either close or remain open depending on how you configure the session. Here are the steps:
1. Bring up the PuTTY application and select the server you wish to connect to.
2. At the bottom of the Basic Options dialog box (left image of Figure 9-1) in the section titled: Close window on exit, select the Never radio button. This will keep the window open after the command has finished executing so that you can see any results in the terminal window.
3. In the m enu bar along the left side of the dialog box, click the SSH menu near the bottom. The following screen will be presented:
3. Into the textbox titled, Remote command type the full command line you wish to have executed on the remote machine.
4. You are now ready to execute this command on the remote machine, simply click the Open button at the bottom of the dialog.
5. You will have to provide an account name and password in the terminal window to complete the process.
Page 98 of 160 PR2: 04/22/13
Page 99
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 9: RS232 COMMUNICATION

9.2 RS232 COMMUNICATION SETUP

Regardless of the terminal emulation utilized, the following guidelines must be adhered to when setting up the RS232 communicati on link:
o Baud Rate – The baud rates which can be used with the C-More Control Panel are:
2400
4800
9600 (Default)
19.2K
o Data Format – The program must be set for: 8 data bits, 1 stop bit, no parity and either
Xon/Xoff or No flow control.

9.3 MENU PROCESSING UTILI ZING RS232 COMMUNICATION

Viewing data logs and viewing or changing Control Panel menu options using RS232 communication is accomplished as follows:
1. Start the emulator software program and ensure that the specified baud rate and data formats have been entered.
2. Press the Enter key on the laptop. An asterisk (*) prompt should appear.
3. At the prompt, enter the valid RS232 password (jaguar) in lower case letters and press Enter.
4. “Welcome to Aerco” will appear in the laptop or “dumb terminal” display with a listing of the following available entry choices:
M = Display next Menu D = Display menu items N = Display next menu items Cxx = Change item xx F = Fault log display S = Sensor log display T = Time line display L = Log off
NOTE
The Level 1 password (159) must be entered to change options in the Setup, Configuration and Tuning Menus. The Level 2 password (6817) must be entered to view or change options in the Calibration and Diagnostics Menus. With the exception of the password entry, all other keyboard entries can be made using either upper or lower case.
5. To view the available menus in the t op-down sequence shown in Figure 3-2, enter M <Rtn>. The Menu title and first 10 options will be displayed.
6. W hen viewing menus containing more than 10 options, enter N <Rt n> to display the remaining options.
7. Shortcut keys are also available to go directly to a specific menu. These shortcut keys are:
m0 = Default (Operating) Menu m1 = Setup Menu m2 = Configuration Menu
PR2: 04/22/13 Page 99 of 160
Page 100
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
OMM-0052_0E
GF-127
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
CHAPTER 9: RS232 COMMUNICATION
m3 = Tuning Menu m4 = Calibration Menu m5 = Diagnostic Menu
8. To change a value or setting for a displayed menu option, proceed as follows:
a) Enter C, followed by the number to the right of the displayed option to be changed,
and then press <Rtn>.
b) Enter the desired value or setting for the option and press <Rtn>. Refer to Chapter 3,
Tables 3-2 through 3-5 for allowable entry ranges and settings for the Operating, Setup, Configuration and Tuning Menus. (The Calibration and Diagnostic Menus should only be used by Factory-Trained service personnel).
c) Menu changes will be stored in non-volatile memory.
9. To redisplay the menu and view the option which was just changed in step 5, enter D and press
<Rtn>.
10. To display the Fault (F) Log, Sensor (S) Log or Time (T) Line Log, press F, S or T followed by <Rtn>. Refer to paragraph 9.4 for descriptions and samples of these data logs.
11. To log off and terminate the RS232 communication link, press L followed by <Rtn>.

9.4 DATA LOGGING

During operation, the C-More Control Panel continuously monitors and logs data associated with operational events, faults and sensor readings associated with the boiler or water heater system. Descriptions of these data logs are provided in the following paragraphs. The basic procedur e for accessing each data log is described in paragraph 9.3, step 7.

Fault Log 9.4.1

The C-More Control Panel logs the last 20 faults (0 – 19) starting with the most recent (#0). They can be viewed in the front panel display or via the RS232 port. The Fault Log cannot be cleared. If the Fault Log already contains 10 faults, the earliest fault is overwritten when a new fault occurs. A sample Fault Log display is shown in Table 9-1.
NOTE
The Operation Time (T) Log can store thousands of records. Therefore, to view the most recently logged record, enter “T” followed by 0 (zero) and press Enter (i.e. T0 <Enter>). To view earlier records in reverse chronological order, enter T and press Enter. To go back 200 or 1000 records, enter T200 or T1000, etc. and press Enter.

Operation Time Log 9.4.2

The Operation Time Log consists of a string of ASCII records stored in non-volatile memor y within the C-More Control Panel. Events such as power-up, ignition and turn-off are time stamped. Data logged while the unit is running are run-length encoded. Data is logged or the run-length incremented every 30 seconds. For a new run record to be logged, the fire rate or flame strength must change by more than 5%, or the run mode must change. At steady-state, the run-length is allowed to reach a maximum of 30 minutes before the record is logged. This means that no more than 30 minutes of data can be lost if the unit loses power. Table 9-2 shows a sample Operation Time Log for a boiler:
The Operation Time Log can only be accessed through the RS232 interface using a laptop or other
Page 100 of 160 PR2: 04/22/13
Loading...