Aerco BMK 750P, BMK 750, BMK 1500DF, BMK 1000P, BMK 1500P User Manual

...
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
GF-206
Natural Gas:
APPLIES TO MODELS:
Applies to Serial Numbers:
G-17-2400 and above.
USER MANUAL
SEE ALSO: Benchmark
750, 1000, 1500, 2000, 2500, and 3000 MBH Boilers
Propane:
BMK 2000P
(2 of 2)
Natural Gas, Propane Gas, or Dual Fuel Fired Modulating, Condensing Boilers
Installation and Startup Guide,
Dual-Fuel (NG/P):
BMK 750
BMK 1000
BMK 1500
BMK 2000
BMK 2500
BMK 3000
BMK 750P
BMK 1000P
BMK 1500P
BMK 1500DF
BMK 2000DF
BMK 2500DF
BMK 3000DF
BMK 2500P
BMK 3000P
Latest Update: 11/29/2017
OMM-0122_0C AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 1 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
CONTENTS
TABLE OF CONTENTS
FOREWORD ...................................................................................................... 5
SECTION 1: SAFETY PRECAUTIONS ................................................................... 9
1.1 WARNINGS & CAUTIONS ..................................................................................................................... 9
1.2 EMERGENC Y SHUT D OWN ................................................................................................................. 10
1.3 PROLONGED SHUTDOWN ................................................................................................................. 10
1.4 IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS ............................................................... 11
SECTION 2: OPERATION ................................................................................. 13
2.1 INTRODUCTION ................................................................................................................................... 13
2.2 C-MORE CONTROLLER DESCRIPTION ............................................................................................ 14
2.3 C-MORE CONTROLLER MENUS ........................................................................................................ 17
2.3.1 Menu Navigation and Processing Procedure .................................................................................................. 17
2.4 OPERATING MENU ............................................................................................................................. 19
2.5 SETUP MENU ....................................................................................................................................... 20
2.6 CONFIGURATION MENU .................................................................................................................... 21
2.7 TUNING MENU ..................................................................................................................................... 23
2.8 COMBUSTION CAL MENU .................................................................................................................. 23
2.8.1 BMK 750/1000 COMBUSTION CAL Menu ....................................................................................................... 23
2.8.2 BMK 1500/2000 COMBUSTION CAL Menus ................................................................................................... 24
2.8.3 BMK 2500/3000 COMBUSTION CAL Menus ................................................................................................... 25
2.9 BST (BOILER SEQUENCING TECHNOLOGY) MENU ....................................................................... 26
2.10 CALIBRATION MENU......................................................................................................................... 29
SECTION 3: MODES OF OPERATION ............................................................... 31
3.1 INTRODUCTION ................................................................................................................................... 31
3.2 INDOOR/OUTDOOR RESET MODE ................................................................................................... 31
3.2.1 Reset Ratio ...................................................................................................................................................... 31
3.2.2 Building Reference Temperature .................................................................................................................... 31
3.2.3 Outdoor Air Temperature Sensor Installation ................................................................................................ 31
3.2.4 Indoor/Outdoor Startup ................................................................................................................................. 32
3.3 CONSTANT SETPOINT MODE ........................................................................................................... 32
3.3.1 Setting the Setpoint ........................................................................................................................................ 33
3.4 REMOTE SETPOINT MODES ............................................................................................................. 33
3.4.1 Remote Setpoint Field Wiring ......................................................................................................................... 34
3.4.2 Remote Setpoint Startup ................................................................................................................................ 34
3.5 DIRECT DRIVE MODES....................................................................................................................... 34
3.5.1 Direct Drive Field Wiring ................................................................................................................................. 35
3.5.2 Direct Drive Startup ........................................................................................................................................ 35
3.6 AERCO CONTROL SYSTEM (ACS) .................................................................................................... 36
3.6.1 ACS External Field Wiring................................................................................................................................ 36
3.6.2 ACS Setup and Startup .................................................................................................................................... 36
3.7 COMBINATION CONTROL SYSTEM (CCS) ....................................................................................... 37
3.7.1 Combination Control System Field Wiring ...................................................................................................... 38
3.7.2 Combination Control System Setup and Startup ............................................................................................ 38
SECTION 4: MAINTENANCE ............................................................................ 39
4.1 MAINTENANCE SCHEDULE ............................................................................................................... 39
4.2 IGNITER-INJECTOR ............................................................................................................................ 40
Page 2 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
CONTENTS
4.3 FLAME DETECTOR ............................................................................................................................. 45
4.4 O2 SENSOR .......................................................................................................................................... 45
4.5 SAFETY DEVICE TESTING ................................................................................................................. 46
4.6 BURNER INSPECTION ........................................................................................................................ 46
4.6.1 BMK 750/1000 BURNER INSPECTION ............................................................................................................. 47
4.6.2 BMK 1500 – 3000 BURNER INSPECTION ......................................................................................................... 49
4.7 CONDENSATE DRAIN TRAP .............................................................................................................. 53
4.8 AIR FILTER CLEANING AND REPLACEMENT .................................................................................. 54
4.9 WATER CUTOFF (LWCO) CAPACITOR INTEGRITY TEST ............................................................... 55
4.9.1 Low Water Cutoff (LWCO) - Capacitor Electrical Short Test ........................................................................... 56
4.9.2 Low Water Cutoff (LWCO) - Standard C-More Test ........................................................................................ 57
4.10 SHUTTING BOILER DOWN FOR EXTENDED PERIOD ................................................................... 57
4.11 PLACING THE BO IL E R BACK IN SER VI C E AF TER A PRO LO N G ED SHUTDOWN ....................... 57
4.12 SPARK MONITOR (AC CURRENT TRANSDUCER) ......................................................................... 58
SECTION 5: TROUBLESHOOTING GUIDE ......................................................... 59
5.1 INTRODUCTION ................................................................................................................................... 59
5.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES .................................................... 71
APPENDIX A: BOILER MENU ITEM DESCRIPTIONS ............................................. 73
TABLE A-1: OPERATING MENU ITEM DESCRIPTIONS ......................................................................... 73
TABLE A-2: SETUP MENU ITEM DESCRIPTIONS ................................................................................... 75
TABLE A-3: CONFIGURATION MENU ITEM DESCRIPTIONS ................................................................ 76
TABLE A-4: TUNING MENU ITEM DESCRIPTIONS ................................................................................. 79
TABLE A-5: COMBUSTION CALIBRATION MENU ITEM DESCRIPTIONS ............................................. 80
TABLE A-6: CALIBRATION MENU ITEM DESCRIPTIONS ....................................................................... 81
APPENDIX B: STARTUP, STATUS, & FAULT MESSAGES ...................................... 85
TABLE B-1: STARTUP AND STATUS MESSAGES .................................................................................. 85
TABLE B-2: FAULT MESSAGES ............................................................................................................... 86
APPENDIX C: SENSOR RESISTANCE/VOLTAGE CHART ........................................ 89
APPENDIX D: RECOMMENDED PERIODIC TESTING ............................................ 91
APPENDIX E: INDOOR/OUTDOOR RESET RATIO CHARTS .................................. 93
APPENDIX F: BENCHMARK 750/1000 PART LIST ............................................... 97
APPENDIX G: BENCHMARK 1500/2000 PART LIST ........................................... 107
APPENDIX H: BENCHMARK 2500/3000 PART LIST ........................................... 123
APPENDIX I: WIRING DIAGRAMS ................................................................... 145
APPENDIX J: C-MORE CONTROLLER VIEWS .................................................... 161
APPENDIX K: RECOMMENDED SPARES ........................................................... 163
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 3 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
CONTENTS
(This page intentionally blank)
Page 4 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
FORWARD
FOREWORD
The AERCO Benchmark (BMK) 750, 1000, 1500, 2000, 2500, and 3000 natural gas and propane fueled boilers are modulating and condensing units. They represent a true industry advance that meets the needs of today's energy and environmental concerns. Designed for application in any closed loop hydronic system, the Benchmark's modulating capability relates energy input directly to fluctuating system loads. These BMK models provide extremely high efficiency operation and are ideally suited f or modern low temperature, as well as, conventional heating systems.
The Benchmark models operate within the following input and output ranges:
IMPORTANT!
Unless otherwise specified, all measurements apply to both natural gas and propane models.
Benchmark Boiler Intake and Output Ranges
INPUT RANGE (BTU/HR.) OUTPUT RANGE (BTU/HR.)
MODEL
MINIMUM MAXIMUM MINIMUM MAXIMUM
BMK 750 50,000 (14.6 kW) 750,000 (220 kW) 47,750 (14 kW) 716,250 (210 kW)
BMK 1000 50,000 (14.6 kW) 1,000,000 (293 kW) 48,300 (14.15 kW) 968,000 (284 kW)
BMK 1500 75,000 (22 kW) 1,500,000 (440 kW) 64,500 (18.9 kW) 1,395,000 (409 kW)
BMK 2000 100,000 (29.3 kW) 2,000,000 (586 kW) 86,000 (25.2 kW) 1,860,000 (545 kW)
BMK 2500 167,000 (48.9 kW) 2,500,000 (732 kW) 144,000 (42.2 kW) 2,395,000 (702 kW)
BMK 3000 200,000 (58.6 kW) 3,000,000 (879 kW) 174,000 (51.0 kW) 2,874,000 (842 kW)
The output of the boiler is a function of the unit’s firing rate (valve position) and return water temperature.
When installed and operated in accordance with this Instruction Manual, these boilers comply with the NO
(SCAQMD), Rule 1146.2. In addition, the BMK 750 & 1000 comply with the Bay Area Air Quality Management District regulation 9, Rule 7.
Whether used in singular or modular arrangements, the BMK boilers offer the maximum venting flexibility with minimum installation space requirements. These boilers are Categ ory II and IV, positive pressure appliances. Single and/or multiple breeched units are capable of operation in the following vent configurations:
Room Combustion Air:
Ducted Combustion Air:
emission standards outlined in: South Coast Air Quality Management District
x
o Vertical Discharge o Horizontal Discharge
o Vertical Discharge o Horizontal Discharge
These boilers are capable of being vented utilizing Polypropylene and AL29-4C vent systems. The Benchmark's advanced electronics are available in several selectable modes of operation
offering the most efficient operating methods and energy management system integration.
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 5 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
A (Amp)
Ampere
(see below)
British Thermal Unit. A unit of energy approximately equal to the BTU/HR
BTUs p er Hour
CCP
Combination Control Panel
CCS
Combination Control System
system developed by AERCO and currently used in all
3
Double Block and Bleed, a gas trains containing 2 Safety Shutoff
FORWARD
AERCO Technical Terminology Meanings
TERMINOLOGY MEANING
ACS AERCO Control System, AERCO’s boiler management systems ADDR Address AGND Anal og Ground ALRM Alarm ANSI American National Standards Institute, ASME American Society of Mechanical Engineers AUX Auxiliary
BAS
Building Automation System, often used interchangeably with EMS
Symbol rate, or simply the number of distinct symbol changes
Baud Rate
(signaling events) transmitted per second. It is not equal to bits per
second, unless each symbol is 1 bit long. BMK (Benchmark) AERCO’s Benchmark series boilers BMS or BMS II AERCO Boiler Management Systems
BLDG (Bldg) Building BST AERCO on-board Boiler Sequencing Technology
BTU
C-More Controller CFH Cubic Feet per Hour (1 CFH = 0.028 m
heat required to raise 1 pound (0.45 kg) of water 1°F (0.55 °C)
(1 BTU/hr = 0.29 W)
A control
Benchmark, Innovation and KC1000 Series product lines.
/hr)
CO Carbon Monoxide COMM (Comm) Communication Cal. Calibration CNTL Control CPU Central Processing Unit
DBB
Valves (SSOVs) and a solenoid operated vent valve. DIP Dual In-Line Package, a type of switch
ECU Electronic Control Unit (O2 sensor) EMS Energy Management System; often used interchangeably with BAS FM Factor y Mutual. Used to define boiler gas trains. GF-xxxx Gas Fired (an AERCO document numbering system) GND Ground
Page 6 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C
11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
HDR
Header
MBH
1000 BTUs per Hour
duplex data transmission protocol developed by AEG
POC
Proof of Clos ure
PPM
Parts per Million
PSI
Pounds per Square Inch (1 PSI = 6.89 kPa)
PTP
Point-to-Point (usually over RS232 networks)
FORWARD
AERCO Technical Terminology Meanings
TERMINOLOGY MEANING
Hex Hexadecimal Number (0 – 9, A – F) HP Horse Power HX Heat Exchanger Hz Hertz (Cycles Per Second) I.D. Inside Diameter IGN Ignition IGST Board Ignition/Stepper Board, contained in the C-More Controller INTLK (INTL’K) Interlock I/O Input/Output
I/O Box
Input/Output (I/O) Box currently used on Benchmark, Innovation and
KC1000 Series products IP Internet Protocol ISO International Organization for Standardization Lbs. Pounds (1 lb = 0.45 kg) LED Light Emitting Diode LN Low Nitrogen Oxide MA (mA) Milliampere (1 thousandth of an ampere) MAX (Max) Maximum
MIN (Min) Minimum Modbus®
A serial, half-
Modicon NC (N.C.) Normally Closed NO (N.O.) Normally Open NOx Nitrogen Oxide NPT National Pipe Thread O2 Oxygen O.D. Outside Diameter OMM & O&M Oper ation and Maintenance Manual onAER
AERCO’s on-line remote monitoring system PCB Printed Circuit Board PMC Board Primary Micro-Controller (PMC) board, contained in the C-More P/N Part Number
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 7 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
P&T
Pressure and Temperature
(or EIA-232)
duplex (FDX) transmission of data based
on the RS232 Standard
duplex (FDX) transmission of data based
(or EIA-485)
on the RS485 Standard
data in the
FORWARD
AERCO Technical Terminology Meanings
TERMINOLOGY MEANING
ProtoNode Hardware interface between BAS and a boiler or water heater PVC Poly Vinyl Chloride, a common synthetic plastic PWM Pulse Width Modulation REF (Ref) Reference RES. Resistive RS232
RS422 (or EIA-422)
RS485
A standard for serial, full-
A standard for serial, full-
on the RS422 Standard
A standard for serial, half-duplex (HDX) transmission of data based
RTN (Rtn) Return SETPT (Setpt) Setpoint Temperature SHLD (Shld) Shield SPDT Single Pole Double Throw, a type of switch SSOV Safety Shut Off Valve TEMP (Temp) Temperature
A resistor placed at each end of a daisy-chain or multi-drop network Terminating Resistor
in order to prevent reflections that may cause invalid
communication Tip-N-Tell A device that indicates if a package was tipped during shipping UL A business that tests and validates products VAC Volts, Alternating Current VDC Volts, Direct Current VFD Vacuum Fluor escent Display, also Variable Frequency Drive W Watt W.C. Water Column, a unit of pressure (1 W.C. = 249 Pa) µA Micro amp (1 millionth of an ampere)
Page 8 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
SECTION 1: SAFETY PRECAUTIONS
SECTION 1: SAFETY PRECAUTIONS
1.1 WARNINGS & CAUTIONS
Installers and operating personnel MUST, at all times, observe all safety regulations. The following warnings and cautions are general and must be given the same attention as specific precautions included in these instructions. In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54) for gas-fired boilers and ANSI/NFPASB for LP gas-fired boilers. Where applicable, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CSA B149.1, and applicable Provincial regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
See section 1.4 for important information regarding installation of units within the Commonwealth of Massachusetts.
IMPORTANT!
This Instruction Manual is an integral part of the product and must be maintained in legible condition. It must be given to the user by the installer and kept in a safe place for future reference.
WARNING!
Do not use matches, candles, flames, or other sources of ignition to check for gas leaks.
Fluids under pressure may cause injury to personnel or damage to equipment when
released. Be sure to shut off all incoming and outgoing water shutoff valves. Carefully decrease all trapped pressures to zero before performing maintenance.
Before attempting to perform any maintenance on the unit, shut off all gas and electrical
inputs to the unit.
The exhaust vent pipe of the unit operates under a positive pressure and therefore must be
completely sealed to prevent leakage of combustion products into living spaces.
Electrical voltages up to 120 VAC may be used in this equipment. Therefore the cover on
the unit’s power box (located behind the front panel door) must be installed at all times, except during maintenance and servicing.
A three-pole switch must be installed on the electrical supply line of the unit. The switch
must be installed in an easily accessible position to quickly and safely disconnect electrical service. Do not affix switch to unit sheet metal enclosures.
CAUTION!
Many soaps used for gas pipe leak testing are corrosive to metals. The piping must be
rinsed thoroughly with clean water after leak checks have been completed.
DO NOT use this boiler if any part has been under water. Call a qualified service technician
to inspect and replace any part that has been under water.
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 9 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
VALVE
CLOSED
SECTION 1: SAFETY PRECAUTIONS
1.2 EMERGENCY SHUTDOWN
If overheating occurs or the gas supply fails to shut off, close the manual gas shutoff valve (Figure 1-1) located external to the unit.
NOTE:
The Installer must identify and indicate the location of the emergency shutdown manual gas valve to operating personnel.
MANUAL GAS SHUT-OFF VALVE
VALVE
OPEN
Figure 1-1: Manual Gas Shutoff Valve
1.3 PROLONGED SHUTDOWN
After prolonged shutdown, it is recommended that the startup procedures and safety device test procedures, described in Section 4 and 5, respectively of the Benchmark 750 – 3000 Installation and Startup Guide, OMM-0121 (GF-205) be performed to verify all system-operating parameters. If there is an emergency, turn off the electrical power supply to the AERCO boiler and close the manual gas valve located upstream the unit. The installer must identify the emergency shut-off device.
Page 10 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C
11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
Requirements For Massachusetts Installations
Boiler Installations within the Commonwealth of Massachusetts must conform to the
l side wall horizontally vented gas fueled equipment installed in every dwelling,
monoxide detector with an alarm is installed on each additional level of the dwelling,
be the responsibility of the property owner to secure the services of qualified licensed
the above requirements; provided, however, that during said thirty (30) day period, a
Each carbon monoxide detector as
accordance with the above provisions shall comply with NFPA 720 and be
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS". (Continued)
SECTION 1: SAFETY PRECAUTIONS
1.4 IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS
following requirements:
Boiler must be installed by a plumber or a gas fitter who is licensed within the
Commonwealth of Massachusetts.
Prior to unit operation, the complete gas train and all connections must be leak
tested using a non-corrosive soap.
The vent termination must be located a minimum of 4 feet above grade level. If
side-wall venting is used, the installation must conform to the following requirements extracted from 248 CMR 5.08 (2):
(a) For al building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS: At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon
building or structure served by the side wall horizontal vented gas fueled equipment. It shall
professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with
battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS: required in
ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE: A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 11 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
Requirements For Massachusetts Installations
observes carbon monoxide detectors and signage installed in accordance with the
venting system design or venting system components with the equipment, the instructions
When the manufacturer of a Product Approved side wall horizontally vented gas fueled
stems" shall be Product Approved by the Board, and the
SECTION 1: SAFETY PRECAUTIONS
4. INSPECTION: The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector
provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Section 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a
provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting sy instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
……………….[End of Extracted Information From 248 CMR 5.08 (2)]…………………
Page 12 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
SECTION 2: OPERATION
SECTION 2: OPERATION
2.1 INTRODUCTION
The information in this section provides a guide to the operation of the Benchmark Boiler using the C-More Controller mounted on the front of the unit. It is imperative that the initial startup of this unit be performed by factory trained personnel. Operation prior to initial startup by factory trained personnel may void the equipment warranty. In addition, the following W AR NINGS and CAUTIONS must be observed at all times.
WARNING!
ELECTRICAL VO LTAGES IN THIS SYSTEM INCLUDE 120 VAC (BMK 750 – 2000) and
208 or 460 VAC (BMK 2500/3000) and 24 volts AC. It must be serviced only by factory
certified service technicians.
DO NOT ATTEMPT TO DRY FIRE THE UNIT. Starting the unit without a full water level
can seriously damage the unit and may result in injury to personnel or property damage. This situation will void any warranty.
CAUTION!
All of the installation procedures in the Benchmark 750 – 3000 Installation and Startup Guide, OMM-0121 (GF-205) must b e completed before attempti ng to start the unit.
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 13 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
SECTION 2: OPERATION
2.2 C-MORE CONTROLLER DESCRIPTION
All Benchmark boilers utilize the C-More Controller shown in Figure 2-1. This panel contains all of the controls, indicators and displays necessary to operate, adjust and troubleshoot the boiler. These operating controls, indicators and displays are listed and described in Table 2-1. Additional information on these items is provided in the individual operating procedures and menu descriptions provided in this section.
2
1
3
12
11
10
9
4
5
6
7
8
Figure 2-1: C-More Controller Front View
Page 14 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
Segment LED display continuously displays the outlet
blinks when operating in the
On a BST Manager, display flashes & shows header temperature.
of displaying up to 16 alphanumeric characters. The information
trained personnel to monitor
communications, in combination with the RS232 Adaptor
LED indicator lights when a boiler alarm condition
be cleared by simply pressing this key. Troubleshooting
conditions have been satisfied.
8
opens the water level probe circuit and
SECTION 2: OPERATION
TABLE 2-1: Controls, Indicators, And Displays (ref. Figure 2-1)
ITEM
1
2
CONTROL, INDICATOR
or DISPLAY
COMM =
MANUAL =
REMOTE =
DEMAND =
OUTLET TEMPERATURE
Display
Four Status LEDs indicate the current operating status as follows:
Lights when RS232 communication is occurring – see Item 4. Lights when the valve position (fire rate) is being controlled using the front
panel keypad. This mode of operation is for service technician use only. Lights when the unit is being controlled by an external signal from an Energy
Management System. Lights when there is a demand for heat.
FUNCTION
LED STATUS INDICATORS
3–Digit, 7– water temperature. The °F or °C LED next to the display lights to indicate whether the displayed temperature is in degrees Fahrenheit or degrees Celsius. The °F or °C DEADBAND mode.
Vacuum Fluorescent Display (VFD) consists of 2 lines each capable displayed includes:
3
4
5
6
7
9
VFD Display
RS232 Port
FAULT Indicator
CLEAR Key
READY Indicator ON/OFF switch
LOW WAT ER LEVEL
TEST/RESET
switches
Startup Messages
Fault Messages
Operating Status Messages
Menu Selection
BST Messages
This port is used only by factory­onAER Cable (P/N 124675).
Red FAULT occurs. An alarm message will appear in the VFD.
Turns off the FAULT indicator and clears the alarm message if the alarm is no longer valid. Lockout type alarms will be latched and cannot may be required to clear these types of alarms.
Lights when ON/OFF switch is set to ON and when all Pre-Purge
Enables and disables boiler operation.
Allows operator to test operation of the water level monitor.
Pressing TEST
simulates a Low Water Level alarm.
Pressing RESET resets the water level monitor circuit.
Pressing the CLEAR key (item 6) resets the display.
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 15 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
Six (6) keys which provide the following functions for the C-More Controller menus:
Allows you to go back to the previous menu level without changing any information. Continuously pressing this key will bring you back to the
the top of a main menu category.
arrow key will
key is
ement the
Saves the modified menu settings in memory. The display will stop
SECTION 2: OPERATION
TABLE 2-1: Controls, Indicators, And Displays (ref. Figure 2-1)
ITEM
10
CONTROL, INDICATOR
or DISPLAY
MENU
BACK
(UP)
Arrow
(DOWN)
Arrow
Steps through the main menu categories shown in Figure 2-2. T he menu categories wrap around in the order shown.
default status display in the VFD. Also, this key allows you to go back to
When in one of the main menu categories (Figure 2-2), pressing the arrow key will select the displayed menu category. If the CHANGE key was pressed and the menu item is flashing, pressing the increment the selected setting.
When in one of the main menu categories (Figure 2-2), pressing this key will select the displayed menu category. If the CHANGE k ey was pressed and the menu item is flashing, pressing the ▼ arrow key will decrement the selected setting.
FUNCTION
MENU KEYPAD
Permits a setting to be changed (edited). When the CHANGE
CHANGE
pressed, the displayed menu item will begin to flash. Pressing the ▲ or ▼ arrow key when the item is flashing will increment or decr displayed setting.
ENTER
11
12
AUTO/MAN switch
VALVE POSITION
Bargraph
flashing.
This switch toggles the boiler between the AUTOMATIC and MANUAL modes of operation. When in the MANUAL (MAN) mode, the front panel controls are enabled and the MANUAL status LED lights. Manual operation is for service only.
When in the AUTOMATIC (AUTO) mode, the MANUAL status LED will be off and the front panel controls disabled.
20 segment red LED bargraph continuously shows the Air/Fuel Valve position in 5% increments from 0 to 100%
Page 16 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
Menu Navigation and Processing Proce dure Instructions
menu, which is the next menu
in the
Continue to press the ▲ or ▼ arrow key until the desired menu option is displayed.
SECTION 2: OPERATION
2.3 C-MORE CONTROLLER MENUS
The C-More Controller incorporates an extensive menu structure which permits the operator to set up, and configure the unit. The menu structure consists of five major menu categories which are applicable to this manual. These categories are shown in Figure 2-2. Each of the menus shown, contain options which permit operating parameters to be viewed or changed. The menus are protected by password levels to prevent unauthorized use.
Prior to entering the correct password, the options contained in the Operation, Setup, Configuration and Tuning menu categories can be viewed. However, with the exception of Internal Setpoint Temperature (Configuration menu), none of the viewable menu options can be changed.
Once the valid level 1 password (159) is entered, the options listed in the Setup, Configuration and Tuning menus can be viewed and changed, if desired. The Combustion Cal menu is protected by the level 2 password (6817), which is used in initial startup (see Section 4: Initial Startup of the Benchmark 750 – 3000 I nstallation and Startup Guide, OMM-0121 (GF-205)), to perform combustion calibration prior to service use.
2.3.1 Menu Navigation and Processing Procedure
Accessing and initiating each menu and option is accomplished using the menu keys shown in Figure 2-1. Therefore, it is imperative that you be thoroughly familiar with the following basic steps before attempting to perform specific menu procedures:
1. The C-More Controller will normally be in the Operating menu and the VFD will display the
current unit status. Pressing the ▲ or ▼ arrow key will display the other available data
items in the Operating menu.
2. Press the MENU key. The display will show the Setup
category shown in Figure 2-2. This menu contains the Password option which must be entered if other menu options will be changed.
3. Continue pressing the MENU key until the desired menu is displayed.
4. With the desired menu displayed, press the ▲ or ▼ arrow key. The first option
selected menu will be displayed.
5.
Pressing the ▲ arrow key will display the available menu options in the Top-Down sequence. Pressing the ▼ arrow key will display the options in the Bottom-Up sequence.
The menu options will wrap-around after the first or last available option is reached.
6. To change the value or setting of a displayed menu option, press the CHANGE key. The
displayed option will begin to flash. Press the ▲ or ▼ arrow key to scroll through the available menu option choices for the option to be changed. The menu option choices do not wrap around.
7. To select and store a changed menu item, press the ENTER key.
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 17 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
SECTION 2: OPERATION
* Only if BST is enabled. BST is described in detail in Section 6 of the Benchmark 750 – 3000 Installation and Startup Guide, OMM-0121 (GF-205).
NOTE:
The following sections provide brief descriptions of the options contained in each menu. Refer to Appendix A for detailed descriptions of each menu option. Refer to Appendix B for a list and descriptions of startup, status and error messages.
Page 18 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Figure 2-2: Menu Structure
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-2: OPERATING Menu
Minimum
Maximum
30°F (-1.1°C)
240°F (115.6°C)
SECTION 2: OPERATION
2.4 OPERATING Menu
The Operating menu displays a number of key operating parameters for the unit. All items in this menu except O2 Monitor (item 15) are “Read-Only” and cannot be changed. T his menu can be accessed without entering a password.
A full description of each item appears in Appendix A-1.
MENU ITEM DISPLAY
1
Active Setpoint
2
Outlet Temp
3
Inlet Temp
4
Air Temp
5
Outdoor Temp
6
Valve Position In 0% 100%
7
Valve Position Out 0% 100% Configuration Menu
8
FFWD Temp
9
Exhaust Temp Displays current exhaust temperature
10
Flame Strength 0% 100%
11
Min Flame Str Not Used
12
O2 Monitor Enable Disable O2 Monitor = Enabled
13
Oxygen Level 0% 21%
14
Ignition Time 0.00 10.00
AVAILABLE CHOICES OR LIMIT
40°F (4.4°C) 240°F (116°C) 30°F (-1.1°C) 240°F (116°C) 30°F (-1.1°C) 240°F (116°C)
-70°F (-56.7°C) 245°F (118°C)
-70°F (-56.7°C) 130°F (54.4°C)
Appears Only If
Enabled in:
Configuration Menu
Configuration Menu
15
SSOV Time to OPN 0.00 10.00
16
Spark Current
17
Run Cycles 0 999,999,999
18
Run Hours 0 999,999,999
19
Fault Log 0 19
An additional parameter associated with the Operating menu, (Min = 0, Max = 100) does not appear in this menu, but can be displayed by pushing the Auto/Man button on the C-More Controller’s front face.
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 19 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
0 amps 2.5 amps
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-3: SETUP Menu
2
Language
English
English
3
Time
12:00 am
11:59 pm
12:00
4
5
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
6
7
Baud Rate
2400, 4800, 9600, 19.2K
9600
SECTION 2: OPERATION
2.5 SETUP Menu
The Setup menu permits the operator to enter the unit password (159) which is required to change the menu options. To prevent unauthorized use, the password will time-out after 1 hour. Therefore, the correct password must be reentered when required. In addition to permitting password entries, the Setup menu is also used to enter date and time, and units of temperature measurements. A view-only software version display is also provided to indicate the current C­More Controller software version.
A full description of each item appears in Appendix A-2.
MENU ITEM DISPLAY
AVAILABLE CHOICES OR LIMIT
Minimum Maximum
1
Password 0 9999 0
Date 01/01/00 12/31/99 01/01/00
Comm Address 0 127 0
8
onAER Mode Et hernet or SD Card Ethernet
9
Min Upload Timer 0 9,999 Sec 0
10
Unit Alpha E, G, H, R, N or A A
11
Unit Year 0 99 0
12
Unit Serial # 0 9999 0
13
Software Ver 0.00 Ver 9.99
Current software
DEFAULT
version
Page 20 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
AVAILABLE CHOICES OR LIMIT
Minimum
Maximum
SECTION 2: OPERATION
2.6 CONFIGURATION Menu
The Configuration menu permits adjustment of the Internal Setpoint (Setpt) temperature regardless of whether the valid password has been entered. Setpt is required for operation in the CONSTANT SETPOINT mode. The remaining options in this menu require the valid password to be entered, prior to changing existing entries. This menu contains a number of other configuration settings which may or may not be displayed, depending on the current operating mode setting.
A full description of each item appears in Appendix A-3.
NOTE:
The Configuration menu set tings are Factory-Set in accordance with the requirements specified for each individual order. Under normal operating conditions, no changes will be required.
TABLE 2-4: CONFIGURATION Menu
MENU ITEM DISPLAY
Internal Setpt
1
2
Unit Type
Unit Size
3
(Only displays sizes available for the unit)
4
Fuel Type
5
Boiler Mode
Remote Signal (If Mode = Remote
6
Setpoint, Direct Drive or Combination)
40°F (4.4°C) 240°F (115.6°C)
BMK Blr Std, BMK Blr Std Dual,
BMK Blr LN, BMK Blr LN Dual
750 MBH (220 kW), 1000 MBH (293
kW), 1500 MBH (439.6 kW), 2000 MBH
(586.1 kW), 2500 MBH (732.6 kW), 3000
MBH (879.2 kW)
Natural Gas or Propane
Constant Setpoint, Remote Setpoint,
Direct Drive, Combination,
Outdoor Reset
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (Legacy BMS), Network
DEFAULT
130°F (54.4°
BMK Boiler LN
750 MBH (220 kW),
Natural Gas in
standard and dual fuel
models, Propane in
propane only models
Constant Setpoint
4 – 20 mA,
1-5V
C)
7
Outdoor Sensor * Bldg Ref Temp
8
(If Mode = Outdoor Reset)
* Reset Ratio
9
(If Mode = Outdoor Reset)
* System Start Tmp
10
(If Outdoor Sensor = Enabled)
Setpt Lo Limit
11
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 21 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Enabled or Disabled Disabled
40°F
(4.4°C)
0.1 9.9 1.2
30°F
(-1.1°C)
40°F (4.4°C) Setpt Hi Limit 60°F (15.6°C)
230°F
(110°C)
100°F
(37.8°C)
70°F
(21.1°C)
60°F
(15.6°C)
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
AVAILABLE CHOICES OR LIMIT
Minimum
Maximum
(Do NOT change)
22
SECTION 2: OPERATION
TABLE 2-4: CONFIGURATION Menu
MENU ITEM DISPLAY
Setpt Hi Limit
12
Temp Hi Limit 40°F (4.4°
13
Max Valve Position
14
Pump Delay Timer
15
Aux Start On Dly
16
Failsafe Mode
17 18
Analog Output Low Fire Timer
19
Setpt Limiting
20
Setpt Limit Band
21
Network Timeout Shutoff Dly Temp 0°F (0°C) 25°F (13.75°C) 10°F (5.5°C)
23
Demand Offset
24
Deadband High
25
Setpt Lo Limit 210°F (98.9°C) 180°F (82.2°C)
C) 210°F (98.9°C) 195°F (90.6°C)
40% 100% 100% 0 min. 30 min. 0 min. 0 sec. 120 sec. 0 sec.
Shutdown or Constant Setpt Constant Setpt
Off, Setpoint, Outlet Temp, Valve Pos 4-
Valve Pos 0-10v
20mA, valve Pos 0-10v
2 sec. 600 sec. 2 sec.
Enabled or Disabled Disabled
0°F (0°C) 10°F (5.5°C) 5°F (2.75°C)
5 sec. 999 sec. 30 sec.
0°F (0°C) 25°F (13.75°C) 10°F (5.5°C) 0°F (0°C) 25°F (13.75°C) 5°F (2.75°C)
DEFAULT
Deadband Low
26 27
IGST Version
28
IGN Time Setting Displays 4 sec. or 7 sec. depending on wiring harness installed
29
Slow Shutdown Enabled or Disabled Disabled
30
Slow Sht Duration 0 sec. 9,999 sec. 60 sec. Slow Sht Threshold 40% 100% 60
31
O2 Warnings Enabled or Disabled Disabled
32
O2 Trim ID Displays 4 digit AERtrim ID
33
Fixed ID Displays unit’s fixed 4 dig it ID
34
O2 Trim Key Displays AERtrim 4 digit licens e key
35
O2 Trim Menu Enabled or Disabled Disabled
36 37
BST Menu Enabled or Disabled Disabled
0°F (0°C) 25°F (13.75°C) 5°F (2.75°C)
Displays current IGST version
V2.02
*NOTE
The Bldg Ref Temp and Reset Ratio menu Items are only displayed when the Outdoor Sensor, item # 7 is set to Enabled.
CAUTION!
DO NOT change the Analog Output menu item from its default setting (Valve Position 0-10V).
Page 22 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-5: TUNING Menu
1
Prop Band
5
6
7
TABLE 2-6: COMBUSTION CAL Menu: BMK 750/1000
Natural gas
Propane
1
0.25
10.00
2
0.25
10.00
3
0.25
10.00
4
0.25
10.00
5
0.25
10.00
6
0.25
10.00
7
8
9
10
SECTION 2: OPERATION
2.7 TUNING Menu
The Tuning menu items are Factory set for each individual unit. Do not change these menu entries unless specifically requested to do so by factory-trained personnel.
A full description of each item appears in Appendix A-4.
MENU ITEM DISPLAY MINIMUM MAXIMUM DEFAULT
1°F (0.55°C) 120°F (66°C) 70°F (38.5°C)
2
Integral Gain 0.00 2.00 1.00
3
Derivative Time 0.0 min 2.00 min 0.0min
4
Warmup Prop Band
1°F (0.55°C) 120°F (66°C) 95 °F (52°C) Warmup Int Gain 0.00 2.00 0.50 Warmup PID timer 0 sec. 240 sec. 20 sec. Reset Defaults? Yes, No, Are You Sure? No
2.8 COMBUSTION CAL Menu
The Com bustion Cal (Calibration) menu is protected by the level 2 password (6817) which must be entered to view or change the menu items shown in Table 2-6, 2-7 and 2-8. These menu items are used to vary the speed of the unit’s blower motor based on air temperature and air density at prescribed Air/Fuel Valve positions (% open). This is accomplished by providing a DC drive voltage to the motor, which then adjusts the rotational speed of the blower to maximize combustion efficiency and ensure the unit conforms to the Nitrogen Oxide (NO Monoxide (CO) emissions specified in the combustion calibration instructions in Section 4.4 of the Benchmark 750 – 3000 Installation and Startup Guide, OMM-0121 (GF-205).
CAL Voltage values are factory adjusted for each unit prior to shipping, and so may differ from the defaults shown in the tables below. A full description of each item appears in Appendix A-5.
2.8.1 BMK 750/1000 COMBUSTION CAL Menu
) and Carbon
x
MENU ITEM DISPLAY
CAL Voltage 18% CAL Voltage 30% CAL Voltage 45% CAL Voltage 60% CAL Voltage 80% CAL Voltage 100% SET Valve Position 0% 100% 0% 0% Blower Output Monitor Blower Output Voltage 0.00 0.00 Set Stdby Volt 0 V 10.0 V 2.00 2.00 Oxygen Level 0% 25% 0.0 0.0
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 23 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
MINIMUM MAXIMUM
DEFAULT
2.10 2.10
2.55 2.55
3.10 3.10
3.50 3.50
4.60 4.60
5.60 5.60
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
7
SET Valve Position
0%
100%
Variable
TABLE 2-7b: COMBUSTION CAL Menu: BMK 1500/2000
0.25
10.00
– – 1.20
2.10
0.25
10.00
2.60
4.50
2.30
3.50
3
0.25
10.00
3.20
4.50
2.80
3.90
0.25
10.00
4.10
4.80
3.50
4.10
0.25
10.00
8.30
9.80
7.70
8.90
0
10.0
2.00
2.00
2.00
2.00
10
Displays current value
SECTION 2: OPERATION
2.8.2 BMK 1500/2000 COMBUSTION CAL Menus
TABLE 2-7a: COMBUSTION CAL Menu: BMK 1500/2000 SINGLE FUEL – NATURAL GAS
MENU ITEM DISPLAY MINIMUM MAXIMUM
CAL Voltage 16%
1
CAL Voltage 18% 1.40
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
8
Blower Output Displays current value
9
Set Stdby Volt 0 10.00 V 2.00 V 2.00 V
10
Oxygen Level Displays current value
0.25 10.00
0.25 10.00 2.30 3.80
0.25 10.00 2.50 4.30
0.25 10.00 2.90 5.40
0.25 10.00 3.80 6.40
0.25 10.00 7.90 9.50
DUAL FUEL
DEFAULT
BMK 1500 BMK 2000
1.80
DEFAULT
MENU ITEM DISPLAY
CAL Voltage: 16%
1
CAL Voltage: 18%
2
CAL Voltage 30% CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt Oxygen Level
MINIMUM MAXIMUM
0.25 10.00 1.50
0.25 10.00 3.30 4.50 3.00 4.10
0 100 Variable
NATURAL GAS *
BMK 1500 BMK 2000 BMK 1500 BMK 2000
2.10
Displays current value
PROPANE
* The default values for Natural Gas on Dual Fuel units are different than the default values for
Natural Gas on Single Fuel units. These values do NOT apply to single fuel units.
Page 24 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-8a: COMBUSTION CAL Menu: BMK 2500/3000
SINGLE FUEL – NATURAL GAS
DEFAULT
BMK 2500
BMK 3000
TABLE 2-8b: COMBUSTION CAL Menu: BMK 2500/3000 DUAL FUEL
*
0.25
10.00
16%
0.25
10.00
0.25
10.00
2.10 – –
0.25
10.00 – –
2.00
2
0.25
10.00
5.40
3.30
4.40
0.25
10.00
7.00
5.70
0.25
10.00
6.60
5.60
0.25
10.00
8.00
7.00
0.25
10.00
8.70
7.90
8.60
7
0
100
Variable
0
10.0
2.00
2.00
2.00
2.00
Displays current value
SECTION 2: OPERATION
2.8.3 BMK 2500/3000 COMBUSTION CAL Menus
MENU ITEM DISPLAY MINIMUM MAXIMUM
CAL Voltage 16%
1
CAL Voltage 14% 2.80
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position 0% 100% Variable
8
Blower Output Displays current value
9
Set Stdby Volt 0 10.00 V 2.00 V 2.00 V
10
Oxygen Level Displays current value
0.25 10.00
0.25 10.00 4.10 4.60
0.25 10.00 4.80 5.00
0.25 10.00 5.30 5.50
0.25 10.00 6.80 6.90
0.25 10.00 8.50 9.10
2.20
DEFAULT
MENU ITEM DISPLAY
CAL Voltage: 14% CAL Voltage:
1
CAL Voltage: 18% CAL Voltage: 20% CAL Voltage: 22%
CAL Voltage 30%
3
CAL Voltage 45%
4
CAL Voltage 65% CAL Voltage 70%
5
CAL Voltage 75% CAL Voltage 85%
6
CAL Voltage 100% SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level
MINIMUM MAXIMUM
0.25 10.00
0.25 10.00
0.25 10.00
NATURAL GAS
BMK 2500 BMK 3000 BMK 2500 BMK 3000
2.40
2.15
3.90
5.60
– –
8.50
Displays current value
– –
6.60 4.60 5.40
* The default values for Natural Gas on Dual Fuel units are different than the default values for
Natural Gas on Single Fuel units. These values shown DO NOT APPLY to single fuel units.
PROPANE
2.00 2.30
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 25 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-9: BST Menu
AVAILABLE CHOICES OR LIMIT
1
BST Mode
9
12
*BST SETUP MENU*
Disabled
Enabled
Disabled
Remote
Setpoint
Outdoor
Reset
0-20 mA/0-5
VDC
16
SECTION 2: OPERATION
2.9 BST (Boiler Sequencing Technology) Menu
The BST menu must be enabled in order to be displayed and accessed. The BST Menu item, located at the end of the Configuration menu (item 37 in Table 2-4), must be set to Enabled.
The BST menu contains all of the items required to configure, operate and monitor the functionality of the BST System. There are over 50 items in this menu, and selecting any particular item from the list, for inspection or modification, could be time consuming. As a result, the BST menu has been segmented into FIVE logical groups based on functionality.
The five Item groups are:
1. BST Monitor Items
2. *BST SETUP MENU*
3. *OPERATE MENU*
4. * TEMP CTRL MENU*
5. * BST COMM MENU*
These displayed item groups are displayed in UPPER CASE letters, and are bounded by an asterisk * in order to readily identify them within the item list.
The Items contained in group 1 (BST Monitor Items) are always displayed within the menu, as these items are critical for proper system operation. Therefore, the BST Monitor Items Header itself is not displayed.
The Items contained in groups 2-5 are not displayed unless that particular item g roup has been enabled from the C-More keypad.
MENU ITEM DISPLAY
2
BST Setpoint BST Setpt Lo Limit BST Setpt Hi Limit 130°F (54.4°C)
3
Header Temp Read Only – current Header temperature in °F N/A
4
BST Fire Rate 0 100% Fire rate %
5
BST Ave Fire Rate 0 100% Avg Fire Rate %
6
BST Outdoor Temp Read Only – current outdoor temperature in °F N/A
7
Units Available 0 8 Units Present
8
Units Ignited 0 8 Units firing BST Valve State 0 (CLOSED) 1 (OPEN) 0
10
1 BST Comm Errors 8 0 9 0
11
1 BST Units 8 0 – 8 (see * NOTE below) 0
Minimum Maximum
Off BST Client BST Manager Off
DEFAULT
13
BST Setpoint Mode
14
BST Remote Signl 4-20 mA/1-5 VDC
15
Head Temp Source Network FFWD Temp FFWD Temp
Mdbus Temp Units Degrees C or Degrees F Degrees C
Page 26 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C
11/29/2017 Ph.: 800-526-0288 GF-206
Constant Setpoint
Constant Setpt
Network Network
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-9: BST Menu
AVAILABLE CHOICES OR LIMIT
19
Yes
feature.
25
On-Outlet
Temp
28
32
*OPERATE MENU*
36
40
44
*TEMP CTRL MENU*
48
SECTION 2: OPERATION
MENU ITEM DISPLAY
DEFAULT
Minimum Maximum
17
Header Temp Addr 0 255 240
18
Header Temp Point 0 255 14 BST Outdoor Sens Disabled Enabled Disabled
20
Outdr Tmp Source Outdoor Temp Network Outdoor Temp
21
Outdoor Tmp Addr 0 255 240
22
Outdoor Tmp Pnt 0 255 215
NOTE! A Modbus
23
BST Auto Mstr No
24
BST Auto Timer 10 sec 120 sec 30 sec
temperature transmitter must be installed in conjunction with this
Remote Intlk Use Boiler Shutdown System Shutdown System Shutdown
26
One Boiler Mode Off
27
1 Blr Threshold 10 35 25
On-Avg Temp Off
Setpoint Setback Disable Enable Disable
29
Setback Setpoint BST Setpt Lo Limit BST Setpt HI Limit 130°F (54.4°C)
30
Setback Start 12:00am 11:59pm 12.00am
31
Setback End 12:00am 11:59pm 12.00am Rate Threshold 1°F (0.55°C) 30°F (16.5°C) 15°F (8.25°C)
No
33 34 35
37 38 39
41 42 43
45 46 47
49 50
Disabled Enabled Disabled BST Next On VP 16% 100% 50% BST Max Boilers 1 8 8 BST On Delay 30 sec 300 sec 60 sec BST On Timeout 15 sec 300 sec 60 Sec Valve Override Off Closed Open Off Valve Off Delay 0 15 min 1 min BST Sequencing Run Hours Unit Size Select Lead Run Hours Select Lead Unit 0 127 0 Select Lag Unit 0 127 0 Lead/Lag Hours 25 hours 225 hours 72 hours
Disabled Enabled Disabled BST Temp Hi Limit 40°F (4.4°C) 210°F (98.9°C) 210°F (98.9°C) BST Setpt Lo Limit 40°F (4.4°C) BST Setpt HI Limit 60°F (15.5°C) BST Setpt HI Limit BST Setpt Lo Limit 220°F (104.4°C) 195°F (90.6°C) BST Prop Band 1°F (-17.2°C) 120°F (48.9°C) 100°F (37.8°C) BST Intgral Gain 0.00 2.00 0.50 BST Deriv Time 0.00 Min 2.00 Min 0.10 Min
OMM-0122_0C AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 27 of 164
GF-206 Ph.: 800-526-0288 11/29/2017
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-9: BST Menu
AVAILABLE CHOICES OR LIMIT
53
57
*BST COMM MENU*
61
65
SECTION 2: OPERATION
MENU ITEM DISPLAY
51
BST Deadband Hi 0 25 1
52
BST Deadband Lo 0 25 1 Deadband En Time 0 120 Sec 30 Sec
54
BST FR Up Rate 1 120 20
55
BST Bldg Ref Tmp 40°F (4.4°C) 230°F (110°C) 70°F (21.1°C)
56
BST Reset Ratio 0.1 9.9 1.2 System Start Tmp 30°F (-1.1°C) 120°F (48.9°C) 60°F (15.6°C)
58 59
Comm Address 0 127 0
60
BST Min Addr 1 128 1 BST Max Addr 1 128 8
62
SSD Address 0 250 247
63
SSD Poll Control 0 1000 0
64
Err Threshold 1 9 5 SSD Temp Format Degrees Points Degrees
66
BST Upld Timer 0 9999 sec 0
Minimum Maximum
Disabled Enabled Disabled
DEFAULT
* NOTE:
The 1 BST Units 8
menu item shows the current status for each unit controlled by BST, up to
a maximum of 8 units. The possible characters displayed are:
- = Off Line * = Not Available (fault, etc.) 0 = Off 1 = On, A = Lead On a = Lead Off B = Lag On b = Lag Off S = Setpoint Limit Active
The following example shows the status of 5 units being controlled by BST where:
Unit 1 & 3 are On Unit 2 is Off Unit 4 is Not Available Unit 5 is Lead On Unit 6 is Lag Off
1 BST Units 8
1 0 1 * A b
Page 28 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-10: CALIBRATION Menu
Minimum
Maximum
SECTION 2: OPERATION
2.10 CALIBRATION MENU
The Calibration menu is used by factory trained service personnel to adjust or reset the parameters listed below.
A full description of each item appears in Appendix A-6.
MENU ITEM DISPLAY
1
Stepper Fbk Cal 0%, Verify 50%, Cal 100% Cal 0 %
2
Purge Timer 5 sec. 60 sec Depends on unit type/size
3
Post Purge Timer 0 sec. 60 sec. 0 sec.
4
IGN Position 5% 60% Depends on unit type/size
5
Ign Pos Hold Tmr 0 sec. 60 sec. 0 sec.
6
FFWD Temp Disply Enabled or Disabled
7
Outlet Tmp Dsply Enabled or Disabled
8
Inlet Tmp Dsply Enabled or Disabled
9
Valv Pos Out Dsp Enabled or Disabled
10
Exhaust Tmp Dsp Enabled or Disabled
11
Exhaust Safety Enabled or Disabled
12
Flue Material PVC,CPVC; PolyPro; Stainless PVC,CPVC
13
Exhst Fault Temp 100 °F 500 °F 200 °F
14
Exhst Module Temp 100 °F 500 °F 190 °F
DEFAULT
Disabled Disabled Disabled
Enabled
Disabled
Enabled
AVAILABLE CHOICES OR LIMIT
15
Exhst Warn Temp 100 °F 500 °F 180 °F
16
Exhst Tmp VP Adj 0 10 5
17
Exhst Adj Rate 1 600 30
18
VP Change Rate 5 600 25
19
VP Up Rate 0.5 60.0 Depends on unit type/size
20
VP Down Rate 0.5 60.0 Depends on unit type/size
21
Purge Blwr Offst -1.0 8.0 Depends on unit type/size
22
4-20mA Purge Pct 60% 100% 70%
23
PWM In Adj -5.0% 5.0% 0.0%
24
Analog In Adj
25
Flow In Adj
26
Supply Gas Pressure In Adj
27
Gas Plate dp In Adj -5.0% 5.0% 0.0%
28
mA Out Adj -1.0 mA 1.0 mA 0.0 mA
OMM-0122_0C AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 29 of 164 GF-206 Ph.: 800-526-0288 11/29/2017
-5.0% 5.0% 0.0%
-5.0% 5.0% 0.0%
-5.0% 5.0% 0.0%
Benchmark 750-3000 Boiler Operation, Service & Maintenance Guide
TABLE 2-10: CALIBRATION Menu
AVAILABLE CHOICES OR LIMIT
Minimum
Maximum
SECTION 2: OPERATION
MENU ITEM DISPLAY
29
A/F Sensitivity 1% 5% 2%
30
Power Reset Automatic or Manual Automatic
31
Water Temp Reset Automatic or Manual Automatic
32
Gas Press Reset Automatic or Manual Manual
33
Min Off Time 0 Min 15 Min 1 Min
34
Heatr Tuning Dsp Enabled or Disabled Disabled
35
Heatr Bkpt Dsp Enabled or Disabled Disabled
36
Stop Level 0% Start Level 16
37
Start Level Stop Level 40% 22
38
Skip Range Cntr 10 95 40
39
Skip Range Span 0 3 0%
40
Skip Speed 0.5 2.0 0.5%
41
O2 Gain 0.500 1.500 1.000
42
O2 Offset -24.0 +2.0 1.0
DEFAULT
43
O2 Sensor Enabled or Disabled Depends on unit type/size
44
Cal Temp Sensors
45
FFWD Temp Offset -20 +20 0
46
Exhst Tmp Offset -20 +20 0
47
Outdr Air Offset -20 +20 0
48
Inlet Air Offset -20 +20 0
49
Inlet Wtr Offset -20 +20 0
50
Outlet Wtr Offset -20 +20 0
51
24 hr Max Cycles 0 9999 0
52
24 hr Max Ovrtemp 0 9999 0
53
0-10v Out Test 0.0 10.0 0.00
54
Spark Monitor Enabled or Disabled Depends on unit type/size
55
Min Spark Amps 0.0 Amps 2.5 Amps 0.10 Amps
56
Max Spark Amps 0.0 Amps 2.5 Amps 0.40 Amps
Off or Start Off
Page 30 of 164 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0122_0C 11/29/2017 Ph.: 800-526-0288 GF-206
Loading...
+ 134 hidden pages