AERCO BMK 2000DF User Manual

Benchmark 1500DF - 2000DF Boilers
Installation, Operation & Maintenance Manual (IOMM)
Natural Gas Modulating & Condensing Hot Water
USER MANUAL
Installation, Operation and Maintenance
Boiler Models:
BMK 1500DF
BMK 2000DF
Applicable to Serial Numbers:
G-14-0304 and Above
1500DF / 2000DF
DUAL FUEL
Gas-Fired Boilers
Release Date: 04/01/2014
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 1 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
Installation, Operation & Maintenance Manual (IOMM)
Technical Support
(Mon-Fri, 8am-5pm EST)
1-800-526-0288
www.aerco.com
Disclaimer
The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
Page 2 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
Installation, Operation & Maintenance Manual (IOMM)
TABLE OF CONTENTS
FOREWORD ......................................................................................................................................... 7
CHAPTER 1. SAFETY PRECAUTIONS ......................................................................................... 11
1.1 WARNINGS & CAUTIONS ................................................................................................................... 11
1.2 EMERGENCY SHUTDOWN ................................................................................................................. 12
1.3 PROLONGED SHUTDOWN ................................................................................................................. 12
CHAPTER 2. INSTALLATION ........................................................................................................ 15
2.1 INTRODUCTION ................................................................................................................................... 15
2.2 RECEIVING THE UNIT ......................................................................................................................... 15
2.3 UNPACKING ......................................................................................................................................... 15
2.4 SITE PREPARATION ........................................................................................................................... 16
2.4.1 Installation Clearances .................................................................................................................................... 16
2.4.2 Setting the Unit ............................................................................................................................................... 17
2.5 SUPPLY AND RETURN PIPING .......................................................................................................... 19
2.6 PRESSURE RELIEF VALVE INSTALLATION ..................................................................................... 19
2.7 CONDENSATE DRAIN & PIPING ........................................................................................................ 20
2.8 GAS SUPPLY PIPING .......................................................................................................................... 22
2.8.1 Gas Supply Specifications ............................................................................................................................... 22
2.8.2 Manual Gas Shutoff Valve .............................................................................................................................. 22
2.8.3 External Gas Supply Regulator ........................................................................................................................ 23
2.9 AC ELECTRICAL POWER WIRING ..................................................................................................... 24
2.9.1 Electrical Power Requirements ....................................................................................................................... 25
2.10 FIELD CONTROL WIRING ................................................................................................................. 26
2.10.1 Outdoor Air In (OUT) & Air Sensor Common (COM) .................................................................................... 28
2.10.2 COMBUSTION AIR Terminal .......................................................................................................................... 29
2.10.3 O2 SENSOR (O2+ & O2-) ................................................................................................................................ 29
2.10.4 SPARK SIGNAL (FLW+ & FLW-) ...................................................................................................................... 29
2.10.5 Analog In (+ & -) ............................................................................................................................................ 29
2.10.6 B.M.S. (PWM) In (BMS+ & BMS-) .................................................................................................................. 29
2.10.7 Shield (SHLD & SHLD) .................................................................................................................................... 29
2.10.8 Analog Output (+ & -) ................................................................................................................................... 29
2.10.9 RS-485 Comm (+, GND, & -) .......................................................................................................................... 30
2.10.10 RS-232 Comm (TxD & RxD) ......................................................................................................................... 30
2.10.11 VFD/Blower (0-10 & AGND) ........................................................................................................................ 30
2.10.12 Interlocks .................................................................................................................................................... 30
2.10.13 Fault Relay (NC, COM, & NO) ...................................................................................................................... 31
2.10.14 Auxiliary Relay Contacts (NC, COM, & NO) ................................................................................................. 31
2.11 FLUE GAS VENT INSTALLATION ..................................................................................................... 31
2.12 COMBUSTION AIR ............................................................................................................................. 32
2.12.1 Combustion From Outside the Building ....................................................................................................... 32
2.12.2 Combustion Air from Inside the Building ...................................................................................................... 32
2.13 DUCTED COMBUSTION AIR ............................................................................................................. 32
2.14 SEQUENCING VALVE INSTALLATION............................................................................................. 33
CHAPTER 3. OPERATION .............................................................................................................. 35
3.1 INTRODUCTION ................................................................................................................................... 35
3.2 CONTROL PANEL DESCRIPTION ...................................................................................................... 35
3.3 CONTROL PANEL MENUS .................................................................................................................. 39
3.3.1 Menu Processing Procedure ........................................................................................................................... 39
3.4 OPERATING MENU ............................................................................................................................. 41
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 3 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
3.5 SETUP MENU ....................................................................................................................................... 41
3.6 CONFIGURATION MENU .................................................................................................................... 42
3.7 TUNING MENU ..................................................................................................................................... 44
3.8 COMBUSTION CAL MENU .................................................................................................................. 45
3.9 BST (BOILER SEQUENCING TECHNOLOGY) MENU ....................................................................... 45
3.10 START SEQUENCE ........................................................................................................................... 48
3.11 START/STOP LEVELS ....................................................................................................................... 52
CHAPTER 4. INITIAL START-UP .................................................................................................. 53
4.1 INITIAL START-UP REQUIREMENTS ................................................................................................. 53
4.2 TOOLS AND INSTRUMENTATION FOR COMBUSTION CALIBRATION .......................................... 53
4.2.1 Required Tools & Instrumentation ................................................................................................................. 53
4.2.2 Installing Gas Supply Manometer ................................................................................................................... 54
4.2.3 Accessing the Analyzer Probe Port ................................................................................................................. 55
4.3 NATURAL GAS COMBUSTION CALIBRATION .................................................................................. 56
4.4 PROPANE COMBUSTION CALIBRATION .......................................................................................... 60
4.5 DUAL-FUEL SWITCHOVER INSTRUCTIONS .................................................................................... 63
4.5.1 Switchover from NATURAL GAS to PROPANE ................................................................................................. 63
4.5.2 Switchover from PROPANE to NATURAL GAS ................................................................................................. 64
4.6 REASSEMBLY ...................................................................................................................................... 65
4.7 OVER-TEMPERATURE LIMIT SWITCHES ......................................................................................... 65
4.7.1 Digital Alarm Switch Checks and Adjustments ............................................................................................... 66
CHAPTER 5. MODE OF OPERATION ........................................................................................... 69
5.1 INTRODUCTION ................................................................................................................................... 69
5.2 INDOOR/OUTDOOR RESET MODE ................................................................................................... 69
5.2.1 Reset Ratio ...................................................................................................................................................... 69
5.2.2 Building Reference Temperature .................................................................................................................... 69
5.2.3 Outdoor Air Temperature Sensor Installation ................................................................................................ 69
5.2.4 Indoor/Outdoor Startup ................................................................................................................................. 69
5.3 CONSTANT SETPOINT MODE ........................................................................................................... 70
5.3.1 Setting the Setpoint ........................................................................................................................................ 70
5.4 REMOTE SETPOINT MODES ............................................................................................................. 71
5.4.1 Remote Setpoint Field Wiring ......................................................................................................................... 71
5.4.2 Remote Setpoint Startup ................................................................................................................................ 72
5.5 DIRECT DRIVE MODES....................................................................................................................... 72
5.5.1 Direct Drive Field Wiring ................................................................................................................................. 73
5.5.2 Direct Drive Startup ........................................................................................................................................ 73
5.6 AERCO CONTROL SYSTEM (ACS) .................................................................................................... 73
5.6.1 ACS External Field Wiring................................................................................................................................ 73
5.6.2 ACS Setup and Startup .................................................................................................................................... 74
5.7 COMBINATION CONTROL SYSTEM (CCS) ....................................................................................... 74
5.7.1 Combination Control System Field Wiring ...................................................................................................... 75
5.7.2 Combination Control System Setup and Startup ............................................................................................ 75
CHAPTER 6. SAFETY DEVICE TESTING ..................................................................................... 77
6.1 TESTING OF SAFETY DEVICES ......................................................................................................... 77
6.2 LOW GAS PRESSURE FAULT TEST .................................................................................................. 78
6.3 HIGH GAS PRESSURE TEST ............................................................................................................. 79
6.4 LOW WATER LEVEL FAULT TEST ..................................................................................................... 80
6.5 WATER TEMPERATURE FAULT TEST .............................................................................................. 81
6.6 INTERLOCK TESTS ............................................................................................................................. 82
6.6.1 Remote Interlock Test..................................................................................................................................... 82
Installation, Operation & Maintenance Manual (IOMM)
Page 4 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
6.6.2 Delayed Interlock Test .................................................................................................................................... 83
6.7 FLAME FAULT TESTS ......................................................................................................................... 83
6.8 AIR FLOW FAULT TESTS .................................................................................................................... 85
6.8.1 Blower Proof Switch Test ................................................................................................................................ 85
6.8.2 Blocked Inlet Switch Test ................................................................................................................................ 85
6.9 SSOV PROOF OF CLOSURE SWITCH ............................................................................................... 87
6.10 PURGE SWITCH OPEN DURING PURGE ........................................................................................ 88
6.11 IGNITION SWITCH OPEN DURING IGNITION ................................................................................. 89
6.12 SAFETY PRESSURE RELIEF VALVE TEST ..................................................................................... 90
CHAPTER 7. MAINTENANCE ......................................................................................................... 91
7.1 MAINTENANCE SCHEDULE ............................................................................................................... 91
7.2 IGNITER-INJECTOR ............................................................................................................................ 92
7.3 FLAME DETECTOR ............................................................................................................................. 94
7.4 O2 SENSOR 95
7.5 SAFETY DEVICE TESTING ................................................................................................................. 95
7.6 BURNER ASSEMBLY INSPECTION ................................................................................................... 96
7.7 CONDENSATE DRAIN TRAP ............................................................................................................ 100
7.8 AIR FILTER CLEANING & REPLACEMENT ...................................................................................... 101
7.9 SHUTTING THE BOILER DOWN FOR AN EXTENDED PERIOD OF TIME ..................................... 102
7.10 PLACING THE BOILER BACK IN SERVICE AFTER A PROLONGED SHUTDOWN ..................... 102
CHAPTER 8. TROUBLESHOOTING GUIDE ............................................................................. 103
8.1 INTRODUCTION ................................................................................................................................. 103
8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES .................................................. 115
CHAPTER 9. RS-232 COMMUNICATION................................................................................. 117
9.1 INTRODUCTION ................................................................................................................................. 117
9.1.1 Acquiring the PuTTY Application .................................................................................................................. 117
9.1.2 Running a Command on a Remote Machine Using PuTTY ........................................................................... 118
9.2 RS-232 COMMUNICATION SETUP ................................................................................................... 119
9.3 MENU PROCESSING UTILIZING RS-232 COMMUNICATION ........................................................ 119
9.4 DATA LOGGING ................................................................................................................................. 120
9.4.1 Fault Log ....................................................................................................................................................... 121
9.4.2 Operation Time Log ...................................................................................................................................... 121
9.4.3 Sensor Log ..................................................................................................................................................... 122
CHAPTER 10. BOILER SEQUENCING TECHNOLOGY ............................................................. 123
10.1 INTRODUCTION ............................................................................................................................... 123
10.2 AERCO BST QUICK START CHART ............................................................................................... 124
10.3 BST IMPLEMENTATION INSTRUCTION ........................................................................................ 125
10.3.1 Option 1 - Constant Setpoint with DIRECT Wired Header Sensor .............................................................. 125
10.3.2 Option 2 - Constant Setpoint with MODBUS Wired Header Sensor ........................................................... 126
10.3.3 Option 3 - Outdoor Reset with DIRECT WIRED Header Sensor AND DIRECT WIRED Outdoor Sensor ....... 127
10.3.4 Option 4 - Outdoor Reset with MODBUS Header Sensor AND MODBUS Outdoor Sensor ........................ 129
10.3.5 Option 5 - Remote Setpoint with DIRECT WIRED Header Sensor AND 4-20ma Setpoint Drive ................. 131
10.3.6 Option 6 - Remote Setpoint with DIRECT WIRED Header Sensor AND MODBUS Setpoint Drive ............... 132
10.3.7 Option 7 - Remote Setpoint with MODBUS Header Sensor AND 4-20ma Setpoint Drive .......................... 133
10.3.8 Option 8 - Remote Setpoint with MODBUS Header Sensor AND MODBUS Setpoint Drive ....................... 135
APPENDIX A: BOILER MENU ITEM DESCRIPTIONS ............................................................. 137
APPENDIX B: STARTUP, STATUS & DISPLAY MESSAGES .................................................. 145
APPENDIX C: SENSOR RESISTANCE/VOLTAGE CHART ...................................................... 149
APPENDIX D: BOILER DEFAULT SETTINGS ............................................................................ 151
Installation, Operation & Maintenance Manual (IOMM)
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 5 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
APPENDIX E: RECOMMENDED PERIODIC TESTING ............................................................ 153
APPENDIX F: INDOOR/OUTDOOR RESET RATIO CHARTS ............................................... 155
APPENDIX G: DIMENSIONAL AND CLEARANCE DRAWINGS ............................................. 159
APPENDIX H: PART DRAWINGS ................................................................................................. 163
APPENDIX I: WIRING DIAGRAMS ............................................................................................. 175
APPENDIX J: PIPING DRAWINGS .............................................................................................. 183
APPENDIX K: C-MORE CONTROL PANEL VIEWS ................................................................... 189
APPENDIX L: RECOMMENDED SPARES ................................................................................... 191
Installation, Operation & Maintenance Manual (IOMM)
(This Page Is Intentionally Blank)
Page 6 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
Minimum
Maximum
Minimum
Maximum
FORWARD

FOREWORD

The AERCO Benchmark (BMK) 1500 and 2000 MBH boilers are modulating and condensing units. They represent a true industry advance that meets the needs of today's energy and environmental concerns. Designed for application in any closed loop hydronic system, the Benchmark's modulating capability relates energy input directly to fluctuating system loads. The turn down ratios for these boilers is 20:1. These BMK models provide extremely high efficiency operation and are ideally suited for modern low temperature, as well as, conventional heating systems.
The Benchmark Model BMK 1500 and BMK 2000 boilers operate within the following input and output ranges:
Benchmark Model
BMK 1500 75,000 1,500,000 64,500 1,395,000
Input Range (BTU/hr.) Output Range (BTU/hr.)
BMK 2000 100,000 2,000,000 86,000 1,860,000
The output of the boiler is a function of the unit’s firing rate (valve position) and return water temperature.
When installed and operated in accordance with this Instruction Manual, these boilers comply with the NOx emission standards outlined in:
South Coast Air Quality Management District (SCAQMD), Rule 1146.2
Whether used in singular or modular arrangements, the BMK 1500 and BMK 2000 offer the maximum venting flexibility with minimum installation space requirements. These boilers are Category II, III and IV, positive pressure appliances. Single and/or multiple breeched units are capable of operation in the following vent configurations:
Conventional, Vertical Conventional, Sidewall Conventional, Direct Vent, Vertical Sealed, Direct Vent, Horizontal
These boilers are capable of being vented utilizing Polypropylene and AL29-4C vent systems.
The Benchmark's advanced electronics are available in several selectable modes of operation offering the most efficient operating methods and energy management system integration.
IMPORTANT
Unless otherwise specified, all descriptions and procedures provided in this Installation, Operation & Maintenance Manual apply to the Benchmark series of boiler.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 7 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
ASME
American Society of Mechanical Engineers
(see below)
COMM (Comm)
Communication
Double Block and Bleed. Used to define boiler gas trains Energy Management System; often used interchangeably with
FORWARD
Phrases, Abbreviations and Acronyms
Phrase, Abbreviation or
Acronym
Meaning
A (Amp) Ampere
ACS AERCO Control System
ADDR Address
AGND Analog Ground
ALRM Alarm
AUX Auxiliary
BAS
Building Automation System, often used interchangeably with EMS
Symbol rate, or simply the number of distinct symbol changes
Baud Rate
(signaling events) transmitted per second. It is not equal to bits per second, unless each symbol is 1 bit long.
BMK Benchmark series boilers
BMS or BMS II AERCO Boiler Management Systems
BST AERCO on-board Boiler Management Technology
BLDG (Bldg) Building
BTU
British Thermal Unit. A unit of energy approximately equal to the heat required to raise 1 pound of water 1° F.
CCP Combustion Control Panel
C-More Controller (or Control Box)
A control system developed by AERCO and currently used in all Benchmark, Innovation and KC1000 Series product lines.
CO Carbon Monoxide
Cal. Calibration
CNTL Control
DBB
containing 2 Safety Shutoff Valves (SSOVs) and a solenoid operated vent valve. Also known as IRI gas trains(see below)
DIP Dual In-Line Package
EMS
BAS
FM Factory Mutual. Used to define boiler gas trains.
GND Ground
HDR Header
HX Heat Exchanger
Hz Hertz (Cycles Per Second)
I.D. Inside Diameter
IGN Ignition
Page 8 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
Phrase, Abbreviation or
Acronym
FORWARD
Phrases, Abbreviations and Acronyms – Continued
Meaning
IGST Board Ignition/Stepper Board contained in C-More Control Box
INTLK (INTL’K) Interlock
I/O Input/Output
I/O Box
IP Internet Protocol
IRI
ISO Isolated
LED Light Emitting Diode
LN Low NOx
MA (mA) Milliampere (0.001 Amp), one thousandth of an amp
MAX (Max) Maximum
MIN (Min) Minimum
Modbus®
NC (N.C.) Normally Closed
NO (N.O.) Normally Open
NOx Nitrogen Oxide
NPT National Pipe Thread
O2 Oxygen
O.D. Outside Diameter
PMC Board
PPM Parts Per Million
PTP Point-to-Point (usually over RS-232 networks)
PWM Pulse Width Modulation
REF (Ref) Reference
RES. Resistive
RS-232 (or EIA-232)
RS-422 (or EIA-422)
RS-485 (or EIA-485)
RTN (Rtn) Return
SETPT (Setpt) Setpoint Temperature
SHLD (Shld) Shield
Input/Output (I/O) Box currently used on Benchmark, Innovation and KC1000 Series products
Industrial Risk Insurers. A now discontinued code used to define gas trains containing two SSOVs and a solenoid operated vent valve.
A serial, half-duplex data transmission protocol developed by AEG Modicon
A Primary Micro-Controller (PMC) board is contained in the C-More Control Box used on all Benchmark units.
A standard for serial, full-duplex (FDX) transmission of data based on the RS-232 Standard
A standard for serial, full-duplex (FDX) transmission of data based on the RS-422 Standard
A standard for serial, half-duplex (HDX) transmission of data based on the RS-485 Standard
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 9 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
Phrase, Abbreviation or
Acronym
TEMP (Temp)
Temperature
order to prevent reflections that may cause invalid data in the VDC
Volts, Direct Current
W.C.
Water Column (W.C.)
FORWARD
Phrases, Abbreviations and Acronyms – Continued
Meaning
SSOV Safety Shut Off Valve
A resistor placed at each end of a daisy-chain or multi-drop network in
Terminating Resistor
communication
uA Microamp (0.000001 amp), one millionth of an amp
VAC Volts, Alternating Current
VFD Vacuum Fluorescent Display, or Variable Frequency Drive
W Watt
Page 10 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
WARNING
WARNING
WARNING
WARNING
CHAPTER 1 – SAFETY PRECAUTIONS

CHAPTER 1. S AF ET Y PRECAUTIONS

1.1 WARNINGS & CAUTIONS

Installers and operating personnel MUST, at all times, observe all safety regulations. The following warnings and cautions are general and must be given the same attention as specific precautions included in these instructions. In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54) for gas-fired boilers and ANSI/NFPASB for LP gas-fired boilers. Where applicable, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CSA B149.1, and applicable Provincial regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
See pages 13 and 14 for important information regarding installation of units within the Commonwealth of Massachusetts.
IMPORTANT
This Instruction Manual is an integral part of the product and must be maintained in legible condition. It must be given to the user by the installer and kept in a safe place for future reference.
DO NOT USE MATCHES, CANDLES, FLAMES, OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS.
FLUIDS UNDER PRESSURE MAY CAUSE INJURY TO PERSONNEL OR DAMAGE TO EQUIPMENT WHEN RELEASED. BE SURE TO SHUT OFF ALL INCOMING AND OUTGOING WATER SHUTOFF VALVES. CAREFULLY DECREASE ALL TRAPPED PRESSURES TO ZERO BEFORE PERFORMING MAINTENANCE.
BEFORE ATTEMPTING TO PERFORM ANY MAINTENANCE ON THE UNIT, SHUT OFF ALL GAS AND ELECTRICAL INPUTS TO THE UNIT.
THE EXHAUST VENT PIPE OF THE UNIT OPERATES UNDER A POSITIVE PRESSURE AND THEREFORE MUST BE COMPLETELY SEALED TO PREVENT LEAKAGE OF COMBUSTION PRODUCTS INTO LIVING SPACES.
WARNING
ELECTRICAL VOLTAGES UP TO 480 VAC MAY BE USED IN THIS EQUIPMENT. THEREFORE THE COVER ON THE UNIT’S POWER BOX (LOCATED BEHIND THE FRONT PANEL DOOR) MUST BE INSTALLED AT ALL TIMES, EXCEPT DURING MAINTENANCE AND SERVICING.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 11 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
WARNING
CAUTION
CAUTION
CHAPTER 1 – SAFETY PRECAUTIONS
A THREE-POLE SWITCH MUST BE INSTALLED ON THE ELECTRICAL SUPPLY LINE OF THE UNIT. THE SWITCH MUST BE INSTALLED IN AN EASILY ACCESSIBLE POSITION TO QUICKLY AND SAFELY DISCONNECT ELECTRICAL SERVICE. DO NOT AFFIX SWITCH TO UNIT SHEET METAL ENCLOSURES.
Many soaps used for gas pipe leak testing are corrosive to metals. The piping must be rinsed thoroughly with clean water after leak checks have been completed.
DO NOT use this boiler if any part has been under water. Call a qualified service technician to inspect and replace any part that has been under water.

1.2 EMERGENCY SHUTDOWN

If overheating occurs or the gas supply fails to shut off, close the manual gas shutoff valve (Figure 1-1) located external to the unit.
NOTE
The Installer must identify and indicate the location of the emergency shutdown manual gas valve to operating personnel.
MANUAL GAS SHUT-OFF VALVE
VALVE OPEN VALVE CLOSED
Figure 1-1: Manual Gas Shutoff Valve

1.3 PROLONGED SHUTDOWN

After prolonged shutdown, it is recommended that the startup procedures in Chapter 4 and the safety device test procedures in Chapter 6 of this manual be performed, to verify all system-
Page 12 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
CHAPTER 1 – SAFETY PRECAUTIONS
operating parameters. If there is an emergency, turn off the electrical power supply to the AERCO boiler and close the manual gas valve located upstream the unit. The installer must identify the emergency shut-off device.
IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS
Boiler Installations within the Commonwealth of Massachusetts must conform to the following requirements:
Boiler must be installed by a plumber or a gas fitter who is licensed within the Commonwealth of Massachusetts.
Prior to unit operation, the complete gas train and all connections must be leak tested using a non-corrosive soap.
The vent termination must be located a minimum of 4 feet above grade level. If side-wall venting is used, the installation must conform to the
following requirements extracted from 248 CMR 5.08 (2):
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide det ector as required in accordance with the above provisions shall comply with NFPA 720 and be
ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIO NS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 13 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
CHAPTER 1 – SAFETY PRECAUTIONS
fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
____________________________________________________________________________
[End of Extracted Information From 248 CMR 5.08 (2)]
Page 14 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION

CHAPTER 2. INSTALLATION

2.1 INTRODUCTION

This Chapter provides the descriptions and procedures necessary to unpack, inspect and install the AERCO Benchmark Boiler Model BMK 1500 and BMK 2000.

2.2 RECEIVING THE UNIT

Each Benchmark Boiler System is shipped as a single crated unit. The shipping weight for these BMK models is approximately 1800 pounds. The unit must be moved with the proper rigging equipment for safety and to avoid equipment damage. The unit should be completely inspected for evidence of shipping damage and shipment completeness at the time of receipt from the carrier and before the bill of lading is signed.
NOTE
AERCO is not responsible for lost or damaged freight. Each unit has a Tip-N-Tell indicator on the outside of the crate. This indicates if the unit has been turned on its side during shipment. If the Tip-N-Tell indicator is tripped, do not sign for the shipment. Note the information on the carrier’s paperwork and request a freight claim and inspection by a claims adjuster before proceeding. Any other visual damage to the packaging materials should also be made clear to the delivering carrier.

2.3 UNPACKING

Carefully unpack the unit taking care not to damage the unit enclosure when cutting away packaging materials
After unpacking, a close inspection of the unit should be made to ensure that there is no evidence of damage not indicated by the Tip-N-Tell indicator. The freight carrier should be notified immediately if any damage is detected.
The following accessories come standard with each unit and are either packed separately within the unit’s shipping container or are factory installed on the unit:
Pressure/Temperature Gauge
ASME Pressure Relief Valve
Condensate Drain Trap (part no. 24060)
2” Gas Supply Shutoff Valve
When optional accessories are ordered, they may be packed within the unit’s shipping container, factory installed on the unit, or packed and shipped in a separate container. Any standard or optional accessories shipped loose should be identified and stored in a safe place until ready for installation or use.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 15 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION

2.4 SITE PREPARATION

Ensure that the site selected for installation of the Benchmark 1500/2000 Boiler includes:
Access to AC Input Power at 120 VAC, Single-Phase, 60 Hz @ 20 Amps
Access to Natural Gas line at a minimum pressure of 8 inches W.C. at gas flow for
1,500,000 BTU/hr energy input for the BMK 1500 OR 2,000,000 BTU/hr energy input for the BMK 2000.

2.4.1 Installation Clearances

The Benchmark Model 1500 and 2000 are packaged in an enclosure having identical exterior dimensions. The unit must be installed with the prescribed clearances for service as shown in Figure 2-1a. The minimum clearance dimensions, required by AERCO, are listed below. However, if Local Building Codes require additional clearances, these codes shall supersede AERCO’s requirements. Minimum acceptable clearances required are as follows:
Sides: 24 inches
Front : 24 inches
Rear: 24 inches
Top: 18 inches
All gas piping, water piping and electrical conduit or cable must be arranged so that they do not interfere with the removal of any panels, or inhibit service or maintenance of the unit.
NOTE
Ensure that condensate
assembly is not
located over the
housekeeping
pad.
Figure 2-1a: Benchmark Boiler Model 1500/2000 Clearances
Page 16 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
CAUTION
WARNING
CHAPTER 2 – INSTALLATION
WARNING
KEEP THE UNIT AREA CLEAR AND FREE FROM ALL COMBUSTIBLE MATERIALS AND FLAMMABLE VAPORS OR LIQUIDS
.
While packaged in the shipping container, the unit must be moved by pallet jack or forklift from the FRONT ONLY.
FOR MASSACHUSSETTS ONLY:
For Massachusetts installations, the unit must be installed by a plumber or gas-fitter licensed within the Commonwealth of Massachusetts. In addition, the installation must comply with all requirements specified in Chapter 1 (Safety Precautions), pages 11 and 12.

2.4.2 Setting the Unit

The unit must be installed on a 4 to 8 inch thick concrete housekeeping pad to ensure proper condensate drainage. If anchoring the unit, refer to Figure 2-1b for anchor locations.
A total of 3 lifting lugs are provided at the top of the primary heat exchanger as shown in Figure 2-2. Remove the front top panel from the unit to provide access to the lifting tabs.
Remove the four (4) lag screws securing the unit to the shipping skid. Lift the unit off the shipping skid and position it on the 4 to 6 inch concrete housekeeping pad (required) in the desired location.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 17 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Figure 2-1b: Benchmark 1500/2000 Anchor Bolt Locations
WHEN LIFTING OR MOVING THE BOILER, DO NOT ATTEMPT
TO MANIPULATE THE BOILER USING THE GAS TRAIN OR BLOWER.
Benchmark 1500DF - 2000DF Boilers
GAS INLET
INLET
CHAPTER 2 – INSTALLATION
LIFTING LUGS
(3 POSITIONS)
1” PROPANE
2” NATURAL
Figure 2-2: Boiler Lifting Provisions
In multiple unit installations, it is important to plan the position of each unit in advance. Sufficient space for piping connections and future service/maintenance requirements must also be taken
into consideration. All piping must include ample provisions for expansion.
If installing a Combination Control Panel (CCP) system, it is important to identify the Combination Mode Boilers in advance and place them in the proper physical location. Refer to Chapter 5 for information on Combination Mode Boilers.
Page 18 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
2” NATURAL GAS INLET
BOILER HOT
EXHAUST
MANIFOLD
CONDENSATE
DRAIN PORT
CHAPTER 2 – INSTALLATION

2.5 SUPPLY AND RETURN PIPING

The Benchmark Boiler utilizes 4” 150# flanges for the water system supply and return piping connections. The physical location of the supply and return piping connections are on the rear of the unit as shown in Figure 2-3.
1” PROPANE INLET
WATER OUTLET
(SUPPLY)
AIR INLET
PRIMARY
WATER INLET
(RETURN)
DRAIN VALVE
Figure 2-3: Supply and Return Locations

2.6 PRESSURE RELIEF VALVE INSTALLATION

An ASME rated Pressure Relief Valve is supplied with each Benchmark Boiler. The pressure rating for the relief valve must be specified on the sales order. Available pressure ratings range from 30 psi to 160 psi. The relief valve is installed on the hot water outlet of the boiler as shown in Figure 2-4. A suitable pipe joint compound should be used on the threaded connections. Any excess should be wiped off to avoid getting any joint compound into the valve body. The relief valve must be piped to within 12 inches of the floor to prevent injury in the event of a discharge.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 19 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
PRIMARY WATER INLET
1/4” ANALYZER
NPT PORT
EXHAST
MANIFOLD
CHAPTER 2 – INSTALLATION
are allowed in the discharge line. In multiple unit installations the discharge lines must not be manifolded together. Each must be individually run to a suitable discharge location.
PRESSURE
RELIEF VALVE
4” HOT BOILER
WATER OUTLET
Figure 2-4: P&T Relief Valve Location

2.7 CONDENSATE DRAIN & PIPING

The Benchmark Boiler is designed to condense water vapor from the flue products. Therefore, the installation must have provisions for suitable condensate drainage or collection.
The condensate drain port located on the exhaust manifold (Figure 2-5) must be connected to the condensate trap (P/N 24060) which is packed separately within the unit’s shipping container. The condensate trap inlet features two integral O-rings and a thumbscrew to allow direct connection of the drain port into the trap inlet. See the Condensate trap Installation instructions and Figure 2-6 on the next page.
AIR INLET
DRAIN VALVE
CONDENSATE DRAIN PORT
Figure 2-5: Condensate Drain Connection Location
A sample condensate trap installation is shown in Figure 2-6. The following general guidelines must be observed to ensure proper condensate drainage:
The condensate trap inlet (Figure 2-6) must be level the exhaust manifold drain port.
The base of the condensate trap must be supported to ensure that it is level (horizontal).
The trap must be removable for routine maintenance.
Page 20 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
CAUTION
COMBUTION
PROBE PORT
EXHAUST
MANIFOLD
3/4” NPT
NIPPLES
HOSE CLAMP
TRAP INLET
TOP
(4 ea.)
1” DIAM. HOSE
NOTE
ASSEMBLY.
4” MINIMUM
(8” MAXIMUM)
4”
CHAPTER 2 – INSTALLATION
While observing the above guidelines, install the condensate trap as follows:
Condensate Trap Installat ion
1. Connect the condensate trap inlet to the exhaust manifold drain connection by inserting the drain port directly into the trap adaptor inlet, and then tightening the inlet thumbscrew, as shown in Figure 2-6. The inlet features two integral O-rings to prevent leakage.
2. At the condensate trap outlet, install a 3/4” NPT nipple.
3. Connect a length of 1” diameter polypropylene hose to the trap outlet and secure with a hose clamp.
4. Route the hose on the trap outlet to a nearby floor drain.
If a floor drain is not available, a condensate pump can be used to remove the condensate to
drain. The maximum condensate flow rate is 30 GPH. The condensate drain trap, associated
fittings and drain line must be removable for routine maintenance.
Use PVC, stainless steel, aluminum or polypropylene for condensate drain piping (Figure 2-6). DO NOT use carbon or copper components.
ANALYZER
HOUSKEEPING
PAD MUST NOT
EXTEND
UNDER THE
CONDENSATE
EXHAUST
MANIFOLD
DRAIN PORT
INTEGRAL ADAPTOR AND THUMBSCREW
COVER THUMB
SREWS
CONDENSATE
TRAP (P/N 24060)
T O FLOOR DRAIN
Figure 2-6: Sample Condensate Trap Installation (Right Side View)
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 21 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
CAUTION
CHAPTER 2 – INSTALLATION

2.8 GAS SUPPLY PIPING

The AERCO Benchmark Gas Components and Supply Design Guide, GF-2030 must be consulted prior to designing or installing any gas supply piping.
WARNING
NEVER USE MATCHES, CANDLES, FLAMES OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS
.
Many of the soaps used for gas pipe leak testing are corrosive to metals. Therefore, piping must be rinsed thoroughly with clean
water after leak checks have been completed.
NOTE
All gas piping must be arranged so that it does not interfere with removal of any covers, inhibit service/maintenance, or restrict access between the unit and walls, or another unit.
Benchmark 1500 and 2000 units contain a 2 inch NATURAL GAS inlet connection, and a 1 inch PROPANE gas connection on the top of the unit, as shown in Figures 2-2 and 2-3.
Prior to installation, all pipes should be de-burred and internally cleared of any scale, metal chips or other foreign particles. Do Not install any flexible connectors or unapproved gas fittings. Piping must be supported from the floor, ceiling or walls only and must not be supported by the unit.
A suitable piping compound, approved for use with natural gas, should be used. Any excess must be wiped off to prevent clogging of components.
To avoid unit damage when pressure testing gas piping, the unit must be isolated from the gas supply piping. At no time should the gas pressure applied to the unit exceed 14” W.C. A thorough leak test of all external piping must be performed using a soap and water solution or suitable equivalent. The gas piping used must meet all applicable codes.

2.8.1 Gas Supply Specifications

The gas supply input specifications to the unit for Natural Gas and Propane gas are as follows:
The maximum static pressure to the unit must not exceed 14” W.C.
The gas supply pressure to the unit must be of sufficient capacity to provide 2000 cfh while
maintaining the gas pressure at 6 inches W.C. for FM gas trains operating at maximum capacity.

2.8.2 Manual Gas Shutoff Valve

A manual shut-off valve must be installed in the gas supply line upstream of the boiler as shown in Figure 2-7. Maximum allowable gas pressure to the boiler is 14” W.C.
Page 22 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
NATURAL GAS PRESSURE REGULATOR
NATURAL
SUPPLY
PROPANE
SUPPLY
PROPANE GAS
CHAPTER 2 – INSTALLATION

2.8.3 External Gas Supply Regulator

An external gas pressure regulator is required on the gas inlet piping under most conditions (see sections 2.8.3.1 and 2.8.3.2, below). Regulators must conform to the following specifications:
NATURAL GAS: The external natural gas regulator must be capable of regulating
100,000 – 2,120,000 BTU/HR of natural gas while maintaining a gas pressure of 8.0” W.C. minimum to the unit.
PROPANE GAS: The external propane gas regulator must be capable of regulating
100,000 – 2,120,000 BTU/HR of propane gas while maintaining a gas pressure of 4.0” W.C. minimum to the unit
A lock-up style regulator MUST be used when gas supply pressure will exceed 14” W.C.
2.8.3.1
Massachusetts Installations Only
For Massachusetts installations, a mandatory external gas supply regulator must be positioned as shown in Figure 2-7. The gas supply regulator must be properly vented to outdoors. Consult the local gas utility for detailed requirements concerning venting of the supply gas regulator.
2.8.3.2
All Installations (Except Massachusetts)
For multi-unit installations (other than Massachusetts) that EXCEED 7” W.C. gas pressure, a separate external gas supply regulator, as shown in Figure 2-7, is highly recommended. No regulator is required for gas pressures below 7” W.C. of pressure. Consult the local gas utility for detailed requirements concerning venting of the supply gas regulator.
NATURAL GAS MANUAL SHUT-OFF VALVE
GAS
NATURAL GAS INLET
PROPANE
MANUAL SHUT-
OFF VALVE
PRESSURE
REGULATOR
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 23 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Figure 2-7: Manual Gas Shut-Off Valve Location
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
NOTE
It is the responsibility of the customer to source and purchase the appropriate gas regulator as described above. However, AERCO offers for sale an appropriate regulator, which may be ordered at the time of unit purchase or separately. Contact AERCO for more information.

2.9 AC ELECTRICAL POWER WIRING

The AERCO Benchmark Electrical Power Wiring Guide, GF-2060, must be consulted prior to connecting any AC power wiring to the unit. External AC power connections are made to the unit inside the Power Box on the front of the unit. Remove the front panel to access the Power Box, which is mounted in the upper right corner of the unit as shown in Figure 2-8. Loosen the two upper screws of the Power Box cover and remove cover to access the internal connections shown in Figure 2-9.
Figure 2-8: Power Box Location with Cover Closed
THE POWER BREAKER SHOWN IN FIGURE 2-9 DOES NOT
REMOVE POWER FROM THE TERMINAL BLOCKS.
WARNING
Page 24 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
BREAKER
CHAPTER 2 – INSTALLATION
TRANSFORMER
24V POWER
SUPPLY
12V POWER
SUPPLY
WIRE CONDUITS
POWER
FUSE BLOCKS (2)
TERMINAL BLOCKS
Figure 2-9: Power Box Internal Components
With the exception of the transformer shown in Figure 2-9, all of the components in the Power Box are mounted on a DIN rail.
NOTE
All electrical conduit and hardware must be installed so that it does not interfere with the removal of any unit covers, inhibit service/maintenance, or prevent access between the unit and walls or another unit.

2.9.1 Electrical Power Requirements

The Benchmark 1500 and Benchmark 2000 models are available in one voltage configuration:
120 VAC, Single-Phase, 60 Hz @ 20 Amps
The Power Box contains terminal blocks as shown in Figure 2-9. In addition, a label showing the required AC power connections is provided on the front cover of the Power Box as shown in Figure 2-10.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 25 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
Figure 2-10: Power Box Cover Labels – 120VAC
Each unit must be connected to a dedicated electrical circuit. NO OTHER DEVICES SHOULD BE ON THE SAME ELECTRICAL CIRCUIT AS THE BOILER.
A three-pole switch must be installed on the electrical supply line in an easily accessible location to quickly and safely disconnect electrical service. DO NOT attach the switch to sheet metal enclosures of the unit.
After placing the unit in service, the ignition safety shutoff device must be tested. If an external electrical power source is used, the installed boiler must be electrically bonded to ground in accordance with the requirements of the authority having jurisdiction. In the absence of such requirements, the installation shall conform to National Electrical Code (NEC), ANSI/NFPA 70 and/or the Canadian Electrical Code (CEC) Part I, CSA C22.1 Electrical Code.
For electrical power wiring diagrams, see the AERCO Benchmark Electrical Power Guide, (GF-
2060).

2.10 FIELD CONTROL WIRING

Each unit is fully wired from the factory with an internal operating control system. No field control wiring is required for normal operation. However, the C-More Control system used with all Benchmark units does allow for some additional control and monitoring features. Wiring connections for these features are made on the Input/Output (I/O) board located behind the removable front panel assembly of the unit. The I/O board is located in the upper-left portion on the front of the unit as shown in Figure 2-11. The I/O board terminal strip connections are shown in Figure 2-12. All field wiring is installed from the rear of the panel by routing the wires through one of the four bushings provided on the sides of the I/O board.
Refer to the wiring diagram provided below the I/O Box (Figure 2-12) when making all wiring connections.
Page 26 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
CAUTION
CHAPTER 2 – INSTALLATION
TERMINAL STRIPS
I/O PCB BOARD
Figure 2-11: Input/Output (I/O) Box Location
NOTE
Use Figure 2-12 to determine the functions of the I/O PCB connections. Do not use the silkscreened labels on the PCB itself, as these may not match the function names.
There is a diagram of the connection functions on the cover of the I/O Box as well.
DO NOT make any connections to the I/O Box terminals labeled “NOT USED”. Attempting to do so may cause equipment damage.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 27 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
Figure 2-12: I/O Box Terminal Strips

2.10.1 Outdoor Air In (OUT) & Air Sensor Common (COM)

The OUTDOOR AIR IN terminal is used for connecting an outdoor temperature sensor (AERCO P/N GM-123525) as required primarily for the Indoor/Outdoor reset mode of operation. It can also be used with another mode if it is desired to use the outdoor sensor enable/disable feature. This feature allows the boiler to be enabled or disabled based on the outdoor air temperature.
The factory default for the outdoor sensor is DISABLED. To enable the sensor and/or select an enable/disable outdoor temperature, see the Configuration Menu in Chapter 3.
The outdoor sensor may be wired up to 200 feet from the boiler. It is connected to the OUTDOOR AIR IN and AIR SENSOR COMMON terminals of the I/O PCB (Figure 2-12). Wire the sensor using a twisted shielded pair wire from 18 to 22 AWG. There is no polarity to observe when terminating these wires. The shield is to be connected only to the terminals labeled SHIELD in the I/O Box PCB. The sensor end of the shield must be left free and ungrounded.
When mounting the sensor, it must be located on the North side of the building where an average outside air temperature is expected. The sensor must be shielded from direct sunlight as well as impingement by the elements. If a shield is used, it must allow for free air circulation.
Page 28 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION

2.10.2 COMBUSTION AIR Terminal

The COMBUSTIAN AIR terminal is used to monitor the combustion air temperature sensor. This input is always enabled and is a “to view only” input that can be seen in the operating menu. The sensor is an AERCO BALCO wire sensor P/N 12449. A resistance chart for this sensor is provided in APPENDIX C. This sensor is an active part of the combustion control system and must be operational for accurate air/fuel mixing control.

2.10.3 O2 SENSOR (O2+ & O2-)

The O2 SENSOR (+) and O2 SENSOR (–) terminals are used to connect an integrated oxygen sensor to the I/O Box PCB. The O More Control system after a 60 second warm-up period.

2.10.4 SPAR K SIGNAL (FLW+ & FLW-)

The two SPARK SIGNAL terminals permit an external current sensor to be connected for ignition spark monitoring purposes. If no spark is present during the ignition sequence, the controller will shut down and display a fault message.

2.10.5 Analog In (+ & -)

The two ANALOG IN terminals are used when an external signal is used to change the setpoint (Remote Setpoint Mode) of the boiler.
concentration is displayed in the operating menu of the C-
2
Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA/ 0 to 5 VDC signal may be used to vary the set­point or air/fuel valve position. The factory default setting is for 4 to 20 mA / 1 to 5 VDC, however this may be changed to 0 to 20 mA / 0 to 5 VDC using the Configuration Menu described in Chapter 3.
If voltage rather than current is selected as the drive signal, a DIP switch must be set on the PMC Board located inside the C-More Control Box. Contact the AERCO factory for information on setting DIP switches.
All supplied signals must be floating (ungrounded) signals. Connections between the source and the boiler’s I/O PCB (Figure 2-12) must be made using twisted shielded pair of 18–22 AWG wire such as Belden 9841. Polarity must be maintained and the shield must be connected only at the source end and must be left floating (not connected) at the Boiler’s I/O PCB.
Whether using voltage or current for the drive signal, they are linearly mapped to a 40°F to
240°F setpoint or a 0% to 100% air/fuel valve position. No scaling for these signals is provided

2.10.6 B.M.S. (PWM) In (BMS+ & BMS-)

These terminals are only used to connect to legacy AERCO Boiler Management Systems (BMS), which utilize a 12 millisecond, ON/OFF duty cycle and is Pulse Width Modulated (PWM) to control valve position. A 0% valve position = a 5% ON pulse and a 100% valve position = a 95% ON pulse. Note that these connections cannot be used with the AERCO Control System (ACS).

2.10.7 Shield (SHLD & SHLD)

The SHIELD terminals are used to terminate any shields used on sensor wires connected to the unit. Shields must only be connected to these terminals.

2.10.8 Analog Output (+ & -)

The ANALOG OUT terminals (+ & -) output from 0 to 20 mA and may be used to monitor Setpoint, Outlet Temperature, Valve Position 4-20 mA, Valve Position 0-10v or be set to OFF. Default setting in the C-More controller is Valve Position 0-10v and settings behave as follows:
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 29 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
When 0-10VDC is selected, the voltage output is used by the controller to modulate the combustion blower via the I/O Box terminals labeled VFD/Blower (Section 2.10.11).
If On Board Boiler Sequencing Technology (BST) is enabled, the Analog Output terminals are used to drive the isolation valve, open and closed.
When the 4-20mA is selected for the Analog Output, the 0-10VDC is disabled at the VFD/Blower terminals, and the selected output is available at the terminals labeled Analog Output +/-.

2.10.9 RS-485 Comm (+, GND, & -)

The RS-485 communication terminals are used when the boiler plant is being controlled by an Energy Management System (EMS) or an AERCO Control System (ACS) using Modbus (RS-
485) communication.

2.10.10 RS-232 Comm (TxD & RxD)

The RS-232 communication terminals permit a laptop computer or other suitable terminal to be connected to the boiler. The RS-232 communication feature permits viewing or changing of Control Panel menu options and also provides access to data logs showing fault and sensor log displays.

2.10.11 VFD/Blower (0-10 & AGND)

These terminals (0-10 & AGND) send an analog signal to control the blower speed. When any of the 4-20mA options is selected for the Analog Outputs (Section 2.10.8), the output from the VFD/Blower terminals is disabled.

2.10.12 Interlocks

The unit offers two interlock circuits for interfacing with Energy Management Systems and auxiliary equipment such as pumps or louvers or other accessories. These interlocks are called the Remote Interlock and Delayed Interlock (REMOTE INTL’K IN and DELAYED INTL’K IN in Figure 2-12). Both interlocks, described below, are factory wired in the closed position (using jumpers).
NOTE
Both the Delayed Interlock and Remote Interlock must be in the closed position for the unit to fire.
2.10.12.1
The remote interlock circuit is provided to remotely start (enable) and stop (disable) the unit if desired. The circuit is 24 VAC and comes factory pre-wired closed (jumped).
2.10.12.2
The Delayed Interlock terminals can be used in one of two ways:
Remote Interlock In (OUT & IN)
Delayed Interlock In (OUT & IN)
In conjunction with the optional external sequencing valve (see section 2.14 and Chapter 10 – BST), a component of AERCO’s on-board Boiler Sequencing Technology (BST) solution. By default a cable of the boiler’s wiring harness is connected to these terminals. If BST is implemented, the other end of that cable is connected to the sequencing valve.
Page 30 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Loading...
+ 166 hidden pages