AERCO BMK 2000DF User Manual

Page 1
Benchmark 1500DF - 2000DF Boilers
Installation, Operation & Maintenance Manual (IOMM)
Natural Gas Modulating & Condensing Hot Water
USER MANUAL
Installation, Operation and Maintenance
Boiler Models:
BMK 1500DF
BMK 2000DF
Applicable to Serial Numbers:
G-14-0304 and Above
1500DF / 2000DF
DUAL FUEL
Gas-Fired Boilers
Release Date: 04/01/2014
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 1 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 2
Benchmark 1500DF - 2000DF Boilers
Installation, Operation & Maintenance Manual (IOMM)
Technical Support
(Mon-Fri, 8am-5pm EST)
1-800-526-0288
www.aerco.com
Disclaimer
The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
Page 2 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 3
Benchmark 1500DF - 2000DF Boilers
Installation, Operation & Maintenance Manual (IOMM)
TABLE OF CONTENTS
FOREWORD ......................................................................................................................................... 7
CHAPTER 1. SAFETY PRECAUTIONS ......................................................................................... 11
1.1 WARNINGS & CAUTIONS ................................................................................................................... 11
1.2 EMERGENCY SHUTDOWN ................................................................................................................. 12
1.3 PROLONGED SHUTDOWN ................................................................................................................. 12
CHAPTER 2. INSTALLATION ........................................................................................................ 15
2.1 INTRODUCTION ................................................................................................................................... 15
2.2 RECEIVING THE UNIT ......................................................................................................................... 15
2.3 UNPACKING ......................................................................................................................................... 15
2.4 SITE PREPARATION ........................................................................................................................... 16
2.4.1 Installation Clearances .................................................................................................................................... 16
2.4.2 Setting the Unit ............................................................................................................................................... 17
2.5 SUPPLY AND RETURN PIPING .......................................................................................................... 19
2.6 PRESSURE RELIEF VALVE INSTALLATION ..................................................................................... 19
2.7 CONDENSATE DRAIN & PIPING ........................................................................................................ 20
2.8 GAS SUPPLY PIPING .......................................................................................................................... 22
2.8.1 Gas Supply Specifications ............................................................................................................................... 22
2.8.2 Manual Gas Shutoff Valve .............................................................................................................................. 22
2.8.3 External Gas Supply Regulator ........................................................................................................................ 23
2.9 AC ELECTRICAL POWER WIRING ..................................................................................................... 24
2.9.1 Electrical Power Requirements ....................................................................................................................... 25
2.10 FIELD CONTROL WIRING ................................................................................................................. 26
2.10.1 Outdoor Air In (OUT) & Air Sensor Common (COM) .................................................................................... 28
2.10.2 COMBUSTION AIR Terminal .......................................................................................................................... 29
2.10.3 O2 SENSOR (O2+ & O2-) ................................................................................................................................ 29
2.10.4 SPARK SIGNAL (FLW+ & FLW-) ...................................................................................................................... 29
2.10.5 Analog In (+ & -) ............................................................................................................................................ 29
2.10.6 B.M.S. (PWM) In (BMS+ & BMS-) .................................................................................................................. 29
2.10.7 Shield (SHLD & SHLD) .................................................................................................................................... 29
2.10.8 Analog Output (+ & -) ................................................................................................................................... 29
2.10.9 RS-485 Comm (+, GND, & -) .......................................................................................................................... 30
2.10.10 RS-232 Comm (TxD & RxD) ......................................................................................................................... 30
2.10.11 VFD/Blower (0-10 & AGND) ........................................................................................................................ 30
2.10.12 Interlocks .................................................................................................................................................... 30
2.10.13 Fault Relay (NC, COM, & NO) ...................................................................................................................... 31
2.10.14 Auxiliary Relay Contacts (NC, COM, & NO) ................................................................................................. 31
2.11 FLUE GAS VENT INSTALLATION ..................................................................................................... 31
2.12 COMBUSTION AIR ............................................................................................................................. 32
2.12.1 Combustion From Outside the Building ....................................................................................................... 32
2.12.2 Combustion Air from Inside the Building ...................................................................................................... 32
2.13 DUCTED COMBUSTION AIR ............................................................................................................. 32
2.14 SEQUENCING VALVE INSTALLATION............................................................................................. 33
CHAPTER 3. OPERATION .............................................................................................................. 35
3.1 INTRODUCTION ................................................................................................................................... 35
3.2 CONTROL PANEL DESCRIPTION ...................................................................................................... 35
3.3 CONTROL PANEL MENUS .................................................................................................................. 39
3.3.1 Menu Processing Procedure ........................................................................................................................... 39
3.4 OPERATING MENU ............................................................................................................................. 41
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 3 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 4
Benchmark 1500DF - 2000DF Boilers
3.5 SETUP MENU ....................................................................................................................................... 41
3.6 CONFIGURATION MENU .................................................................................................................... 42
3.7 TUNING MENU ..................................................................................................................................... 44
3.8 COMBUSTION CAL MENU .................................................................................................................. 45
3.9 BST (BOILER SEQUENCING TECHNOLOGY) MENU ....................................................................... 45
3.10 START SEQUENCE ........................................................................................................................... 48
3.11 START/STOP LEVELS ....................................................................................................................... 52
CHAPTER 4. INITIAL START-UP .................................................................................................. 53
4.1 INITIAL START-UP REQUIREMENTS ................................................................................................. 53
4.2 TOOLS AND INSTRUMENTATION FOR COMBUSTION CALIBRATION .......................................... 53
4.2.1 Required Tools & Instrumentation ................................................................................................................. 53
4.2.2 Installing Gas Supply Manometer ................................................................................................................... 54
4.2.3 Accessing the Analyzer Probe Port ................................................................................................................. 55
4.3 NATURAL GAS COMBUSTION CALIBRATION .................................................................................. 56
4.4 PROPANE COMBUSTION CALIBRATION .......................................................................................... 60
4.5 DUAL-FUEL SWITCHOVER INSTRUCTIONS .................................................................................... 63
4.5.1 Switchover from NATURAL GAS to PROPANE ................................................................................................. 63
4.5.2 Switchover from PROPANE to NATURAL GAS ................................................................................................. 64
4.6 REASSEMBLY ...................................................................................................................................... 65
4.7 OVER-TEMPERATURE LIMIT SWITCHES ......................................................................................... 65
4.7.1 Digital Alarm Switch Checks and Adjustments ............................................................................................... 66
CHAPTER 5. MODE OF OPERATION ........................................................................................... 69
5.1 INTRODUCTION ................................................................................................................................... 69
5.2 INDOOR/OUTDOOR RESET MODE ................................................................................................... 69
5.2.1 Reset Ratio ...................................................................................................................................................... 69
5.2.2 Building Reference Temperature .................................................................................................................... 69
5.2.3 Outdoor Air Temperature Sensor Installation ................................................................................................ 69
5.2.4 Indoor/Outdoor Startup ................................................................................................................................. 69
5.3 CONSTANT SETPOINT MODE ........................................................................................................... 70
5.3.1 Setting the Setpoint ........................................................................................................................................ 70
5.4 REMOTE SETPOINT MODES ............................................................................................................. 71
5.4.1 Remote Setpoint Field Wiring ......................................................................................................................... 71
5.4.2 Remote Setpoint Startup ................................................................................................................................ 72
5.5 DIRECT DRIVE MODES....................................................................................................................... 72
5.5.1 Direct Drive Field Wiring ................................................................................................................................. 73
5.5.2 Direct Drive Startup ........................................................................................................................................ 73
5.6 AERCO CONTROL SYSTEM (ACS) .................................................................................................... 73
5.6.1 ACS External Field Wiring................................................................................................................................ 73
5.6.2 ACS Setup and Startup .................................................................................................................................... 74
5.7 COMBINATION CONTROL SYSTEM (CCS) ....................................................................................... 74
5.7.1 Combination Control System Field Wiring ...................................................................................................... 75
5.7.2 Combination Control System Setup and Startup ............................................................................................ 75
CHAPTER 6. SAFETY DEVICE TESTING ..................................................................................... 77
6.1 TESTING OF SAFETY DEVICES ......................................................................................................... 77
6.2 LOW GAS PRESSURE FAULT TEST .................................................................................................. 78
6.3 HIGH GAS PRESSURE TEST ............................................................................................................. 79
6.4 LOW WATER LEVEL FAULT TEST ..................................................................................................... 80
6.5 WATER TEMPERATURE FAULT TEST .............................................................................................. 81
6.6 INTERLOCK TESTS ............................................................................................................................. 82
6.6.1 Remote Interlock Test..................................................................................................................................... 82
Installation, Operation & Maintenance Manual (IOMM)
Page 4 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 5
Benchmark 1500DF - 2000DF Boilers
6.6.2 Delayed Interlock Test .................................................................................................................................... 83
6.7 FLAME FAULT TESTS ......................................................................................................................... 83
6.8 AIR FLOW FAULT TESTS .................................................................................................................... 85
6.8.1 Blower Proof Switch Test ................................................................................................................................ 85
6.8.2 Blocked Inlet Switch Test ................................................................................................................................ 85
6.9 SSOV PROOF OF CLOSURE SWITCH ............................................................................................... 87
6.10 PURGE SWITCH OPEN DURING PURGE ........................................................................................ 88
6.11 IGNITION SWITCH OPEN DURING IGNITION ................................................................................. 89
6.12 SAFETY PRESSURE RELIEF VALVE TEST ..................................................................................... 90
CHAPTER 7. MAINTENANCE ......................................................................................................... 91
7.1 MAINTENANCE SCHEDULE ............................................................................................................... 91
7.2 IGNITER-INJECTOR ............................................................................................................................ 92
7.3 FLAME DETECTOR ............................................................................................................................. 94
7.4 O2 SENSOR 95
7.5 SAFETY DEVICE TESTING ................................................................................................................. 95
7.6 BURNER ASSEMBLY INSPECTION ................................................................................................... 96
7.7 CONDENSATE DRAIN TRAP ............................................................................................................ 100
7.8 AIR FILTER CLEANING & REPLACEMENT ...................................................................................... 101
7.9 SHUTTING THE BOILER DOWN FOR AN EXTENDED PERIOD OF TIME ..................................... 102
7.10 PLACING THE BOILER BACK IN SERVICE AFTER A PROLONGED SHUTDOWN ..................... 102
CHAPTER 8. TROUBLESHOOTING GUIDE ............................................................................. 103
8.1 INTRODUCTION ................................................................................................................................. 103
8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES .................................................. 115
CHAPTER 9. RS-232 COMMUNICATION................................................................................. 117
9.1 INTRODUCTION ................................................................................................................................. 117
9.1.1 Acquiring the PuTTY Application .................................................................................................................. 117
9.1.2 Running a Command on a Remote Machine Using PuTTY ........................................................................... 118
9.2 RS-232 COMMUNICATION SETUP ................................................................................................... 119
9.3 MENU PROCESSING UTILIZING RS-232 COMMUNICATION ........................................................ 119
9.4 DATA LOGGING ................................................................................................................................. 120
9.4.1 Fault Log ....................................................................................................................................................... 121
9.4.2 Operation Time Log ...................................................................................................................................... 121
9.4.3 Sensor Log ..................................................................................................................................................... 122
CHAPTER 10. BOILER SEQUENCING TECHNOLOGY ............................................................. 123
10.1 INTRODUCTION ............................................................................................................................... 123
10.2 AERCO BST QUICK START CHART ............................................................................................... 124
10.3 BST IMPLEMENTATION INSTRUCTION ........................................................................................ 125
10.3.1 Option 1 - Constant Setpoint with DIRECT Wired Header Sensor .............................................................. 125
10.3.2 Option 2 - Constant Setpoint with MODBUS Wired Header Sensor ........................................................... 126
10.3.3 Option 3 - Outdoor Reset with DIRECT WIRED Header Sensor AND DIRECT WIRED Outdoor Sensor ....... 127
10.3.4 Option 4 - Outdoor Reset with MODBUS Header Sensor AND MODBUS Outdoor Sensor ........................ 129
10.3.5 Option 5 - Remote Setpoint with DIRECT WIRED Header Sensor AND 4-20ma Setpoint Drive ................. 131
10.3.6 Option 6 - Remote Setpoint with DIRECT WIRED Header Sensor AND MODBUS Setpoint Drive ............... 132
10.3.7 Option 7 - Remote Setpoint with MODBUS Header Sensor AND 4-20ma Setpoint Drive .......................... 133
10.3.8 Option 8 - Remote Setpoint with MODBUS Header Sensor AND MODBUS Setpoint Drive ....................... 135
APPENDIX A: BOILER MENU ITEM DESCRIPTIONS ............................................................. 137
APPENDIX B: STARTUP, STATUS & DISPLAY MESSAGES .................................................. 145
APPENDIX C: SENSOR RESISTANCE/VOLTAGE CHART ...................................................... 149
APPENDIX D: BOILER DEFAULT SETTINGS ............................................................................ 151
Installation, Operation & Maintenance Manual (IOMM)
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 5 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 6
Benchmark 1500DF - 2000DF Boilers
APPENDIX E: RECOMMENDED PERIODIC TESTING ............................................................ 153
APPENDIX F: INDOOR/OUTDOOR RESET RATIO CHARTS ............................................... 155
APPENDIX G: DIMENSIONAL AND CLEARANCE DRAWINGS ............................................. 159
APPENDIX H: PART DRAWINGS ................................................................................................. 163
APPENDIX I: WIRING DIAGRAMS ............................................................................................. 175
APPENDIX J: PIPING DRAWINGS .............................................................................................. 183
APPENDIX K: C-MORE CONTROL PANEL VIEWS ................................................................... 189
APPENDIX L: RECOMMENDED SPARES ................................................................................... 191
Installation, Operation & Maintenance Manual (IOMM)
(This Page Is Intentionally Blank)
Page 6 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 7
Benchmark 1500DF - 2000DF Boilers
Minimum
Maximum
Minimum
Maximum
FORWARD

FOREWORD

The AERCO Benchmark (BMK) 1500 and 2000 MBH boilers are modulating and condensing units. They represent a true industry advance that meets the needs of today's energy and environmental concerns. Designed for application in any closed loop hydronic system, the Benchmark's modulating capability relates energy input directly to fluctuating system loads. The turn down ratios for these boilers is 20:1. These BMK models provide extremely high efficiency operation and are ideally suited for modern low temperature, as well as, conventional heating systems.
The Benchmark Model BMK 1500 and BMK 2000 boilers operate within the following input and output ranges:
Benchmark Model
BMK 1500 75,000 1,500,000 64,500 1,395,000
Input Range (BTU/hr.) Output Range (BTU/hr.)
BMK 2000 100,000 2,000,000 86,000 1,860,000
The output of the boiler is a function of the unit’s firing rate (valve position) and return water temperature.
When installed and operated in accordance with this Instruction Manual, these boilers comply with the NOx emission standards outlined in:
South Coast Air Quality Management District (SCAQMD), Rule 1146.2
Whether used in singular or modular arrangements, the BMK 1500 and BMK 2000 offer the maximum venting flexibility with minimum installation space requirements. These boilers are Category II, III and IV, positive pressure appliances. Single and/or multiple breeched units are capable of operation in the following vent configurations:
Conventional, Vertical Conventional, Sidewall Conventional, Direct Vent, Vertical Sealed, Direct Vent, Horizontal
These boilers are capable of being vented utilizing Polypropylene and AL29-4C vent systems.
The Benchmark's advanced electronics are available in several selectable modes of operation offering the most efficient operating methods and energy management system integration.
IMPORTANT
Unless otherwise specified, all descriptions and procedures provided in this Installation, Operation & Maintenance Manual apply to the Benchmark series of boiler.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 7 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 8
Benchmark 1500DF - 2000DF Boilers
ASME
American Society of Mechanical Engineers
(see below)
COMM (Comm)
Communication
Double Block and Bleed. Used to define boiler gas trains Energy Management System; often used interchangeably with
FORWARD
Phrases, Abbreviations and Acronyms
Phrase, Abbreviation or
Acronym
Meaning
A (Amp) Ampere
ACS AERCO Control System
ADDR Address
AGND Analog Ground
ALRM Alarm
AUX Auxiliary
BAS
Building Automation System, often used interchangeably with EMS
Symbol rate, or simply the number of distinct symbol changes
Baud Rate
(signaling events) transmitted per second. It is not equal to bits per second, unless each symbol is 1 bit long.
BMK Benchmark series boilers
BMS or BMS II AERCO Boiler Management Systems
BST AERCO on-board Boiler Management Technology
BLDG (Bldg) Building
BTU
British Thermal Unit. A unit of energy approximately equal to the heat required to raise 1 pound of water 1° F.
CCP Combustion Control Panel
C-More Controller (or Control Box)
A control system developed by AERCO and currently used in all Benchmark, Innovation and KC1000 Series product lines.
CO Carbon Monoxide
Cal. Calibration
CNTL Control
DBB
containing 2 Safety Shutoff Valves (SSOVs) and a solenoid operated vent valve. Also known as IRI gas trains(see below)
DIP Dual In-Line Package
EMS
BAS
FM Factory Mutual. Used to define boiler gas trains.
GND Ground
HDR Header
HX Heat Exchanger
Hz Hertz (Cycles Per Second)
I.D. Inside Diameter
IGN Ignition
Page 8 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 9
Benchmark 1500DF - 2000DF Boilers
Phrase, Abbreviation or
Acronym
FORWARD
Phrases, Abbreviations and Acronyms – Continued
Meaning
IGST Board Ignition/Stepper Board contained in C-More Control Box
INTLK (INTL’K) Interlock
I/O Input/Output
I/O Box
IP Internet Protocol
IRI
ISO Isolated
LED Light Emitting Diode
LN Low NOx
MA (mA) Milliampere (0.001 Amp), one thousandth of an amp
MAX (Max) Maximum
MIN (Min) Minimum
Modbus®
NC (N.C.) Normally Closed
NO (N.O.) Normally Open
NOx Nitrogen Oxide
NPT National Pipe Thread
O2 Oxygen
O.D. Outside Diameter
PMC Board
PPM Parts Per Million
PTP Point-to-Point (usually over RS-232 networks)
PWM Pulse Width Modulation
REF (Ref) Reference
RES. Resistive
RS-232 (or EIA-232)
RS-422 (or EIA-422)
RS-485 (or EIA-485)
RTN (Rtn) Return
SETPT (Setpt) Setpoint Temperature
SHLD (Shld) Shield
Input/Output (I/O) Box currently used on Benchmark, Innovation and KC1000 Series products
Industrial Risk Insurers. A now discontinued code used to define gas trains containing two SSOVs and a solenoid operated vent valve.
A serial, half-duplex data transmission protocol developed by AEG Modicon
A Primary Micro-Controller (PMC) board is contained in the C-More Control Box used on all Benchmark units.
A standard for serial, full-duplex (FDX) transmission of data based on the RS-232 Standard
A standard for serial, full-duplex (FDX) transmission of data based on the RS-422 Standard
A standard for serial, half-duplex (HDX) transmission of data based on the RS-485 Standard
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 9 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 10
Benchmark 1500DF - 2000DF Boilers
Phrase, Abbreviation or
Acronym
TEMP (Temp)
Temperature
order to prevent reflections that may cause invalid data in the VDC
Volts, Direct Current
W.C.
Water Column (W.C.)
FORWARD
Phrases, Abbreviations and Acronyms – Continued
Meaning
SSOV Safety Shut Off Valve
A resistor placed at each end of a daisy-chain or multi-drop network in
Terminating Resistor
communication
uA Microamp (0.000001 amp), one millionth of an amp
VAC Volts, Alternating Current
VFD Vacuum Fluorescent Display, or Variable Frequency Drive
W Watt
Page 10 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 11
Benchmark 1500DF - 2000DF Boilers
WARNING
WARNING
WARNING
WARNING
CHAPTER 1 – SAFETY PRECAUTIONS

CHAPTER 1. S AF ET Y PRECAUTIONS

1.1 WARNINGS & CAUTIONS

Installers and operating personnel MUST, at all times, observe all safety regulations. The following warnings and cautions are general and must be given the same attention as specific precautions included in these instructions. In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54) for gas-fired boilers and ANSI/NFPASB for LP gas-fired boilers. Where applicable, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CSA B149.1, and applicable Provincial regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
See pages 13 and 14 for important information regarding installation of units within the Commonwealth of Massachusetts.
IMPORTANT
This Instruction Manual is an integral part of the product and must be maintained in legible condition. It must be given to the user by the installer and kept in a safe place for future reference.
DO NOT USE MATCHES, CANDLES, FLAMES, OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS.
FLUIDS UNDER PRESSURE MAY CAUSE INJURY TO PERSONNEL OR DAMAGE TO EQUIPMENT WHEN RELEASED. BE SURE TO SHUT OFF ALL INCOMING AND OUTGOING WATER SHUTOFF VALVES. CAREFULLY DECREASE ALL TRAPPED PRESSURES TO ZERO BEFORE PERFORMING MAINTENANCE.
BEFORE ATTEMPTING TO PERFORM ANY MAINTENANCE ON THE UNIT, SHUT OFF ALL GAS AND ELECTRICAL INPUTS TO THE UNIT.
THE EXHAUST VENT PIPE OF THE UNIT OPERATES UNDER A POSITIVE PRESSURE AND THEREFORE MUST BE COMPLETELY SEALED TO PREVENT LEAKAGE OF COMBUSTION PRODUCTS INTO LIVING SPACES.
WARNING
ELECTRICAL VOLTAGES UP TO 480 VAC MAY BE USED IN THIS EQUIPMENT. THEREFORE THE COVER ON THE UNIT’S POWER BOX (LOCATED BEHIND THE FRONT PANEL DOOR) MUST BE INSTALLED AT ALL TIMES, EXCEPT DURING MAINTENANCE AND SERVICING.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 11 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 12
Benchmark 1500DF - 2000DF Boilers
WARNING
CAUTION
CAUTION
CHAPTER 1 – SAFETY PRECAUTIONS
A THREE-POLE SWITCH MUST BE INSTALLED ON THE ELECTRICAL SUPPLY LINE OF THE UNIT. THE SWITCH MUST BE INSTALLED IN AN EASILY ACCESSIBLE POSITION TO QUICKLY AND SAFELY DISCONNECT ELECTRICAL SERVICE. DO NOT AFFIX SWITCH TO UNIT SHEET METAL ENCLOSURES.
Many soaps used for gas pipe leak testing are corrosive to metals. The piping must be rinsed thoroughly with clean water after leak checks have been completed.
DO NOT use this boiler if any part has been under water. Call a qualified service technician to inspect and replace any part that has been under water.

1.2 EMERGENCY SHUTDOWN

If overheating occurs or the gas supply fails to shut off, close the manual gas shutoff valve (Figure 1-1) located external to the unit.
NOTE
The Installer must identify and indicate the location of the emergency shutdown manual gas valve to operating personnel.
MANUAL GAS SHUT-OFF VALVE
VALVE OPEN VALVE CLOSED
Figure 1-1: Manual Gas Shutoff Valve

1.3 PROLONGED SHUTDOWN

After prolonged shutdown, it is recommended that the startup procedures in Chapter 4 and the safety device test procedures in Chapter 6 of this manual be performed, to verify all system-
Page 12 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 13
Benchmark 1500DF - 2000DF Boilers
CHAPTER 1 – SAFETY PRECAUTIONS
operating parameters. If there is an emergency, turn off the electrical power supply to the AERCO boiler and close the manual gas valve located upstream the unit. The installer must identify the emergency shut-off device.
IMPORTANT – FOR MASSACHUSETTS INSTALLATIONS
Boiler Installations within the Commonwealth of Massachusetts must conform to the following requirements:
Boiler must be installed by a plumber or a gas fitter who is licensed within the Commonwealth of Massachusetts.
Prior to unit operation, the complete gas train and all connections must be leak tested using a non-corrosive soap.
The vent termination must be located a minimum of 4 feet above grade level. If side-wall venting is used, the installation must conform to the
following requirements extracted from 248 CMR 5.08 (2):
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide det ector as required in accordance with the above provisions shall comply with NFPA 720 and be
ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIO NS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 13 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 14
Benchmark 1500DF - 2000DF Boilers
CHAPTER 1 – SAFETY PRECAUTIONS
fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
____________________________________________________________________________
[End of Extracted Information From 248 CMR 5.08 (2)]
Page 14 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 15
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION

CHAPTER 2. INSTALLATION

2.1 INTRODUCTION

This Chapter provides the descriptions and procedures necessary to unpack, inspect and install the AERCO Benchmark Boiler Model BMK 1500 and BMK 2000.

2.2 RECEIVING THE UNIT

Each Benchmark Boiler System is shipped as a single crated unit. The shipping weight for these BMK models is approximately 1800 pounds. The unit must be moved with the proper rigging equipment for safety and to avoid equipment damage. The unit should be completely inspected for evidence of shipping damage and shipment completeness at the time of receipt from the carrier and before the bill of lading is signed.
NOTE
AERCO is not responsible for lost or damaged freight. Each unit has a Tip-N-Tell indicator on the outside of the crate. This indicates if the unit has been turned on its side during shipment. If the Tip-N-Tell indicator is tripped, do not sign for the shipment. Note the information on the carrier’s paperwork and request a freight claim and inspection by a claims adjuster before proceeding. Any other visual damage to the packaging materials should also be made clear to the delivering carrier.

2.3 UNPACKING

Carefully unpack the unit taking care not to damage the unit enclosure when cutting away packaging materials
After unpacking, a close inspection of the unit should be made to ensure that there is no evidence of damage not indicated by the Tip-N-Tell indicator. The freight carrier should be notified immediately if any damage is detected.
The following accessories come standard with each unit and are either packed separately within the unit’s shipping container or are factory installed on the unit:
Pressure/Temperature Gauge
ASME Pressure Relief Valve
Condensate Drain Trap (part no. 24060)
2” Gas Supply Shutoff Valve
When optional accessories are ordered, they may be packed within the unit’s shipping container, factory installed on the unit, or packed and shipped in a separate container. Any standard or optional accessories shipped loose should be identified and stored in a safe place until ready for installation or use.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 15 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 16
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION

2.4 SITE PREPARATION

Ensure that the site selected for installation of the Benchmark 1500/2000 Boiler includes:
Access to AC Input Power at 120 VAC, Single-Phase, 60 Hz @ 20 Amps
Access to Natural Gas line at a minimum pressure of 8 inches W.C. at gas flow for
1,500,000 BTU/hr energy input for the BMK 1500 OR 2,000,000 BTU/hr energy input for the BMK 2000.

2.4.1 Installation Clearances

The Benchmark Model 1500 and 2000 are packaged in an enclosure having identical exterior dimensions. The unit must be installed with the prescribed clearances for service as shown in Figure 2-1a. The minimum clearance dimensions, required by AERCO, are listed below. However, if Local Building Codes require additional clearances, these codes shall supersede AERCO’s requirements. Minimum acceptable clearances required are as follows:
Sides: 24 inches
Front : 24 inches
Rear: 24 inches
Top: 18 inches
All gas piping, water piping and electrical conduit or cable must be arranged so that they do not interfere with the removal of any panels, or inhibit service or maintenance of the unit.
NOTE
Ensure that condensate
assembly is not
located over the
housekeeping
pad.
Figure 2-1a: Benchmark Boiler Model 1500/2000 Clearances
Page 16 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 17
Benchmark 1500DF - 2000DF Boilers
CAUTION
WARNING
CHAPTER 2 – INSTALLATION
WARNING
KEEP THE UNIT AREA CLEAR AND FREE FROM ALL COMBUSTIBLE MATERIALS AND FLAMMABLE VAPORS OR LIQUIDS
.
While packaged in the shipping container, the unit must be moved by pallet jack or forklift from the FRONT ONLY.
FOR MASSACHUSSETTS ONLY:
For Massachusetts installations, the unit must be installed by a plumber or gas-fitter licensed within the Commonwealth of Massachusetts. In addition, the installation must comply with all requirements specified in Chapter 1 (Safety Precautions), pages 11 and 12.

2.4.2 Setting the Unit

The unit must be installed on a 4 to 8 inch thick concrete housekeeping pad to ensure proper condensate drainage. If anchoring the unit, refer to Figure 2-1b for anchor locations.
A total of 3 lifting lugs are provided at the top of the primary heat exchanger as shown in Figure 2-2. Remove the front top panel from the unit to provide access to the lifting tabs.
Remove the four (4) lag screws securing the unit to the shipping skid. Lift the unit off the shipping skid and position it on the 4 to 6 inch concrete housekeeping pad (required) in the desired location.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 17 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Figure 2-1b: Benchmark 1500/2000 Anchor Bolt Locations
WHEN LIFTING OR MOVING THE BOILER, DO NOT ATTEMPT
TO MANIPULATE THE BOILER USING THE GAS TRAIN OR BLOWER.
Page 18
Benchmark 1500DF - 2000DF Boilers
GAS INLET
INLET
CHAPTER 2 – INSTALLATION
LIFTING LUGS
(3 POSITIONS)
1” PROPANE
2” NATURAL
Figure 2-2: Boiler Lifting Provisions
In multiple unit installations, it is important to plan the position of each unit in advance. Sufficient space for piping connections and future service/maintenance requirements must also be taken
into consideration. All piping must include ample provisions for expansion.
If installing a Combination Control Panel (CCP) system, it is important to identify the Combination Mode Boilers in advance and place them in the proper physical location. Refer to Chapter 5 for information on Combination Mode Boilers.
Page 18 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 19
Benchmark 1500DF - 2000DF Boilers
2” NATURAL GAS INLET
BOILER HOT
EXHAUST
MANIFOLD
CONDENSATE
DRAIN PORT
CHAPTER 2 – INSTALLATION

2.5 SUPPLY AND RETURN PIPING

The Benchmark Boiler utilizes 4” 150# flanges for the water system supply and return piping connections. The physical location of the supply and return piping connections are on the rear of the unit as shown in Figure 2-3.
1” PROPANE INLET
WATER OUTLET
(SUPPLY)
AIR INLET
PRIMARY
WATER INLET
(RETURN)
DRAIN VALVE
Figure 2-3: Supply and Return Locations

2.6 PRESSURE RELIEF VALVE INSTALLATION

An ASME rated Pressure Relief Valve is supplied with each Benchmark Boiler. The pressure rating for the relief valve must be specified on the sales order. Available pressure ratings range from 30 psi to 160 psi. The relief valve is installed on the hot water outlet of the boiler as shown in Figure 2-4. A suitable pipe joint compound should be used on the threaded connections. Any excess should be wiped off to avoid getting any joint compound into the valve body. The relief valve must be piped to within 12 inches of the floor to prevent injury in the event of a discharge.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 19 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 20
Benchmark 1500DF - 2000DF Boilers
PRIMARY WATER INLET
1/4” ANALYZER
NPT PORT
EXHAST
MANIFOLD
CHAPTER 2 – INSTALLATION
are allowed in the discharge line. In multiple unit installations the discharge lines must not be manifolded together. Each must be individually run to a suitable discharge location.
PRESSURE
RELIEF VALVE
4” HOT BOILER
WATER OUTLET
Figure 2-4: P&T Relief Valve Location

2.7 CONDENSATE DRAIN & PIPING

The Benchmark Boiler is designed to condense water vapor from the flue products. Therefore, the installation must have provisions for suitable condensate drainage or collection.
The condensate drain port located on the exhaust manifold (Figure 2-5) must be connected to the condensate trap (P/N 24060) which is packed separately within the unit’s shipping container. The condensate trap inlet features two integral O-rings and a thumbscrew to allow direct connection of the drain port into the trap inlet. See the Condensate trap Installation instructions and Figure 2-6 on the next page.
AIR INLET
DRAIN VALVE
CONDENSATE DRAIN PORT
Figure 2-5: Condensate Drain Connection Location
A sample condensate trap installation is shown in Figure 2-6. The following general guidelines must be observed to ensure proper condensate drainage:
The condensate trap inlet (Figure 2-6) must be level the exhaust manifold drain port.
The base of the condensate trap must be supported to ensure that it is level (horizontal).
The trap must be removable for routine maintenance.
Page 20 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 21
Benchmark 1500DF - 2000DF Boilers
CAUTION
COMBUTION
PROBE PORT
EXHAUST
MANIFOLD
3/4” NPT
NIPPLES
HOSE CLAMP
TRAP INLET
TOP
(4 ea.)
1” DIAM. HOSE
NOTE
ASSEMBLY.
4” MINIMUM
(8” MAXIMUM)
4”
CHAPTER 2 – INSTALLATION
While observing the above guidelines, install the condensate trap as follows:
Condensate Trap Installat ion
1. Connect the condensate trap inlet to the exhaust manifold drain connection by inserting the drain port directly into the trap adaptor inlet, and then tightening the inlet thumbscrew, as shown in Figure 2-6. The inlet features two integral O-rings to prevent leakage.
2. At the condensate trap outlet, install a 3/4” NPT nipple.
3. Connect a length of 1” diameter polypropylene hose to the trap outlet and secure with a hose clamp.
4. Route the hose on the trap outlet to a nearby floor drain.
If a floor drain is not available, a condensate pump can be used to remove the condensate to
drain. The maximum condensate flow rate is 30 GPH. The condensate drain trap, associated
fittings and drain line must be removable for routine maintenance.
Use PVC, stainless steel, aluminum or polypropylene for condensate drain piping (Figure 2-6). DO NOT use carbon or copper components.
ANALYZER
HOUSKEEPING
PAD MUST NOT
EXTEND
UNDER THE
CONDENSATE
EXHAUST
MANIFOLD
DRAIN PORT
INTEGRAL ADAPTOR AND THUMBSCREW
COVER THUMB
SREWS
CONDENSATE
TRAP (P/N 24060)
T O FLOOR DRAIN
Figure 2-6: Sample Condensate Trap Installation (Right Side View)
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 21 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 22
Benchmark 1500DF - 2000DF Boilers
CAUTION
CHAPTER 2 – INSTALLATION

2.8 GAS SUPPLY PIPING

The AERCO Benchmark Gas Components and Supply Design Guide, GF-2030 must be consulted prior to designing or installing any gas supply piping.
WARNING
NEVER USE MATCHES, CANDLES, FLAMES OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS
.
Many of the soaps used for gas pipe leak testing are corrosive to metals. Therefore, piping must be rinsed thoroughly with clean
water after leak checks have been completed.
NOTE
All gas piping must be arranged so that it does not interfere with removal of any covers, inhibit service/maintenance, or restrict access between the unit and walls, or another unit.
Benchmark 1500 and 2000 units contain a 2 inch NATURAL GAS inlet connection, and a 1 inch PROPANE gas connection on the top of the unit, as shown in Figures 2-2 and 2-3.
Prior to installation, all pipes should be de-burred and internally cleared of any scale, metal chips or other foreign particles. Do Not install any flexible connectors or unapproved gas fittings. Piping must be supported from the floor, ceiling or walls only and must not be supported by the unit.
A suitable piping compound, approved for use with natural gas, should be used. Any excess must be wiped off to prevent clogging of components.
To avoid unit damage when pressure testing gas piping, the unit must be isolated from the gas supply piping. At no time should the gas pressure applied to the unit exceed 14” W.C. A thorough leak test of all external piping must be performed using a soap and water solution or suitable equivalent. The gas piping used must meet all applicable codes.

2.8.1 Gas Supply Specifications

The gas supply input specifications to the unit for Natural Gas and Propane gas are as follows:
The maximum static pressure to the unit must not exceed 14” W.C.
The gas supply pressure to the unit must be of sufficient capacity to provide 2000 cfh while
maintaining the gas pressure at 6 inches W.C. for FM gas trains operating at maximum capacity.

2.8.2 Manual Gas Shutoff Valve

A manual shut-off valve must be installed in the gas supply line upstream of the boiler as shown in Figure 2-7. Maximum allowable gas pressure to the boiler is 14” W.C.
Page 22 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 23
Benchmark 1500DF - 2000DF Boilers
NATURAL GAS PRESSURE REGULATOR
NATURAL
SUPPLY
PROPANE
SUPPLY
PROPANE GAS
CHAPTER 2 – INSTALLATION

2.8.3 External Gas Supply Regulator

An external gas pressure regulator is required on the gas inlet piping under most conditions (see sections 2.8.3.1 and 2.8.3.2, below). Regulators must conform to the following specifications:
NATURAL GAS: The external natural gas regulator must be capable of regulating
100,000 – 2,120,000 BTU/HR of natural gas while maintaining a gas pressure of 8.0” W.C. minimum to the unit.
PROPANE GAS: The external propane gas regulator must be capable of regulating
100,000 – 2,120,000 BTU/HR of propane gas while maintaining a gas pressure of 4.0” W.C. minimum to the unit
A lock-up style regulator MUST be used when gas supply pressure will exceed 14” W.C.
2.8.3.1
Massachusetts Installations Only
For Massachusetts installations, a mandatory external gas supply regulator must be positioned as shown in Figure 2-7. The gas supply regulator must be properly vented to outdoors. Consult the local gas utility for detailed requirements concerning venting of the supply gas regulator.
2.8.3.2
All Installations (Except Massachusetts)
For multi-unit installations (other than Massachusetts) that EXCEED 7” W.C. gas pressure, a separate external gas supply regulator, as shown in Figure 2-7, is highly recommended. No regulator is required for gas pressures below 7” W.C. of pressure. Consult the local gas utility for detailed requirements concerning venting of the supply gas regulator.
NATURAL GAS MANUAL SHUT-OFF VALVE
GAS
NATURAL GAS INLET
PROPANE
MANUAL SHUT-
OFF VALVE
PRESSURE
REGULATOR
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 23 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Figure 2-7: Manual Gas Shut-Off Valve Location
Page 24
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
NOTE
It is the responsibility of the customer to source and purchase the appropriate gas regulator as described above. However, AERCO offers for sale an appropriate regulator, which may be ordered at the time of unit purchase or separately. Contact AERCO for more information.

2.9 AC ELECTRICAL POWER WIRING

The AERCO Benchmark Electrical Power Wiring Guide, GF-2060, must be consulted prior to connecting any AC power wiring to the unit. External AC power connections are made to the unit inside the Power Box on the front of the unit. Remove the front panel to access the Power Box, which is mounted in the upper right corner of the unit as shown in Figure 2-8. Loosen the two upper screws of the Power Box cover and remove cover to access the internal connections shown in Figure 2-9.
Figure 2-8: Power Box Location with Cover Closed
THE POWER BREAKER SHOWN IN FIGURE 2-9 DOES NOT
REMOVE POWER FROM THE TERMINAL BLOCKS.
WARNING
Page 24 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 25
Benchmark 1500DF - 2000DF Boilers
BREAKER
CHAPTER 2 – INSTALLATION
TRANSFORMER
24V POWER
SUPPLY
12V POWER
SUPPLY
WIRE CONDUITS
POWER
FUSE BLOCKS (2)
TERMINAL BLOCKS
Figure 2-9: Power Box Internal Components
With the exception of the transformer shown in Figure 2-9, all of the components in the Power Box are mounted on a DIN rail.
NOTE
All electrical conduit and hardware must be installed so that it does not interfere with the removal of any unit covers, inhibit service/maintenance, or prevent access between the unit and walls or another unit.

2.9.1 Electrical Power Requirements

The Benchmark 1500 and Benchmark 2000 models are available in one voltage configuration:
120 VAC, Single-Phase, 60 Hz @ 20 Amps
The Power Box contains terminal blocks as shown in Figure 2-9. In addition, a label showing the required AC power connections is provided on the front cover of the Power Box as shown in Figure 2-10.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 25 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 26
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
Figure 2-10: Power Box Cover Labels – 120VAC
Each unit must be connected to a dedicated electrical circuit. NO OTHER DEVICES SHOULD BE ON THE SAME ELECTRICAL CIRCUIT AS THE BOILER.
A three-pole switch must be installed on the electrical supply line in an easily accessible location to quickly and safely disconnect electrical service. DO NOT attach the switch to sheet metal enclosures of the unit.
After placing the unit in service, the ignition safety shutoff device must be tested. If an external electrical power source is used, the installed boiler must be electrically bonded to ground in accordance with the requirements of the authority having jurisdiction. In the absence of such requirements, the installation shall conform to National Electrical Code (NEC), ANSI/NFPA 70 and/or the Canadian Electrical Code (CEC) Part I, CSA C22.1 Electrical Code.
For electrical power wiring diagrams, see the AERCO Benchmark Electrical Power Guide, (GF-
2060).

2.10 FIELD CONTROL WIRING

Each unit is fully wired from the factory with an internal operating control system. No field control wiring is required for normal operation. However, the C-More Control system used with all Benchmark units does allow for some additional control and monitoring features. Wiring connections for these features are made on the Input/Output (I/O) board located behind the removable front panel assembly of the unit. The I/O board is located in the upper-left portion on the front of the unit as shown in Figure 2-11. The I/O board terminal strip connections are shown in Figure 2-12. All field wiring is installed from the rear of the panel by routing the wires through one of the four bushings provided on the sides of the I/O board.
Refer to the wiring diagram provided below the I/O Box (Figure 2-12) when making all wiring connections.
Page 26 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 27
Benchmark 1500DF - 2000DF Boilers
CAUTION
CHAPTER 2 – INSTALLATION
TERMINAL STRIPS
I/O PCB BOARD
Figure 2-11: Input/Output (I/O) Box Location
NOTE
Use Figure 2-12 to determine the functions of the I/O PCB connections. Do not use the silkscreened labels on the PCB itself, as these may not match the function names.
There is a diagram of the connection functions on the cover of the I/O Box as well.
DO NOT make any connections to the I/O Box terminals labeled “NOT USED”. Attempting to do so may cause equipment damage.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 27 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 28
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
Figure 2-12: I/O Box Terminal Strips

2.10.1 Outdoor Air In (OUT) & Air Sensor Common (COM)

The OUTDOOR AIR IN terminal is used for connecting an outdoor temperature sensor (AERCO P/N GM-123525) as required primarily for the Indoor/Outdoor reset mode of operation. It can also be used with another mode if it is desired to use the outdoor sensor enable/disable feature. This feature allows the boiler to be enabled or disabled based on the outdoor air temperature.
The factory default for the outdoor sensor is DISABLED. To enable the sensor and/or select an enable/disable outdoor temperature, see the Configuration Menu in Chapter 3.
The outdoor sensor may be wired up to 200 feet from the boiler. It is connected to the OUTDOOR AIR IN and AIR SENSOR COMMON terminals of the I/O PCB (Figure 2-12). Wire the sensor using a twisted shielded pair wire from 18 to 22 AWG. There is no polarity to observe when terminating these wires. The shield is to be connected only to the terminals labeled SHIELD in the I/O Box PCB. The sensor end of the shield must be left free and ungrounded.
When mounting the sensor, it must be located on the North side of the building where an average outside air temperature is expected. The sensor must be shielded from direct sunlight as well as impingement by the elements. If a shield is used, it must allow for free air circulation.
Page 28 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 29
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION

2.10.2 COMBUSTION AIR Terminal

The COMBUSTIAN AIR terminal is used to monitor the combustion air temperature sensor. This input is always enabled and is a “to view only” input that can be seen in the operating menu. The sensor is an AERCO BALCO wire sensor P/N 12449. A resistance chart for this sensor is provided in APPENDIX C. This sensor is an active part of the combustion control system and must be operational for accurate air/fuel mixing control.

2.10.3 O2 SENSOR (O2+ & O2-)

The O2 SENSOR (+) and O2 SENSOR (–) terminals are used to connect an integrated oxygen sensor to the I/O Box PCB. The O More Control system after a 60 second warm-up period.

2.10.4 SPAR K SIGNAL (FLW+ & FLW-)

The two SPARK SIGNAL terminals permit an external current sensor to be connected for ignition spark monitoring purposes. If no spark is present during the ignition sequence, the controller will shut down and display a fault message.

2.10.5 Analog In (+ & -)

The two ANALOG IN terminals are used when an external signal is used to change the setpoint (Remote Setpoint Mode) of the boiler.
concentration is displayed in the operating menu of the C-
2
Either a 4 to 20 mA /1 to 5 VDC or a 0 to 20 mA/ 0 to 5 VDC signal may be used to vary the set­point or air/fuel valve position. The factory default setting is for 4 to 20 mA / 1 to 5 VDC, however this may be changed to 0 to 20 mA / 0 to 5 VDC using the Configuration Menu described in Chapter 3.
If voltage rather than current is selected as the drive signal, a DIP switch must be set on the PMC Board located inside the C-More Control Box. Contact the AERCO factory for information on setting DIP switches.
All supplied signals must be floating (ungrounded) signals. Connections between the source and the boiler’s I/O PCB (Figure 2-12) must be made using twisted shielded pair of 18–22 AWG wire such as Belden 9841. Polarity must be maintained and the shield must be connected only at the source end and must be left floating (not connected) at the Boiler’s I/O PCB.
Whether using voltage or current for the drive signal, they are linearly mapped to a 40°F to
240°F setpoint or a 0% to 100% air/fuel valve position. No scaling for these signals is provided

2.10.6 B.M.S. (PWM) In (BMS+ & BMS-)

These terminals are only used to connect to legacy AERCO Boiler Management Systems (BMS), which utilize a 12 millisecond, ON/OFF duty cycle and is Pulse Width Modulated (PWM) to control valve position. A 0% valve position = a 5% ON pulse and a 100% valve position = a 95% ON pulse. Note that these connections cannot be used with the AERCO Control System (ACS).

2.10.7 Shield (SHLD & SHLD)

The SHIELD terminals are used to terminate any shields used on sensor wires connected to the unit. Shields must only be connected to these terminals.

2.10.8 Analog Output (+ & -)

The ANALOG OUT terminals (+ & -) output from 0 to 20 mA and may be used to monitor Setpoint, Outlet Temperature, Valve Position 4-20 mA, Valve Position 0-10v or be set to OFF. Default setting in the C-More controller is Valve Position 0-10v and settings behave as follows:
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 29 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 30
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
When 0-10VDC is selected, the voltage output is used by the controller to modulate the combustion blower via the I/O Box terminals labeled VFD/Blower (Section 2.10.11).
If On Board Boiler Sequencing Technology (BST) is enabled, the Analog Output terminals are used to drive the isolation valve, open and closed.
When the 4-20mA is selected for the Analog Output, the 0-10VDC is disabled at the VFD/Blower terminals, and the selected output is available at the terminals labeled Analog Output +/-.

2.10.9 RS-485 Comm (+, GND, & -)

The RS-485 communication terminals are used when the boiler plant is being controlled by an Energy Management System (EMS) or an AERCO Control System (ACS) using Modbus (RS-
485) communication.

2.10.10 RS-232 Comm (TxD & RxD)

The RS-232 communication terminals permit a laptop computer or other suitable terminal to be connected to the boiler. The RS-232 communication feature permits viewing or changing of Control Panel menu options and also provides access to data logs showing fault and sensor log displays.

2.10.11 VFD/Blower (0-10 & AGND)

These terminals (0-10 & AGND) send an analog signal to control the blower speed. When any of the 4-20mA options is selected for the Analog Outputs (Section 2.10.8), the output from the VFD/Blower terminals is disabled.

2.10.12 Interlocks

The unit offers two interlock circuits for interfacing with Energy Management Systems and auxiliary equipment such as pumps or louvers or other accessories. These interlocks are called the Remote Interlock and Delayed Interlock (REMOTE INTL’K IN and DELAYED INTL’K IN in Figure 2-12). Both interlocks, described below, are factory wired in the closed position (using jumpers).
NOTE
Both the Delayed Interlock and Remote Interlock must be in the closed position for the unit to fire.
2.10.12.1
The remote interlock circuit is provided to remotely start (enable) and stop (disable) the unit if desired. The circuit is 24 VAC and comes factory pre-wired closed (jumped).
2.10.12.2
The Delayed Interlock terminals can be used in one of two ways:
Remote Interlock In (OUT & IN)
Delayed Interlock In (OUT & IN)
In conjunction with the optional external sequencing valve (see section 2.14 and Chapter 10 – BST), a component of AERCO’s on-board Boiler Sequencing Technology (BST) solution. By default a cable of the boiler’s wiring harness is connected to these terminals. If BST is implemented, the other end of that cable is connected to the sequencing valve.
Page 30 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 31
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
If BST is NOT implemented, the second use is typically in conjunction with the
AUXILIARY RELAY CONTACTS described in section 2.10.14. This interlock circuit is located in the purge section of the start string. It can be connected to the proving device (end switch, flow switch etc.) of an auxiliary piece of equipment started by the unit’s auxiliary relay. If the delayed interlock is connected to a proving device that requires time to close (make), a time delay (AUX START ON DLY) that holds the start sequence of the unit long enough for a proving switch to make (close) can be programmed.
To use this option, you must disconnect the harness from the Delayed Interlock terminals and connect the proving device in its place.
Should the proving switch not prove within the programmed time frame, the unit will shut down. The AUX START ON DLY can be programmed from 0 to 120 seconds. This option is located in the Configuration Menu (Chapter 3).

2.10.13 Fault Relay (NC, COM, & NO)

The fault relay is a single pole double throw (SPDT) relay having a normally open and normally closed set of relay contacts that are rated for 5 amps at 120 VAC and 5 amps at 30 VDC. The relay energizes when any fault condition occurs and remains energized until the fault is cleared
and the CLEAR button is depressed. The fault relay connections are shown in Figure 2-12.

2.10.14 Auxiliary Relay Contacts (NC, COM, & NO)

Each unit is equipped with a single pole double throw (SPDT) relay that is energized when there is a demand for heat and de-energized after the demand for heat is satisfied. The relay is provided for the control of auxiliary equipment, such as pumps and louvers, or can be used as a unit status indictor (firing or not firing). Its contacts are rated for 120 VAC @ 5 amps. Refer to Figure 2-12 to locate the AUXILLIARY RELAY terminals for wiring connections.

2.11 FLUE GAS VENT INSTALLATION

AERCO Gas Fired Venting and Combustion Air Guide, GF-2050 must be consulted before any flue or combustion air venting is designed or installed. Suitable, U/L approved, positive pressure, watertight vent materials MUST be used for safety and UL certification. Because the unit is capable of discharging low temperature exhaust gases, the flue must be pitched back towards the unit a minimum of 1/4" per foot to avoid any condensate pooling and to allow for proper drainage.
While there is a positive flue pressure during operation, the combined pressure drop of vent and combustion air systems must not exceed 140 equivalent feet or 0.8” W.C. Fittings as well as pipe lengths must be calculated as part of the equivalent length. For a natural draft installation the draft must not exceed - 0.25” W.C. These factors must be planned into the vent installation. If the maximum allowable equivalent lengths of piping are exceeded, the unit will not operate properly or reliably.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 31 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 32
Benchmark 1500DF - 2000DF Boilers
Selkirk Corporation - Heatfab Division
Watertown Supply M. A. Peacard
www.mapeacard.com
Glover Sheet Meatal, Inc.
www.gloversheetmetal.com
CHAPTER 2 – INSTALLATION
For Massachusetts installations, the following companies provide vent systems which conform to all applicable requirements for installations within the Commonwealth of Massachusetts. Contact information is as follows:
130 Industrial Blvd. Turners Falls, MA 01376 Phone: 1-800-772-0739 www.heat-fab.com
1250 Massachusetts Ave. Boston MA 02125-1689 Phone: (617) 288-0629
33Grove St. Watertown, MA 02472 Phone: (617) 924-2840 http://www.watertownsupply.com/
44 Riverdale Ave. Newton, MA 02485 Phone: (617) 527-8178

2.12 COMBUSTION AIR

The AERCO Benchmark Boiler Venting and Combustion Air Guide, GF-2050 MUST be consulted before any flue or inlet air venting is designed or installed. Air supply is a direct requirement of ANSI 223.1, NFPA-54, CSA B149.1 and local codes. These codes should be consulted before a permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons or other chemicals that can become hazardous when used in gas-fired equipment. Common sources of these compounds are swimming pools, degreasing compounds, plastic processing, and refrigerants. Whenever the environment contains these types of chemicals, combustion air MUST be supplied from a clean area outdoors for the protection and longevity of the equipment and warranty validation.
The more common methods of combustion air supply are outlined in the following sections. For combustion air supply from ducting, consult the AERCO GF-2050, Gas Fired Venting and Combustion Air Guide.

2.12.1 Combustion From Outside the Building

Air supplied from outside the building must be provided through two permanent openings. For each unit these two openings must have a free area of not less than one square inch for each 4000 BTUs input of the equipment or 375 square inches of free area for the BMK 1500 or 500 square inches of free area for the BMK 2000. The free area must take into account restrictions such as louvers and bird screens. For Canada installations, refer to the requirements specified in CSA B149.1-10, sections 8.4.1 and 8.4.3.

2.12.2 Combustion Air from Inside the Building

When combustion air is provided from within the building, it must be supplied through two permanent openings in an interior wall. Each opening must have a free area of not less than one square inch per 1000 BTUH of total input or 3000 square inches of free area. The free area must take into account any restrictions, such as louvers.

2.13 DUCTED COMBUSTION AIR

For ducted combustion air installations, the air ductwork must then be attached directly to the air inlet connection on the sheet metal enclosure.
Page 32 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 33
Benchmark 1500DF - 2000DF Boilers
HOT WATER
SEQUENCING
CHAPTER 2 – INSTALLATION
In a ducted combustion air application, the combustion air ducting pressure losses must be taken into account when calculating the total maximum allowable venting run. See the AERCO Benchmark Venting and Combustion Air Guide, GF-2050. When using the unit in a ducted combustion air configuration, each unit must have a minimum 8 inch diameter connection at the unit.

2.14 SEQUENCING VALVE INSTALLATION

All Benchmark units are shipped with a connection for an optional motorized external sequencing valve (p/n 92084-TAB) included in the shipping container. This valve is an integral component of the AERCO’s on-board Boiler Sequencing Technology (BST) solution. BST allows sites with multiple boilers to have one boiler, acting as a “master” to manage the other boilers at the site in such a way that the efficiency of the entire boiler array is maximized.
The implementation of BST, and the installation and use of this valve is optional. However, the boiler is pre-wired to accept the sequencing valve. Installation consists of installing the sequencing valve in the hot water outlet pipe, and then connecting it into the shell harness, as described below.
1. Install the sequencing valve in the boiler’s hot water outlet pipe.
VALVE
OUTLET
Figure 2-13: Sequencing Valve Installed
2. The boiler’s shell harness has one unused cable. One end of this cable is connected to
the DELAYED INTERLOCK IN terminals in the I/O board (see Figure 2-14) while the other end contains a Molex connector with a jumper wire inserted in it (this jumper wire allows units that do not have a sequencing valve to operate normally). Find the free end of this cable inside the unit’s enclosure.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 33 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 34
Benchmark 1500DF - 2000DF Boilers
CHAPTER 2 – INSTALLATION
Figure 2-14: Sequencing Valve Installed
3. Remove the jumper wire from the Molex connector and then plug it into the sequencing
valve’s connector.
Page 34 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 35
Benchmark 1500DF - 2000DF Boilers
WARNING
CAUTION
CHAPTER 3 – OPERATION

CHAPTER 3. OPERATION

3.1 INTRODUCTION

The information in this Chapter provides a guide to the operation of the Benchmark Boiler using the Control Panel mounted on the front of the unit. It is imperative that the initial startup of this unit be performed by factory trained personnel. Operation prior to initial startup by factory trained personnel may void the equipment warranty. In addition, the following WARNINGS and CAUTIONS must be observed at all times.
WARNING
ELECTRICAL VOLTAGES IN THIS SYSTEM INCLUDE 120 AND 24 VOLTS AC. IT MUST BE SERVICED ONLY BY FACTORY CERTIFIED SERVICE TECHNICIANS.
DO NOT ATTEMPT TO DRY FIRE THE UNIT. STARTING THE UNIT WITHOUT A FULL WATER LEVEL CAN SERIOUSLY DAMAGE THE UNIT AND MAY RESULT IN INJURY TO PERSONNEL OR PROPERTY DAMAGE. THIS SITUATION WILL VOID ANY WARRANTY.
All of the installation procedures in Chapter 2 must be completed before attempting to start the unit.

3.2 CONTROL PANEL DESCRIPTION

All Benchmark boilers utilize the C-More Control Panel shown in Figure 3-1. This panel contains all of the controls, indicators and displays necessary to operate, adjust and troubleshoot the boiler. These operating controls, indicators and displays are listed and described in Table 3-1. Additional information on these items is provided in the individual operating procedures and menu descriptions provided in this Chapter.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 35 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 36
Benchmark 1500DF - 2000DF Boilers
3 1 8
9
10
11 7 6 5 *4
12
2
CHAPTER 3 – OPERATION
Figure 3-1: Control Panel Front View
*NOTE
If there is a requirement to use the RS232 port (Item 4) on the C­More controller front panel, contact AERCO to purchase the RS232 Adaptor Cable (P/N 124675), which is designed for this purpose. This cable features a DB9 connector for connection to older computers with serial ports or can be used with a Serial-to­USB adaptor for use in modern computer USB ports.
Page 36 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 37
Benchmark 1500DF - 2000DF Boilers
CONTROL,
DISPLAY
indicate whether the displayed temperature is in degrees
Vacuum Fluorescent Display (VFD) consists of 2 lines each
BST Messages
permits a Laptop Computer or External Modem to be
8
CLEAR
CHAPTER 3 – OPERATION
Table 3-1: Operating Controls, Indicators and Displays
ITEM
NO.
1
2
3
4
5
6
7
INDICATOR OR
Four Status LEDs indicate the current operating status as follows:
COMM
MANUAL
REMOTE DEMAND
OUTLET TEMPERATURE
Display
VFD Display
RS-232 Port
FAULT Indicator
CLEAR Key
READY Indicator ON/OFF Switch
FUNCTION
LED Status Indicators
Lights when RS-232 communication is occurring
Lights when the valve position (fire rate) is being controlled using the front panel keypad. This mode of operation is for service technician use only.
Lights when the unit is being controlled by an external signal from an Energy Management System
Lights when there is a demand for heat.
3–Digit, 7–Segment LED display continuously displays the outlet
water temperature. The °F or °C LED next to the display lights to Fahrenheit or degrees Celsius. The °F or °C blinks when operating
in the Deadband Mode. On a BST Master, display flashes & shows header temperature.
capable of displaying up to 16 alphanumeric characters. The information displayed includes:
Startup Messages
Fault Messages
Operating Status Messages
Menu Selection
Port connected to the unit’s Control Panel. AERCO offers for purchase the RS232 Adaptor Cable (P/N 124675), which is designed to work with this port. This cable features a DB9 connector for connection to older computers with serial ports or can be used with a Serial-to-USB adaptor for use in modern computer USB ports.
Red FAULT LED indicator lights when a boiler alarm condition
occurs. An alarm message will appear in the VFD.
Turns off the FAULT indicator and clears the alarm message if the
alarm is no longer valid. Lockout type alarms will be latched and cannot be cleared by simply pressing this key. Troubleshooting may be required to clear these types of alarms.
Lights ON/OFF switch is set to ON and all Pre-Purge conditions
have been satisfied.
Enables and disables boiler operation.
Allows operator to test operation of the water level monitor.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 37 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
LOW WATER LEVEL
9
TEST/RESET Switches
Pressing TEST opens the water level probe circuit and simulates a
Low Water Level alarm.
Pressing RESET resets the water level monitor circuit.
Pressing the
key (item 6) resets the display.
Page 38
Benchmark 1500DF - 2000DF Boilers
DISPLAY
2. The Menu categories wrap around in the order
back to the default status display in the
pressing this key will select the displayed menu category.
key was pressed and the menu item is
key will decrement the
Permits a setting to be changed (edited). When the
key is pressed, the displayed menu item will
menu settings in memory. The
mode, the front panel controls are enabled and the
status LED lights. Manual operation is for
status LED will be off and the front panel controls
continuously shows the
CHAPTER 3 – OPERATION
Table 3-1: Operating Controls, Indicators and Displays – Continued
ITEM
NO.
10
CONTROL,
INDICATOR OR
FUNCTION
MENU Keypad
Six (6) keys which provide the following functions for the Control Panel Menus:
Steps through the main menu categories shown in Figure
MENU
3­shown.
Allows you to go back to the previous menu level without changing any information. Continuously pressing this key
BACK
will bring you VFD. Also, this key allows you to go back to the top of a main menu category.
When in one of the main menu categories (Figure 3-2), pressing the ▲ arrow key will select the displayed menu
▲ (UP) Arrow
category. If the CHANGE key was pressed and the menu
item is flashing, pressing the ▲ arrow key will increment the selected setting.
When in one of the main menu categories (Figure 3-2),
▼ (DOWN) Arrow
If the CHANGE
flashing, pressing the ▼ arrow selected setting.
CHANGE
CHANGE
begin to flash. Pressing the ▲ or ▼ arrow key when the item is flashing will increment or decrement the displayed setting.
ENTER
Saves the modified display will stop flashing.
This switch toggles the boiler between the Automatic and
Manual modes of operation. When in the Manual (MAN)
MANUAL
11
AUTO/MAN Switch
service only.
When in the Automatic (AUTO) mode, the MANUAL
disabled.
20 segment red LED bargraph
12
Page 38 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
VALVE POSITION
Bargraph
Air/Fuel Valve position in 5% increments from 0 to 100%
Page 39
Benchmark 1500DF - 2000DF Boilers
CHAPTER 3 – OPERATION

3.3 CONTROL PANEL MENUS

The Control Panel incorporates an extensive menu structure which permits the operator to set up, and configure the unit. The menu structure consists of five major menu categories which are applicable to this manual. These categories are shown in Figure 3-2. Each of the menus shown, contain options which permit operating parameters to be viewed or changed. The menus are protected by a password levels to prevent unauthorized use.
Prior to entering the correct password, the options contained in the Operation, Setup, Configuration and Tuning Menu categories can be viewed. However, with the exception of Internal Setpoint Temperature (Configuration Menu), none of the viewable menu options can be changed.
Once the valid level 1 password (159) is entered, the options listed in the Setup. Configuration and Tuning Menus can be viewed and changed, if desired. The Combustion Cal Menu is protected by the level 2 password (6817) which is used in Chapter 4 to perform combustion calibration prior to service use.

3.3.1 Menu Processing Procedure

Accessing and initiating each menu and option is accomplished using the Menu Keys shown in Figure 3-1. Therefore, it is imperative that you be thoroughly familiar with the following basic steps before attempting to perform specific menu procedures:
Menu Processing Procedure
1. The Control Panel will normally be in the Operating Menu and the VFD will display the current unit status. Pressing the ▲ or ▼ arrow key will display the other available data items in the Operating Menu.
2. Press the MENU key. The display will show the Setup Menu, which is the next menu
category shown in Figure 3-2. This menu contains the Password option which must be entered if other menu options will be changed.
3. Continue pressing the MENU key until the desired menu is displayed.
4. With the desired menu displayed, press the ▲ or ▼ arrow key. The first option in the selected menu will be displayed.
5. Continue to press the ▲ or ▼ arrow key until the desired menu option is displayed. Pressing the ▲ arrow key will display the available menu options in the Top-Down sequence. Pressing the ▼ arrow key will display the options in the Bottom-Up sequence. The menu options will wrap-around after the first or last available option is reached.
6. To change the value or setting of a displayed menu option, press the CHANGE key. The
displayed option will begin to flash. Press the ▲ or ▼ arrow key to scroll through the available menu option choices for the option to be changed. The menu option choices do not wrap around.
7. To select and store a changed menu item, press the ENTER key.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 39 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 40
Benchmark 1500DF - 2000DF Boilers
CHAPTER 3 – OPERATION
* Only if BST is enabled (see Chapter 10)
Figure 3-2: Menu Structure
NOTE
The following sections provide brief descriptions of the options contained in each menu. Refer to Appendix A for detailed descriptions of each menu option. Refer to Appendix B for listings and descriptions of displayed startup, status and error messages.
Page 40 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 41
Benchmark 1500DF - 2000DF Boilers
Available Choices or Limits
Minimum
Maximum
Status Message
Active Setpoint
40°F
240°F
Inlet Temp
40°F
140°F
Air Temp
-70°F
245°F
Outdoor Temp*
-70°F
130°F
Valve Position In
0%
100%
Valve Position Out*
0%
100%
Exhaust Temp
°F
°F
Flame Strength
0%
100%
Oxygen Level
0%
21%
Run Cycles
0
999,999,999
Run Hours
0
999,999,999
Fault Log
0
19
0
CHAPTER 3 – OPERATION

3.4 OPERATING MENU

The Operating Menu displays a number of key operating parameters for the unit as listed in Table 3-2. This menu is “Read-Only” and does not allow personnel to change or adjust any displayed items. Since this menu is “Read-Only”, it can be viewed at any time without entering a password. Pressing the ▲ arrow key to display the menu items in the order listed (Top-Down). Pressing the ▼ arrow key will display the menu items in reverse order (Bottom-Up).
Table 3-2: Operating Menu
Menu Item Display
Default
*NOTE
The Outdoor Temp and Valve Position Out display items shown with an asterisk in Table 3-2 will not be displayed unless the Outdoor Sensor function has been enabled in the Configuration Menu (Table 3-4).

3.5 SETUP MENU

The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is required to change the menu options. To prevent unauthorized use, the password will time-out after 1 hour. Therefore, the correct password must be reentered when required. In addition to permitting password entries, the Setup Menu is also used to enter date and time, units of temperature measurements and entries required for external communication and control of the unit via the RS-232 port. A view-only software version display is also provided to indicate the current Control Box software version.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 41 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 42
Benchmark 1500DF - 2000DF Boilers
Available Choices or Limits
Minimum
Maximum
Passsword
0
9999
0
Language
English
English
Time
12:00 am
11:59 pm
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
Comm Address
0
127
0
Baud Rate
2400, 4800, 9600, 19.2K
9600
Upload Timer
0 0
Unit Alpha
A Z A
Unit Serial #
0000
9999
0000
C-More Year
0
99
11
C-More Serial #
0
9999
0000
C-More Alpha
A Z A
IP Address
Software
Ver 0.00
Ver 9.99
CHAPTER 3 – OPERATION
Table 3-3: Setup Menu
Menu Item Display
Default
Date 01/01/00 12/31/99
Unit Year 0 99 00

3.6 CONFIGURATION MENU

The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt) temperature regardless of whether the valid password has been entered. Setpt is required for operation in the Constant Setpoint mode. The remaining options in this menu require the valid password to be entered, prior to changing existing entries. This menu contains a number of other configuration settings which may or may not be displayed, depending on the current operating mode setting.
NOTE
The Configuration Menu settings shown in Table 3-4 are Factory­Set in accordance with the requirements specified for each individual order. Therefore, under normal operating conditions, no changes will be required.
Page 42 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 43
Benchmark 1500DF - 2000DF Boilers
Available Choices or Limits
Minimum
Maximum
CHAPTER 3 – OPERATION
Table 3-4: Configuration Menu
Menu Item Display
Internal Setpt Lo Temp Limit Hi Temp Limit 130°F
KC Boiler, KC Boiler LN,
BMK Boiler Std, BMK Boiler LN,
BMK Blr Std Dual, BMK Blr LN, KC
Unit Type
Water Heater,
KC Wtr Heater LN,
Innovation WH,
BMK Blr LN Dual
Unit Size (Only the unit sizes
available for the Unit Type will be displayed)
Fuel Type
750 MBH, 800 MBH 1000 MBH,
1500 MBH, 2000 MBH, 2500 MBH, 3000 MBH,
6000 MBH
Natural Gas or Propane Natural Gas
Constant Setpoint,
Remote Setpoint,
Boiler Mode
Direct Drive,
Combination,
Outdoor Reset
Default
BMK Boiler LN
1500 MBH
or
2000 MBH
Constant
Setpoint
Remote Signal (If Mode = Remote Setpoint, Direct Drive or Combination)
Outdoor Sensor
PWM Input (Legacy BMS), Network
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
4 – 20 mA,
1-5V
Enabled or Disabled Disabled
*Bldg Ref Temp (If Mode = Outdoor
40°F 230°F 70°F
Reset)
*Reset Ratio (If Mode = Outdoor
0.1 9.9 1.2
Reset)
*System Start Tmp (If Outdoor Sensor =
30°F 100°F 60°F
Enabled)
Setpt Lo Limit 40°F Setpt Hi Limit 60°F
Setpt Hi Limit
Setpt Lo Limit 210°F 140°F
Temp Hi Limit 40°F 210°F 160°F
*NOTE
The Bldg Ref Temp and Reset Ratio Menu Items are only displayed when the Outdoor Sensor is set to “Enabled”.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 43 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 44
Benchmark 1500DF - 2000DF Boilers
Available Choices or Limits
Minimum
Maximum
Available Choices or Limits
Minimum
Maximum
CAUTION
CHAPTER 3 – OPERATION
Table 3-4: Configuration Menu - Continued
Menu Item Display
Max Valve Position
Pump Delay Timer
Aux Start On Dly
40% 100% 100%
0 min. 30 min. 0 min.
0 sec. 120 sec. 0 sec.
Default
Failsafe Mode Shutdown or Constant Setpt Shutdown
Low Fire Timer 2 sec. 600 sec. 2 sec.
Setpt Limiting Enabled or Disabled Disabled
Setpt Limit Band 0°F 10°F 0
Network Timeout 5 Sec 999 Sec 30 Sec
HI DB Setpt EN 0% 100% 30%
Demand Offsert 0 25 0
Deadband High 0 25 0
Deadband Low 0 25 0
DO NOT CHANGE the Analog Output Menu Item from its Default
setting (Valve Position 0-10V).

3.7 TUNING MENU

The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change these menu entries unless specifically requested to do so by factory-trained personnel.
Table 3-5: Tuning Menu
Menu Item Display
Prop Band
Integral Gain 0.00 2.00 1.6
Derivative Time 0.0 min 2.00 min 0.10 min
Warmup Prop Band 0°F 120°F 95°F
Warmup Int Gain 0 2.00 0.50
Warmup PID timer 0 sec. 240 sec. 20 sec.
Reset Defaults? Yes, No, Are You Sure? No
1°F
120°F 8°F
Default
Page 44 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 45
Benchmark 1500DF - 2000DF Boilers
CHAPTER 3 – OPERATION

3.8 COMBUSTION CAL MENU

The Combustion Cal (Calibration) Menu is protected by the level 2 password (6817) which must be entered to view or change the menu items shown in Table 3-6. These menu items are used to vary the speed of the unit’s blower motor based on air temperature and air density at prescribed Air/Fuel Valve positions (% open). This is accomplished by providing a DC drive voltage to the motor which adjusts the rotational speed of the blower to maximize combustion efficiency and ensure the unit conforms to the Nitrogen Oxide (NOx) and Carbon Monoxide (CO) emissions specified in Chapter 4. The valve positions (%) and default drive voltages are listed in Table 3-6.
Table 3-6: Combustion Cal Menu
Menu Item Display
BMK 1500DF BMK 2000DF
CAL Voltage 16% CAL Voltage 14%
CAL Voltage 30% CAL Voltage 30%
CAL Voltage 45% CAL Voltage 45%
CAL Voltage 60% CAL Voltage 60%
CAL Voltage 80% CAL Voltage 80%
CAL Voltage 100% CAL Voltage 100%
SET Valve Position SET Valve Position
Blower Output Blower Output
Set Stdby Volt Set Stdby Volt
Oxygen Level Oxygen Level

3.9 BST (Boiler Sequencing Technology) Menu

The BST Menu must be Enabled in order to be displayed and accessed. The BST Enable item is located at the end of the Configuration Menu.
The Boiler Sequencing Technology (BST) Menu contains all of the items required to Configure, Operate and Monitor the functionality of the BST System. There are over 50 items in this menu, and selecting any particular item from the list, for inspection or modification, could be time consuming. As a result, the BST Menu has been segmented into FIVE logical groups based on functionality.
The five Item groups are:
1. BST Monitor Items
2. BST SETUP MENU*
3. * OPERATE MENU *
4. *TEMP CTRL MENU*
5. *BST COMM MENU*
These displayed item groups are displayed in UPPER CASE letters, and are bounded by an asterisk * in order to readily identify them within the item list.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 45 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 46
Benchmark 1500DF - 2000DF Boilers
Available Choices or Limits
Minimum
Maximum
Header Temp
Outdoor Temp
Units Available 0 8
Units Present
Units Ignited 0 8
Units firing
1 BST Units 8
0 (see table)
0 (see table)
0
Head Temp Source
Network
FFWD Temp
FFWD Temp
Header Temp Addr
0
255
240
Outdr Tmp Source
Outdoor Temp
Network
Outdoor Temp
Outdoor Tmp Addr
0
255
240
0-20 mA/0-5
Yes
conjunction with this feature.
BST Auto Timer
10 sec
120 sec
30 sec
System
Shutdown
On-Outlet
Temp
1 Blr Threshold
10
35
25
CHAPTER 3 – OPERATION
The Items contained in group 1 (BST Monitor Items) are ALWAYS displayed within the menu, as these items are critical for proper system operation. Therefore, the BST Monitor Items Header itself is NOT displayed.
The Items contained in groups 2-5 are NOT DISPLAYED unless that particular item group has been enabled from the C-More keypad.
Table 3-7: BST Menu
Menu Item Display
BST Mode
BST Setpoint BST Setpt Lo Limit BST Setpt Hi Limit 130°F
Header Temp NA
BST Fire Rate 0 100% Fire rate %
BST Ave Fire Rate 0 100% Avg Fire Rate %
BST Outdoor Temp NA
BST Valve State 0 (CLOSED) 1 (OPEN) 0
1 Comm Errors 8 0 9 0
*BST SETUP MENU*
BST Setpoint Mode Constant Setpoint Remote Setpoint Outdoor Reset Constant Setpt
Off BST Slave BST Master Off
Disabled Enabled Disabled
Default
(°F)
(°F)
Header Temp Point 0 255 14
BST Outdoor Sens Disabled Enabled Disabled
Outdoor Tmp Pnt 0 255 215
BST Remote Signal 4-20 mA/1-5 Vdc;
BST Auto Mstr No
Remote Intlk Use Boiler Shutdown System Shutdown
One Boiler Mode Off
Setpoint Setback Disable Enable Disable
Page 46 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Vdc;
NOTE! A Modbus temperature transmitter must be installed in
Network Network
On-Avg Temp Off
No
Page 47
Benchmark 1500DF - 2000DF Boilers
Available Choices or Limits
Minimum
Maximum
Setback End
12:00am
11:59pm
12.00am
MENU*
BST Max Boilers
1
8
8
BST On Delay
30 sec
300 sec
60 sec
Valve Off Delay
0
15 min
1 min
Lead/Lag Hours
25 hours
225 hours
72 hours
MENU*
BST Temp Hi Limit
40°F
210°F
210°F
BST Setpt Lo Limit
40°F
BST Setpt HI Limit
60°F
BST Intgral Gain
0.00
2.00
0.50
BST Deriv Time
0.00 Min
2.00 Min
0.10 Min
Deadband En Time
0
120 Sec
30 Sec
BST FR Up Rate
1
120
20
System Start Tmp
30°F
120°F
60°F
*BST COMM MENU*
Disabled
Enabled
Disabled
Comm Address
0
127
0
SSD Address 0 250
247
SSD Poll Control
0
1000
0
CHAPTER 3 – OPERATION
Menu Item Display
Setback Setpoint BST Setpt Lo Limit BST Setpt HI Limit 130°F
Setback Start 12:00am 11:59pm 12.00am
Rate Threshold 1°F 30°F 15°F
*BST OPERATE
BST Next On VP 16% 100% 50%
BST On Timeout 15 sec 300 sec 60 Sec
Valve Override Off Closed Open Off
BST Sequencing Run Hours Unit Size Select Lead Run Hours
Select Lead Unit 0 127 0
Select Lag Unit 0 127 0
Disabled Enabled Disabled
Default
*BST TEMP CTRL
BST Setpt HI Limit BST Setpt Lo Limit 220°F 195°F
BST Prop Band 1°F 120°F 100°F
BST Deadband Hi 0 25 1
BST Deadband Lo 0 25 1
BST Bldg Ref Tmp 40°F 230°F 70°F
BST Reset Ratio 0.1 9.9 1.2
BST Min Addr 1 128 1
BST Max Addr 1 128 8
Disabled Enabled Disabled
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 47 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 48
Benchmark 1500DF - 2000DF Boilers
Available Choices or Limits
Minimum
Maximum
BST Upld Timer
0
9999 sec
0
CHAPTER 3 – OPERATION
Menu Item Display
Err Threshold 1 9 5
SSD Temp Format Degrees Points Degrees
Default

3.10 START SEQUENCE

When the Control Box ON/OFF switch is set to the ON position, it checks all pre-purge safety
switches to ensure they are closed. These switches include:
Safety Shut-Off Valve (SSOV) Proof of Closure (POC) switch
Low Water Level switch
High Water Temperature switch
High Gas Pressure switch
Low Gas Pressure switch
Blower Proof switch
Blocked Inlet switch
If all of the above switches are closed, the READY light above the ON/OFF switch will light and
the unit will be in the Standby mode.
When there is a demand for heat, the following events will occur:
NOTE
If any of the Pre-Purge safety device switches are open, the appropriate fault message will be displayed. Also, the appropriate messages will be displayed throughout the start sequence, if the required conditions are not observed.
1. The DEMAND LED status indicator will light.
2. The unit checks to ensure that the Proof of Closure (POC) switches in the downstream
Safety Shut-Off Valve (SSOV) are closed. See Figure 3-3 for SSOV locations.
Page 48 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 49
NATURAL GAS
INLET
TO
VALVE
NATURAL GAS
SWITCH
NATURAL GAS
PROPANE
PROPANE
INLET
NATURAL GAS
AIR/FUEL
MANUAL SHUT-
OFF VALVE
SSOV
SSOV
PROPANE
HIGH GAS PRESSURE
SWITCH
Benchmark 1500DF - 2000DF Boilers
CHAPTER 3 – OPERATION
HIGH GAS PRESSURE SWITCH
LOW GAS PRESSURE
PROPANE
LOW GAS PRESSURE
SWITCH
Figure 3-3:
BMK 1500DF/2000DF:
SSOV Location
3. With all required safety device switches closed, a purge cycle will be initiated and the
following events will occur:
a. The Blower relay energizes and turns on the blower.
b. The Air/Fuel Valve rotates to the full-open purge position and closes purge position
switch. The dial on the Air/Fuel Valve (Figure 3-4) will read 100 to indicate that it is
full-open (100%).
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 49 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 50
Benchmark 1500DF - 2000DF Boilers
STEPPER MOTOR
TO BLOWER
AIR IN
AIR/FUEL VALVE OUTLET TO BLOWER
SWITCH
BLOWER
SWITCH
AIR/FUEL VALVE
TRAIN
CHAPTER 3 – OPERATION
c. The VALVE POSITION bargraph will show 100%.
PURGE
VALVE POSITIO N
DIAL AT 100%
Figure 3-4: Air/Fuel Valve In Purge Position
4. Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display will
show Purging and indicate the elapsed time of the purge cycle in seconds.
PROOF
INLET FROM GAS
BLOCKED
INLET
5. Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the
following events occur:
(a) The Air/Fuel Valve rotates to the low-fire (Ignition Position) position and closes the
Page 50 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Figure 3-5: Blower Proof Switch
ignition switch. The Dial on the Air/Fuel Valve (Figure 3-6) will read between 25 and 35 to indicate that the valve is in the low fire position.
Page 51
Benchmark 1500DF - 2000DF Boilers
TO BLOWER
AIR IN
STEPPER MOTOR
CHAPTER 3 – OPERATION
(b) The “Spark Cycle Time” item in the Factory menu can be set to either 0 Sec, 2 Sec
or 7 Sec to define the duration of the Spark Element Cleaning Cycle. This cycle turns on the spark transformer to produce a spark (with no gas flowing) to clean the spark element of moisture or carbon buildup.
For the duration of this cycle, the C-More will display the “CLEANING IGNITER” message.
(c) Following the Spark Element Cleaning Cycle, power is applied to the Gas Safety
Shut-off Valve (SSOV) and the C-More displays the “PRE IGNITION” message. When the SSOV indicates the Gas Valve is OPEN (POC), the C-More displays the “IGNITION TRIAL” message.
(d) If no spark is present 3 seconds into the IGNITION TRIAL, the C-More will abort the
Ignition Cycle and shut down the boiler. Refer to Chapter 8: Troubleshooti ng for
guidance if this occurs.
IGNITION
VALVE POSITIO N
DIAL AT
25% to 35%
Figure 3-6: Air/Fuel Valve In Ignition Position
6. Up to 4 seconds will be allowed for ignition to be detected. The igniter relay will be turned
off one second after flame is detected.
7. After 2 seconds of continuous flame, Flame Proven will be displayed and the flame
strength will be indicated. After 5 seconds, the current date and time will be displayed in place of the flame strength.
8. With the unit firing properly, it will be controlled by the temperature controller circuitry. The
boiler’s VALVE POSITION will be continuously displayed on the front panel bargraph.
Once the demand for heat has been satisfied, the Control Box will turn off the SSOV gas valve.
The blower relay will be deactivated and the Air/Fuel Valve will be closed. Standby will be
displayed.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 51 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 52
Benchmark 1500DF - 2000DF Boilers
Start Level:
24%
24%
24%
24%
Stop Level:
16%
16%
18%
16%
16% (Stop Level)
75,000
5.0%
18% 75,000
5.0%
20%
107,000
7.1%
93,700
6.2%
30%
281,000
18.7%
254,000
16.9%
40%
536,000
35.7%
505,000
33.7%
50%
717,000
47.8%
680,000
45.3%
60%
848,000
56.5%
807,000
53.8%
70%
992,000
66.1%
947,000
63.1%
80%
1,184,000
78.9%
1,157,000
77.1%
90%
1,393,000
92.9%
1,379,000
91.9%
100%
1,507,000
100%
1,503,000
100%
16% (Stop Level)
100,000
5.0%
100,000
5.0%
20%
132,000
6.6%
126,600
6.3%
30%
410,000
20.5%
363,000
18.2%
40%
786,000
39.3%
677,000
33.9%
50%
1,045,000
52.3%
898,000
44.9%
60%
1,280,000
64.0%
1,070,000
53.5%
70%
1,546,000
77.3%
1,242,000
62.1%
80%
1,686,000
84.3%
1,523,000
76.2%
90%
1,866,000
93.3%
1,845,000
92.3%
100%
2,000,000
100%
2,000,000
100%
CHAPTER 3 – OPERATION

3.11 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit, based on load. These levels are Factory preset as follows and should not require adjustment:
BMK 1500 BMK 2000 BMK 1500 BMK 2000
Natural Gas Propane Gas
Note that the energy input of the boiler is not linearly related to the Air/Fuel Valve position. Refer to Table 3-8a and 3-8b for the relationship between the energy input and Air/Fuel Valve position for a BMK 1500 MBH boiler running on natural gas.
Table 3-8a:
BMK 1500:
Relationship Between Air/Fuel Valve Position and
Energy Input
Natural Gas Propane Gas
Air/Fuel Valve
Position
(% Open)
Energy Input
(BTU/Hr)
Boiler Energy
Input (% of Full
Capacity)
Energy Input
(BTU/Hr)
Boiler Energy
Input (% of Full
Capacity)
Table 3-8b:
BMK 2000:
Relationship Between Air/Fuel Valve Position and
Energy Input Running
Natural Gas Propane Gas
Air/Fuel Valve
Position
(% Open)
Page 52 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Energy Input
(BTU/Hr)
Boiler Energy
Input (% of
Full Capacity)
Energy Input
(BTU/Hr)
Boiler Energy
Input (% of Full
Capacity)
Page 53
Benchmark 1500DF - 2000DF Boilers
WARNING
CHAPTER 4 – INITIAL START-UP

CHAPTER 4. INITIAL START-UP

4.1 INI TIAL START-UP REQUIREMENTS

The requirements for the initial start-up of the Benchmark boiler consists of the following:
Complete installation (Chapter 2)
Set proper controls and limits (Chapter 3)
Perform combustion calibration (Chapter 4)
Test safety devices (Chapter 6)
All applicable installation procedures in Chapter 2 must be fully completed prior to performing the initial start-up of the unit. The initial start-up must be successfully completed prior to putting the unit into service. Starting a unit without the proper piping, venting, or electrical systems can be dangerous and may void the product warranty. The following start-up instructions should be followed precisely in order to operate the unit safely and at a high thermal efficiency, with low flue gas emissions.
Initial unit start-up must be performed ONLY by AERCO factory trained start-up and service personnel. After performing the start-up procedures in this Chapter, it will be necessary to perform the Safety Device Testing procedures specified in Chapter 6 to complete all initial unit start-up requirements.
An AERCO Gas Fired Startup Sheet, included with each Benchmark unit, must be completed for each unit for warranty validation and a copy must be returned promptly to AERCO via e-mail
at: STARTUP@AERCO.COM.
DO NOT ATTEMPT TO DRY FIRE THE UNIT. STARTING THE UNIT WITHOUT A FULL WATER LEVEL CAN SERIOUSLY DAMAGE THE UNIT AND MAY RESULT IN INJURY TO PERSONNEL OR PROPERTY DAMAGE. THIS SITUATION WILL VOID ANY WARRANTY.
NOTE
ALL APPLICABLE INSTALLATION PROCEDURES IN CHAPTER 2 MUST BE COMPLETED BEFORE ATTEMPTING TO START THE UNIT.

4.2 TOOLS AND INSTRUMENTATION FOR COMBUSTION CALIBRATION

To properly perform combustion calibration, the proper instruments and tools must be used and correctly attached to the unit. The following sections outline the necessary tools and instrumentation as well as their installation.

4.2.1 Required Tools & Instrumentation

The following tools and instrumentation are necessary to perform combustion calibration of the unit:
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 53 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 54
Benchmark 1500DF - 2000DF Boilers
NATURAL GAS
NATURAL GAS
SWITCH
NATURAL GAS
PRESSURE SWITCH
PROPANE
PROPANE INLET
1/4” NPT PLUG
1/4” NPT PLUG
Calibration)
NATURAL GAS
DETECTION BALL VALVE
PROPANE
BALL VALVE
CHAPTER 4 – INITIAL START-UP
Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and Nitrogen Oxide (NOx) resolution to 1PPM.
16 inch W.C. manometer or equivalent gauge and plastic tubing.
1/4 inch NPT-to-barbed fittings for use with gas supply manometer or gauge.
Small and large flat blade screwdrivers.
Tube of silicone adhesive

4.2.2 Installing Gas Supply Manometer

The gas supply manometer (or gauge) is used to monitor the gas pressure on the downstream side of the SSOV during the Combustion Calibration procedures described in section 4.3.
The gas supply manometer is installed at the upstream and/or downstream location shown in Figure 4-1.
TO AIR/FUEL VALVE
MANUAL SHUT-
OFF VALVE
NATURAL GAS
SSOV
SSOV
PROPANE
HIGH GAS PRESSURE
SWITCH
PROPANE
LOW GAS PRESSURE
SWITCH
(Install manometer here for
PROPANE Combustion
HIGH GAS
LOW GAS PRESSURE
LOW GAS PRESSURE LEAK
(Install manometer here for
NATURAL GAS Combustion
Calibration)
GAS LEAK DETECTION
Figure 4-1: BMK 1500DF/2000DF: 1/4 Inch Gas Plug Locations for Combustion
Page 54 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Calibration
Page 55
Benchmark 1500DF - 2000DF Boilers
EXHAST MANIFOLD AIR INLET
ANALYZER PORT
CONDENSATE DRAIN
DRAIN VALVE
CHAPTER 4 – INITIAL START-UP
Install the 16” W.C. manometer(s) as described in the following steps:
Installing Gas Supply Manom eter
1. Turn off the main gas supply upstream of the unit.
2. Remove the top panel and front panel from the boiler to access the gas train components.
3. To monitor the gas pressure on the downstream side of the SSOV during Combustion Calibration (section 4.3), remove the 1/4” NPT plug from the leak detection ball valve on the downstream side of the SSOV as shown in Figure 4-1.
4. Install a NPT-to-barbed fitting into the tapped plug port.
5. Attach one end of the plastic tubing to the barbed fitting and the other end to the 16” W.C. manometer.

4.2.3 Accessing the Analyzer Probe Port

The unit contains a 1/4” NPT port on the side of the exhaust manifold as shown in Figure 4-2. Prepare the port for the combustion analyzer probe as follows:
Accessing the Analyzer Probe Port
1. Refer to Figure 4-2 and remove the 1/4” NPT plug from the exhaust manifold.
2. If necessary, adjust the stop on the combustion analyzer probe so it will extend mid-way into the flue gas flow. DO NOT install the probe at this time.
PRIMARY HOT WATER INLET
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 55 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Figure 4-2: Analyzer Probe Port Location (Right Side Partial View)
Page 56
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP

4.3 NATURAL GAS COMBUSTION CALIBRATION

The Benchmark boiler is combustion calibrated at the factory prior to shipping. This gas
pressure must be within the following ranges for each model of boiler at full fire:
Table 4-1: Nominal Gas Pressure – NATURAL GAS
BMK Boiler Model Nominal Gas Pressure
BMK 1500DF BMK 2000DF
Recalibration as part of initial start-up is necessary due to changes in the local altitude, gas BTU content, gas supply piping and supply regulators. Combustion Calibration Test Data sheets are shipped with each unit. These sheets must be filled out and returned to AERCO for proper Warranty Validation.
It is important to perform the following procedure as outlined. This will keep readjustments to a minimum and provide optimum performance.
The following Instructions for NATURAL GAS combustion calibration apply to both BMK 1500DF and BMK 2000DF model units.
3.5” W.C. ±0.2” W.C.
6.3” W.C. ±0.2” W.C.
NATURAL GAS Combustion Cali bration
1. Open the water supply and return valves to the unit and ensure that the system pumps are running.
2. Open the natural gas supply valve to the unit.
3. Set the control panel ON/OFF switch to the OFF position
4. Turn on external ac power to the unit. The display will show loss of power and the time and date.
5. Set the unit to the manual mode by pressing the AUTO/MAN key. A flashing manual valve position message will be displayed with the present position in %. Also, the MANUAL LED will light.
6. Adjust the air/fuel valve position to 0% by pressing the ▼ arrow key.
7. Ensure that the leak detection ball valve downstream of the SSOV is open.
8. Set the ON/OFF switch to the ON position.
9. Change the valve position to 30% using the ▲ arrow key. The unit should begin its start sequence and fire.
10. Next, verify that the gas pressure downstream of the SSOV is set to the proper value, listed in Table 4-1. If gas pressure adjustment is required, remove the brass hex nut on the SSOV actuator to access the gas pressure adjustment screw (Figure 4-3). Make gas
pressure adjustments using a flat-tip screwdriver to obtain the proper gas pressure.
11. Using the ▲ arrow key, increase the valve open position to 100%. Verify that the gas pressure on the downstream side of the SSOV settles within the range listed in Table 4-1.
Readjust the gas pressure if necessary.
12. With the valve position at 100%, insert the combustion analyzer probe into the flue probe opening and allow enough time for the combustion analyzer reading to stabilize.
Page 56 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 57
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP
NATURAL GAS Combustion Cali bration – Continued
13. Compare the oxygen readings on the combustion analyzer to the on-board O2 sensor value displayed in the Operating Menu of the C-More Control Panel. If the values differ by more than ±1.5% and your combustion analyzer is correctly calibrated, the on-board O sensor may be defective and need to be replaced.
14. Compare the measured oxygen level to the oxygen range shown below. Also, ensure that the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the values shown. If you are not in a “NOx-limited” area and/or do not have a NOx measurement in your analyzer, set the oxygen (O
Combustion Calibration Readings – 100% valve Position
Valve Position Oxygen (O2) % Nitrogen Oxide (NOx) Carbon Monoxide (CO)
100% 5.0% - 6.0% ≤20 ppm <100 ppm
15. If the oxygen level is not within the required tolerance, the gas pressure on the downstream side of the SSOV must be adjusted using the gas pressure adjustment screw on the SSOV (Figure 4-3). Slowly rotate the gas pressure adjustment (approximately 1/4-turn increments). Allow the combustion analyzer to stabilize following each adjustment. Clockwise rotation reduces the oxygen level, while counterclockwise rotation increases the oxygen level.
) at 5.5% ± 0.5%.
2
2
16. Once the oxygen level is within the specified range at 100%, record the O
, NOx and CO
2
readings on the Combustion Calibration Data Sheets provided with the unit.
17. Lower the valve position to 80% using the ▼arrow key.
NOTE
The remaining combustion calibration steps are performed using
the Combustion Cal Menu included in the C-More Control System.
The combustion calibration control functions will be used to adjust the oxygen level (%) at valve positions of 80%, 60%, 45%, 30% and 16% as described in the following steps. These steps assume that the inlet air temperature is within the range of 50°F to 100°F. If NOx readings exceed the target values shown, increase the O level up to 1% higher than the listed calibration range. Record the increased O
value on the Combustion Calibration sheet.
2
18. Press the MENU key on the front panel of the C-MORE and access the Setup menu. Enter password 6817 and then press the ENTER key.
19. Press the MENU key on the front panel of the C-MORE until Combustion Cal Menu
appears on the display.
20. Press the ▲ arrow key until SET Valve Position appears on the display.
21. Press the CHANGE key. SET Valve Position will begin to flash.
22. Press the ▲ arrow key until the SET Valve Position reads 80%. Press the ENTER key.
2
23. Next, press the down (▼) arrow key until CAL Voltage 80% is displayed.
24. Press the CHANGE key and observe that CAL Voltage 80% is flashing.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 57 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 58
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP
NATURAL GAS Combustion Cali bration – Continued
25. The oxygen level at the 80% valve position should be as shown below. Also, ensure that the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the following values:
Combustion Calibration Readings – 80% valve Position
Valve Position Oxygen (O2) % Nitrogen Oxide (NOx) Carbon Monoxide (CO)
80% 5.4% ± 0.5% ≤50 ppm <150 ppm
26. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼ arrow key decreases the oxygen level.
27. Once the oxygen level is within the specified range at 80%, press the ENTER key to
store the selected blower output voltage for the 80% valve position. Record all readings on the Combustion Calibration Sheets provided.
28. Repeat steps 20 through 27 for valve positions of 60%, 45%, 30% and 16%. The oxygen (O
), nitrogen oxide (NOx) and carbon monoxide (CO) should remain within the same
2
limits for all valve positions as shown in the following table.
NOTE
If NOx readings exceed the target values shown (<20 ppm), increase the O range shown in the table. Record the increased O
level up to 1% higher than the listed calibration
2
value on the
2
Combustion Calibration sheet.
Combustion Calibration Readings
Valve Position Oxygen (O2) % Nitrogen Oxide (NOx) Carbon Monoxide (CO)
60% 6.0% ± 0.5 <20 ppm <100 ppm
45% 6.3% ± 0.5 <20 ppm <100 ppm
30% 6.3% ± 0.5 <20 ppm <100 ppm
16% 6.0% ± 0.5 <20 ppm <100 ppm
29. If the oxygen level at the 16% valve position is too high and the Blower voltage is at the minimum value, you can adjust the idle screw (TAC valve) which is recessed in the top of the Air/Fuel Valve (see Figure 4-4). Rotate the screw 1/2 turn clockwise (CW) to add fuel and reduce the O 60% down to 16% after making a change to the idle screw (TAC valve).
to the specified level. Recalibration MUST be performed again from
2
30. This completes the NATURAL GAS combustion calibration procedures.
Page 58 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 59
Benchmark 1500DF - 2000DF Boilers
BRASS HEX HEAD
CHAPTER 4 – INITIAL START-UP
(Remove to access the Gas Pressure Adjustment Screw).
Figure 4-3: Gas Pressure Adjustment Screw Location
Figure 4-4: TAC Valve Adjust (Idle Screw)
TAC VALVE
IDLE SCREW
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 59 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 60
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP

4.4 PROPANE COMBUSTION CALIBRATION

If the boiler is currently running Natural Gas, complete the instructions in section 4.5.1 to switch the boiler fuel source from NATURAL GAS to PROPANE Gas.
The Benchmark boiler is combustion calibrated at the factory prior to shipping. This gas
pressure must be within the following ranges for each model of boiler at full fire:
Table 4-2: Nominal Gas Pressure – PROPANE
BMK Boiler Model Nominal PROPANE Gas Pressure
BMK 1500DF BMK 2000DF
1.4” W.C. ±0.2” W.C.
2.5” W.C. ±0.2” W.C.
Recalibration as part of initial start-up is necessary due to changes in the local altitude, gas BTU content, gas supply piping and supply regulators. Combustion Calibration Test Data sheets are shipped with each unit. These sheets must be filled out and returned to AERCO for proper Warranty Validation.
It is important to perform the following procedure as outlined. This will keep readjustments to a minimum and provide optimum performance.
The following Instructions for PROPANE combustion calibration apply to both BMK 1500DF and BMK 2000DF model units.
PROPANE Combustion Calibration
1. Open the water supply and return valves to the unit and ensure that the system pumps are running.
2. Open the PROPANE supply valve to the unit.
3. Set the control panel ON/OFF switch to the OFF position
4. Turn on external ac power to the unit. The display will show loss of power and the time and date.
5. Set the unit to the manual mode by pressing the AUTO/MAN key. A flashing manual valve position message will be displayed with the present position in %. Also, the MANUAL LED will light.
6. Adjust the air/fuel valve position to 0% by pressing the ▼ arrow key.
7. Ensure that the leak detection ball valve downstream of the SSOV is open.
8. Set the ON/OFF switch to the ON position.
9. Change the valve position to 30% using the ▲ arrow key. The unit should begin its start sequence and fire.
10. Next, verify that the gas pressure downstream of the SSOV s set to the proper value, listed in Table 4-2. If gas pressure adjustment is required, remove the brass hex nut on the SSOV actuator to access the gas pressure adjustment screw (Figure 4-3, above). Make gas pressure adjustments using a flat-tip screwdriver to obtain the proper gas
pressure.
11. Using the ▲ arrow key, increase the valve open position to 100%. Verify that the gas pressure on the downstream side of the SSOV settles within the range listed in Table 4-2.
Readjust the gas pressure if necessary.
Page 60 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 61
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP
PROPANE Combustion Cal ibration – Continued
12. With the valve position at 100%, insert the combustion analyzer probe into the flue probe opening and allow enough time for the combustion analyzer reading to stabilize.
13. Compare the oxygen readings on the combustion analyzer to the on-board O
sensor
2
value displayed in the Operating Menu of the C-More Control Panel. If the values differ by more than ±1.5% and your combustion analyzer is correctly calibrated, the on-board O2 sensor may be defective and need to be replaced.
14. Compare the measured oxygen level to the oxygen range shown below. Also, ensure that the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the values shown. If you are not in a “NOx-limited” area and/or do not have a NOx measurement in your analyzer, set the oxygen (O
) at 4.5% ± 0.5%.
2
Combustion Calibration Readings – 100% valve Position
Valve Position Oxygen (O2) % Nitrogen Oxide (NOx) Carbon Monoxide (CO)
100% 4.0% - 5.0% ≤50 ppm <150 ppm
15. If the oxygen level is not within the required tolerance, the gas pressure on the downstream side of the SSOV must be adjusted using the gas pressure adjustment screw on the SSOV (Figure 4-3). Slowly rotate the gas pressure adjustment (approximately 1/4­turn increments). Allow the combustion analyzer to stabilize following each adjustment. Clockwise rotation reduces the oxygen level, while counterclockwise rotation increases the oxygen level.
16. Once the oxygen level is within the specified range at 100%, record the O readings on the Combustion Calibration Data Sheets provided with the unit.
, NOx and CO
2
17. Lower the valve position to 80% using the ▼arrow key.
NOTE
The remaining combustion calibration steps are performed using
the Combustion Cal Menu included in the C-More Control System.
The combustion calibration control functions will be used to adjust the oxygen level (%) at valve positions of 80%, 60%, 45%, 30%
and 18% (on the BMK 1500DF only) or 16% (on the BMK 2000DF
only), as described below. These steps assume that the inlet air temperature is within the range of 50°F to 100°F. If NOx readings exceed the target values shown, increase the O higher than the listed calibration range. Record the increased O value on the Combustion Calibration sheet.
18. Press the MENU key on the front panel of the C-MORE and access the Setup menu. Enter password 6817 and then press the ENTER key.
19. Press the MENU key on the front panel of the C-MORE until Combustion Cal Menu
appears on the display.
20. Press the ▲ arrow key until SET Valve Position appears on the display.
21. Press the CHANGE key. SET Valve Position will begin to flash.
22. Press the ▲ arrow key until the SET Valve Position reads 80%. Press the ENTER key.
level up to 1%
2
2
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 61 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 62
Benchmark 1500DF - 2000DF Boilers
Oxygen (O2)
%
Nitrogen Oxide
(NOx)
Carbon Monoxide
(CO)
CHAPTER 4 – INITIAL START-UP
PROPANE Combustion Cal ibration – Continued
23. Next, press the down (▼) arrow key until CAL Voltage 80% is displayed.
24. Press the CHANGE key and observe that CAL Voltage 80% is flashing.
25. The oxygen level at the 80% valve position should be as shown below. Also, ensure that the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the following values:
Combustion Calibration Readings – 80% valve Position
Valve Position Oxygen (O2) % Nitrogen Oxide (NOx) Carbon Monoxide (CO)
80% 5.4% ± 0.5% ≤50 ppm <150 ppm
26. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow keys. This will adjust the output voltage to the blower motor as indicated on the display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼ arrow key decreases the oxygen level.
27. Once the oxygen level is within the specified range at 80%, press the ENTER key to
store the selected blower output voltage for the 80% valve position. Record all readings on the Combustion Calibration Sheets provided.
28. Repeat steps 20 through 27 for valve positions of 60%, 45%, 30% and 18% (on the BMK
1500DF only) or 16% (on the BMK 2000DF only). The oxygen (O
), nitrogen oxide (NOx)
2
and carbon monoxide (CO) should remain within the same limits for all valve positions as shown in the following table.
NOTE
If NOx readings exceed the target values shown (<50 ppm), increase the O range shown in the table. Record the increased O
level up to 1% higher than the listed calibration
2
value on the
2
Combustion Calibration sheet.
Combustion Calibration Readings
Valve Position
60% 5.5% ± 0.5 <50 ppm <150 ppm 45% 5.5% ± 0.5 <50 ppm <150 ppm 30% 6.3% ± 0.5 <50 ppm <150 ppm
18% BMK 1500DF
6.0% ± 0.5 <50 ppm <150 ppm
16% BMK 2000DF
29. If the oxygen level at the 18% (BMK1500DF) or 16% (BMK2000DF) valve position is too
high and the Blower voltage is at the minimum value, you can adjust the idle screw (TAC valve) which is recessed in the top of the Air/Fuel Valve (see Figure 4-4). Rotate the screw 1/2 turn clockwise (CW) to add fuel and reduce the O
Recalibration MUST be performed again from 60% down to 18% (BMK1500DF) or 16%
(BMK2000DF) after making a change to the idle screw (TAC valve).
to the specified level.
2
30. This completes the PROPANE combustion calibration procedure.
Page 62 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 63
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP

4.5 DUAL-FUEL SWITCHOVER INS T RUCTIONS

4.5.1 Switchover from NATURAL GAS to PROPANE

To switch from Natural Gas to Propane Gas operation, proceed as follows:
Switchover from NATURAL GAS to PROPANE
1. Set the ON/OFF switch on the C-More Controller to the OFF position.
2. Close the external Natural Gas supply valves.
3. Open the external Propane Gas supply valves.
4. Refer to Figure 4-6 and locate the Fuel Selector Switch on the unit, behind the front door.
5. Set the Fuel Selector Switch to the PROPANE position. A Gas pressure Fault message will be displayed on the Control Box.
6. Clear the Gas Pressure Fault by pressing the CLEAR key.
7. Set the ON/OFF switch on the C-More /control Box to the ON position.
8. Press the MENU key once. Setup Menu will be displayed.
9. Press the ▲ arrow key once. Password will be displayed.
10. Press the CHANGE key. Password will begin to flash.
11. Using the ▲ arrow key, increment the display and stop at 159.
12. Press the ENTER key to store the displayed password.
13. Password 1 will be displayed, indicating that the valid Level 1 password has been stored.
14. Next, access the Configuration Menu by pressing the MENU key once.
15. Using the ▲ and ▼ arrow keys, scroll through the Configuration Menu and stop at Fuel Type.
16. Press the CHANGE key. Fuel Type will begin to flash.
17. Press the ▲ arrow key. Propane will be displayed.
18. Press the ENTER key to store the Propane Fuel type.
19. Replace the front door panel previously removed from the boiler.
20. This completes the switchover from NATURAL GAS to PROPANE.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 63 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 64
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP
C-MORE CONTROLER
FRONT VIEW
DUAL FUEL
CUTOVER SWITCH
Figure 4-6: Duel Fuel Switch Location

4.5.2 Switchover from PROPANE to NATURAL GAS

To switch from Propane to Natural Gas, proceed as follows:
Switchover from PROPANE to NATURAL GAS
1. Set the ON/OFF switch on the C-More Controller to the OFF position.
2. Close the external Propane Gas supply valves.
3. Open the external Natural Gas supply valves.
4. Refer to Figure 4-6 and locate the Fuel Selector Switch on the front of the unit.
5. Set the Fuel Selector Switch to the NATURAL GAS position. A Gas pressure Fault
message will be displayed on the Control Box.
6. Clear the Gas Pressure Fault by pressing the CLEAR key.
7. Apply AC power to the boiler.
8. Press the MENU key once. Setup Menu will be displayed.
9. Press the ▲ arrow key once. Password will be displayed.
10. Press the CHANGE key. Password will begin to flash.
11. Using the ▲ arrow key, increment the display and stop at 159.
12. Press the ENTER key to store the displayed password.
13. Password 1 will be displayed, indicating that the valid Level 1 password has been stored.
14. Next, access the Configuration Menu by pressing the MENU key once.
Page 64 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 65
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP
Switchover from PROPANE to NATURAL GAS – Continued
15. Using the ▲ and ▼ arrow keys, scroll through the Configuration Menu and stop at Fuel Type.
16. Press the CHANGE key. Fuel Type will begin to flash.
17. Press the ▼ arrow key. Natural Gas will be displayed.
18. Press the ENTER key to store the Natural Gas Fuel type.
19. Replace the front door panel previously removed from the boiler.
20. This completes the steps necessary to switch from PROPANE Gas to NATURAL GAS.

4.6 REASSEMBLY

Once the combustion calibration adjustments are properly set, the unit can be reassembled for service operation.
Reassembly
1. Set the ON/OFF switch in the OFF position.
2. Disconnect AC power from the unit.
3. Shut off the gas supply to the unit.
4. Remove the manometer and barbed fittings and reinstall the NPT plug using a suitable pipe thread compound.
5. Remove the combustion analyzer probe from the 1/4” vent hole in the exhaust manifold. Replace the 1/4” NPT plug in the manifold.
6. Replace all previously removed sheet metal enclosures on the unit.
7. This concludes reassembly of the unit after combustion calibration.

4.7 OVER-TEMPERATURE LIMIT SWITCHES

The unit contains three (3) types of over-temperature limit switches. These switches consist of a manual reset switch, a rotary dial adjustable switch and a digital alarm switch. These switches are mounted on a plate as shown in Figure 4-5. The switches can be accessed by opening the front panel door of the unit.
The manual reset switch is not adjustable and is permanently fixed at 210°F. This switch will shut down and lock out the boiler if the water temperature exceeds 210°F. Following an over­temperature condition, it must be manually reset by pressing the manual reset button shown in Figurer 4-5 before the boiler can be restarted.
The rotary dial over-temperature switch is manually adjustable from xxx to yyy ºF. This switch allows the boiler to restart, once the temperature drops below the selected temperature setting on the dial. Set the dial on this over-temperature switch to the desired setting.
The digital alarm switch shown in Figures 4-5 and 4-6 is preset at the factory to 210ºF and should not be changed. If an over-temperature condition is detected, this switch automatically shuts down the boiler and sounds an audible alarm. If desired, the over-temperature alarm switch settings can be checked or adjusted using the procedure in section 4.5.1.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 65 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 66
Benchmark 1500DF - 2000DF Boilers
F
Alarm
RST
SET
Limit Control
CONTROL OR
DISPLAY
DIGITAL OVER-TEMPERATURE ADJUSTABLE TEMPERATURE
RESET BUTTON FOR MANUAL MANUAL TEMPERATURE LIMIT
FUEL SELECTOR SWITCH
CHAPTER 4 – INITIAL START-UP
ALARM SWITCH
LIMIT SWITCH
TEMPERATURE LIMIT SWITCH
SWITCH
Figure 4-5: Over-Temperature Limit Switch Locations

4.7.1 Digital Alarm Switch Checks and Adju st ments

The digital alarm switch settings can be checked or adjusted using the controls and display on the front panel of the switch illustrated and described in Figure 4-6 and Table 4-1.
Figure 4-6: Digital Over-Temperature Alarm Switch Front Panel
Table 4-1: Digital Alarm Switch Controls and Display
MEANING FUNCTION
LED Display
RST
TEMP status
RESET Button Resets the unit after an alarm condition.
UP Button Increases the displayed temperature.
Displays current water temperature or setpoint.
SET
Page 66 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
DOWN Button Decreases the displayed temperature.
SET Button
Used to access and store parameters in the unit.
Page 67
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP
Perform the following steps to check or adjust the digital alarm switch settings:
Digital Alarm Settings
1. Set the ON/OFF to the ON position.
2. Press the SET button on the Digital Alarm Switch. SP will appear in the display.
3. Press the SET button again. The current over-temperature limit value stored in memory will
be displayed. (default = 210°F).
4. If the display does not show the required over-temperature alarm setting, press the ▲ or ▼ arrow button to change the display to the desired temperature setting.
5. Once the desired over-temperature alarm setting (210ºF) is displayed, press the SET button
to store the setting in memory.
6. To calibrate the offset (P1), press and hold the SET button for 8 seconds on the Digital
Alarm Switch. Access code value 0 should appear in the display. The switch comes from the factory with the code set at 0. AERCO recommends that you do not change this code.
7. Press the SET button again to enter the code. The first parameter label (SP) will appear in
the display.
8. Using the ▲ and ▼ arrow keys, select parameter P1.
9. Press SET to view the value stored in memory.
10. If the desired value is not displayed, modify the setting using the ▲ and ▼ arrow keys. The
value can be changed from -10° to +10° offset. Press SET to enter the value and exit to the
text parameter.
11. To exit the programming mode, press the SET and ▼ buttons simultaneously, or simply wait
one minute and the display will automatically exit the programming mode.
12. Once the programming mode has been exited, the display will show the current outlet water temperature of the boiler.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 67 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 68
Benchmark 1500DF - 2000DF Boilers
CHAPTER 4 – INITIAL START-UP
(This Page Is Intentionally Blank)
Page 68 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 69
Benchmark 1500DF - 2000DF Boilers
CHAPTER 5 – MODE OF OPERATION

CHAPTER 5. MODE OF OPERATION

5.1 INTRODUCTION

The boiler is capable of being operated in any one of six different modes. The following sections in this Chapter provide descriptions of each of these operating modes. Each boiler is shipped from the factory tested and configured for the ordered mode of operation. All temperature related parameters are at their factory default values which work well in most applications. However, it may be necessary to change certain parameters to customize the unit to the system environment. A complete listing and descriptions of the temperature related parameters are included in Appendix A. Factory defaults are listed in Appendix D. After reading this chapter, parameters can be customized to suit the needs of the specific application.

5.2 INDOOR/OUTDOOR RESET MODE

This mode of operation is based on outside air temperatures. As the outside air temperature decreases, the supply header temperature will increase and vice versa. For this mode, it is necessary to install an outside air sensor as well as select a building reference temperature and a reset ratio.

5.2.1 Reset Ratio

Reset ratio is an adjustable number from 0.1 to 9.9. Once adjusted, the supply header temperature will increase by that number for each degree that the outside air temperature decreases. For instance, if a reset ratio of 1.6 is used, for each degree that outside air temperature decreases the supply header temperature will increase by 1.6 degrees.

5.2.2 Building Reference Temperature

This is a temperature from 40°F to 230°F. Once selected, it is the temperature that the system references to begin increasing its temperature. For instance, if a reset ratio of 1.6 is used, and we select a building reference temperature of 70°F, then at an outside temperature of 69°F, the supply header temperature will increase by 1.6° to 71.6°F.

5.2.3 Outdoor Air Temperature Sensor Installation

The outdoor air temperature sensor must be mounted on the North side of the building in an area where the average outside air temperature is expected. The sensor must be shielded from the sun's direct rays, as well as direct impingement by the elements. If a cover or shield is used, it must allow free air circulation. The sensor may be mounted up to two hundred feet from the unit. Sensor connections are made at the Input/Output (I/O) Box on the front of the boiler. Connections are made at the terminals labeled OUTDOOR AIR IN and AIR SENSOR COM inside the I/O Box. Use shielded 18 to 22 AWG wire for connections. A wiring diagram is provided on the cover of the I/O Box. Refer to Chapter 2, section 2.9.1 for additional wiring information.

5.2.4 Indoor/Outdoor Startup

Startup in the Indoor/Outdoor Reset Mode is accomplished as follows:
NOTE
A design engineer typically provides design outdoor air temperature and supply header temperature data
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 69 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 70
Benchmark 1500DF - 2000DF Boilers
Menu Option
CHAPTER 5 – MODE OF OPERATION
Indoor/Outdoor Start up
1. Refer to the Indoor/Outdoor reset ratio charts in Appendix F.
2. Choose the chart corresponding to the desired Building Reference Temperature.
3. Go down the left column of the chart to the coldest design outdoor air temperature expected in your area.
4. Once the design outdoor air temperature is chosen, go across the chart to the desired supply header temperature for the design temperature chosen in step 3.
5. Next, go up that column to the Reset Ratio row to find the corresponding reset ratio.
6. Access the Configuration Menu and scroll through it until the display shows Bldg Ref Temp. (Building Reference Temperature). If necessary, refer to section 3.3 for detailed instructions on menu changing.
7. Press the CHANGE key. The display will begin to flash.
8. Use the ▲ and ▼ arrow keys to select the desired Building Reference Temperature.
9. Press ENTER to save any changes.
10. Next, scroll through the Configuration Menu until the display shows Reset Ratio.
11. Press the CHANGE key. The display will begin to flash.
12. Use the ▲ and ▼ arrow keys to select the Reset Ratio determined in step 5.
13. Press ENTER to save the change. This completes

5.3 CONSTANT SETPOINT MODE

The Constant Setpoint mode is used when a fixed header temperature is desired. Common uses of this mode of operation include water source heat pump loops, and indirect heat exchangers for potable hot water systems or processes.
No external sensors are required to operate in this mode. While it is necessary to set the desired setpoint temperature, it is not necessary to change any other temperature-related functions. The unit is factory preset with settings that work well in most applications. Prior to changing any temperature-related parameters, other than the setpoint, it is suggested that an AERCO representative be contacted. For descriptions of temperature-related functions and their factory defaults, see Appendices A and E.

5.3.1 Setting the Setpoint

The setpoint temperature of the unit is adjustable from 40°F to 240°F. To set the unit for operation in the Constant Setpoint Mode, the following menu settings must be made in the Configuration Menu:
Boiler Mode Constant Setpoint
Internal Setpt Select desired setpoint using ▲ and ▼ arrow keys (40°F to 240°F)
Refer to section 3.3 for detailed instructions on changing menu options.
Page 70 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Setting
Page 71
Benchmark 1500DF - 2000DF Boilers
Menu Option
Setting
CHAPTER 5 – MODE OF OPERATION

5.4 REMOTE SETPOINT MODES

The unit’s setpoint can be remotely controlled by an Energy Management System (EMS) or Building Automation System (BAS). The Remote Setpoint can be driven by a current or voltage signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Remote Setpoint mode is 4 - 20 mA/1 - 5 Vdc. With this setting, a 4 to 20 mA/1 to 5 Vdc signal, sent by an EMS or BAS, is used to change the unit's setpoint. The 4 mA/1V signal is equal to a 40°F setpoint while a 20 mA /5V signal is equal to a 240°F setpoint. When a 0 to 20 mA/0 to 5 Vdc signal is used, 0 mA is equal to a 40°F setpoint.
In addition to the current and voltage signals described above, the Remote Setpoint mode can also driven by a RS-485 Modbus Network signal from an EMS or BAS.
The Remote Setpoint modes of operation can be used to drive single as well as multiple units.
NOTE
If a voltage, rather than current signal is used to control the remote setpoint, a DIP switch adjustment must be made on the PMC Board located in the Control Panel Assembly. Contact your local AERCO representative for details.
In order to enable the Remote Setpoint Mode, the following menu setting must be made in the Configuration Menu:
Boiler Mode Remote Setpoint
Remote Signal 4-20mA/1-5V, 0-20mA/0-5V, or Network
Refer to section 3.3 for detailed instructions on changing menu options.
If the Network setting is selected for RS-485 Modbus operation, a valid Comm Address must be entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional information.
While it is possible to change the settings of temperature related functions, the unit is factory preset with settings that work well in most applications. It is suggested that an AERCO representative be contacted, prior to changing any temperature related function settings. For descriptions of temperature-related functions and their factory defaults, refer to Appendices A and E.

5.4.1 Remote Setpoint Field Wiring

The only wiring connections necessary for the Remote Setpoint mode are connection of the remote signal leads from the source to the unit’s I/O Box. The I/O Box is located on the front panel of the boiler. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the connections are made at the ANALOG IN terminals in the I/O Box. For a Network setting, the connections are made at the RS-485 COMM terminals in the I/O Box. The signal must be floating, (ungrounded) at the I/O Box and the wire used must be a two wire shielded pair from 18 to 22 AWG. Polarity must be observed. The source end of the shield must be connected at the source. When driving multiple units, each unit’s wiring must conform to the above.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 71 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 72
Benchmark 1500DF - 2000DF Boilers
Menu Option
Setting
CHAPTER 5 – MODE OF OPERATION

5.4.2 Remote Setpoint Startup

Since this mode of operation is factory preset and the setpoint is being externally controlled, no
startup instructions are necessary. In this mode, the REMOTE LED will light when the external
signal is present.
To operate the unit in the Manual mode, press the AUTO/MAN switch. The REMOTE LED will go off and the MANUAL LED will light.
To change back to the Remote Setpoint mode, simply press the AUTO/MAN switch. The
REMOTE LED will again light and the MANUAL LED will go off.

5.5 DIRECT DRIVE MODES

The unit’s air/fuel valve position (% open) can be changed by a remote signal which is typically sent from an Energy Management System (EMS) or from a Building Automation System (BAS). The Direct Drive mode can be driven by a current or voltage signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Direct Drive mode is 4-20 mA/1-5 Vdc. With this setting, a 4 to 20 mA signal, sent by an EMS or BAS is used to change the unit’s valve position from 0% to 100%. A 4 mA/1V signal is equal to a 0% valve position, while a 20 mA /5V signal is equal to a 100% valve position. When a 0-20 mA/0-5 Vdc signal is used, zero is equal to a 0% valve position.
In addition to the current and voltage signals described above, the Direct Drive mode can also driven by a RS-485 Modbus Network signal from an EMS or BAS.
When in a Direct Drive mode, the unit is a slave to the EMS or BAS and does not have a role in temperature control. Direct Drive can be used to drive single, or multiple units.
NOTE
If a voltage, rather than current signal is used to control the remote setpoint, a DIP switch adjustment must be made on the CPU Board located in the Control Box Assembly. Contact your local AERCO representative for details.
To enable the Direct Drive Mode, the following menu setting must be made in the Configuration Menu:
Boiler Mode Direct Drive
Remote Signal 4-20mA/1-5V, 0-20mA/0-5V, or Network
Refer to section 3.3 for instructions on changing menu options.
If the Network setting is selected for RS-485 Modbus operation, a valid Comm Address must be entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional information.
Page 72 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 73
Benchmark 1500DF - 2000DF Boilers
Menu Option
Setting
CHAPTER 5 – MODE OF OPERATION

5.5.1 Direct Drive Field Wiring

The only wiring connections necessary for Direct Drive mode are connection of the remote signal leads from the source to the unit’s I/O Box. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the connections are made at the ANALOG IN terminals in the I/O Box. For a Network setting, the connections are made at the RS-485 COMM terminals in the I/O Box. The signal must be floating, (ungrounded) at the I/O Box and the wire used must be a two wire shielded pair from 18 to 22 AWG. Polarity must be observed. The source end of the shield must be connected at the source. When driving multiple units, each unit’s wiring must conform to the above.

5.5.2 Direct Drive Startup

Since this mode of operation is factory preset and the valve position is being externally
controlled, no startup instructions are necessary. In this mode, the REMOTE LED will light when
the signal is present.
To operate the unit in manual mode, press the AUTO/MAN switch. The REMOTE LED will go off and the MANUAL LED will light.
To change back to the Direct Drive mode, simply press the AUTO/MAN switch. The REMOTE LED will again light and the MANUAL LED will go off.

5.6 AERCO CONTROL SYSTEM (ACS)

NOTE
ACS can utilize only RS-485 signaling to the boiler.
The ACS mode of operation is used in conjunction with an AERCO Control System. The ACS mode is used when it is desired to operate multiple units in the most efficient manner possible. For this mode of operation, an ACS Header Sensor must be installed between 2 and 10 feet downstream of the LAST boiler in the boiler plant's supply water header. The ACS can control up to 40 boilers; Up to 32 via Modbus (RS-485) network communication. For ACS programming, operation, and Header Sensor installation details, see ACS Operations Guide, GF-131. For operation via an RS-485 Modbus network, refer to Modbus Communication Manual GF-114.
To enable the ACS Mode, the following menu settings must be made in the Configuration Menu:
Boiler Mode Direct Drive
Remote Signal Network (RS-485)
Refer to section 3.3 for instructions on changing menu options.

5.6.1 ACS External Field Wiring

Wiring connections for RS-485 Modbus control are made between the 485 A- and 485 B+ terminals on the ACS (boilers 9 through 40) and the RS-485 COMM terminals in the I/O Box on the front of the boilers.
Wire the units using shielded twisted pair wire between 18 and 22 AWG. Observe the proper polarity for the ACS RS-485 COMM wiring connections. Shields should be terminated only at the ACS and the boiler end must be left floating. Each unit’s wiring must conform to the above.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 73 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 74
Benchmark 1500DF - 2000DF Boilers
CHAPTER 5 – MODE OF OPERATION

5.6.2 ACS Setup and Startup

This mode of operation is factory preset and the ACS controls the firing rate (air/fuel valve % open position). There are no setup instructions for each individual unit.
To operate the unit in manual mode, press the AUTO/MAN switch. The REMOTE LED will go off and the MANUAL LED will light
To change back to the ACS mode, simply press the AUTO/MAN switch. The REMOTE LED will again light and the MANUAL LED will go off.

5.7 COMBINATION CONTROL SYSTEM (CCS)

NOTE
Only ACS can be utilized for the Combination Control System.
A Combination Control System (CCS) is one that uses multiple boilers to cover both space­heating and domestic hot water needs. The theory behind this type of system is that the maximum space-heating load and the maximum domestic hot water load do not occur simultaneously. Therefore, boilers used for domestic hot water are capable of switching between constant setpoint and ACS control.
For a typical CCS, an adequate number of boilers are installed to cover the space-heating load on the design-day. However, one or more units are used for the domestic hot water load as well. These boilers are the combination units and are referred to as the combo boilers. The combo boilers heat water to a constant setpoint temperature. That water is then circulated through a heat exchanger in a domestic hot water storage tank.
Only the AERCO Control System (ACS) is necessary to configure this system if only a single valve is used to switch from space heating to domestic hot water. However, the ACS Relay Panel is required in combination with the ACS when there are up to two isolation valves, boiler interlocks, and/or a Domestic Hot Water (DHW) pump in a Combination heating plant where AERCO boilers are being used for both Building Heat and Domestic Hot Water heating.
The following two options are available for using a combination system; one that uses only the ACS, and one that requires the optional ACS Relay Box:
OPTION 1 - This option is selected when the ACS controls a boiler plant containing up to
eight combination boilers that are Domestic Hot Water Priority (DHW PRIORITY) boilers,
along with building heat (BLDG HEAT) boilers, and one hydronic isolation valve in the main
header between the BLDG HEAT boilers and the DHW PRIORITY boilers.
OPTION 2 – When this option is selected, the ACS Relay Panel must be used in
conjunction with the ACS. For this option, the ACS controls a boiler plant containing up to eight combination boilers that are divided up into Building Priority (BLDG PRIORITY) boilers and Domestic Hot Water Priority (DHW PRIORITY) boilers, along with building heat
(BLDG HEAT) boilers, and using two hydronic isolation valves in the main header, one
between the BLDG HEAT and BLDG PRIORITY boilers, and the other between the BLDG PRIORITY and the DHW PRIORITY boilers.
In Option 2, when the space-heating load is such that when all the space-heating boilers are at the 100% valve position, the ACS will then ask the ACS Relay Box for the domestic boilers to become space-heating boilers. Provided the domestic hot water load is satisfied, the combo (hot water) boilers will then become space-heating boilers. If the domestic hot water load is not satisfied, the combo boiler(s) remain on the domestic hot water load. If the combo boilers switch over to space heating, but there is a call for domestic hot water, the ACS Relay Box switches the combo units back to the domestic load. The ACS in combination with the ACS Relay Box
Page 74 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 75
Benchmark 1500DF - 2000DF Boilers
Menu Option
Setting
Boiler Mode
Combination
CHAPTER 5 – MODE OF OPERATION
will ask the BLDG PRIORITY boilers to help with domestic hot water heating if the DHW PRIORITY boilers are not able to satisfy the domestic hot water demand.
When the combo units are satisfying the domestic load, they are in the constant setpoint mode of operation. When the combo units switch over to space heating, their mode of operation changes to follow the ACS command. For more information concerning the operation of the ACS, consult the ACS Operations Guide, GF-131. For more information on the ACS Relay Box, see section 2.14 in the same manual.

5.7.1 Combination Control System Field Wiring

Wiring for this system is between the ACS, the ACS Relay Box, and the terminals in the I/O Box. Wire the units using a shielded twisted pair of 18 to 22 AWG wire. When wiring multiple units, each unit’s wiring must conform to the above.

5.7.2 Combination Control System Setup and Startup

Setup for the Combination Mode requires entries to be made in the Configuration Menu for boiler mode, remote signal type and setpoint. The setpoint is adjustable from 40°F to 190°F.
Enter the following settings in the Configuration Menu:
Remote Signal Network
Internal Setpt 40°F to 190°F
Refer to section 3.3 for instructions on changing menu options.
While it is possible to change other temperature-related functions for combination mode, these functions are preset to their factory default values. These default settings work well in most applications. It is suggested that AERCO be contacted prior to changing settings other than the unit’s setpoint. For a complete listing of temperature related function defaults, see Appendix D.
To set the unit to the manual mode, press the AUTO/MAN switch. The MANUAL LED will light. To set the unit back to the auto mode, press the AUTO/MAN switch. The MANUAL LED will go
off and the REMOTE LED will light.
When the boiler is switched to ACS control, the ACS controls the valve position. There are no setup requirements to the boiler(s) in this mode.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 75 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 76
Benchmark 1500DF - 2000DF Boilers
CHAPTER 5 – MODE OF OPERATION
(This Page Is Intentionally Blank)
Page 76 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 77
Benchmark 1500DF - 2000DF Boilers
WARNING
CHAPTER 6 – SAFETY DEVICE TESTING

CHAPTER 6. SAFETY DE VI CE TE STING

6.1 TESTING OF SAFETY DEVICES

Periodic safety device testing is required to ensure that the control system and safety devices are operating properly. The boiler control system comprehensively monitors all combustion­related safety devices before, during and after the start sequence. The following tests check to ensure that the system is operating as designed.
Operating controls and safety devices should be tested on a regular basis or following service or replacement. All testing must conform to local codes such as ASME CSD-1.
NOTE
MANUAL and AUTO modes of operation are required to perform the following tests. For a complete explanation of these modes, see Chapter 3.
NOTE
It will be necessary to remove the front door and side panels from the unit to perform the following tests.
ELECTRICAL VOLTAGES IN THIS SYSTEM MAY INCLUDE 208­230 OR 460, 120 AND 24 VOLTS AC. POWER MUST BE REMOVED PRIOR TO PERFORMING WIRE REMOVAL OR OTHER TEST PROCEDURES THAT CAN RESULT IN ELECTRICAL SHOCK.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 77 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 78
Benchmark 1500DF - 2000DF Boilers
NATURAL GAS
SWITCH
NATURAL GAS
PRESSURE SWITCH
PROPANE
NATURAL GAS
pressure fault test
1/4” NPT PLUG
pressure fault test
NATURAL GAS
DETECTION BALL VALVE
PROPANE
BALL VALVE
CHAPTER 6 – SAFETY DEVICE TESTING

6.2 LOW GAS PRESSURE FAULT TEST

The instructions below apply to both the BMK 1500DF and BMK 2000DF and to both the NATURAL GAS and PROPANE gas trains.
TO AIR/FUEL VALVE
NATURAL GAS INLET
PROPANE INLET
MANUAL SHUT-
OFF VALVE
SSOV
SSOV
PROPANE
HIGH GAS PRESSURE
SWITCH
PROPANE
LOW GAS PRESSURE
SWITCH
(Install manometer here for
PROPANE LOW gas
HIGH GAS
LOW GAS PRESSURE
LOW GAS PRESSURE LEAK
1/4” NPT PLUG
(Install manometer here for
NATURAL GAS LOW gas
GAS LEAK DETECTION
Figure 6-1a: Low Gas Pres sure Test
To simulate a low gas pressure fault, refer to Figure 6-1a and perform the following steps:
1. Ensure that the appropriate low gas pressure leak detection ball valve (Natural Gas or Propane) is closed (see Figure 6-1a). Note that there are two Natural Gas leak detection ball valves (for high and low pressure) but only one on the Propane gas train.
2. Remove the 1/4“ plug from the appropriate (Natural Gas or Propane) ball valve at the associated low gas pressure switch as shown in Figure 6-1a.
3. Install a 0 – 16“ W.C. manometer or a W.C. gauge where the 1/4" plug was removed.
4. Slowly open the ball valve near the low gas pressure switch.
5. Place the unit in Manual Mode and adjust the Air/Fuel Valve position (% open) between 25 and 30%.
6. While the unit is firing, slowly close the external manual gas shut-off valve.
Page 78 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Low Gas Pressure Fault Test
Page 79
Benchmark 1500DF - 2000DF Boilers
NATURAL GAS
NATURAL GAS
PROPANE
pressure fault test
fault test
NATURAL GAS
DETECTION BALL VALVE
PROPANE
BALL VALVE
CHAPTER 6 – SAFETY DEVICE TESTING
Low Gas Pressure Fault Test – Continued
7. The unit should shut down and display a GAS PRESSURE fault message at
approximately 2.6” W.C..
8. Fully open the external manual gas shut-off valve and press the CLEAR button on the
Control Box.
9. The fault message should clear and the FAULT indicator should go off. The unit should
restart.
10. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4“ plug removed in step 1.

6.3 HIGH GAS PRESSURE TEST

The instructions below apply to both the BMK 1500DF and BMK 2000DF and to both the NATURAL GAS and PROPANE gas trains.
NATURAL GAS INLET
TO AIR/FUEL VALVE
MANUAL SHUT-
OFF VALVE
SSOV
PROPANE
SSOV
PROPANE
HIGH GAS PRESSURE
SWITCH
LOW GAS PRESSURE
SWITCH
PROPANE INLET
HIGH GAS PRESSURE SWITCH
HIGH GAS PRESSURE LEAK
NATURAL GAS
LOW GAS PRESSURE SWITCH
1/4” NPT PLUG
(Install manometer here for
NATURAL GAS HIGH gas
GAS LEAK DETECTION
1/4” NPT PLUG
(Install manometer here for
PROPANE HIGH gas pressure
To simulate a high gas pressure fault, refer to Figure 6-1b and perform the following steps:
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 79 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Figure 6-1b: BMK 1500DF/2000DF: High Gas Pressure Fault Test
Page 80
Benchmark 1500DF - 2000DF Boilers
CHAPTER 6 – SAFETY DEVICE TESTING
High Gas Pressure Test
1. Ensure that the appropriate high gas pressure leak detection ball valve (Natural Gas or Propane) is closed (see Figure 6-1b). Note that there are two Natural Gas leak detection ball valves (for high and low pressure) but only one on the Propane gas train.
2. Remove the 1/4“ plug from the leak detection ball valve shown in Figure 6-1b.
3. Install a 0 – 16” W.C. manometer (or W.C. gauge) where the 1/4” plug was removed.
4. Slowly open the leak detection ball valve.
5. Start the unit in Manual mode at a valve position (firing rate) between 25 and 30%.
6. With the unit running, monitor the gas pressure on the manometer installed in step 2 and record the gas pressure reading.
7. Slowly increase the gas pressure using the adjustment screw on the SSOV (see Figure 4-3).
8. The unit should shut down and display a HIGH GAS PRESSURE fault message when the gas pressure exceeds the value in the Gas Pressure column in Table 6-1, below.
Table 6-1: High Gas Pressure Switch Test
Unit Fuel SwitchSetting Gas Pressure
BMK 1500DF Natural Gas 4.7” W.C. 3.5” W.C.
BMK 1500DF Propane 3.5” W.C. 1.4” W.C.
BMK 2000DF Natural Gas 7.5” W.C. 6.3” W.C.
BMK 2000DF Propane 3.5” W.C. 2.5” W.C.
9. Reduce the gas pressure back to the value recorded in step 6. This pressure should be within the range of the value in Table 6-1, above.
10. Press the CLEAR button on the Control Box to clear the fault.
11. The fault message should clear and the FAULT indicator should go off. The unit should
restart.
12. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4“ plug removed in step 1.

6.4 LOW WATER LEVEL FAULT TEST

To simulate a low water level fault, proceed as follows:
Low Water Level Fault
1. Set the ON/OFF switch to the OFF position
2. Close the water shut-off valves in the supply and return piping to the unit.
3. Slowly open the drain valve on the rear of the unit. If necessary the unit’s relief valve may be opened to aid in draining.
4. Continue draining the unit until a LOW WATER LEVEL fault message is displayed and the FAULT indicator flashes.
5. Place the unit in the Manual Mode and raise the valve position above 30%.
6. Set the ON/OFF switch to the ON position. The READY light should remain off and the
unit should not start. If the unit does start, shut the unit off immediately and refer fault to qualified service personnel.
Page 80 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 81
Benchmark 1500DF - 2000DF Boilers
CHAPTER 6 – SAFETY DEVICE TESTING
Low Water Level Fault – Continued
7. Close the drain and pressure relief valve used in draining the unit.
8. Open the water shut-off valve in the return piping to the unit.
9. Open the water supply shut-off valve to the unit to refill.
10. After the shell is full, press the LOW WATER LEVEL RESET button to reset the low
water cutoff.
11. Press the CLEAR button to reset the FAULT LED and clear the displayed error
message.
12. Set the ON/OFF switch to the ON position. The unit is now ready for operation.

6.5 WATER TEMPERATURE FAULT TEST

A high water temperature fault is simulated by adjusting the automatic over-temperature switch. This switch is accessible from the front of the unit as shown in Figure 6-2.
Water Temperature Fault Test
1. Start the unit in the normal operating mode. Allow the unit to stabilize at its setpoint.
2. Lower the adjustable over-temperature switch setting to match the displayed OUTLET TEMPERATURE.
3. Once the adjustable over-temperature switch setting is approximately at, or just below,
the actual outlet water temperature, the unit should shut down. The FAULT indicator should start flashing and a HIGH WATER TEMP SW ITCH OPEN fault message should
be displayed. It should not be possible to restart the unit.
4. Reset the adjustable over-temperature switch to its original setting.
5. The unit should start once the adjustable temperature limit switch setting is above the actual outlet water temperature.
6. Once the adjustable over-temperature switch setting is approximately at, or just below,
the actual outlet water temperature, the unit should shut down. The FAULT indicator should start flashing and a HIGH WATER TEMP SW ITCH OPEN fault message should
be displayed. It should not be possible to restart the unit.
7. Reset the adjustable over-temperature switch to its original setting.
8. The unit should start once the adjustable temperature limit switch setting is above the actual outlet water temperature.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 81 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 82
MANUAL
BUTTON
OVER
CONTROLLER
9.
Benchmark 1500DF - 2000DF Boilers
CHAPTER 6 – SAFETY DEVICE TESTING
MANUAL TEMPERATURE LIMIT SWITCH
TEMPERATURE LIMIT DIGITAL
ADJUSTABLE TEMPERATURE LIMIT SWITCH
SWITCH RESET
FUEL SELECTION SWITCH
Figure 6-2: Temperature Limit Switch Location

6.6 INTERLOCK TESTS

The unit is equipped with two interlock circuits called the Remote Interlock and Delayed Interlock. Terminal connections for these circuits are located in the I/O Box (Figure 2-12) and are labeled REMOTE INTL’K IN and DELAYED INTL’K IN. These circuits can shut down the unit in the event that an interlock is opened. These interlocks are shipped from the factory jumpered (closed). However, each of these interlocks may be utilized in the field as a remote stop and start, an emergency cut-off, or to prove that a device such as a pump, gas booster, or louver is operational.

6.6.1 Remote Interlock Test

Remote Interlock Test
1. Remove the cover from the I/O Box and locate the REMOTE INTL’K IN terminals.
2. Start the unit in the Manual Mode and set the valve position between 25% and 30%.
3. If there is a jumper across the REMOTE INTL’K IN terminals, remove one side of the jumper. If the interlock is being controlled by an external device, either open the interlock via the external device or disconnect one of the wires leading to the external device.
4. The unit should shut down and display INTERLOCK OPEN.
5. Once the interlock connection is reconnected, the INTERLOCK OPEN message should automatically clear and the unit should restart.
Page 82 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 83
Benchmark 1500DF - 2000DF Boilers
CHAPTER 6 – SAFETY DEVICE TESTING

6.6.2 Delayed Interlock Test

Delayed Interlock Test
1. Remove the cover from the I/O Box and locate the DELAYED INTL’K IN terminals.
2. Start the unit in the Manual Mode at a valve position between 25% and 30%.
3. If there is a jumper across the DELAYED INTL’K IN terminals, remove one side of the jumper. If the interlock is connected to a proving switch of an external device, disconnect one of the wires leading to the proving switch.
4. The unit should shut down and display a DELAYED I NTERLOCK OPEN fault message. The FAULT LED should be flashing.
5. Reconnect the wire or jumper removed in step 3 to restore the interlock.
6. Press the CLEAR button to reset the fault
7. The unit should start.

6.7 FLAME FAULT TESTS

Flame faults can occur during ignition or while the unit is already running. To simulate each of these fault conditions, proceed as follows:
Flame Fault Tests
1. Set the ON/OFF switch to the OFF position.
2. Place the unit in the Manual Mode and set the valve position between 25% and 30%.
3. Close the manual gas shutoff valve located between the Safety Shut-Off Valve (SSOV) and the Air/Fuel Valve (see Figure 6-3).
4. Set the ON/OFF switch to the ON position to start the unit.
5. The unit should purge and light the Pilot Flame, then it should shut down after reaching
the main burner ignition cycle and display FLAME LOSS DURING IGN.
6. Open the valve previously closed in step 3 and press the CLEAR button.
7. Restart the unit and allow it to prove flame.
8. Once flame is proven, close the manual gas valve located between the SSOV (Figure 6-
3) and the Air/Fuel Valve.
9. The unit should shut down and Lockout, flashing FLDR in the display.
10. Open the valve previously closed in step 8.
11. Press the CLEAR button. The unit should restart and fire.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 83 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 84
IGNITER/INJECTOR
ASSEMBLY
BLOWER
PLENUM
NATURAL GAS
INLET
PROPANE INLET
A/F VALVE
PLENUM
BLOWER
PROOF
SWITCH
Benchmark 1500DF - 2000DF Boilers
CHAPTER 6 – SAFETY DEVICE TESTING
BLOWER
HEAT EXCHANGER
AIR/FUEL
VALVE
BLOCKED
INLET
SWITCH
FILTER
PROPANE
GAS SSOV
MANUAL SHUT-OFF VALVE
NATURAL GAS SSOV
AIR
Figure 6-3: Bare Boiler – Partial View (BMK 1500DF/2000DF)
Page 84 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 85
Benchmark 1500DF - 2000DF Boilers
CHAPTER 6 – SAFETY DEVICE TESTING

6.8 AIR FLOW FAULT TESTS

These tests check the operation of the Blower Proof Switch and Blocked Inlet Switch shown in Figure 6-3.

6.8.1 Blower Proof Switch Test

Blower Proof Switch Test
1. Disable the blower output drive voltage as follows:
(a) Press the MENU key until CONFIGURATION MENU is displayed. (b) Press the ▲ arrow key until the ANALOG OUTPUT function is displayed, then
press the CHANGE key.
(c) Press the ▼ arrow key until OFF is displayed, then press the ENTER key.
2. Start the unit and put the unit in Manual Mode at a valve position between 25% and 30%.
3. The unit should shut down and lockout, showing AIRFLOW FAULT DURING PURGE in
the display.
4. The unit should perform one IGNITION RETRY cycle and then shut down, since the blower is disabled. The unit will then display AIRFLOW FAULT DURING PURGE.
5. Re-enable the blower output drive voltage by performing the following steps:
(a) Press the MENU key until CONFIGURATION MENU is displayed. (b) Press the ▲ arrow key until the ANALOG OUTPUT function is displayed, then
press the CHANGE key.
(c) Press the ▲ arrow key until VALVE POSITION 0-10V is displayed, then press the
ENTER key. (Note, some units will instead display VALVE POSITION 4-20V.)
(d) Press the CLEAR button to clear the airflow fault.
6. Once the unit has proved flame, turn off the blower again by going to the Configuration
Menu, Analog Output menu item and select OFF.
7. The Blower Proof Switch will open and the blower should stop. The unit should shut
down and display AIRFLOW FAULT DURING RUN.
8. Go to the Configuration Menu, Analog Output item and select VALVE POSITION 0-10v.

6.8.2 Blocked Inlet Switch Test

This test will be run in simulated fire mode, with the Blocked Inlet Switch isolated from the rest of the control circuitry.
Blocked Inlet Switch Test
1. Turn off the main ON/OFF switch on the front of the Control Panel.
2. For units that get combustion air from a Combustion Air Duct, remove that duct, located directly above the boiler (see Figure 6.3, above). For units that have an air filter in place of a Combustion Air Duct (not shown), remove the air filter.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 85 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 86
Benchmark 1500DF - 2000DF Boilers
TO WIRE HARNESS
Flame Detector Flame Signal Generator
CHAPTER 6 – SAFETY DEVICE TESTING
Blocked Inlet Switch Test – Continued
WARNING
THE BLOWER SUCTION IS VERY STRONG AND CAN PULL NEARBY OBJECTS INTO THE BLOWER’S FAN BLADES. DO ALLOW ANYTHING TO BE PULLED INTO THE BLOWER. DO NOT WEAR ANYTHING THAT COULD GET CAUGHT AND PULL YOU INTO THE BLOWER.
3. Turn off the gas supply ball valve to the boiler and then complete the following steps:
(a) Use jumper wires to jump out the Low Gas Pressure Switch and the Blower Proof
Switch.
(b) Remove the black connector boot from the Flame Detector.
(c) Connect the Flame Signal Generator to the black connector boot.
Connector Boot
Figure 6.3a: Connecting the Flame Signal Generator
(d) Keep the alligator clip away from bare metal parts until step 3b.
4. Complete the following with the boiler operating in Manual mode:
(a) Ramp the boiler up to 100% fire rate and then turn on the main ON/OFF switch on
the front of the Control Panel.
(b) Push the BACK button three (3) times to return to the upper level menu.
(c) When the Controller gets into the ignition phase, the Control Panel will show
IGNITION TRIAL. At that point attach the alligator clip (see Figure 6.3a) to any bare metal surface or ground. The C-More display should now show FLAME PROVEN and begin to ramp up to 100% fire rate. Note that no gas or flame is present in the boiler at this time.
5. Wait for the boiler to ramp up to at least 90% before continuing.
6. Cover the combustion air inlet opening with a solid, flat object, such as a piece of plywood or metal plate.
7. The unit should shut down and display AIRFLOW FAULT DURING RUN. This step confirms proper operation of the Blocked Inlet Switch.
8. Remove the cover from the air inlet opening and reinstall the Combustion Air Duct or air filter.
9. Remove the jumper wires installed in step 2 and replace the black connector boot on the Flame Detector.
10. Press the CLEAR button. The unit should restart.
Page 86 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 87
Benchmark 1500DF - 2000DF Boilers
PRIMARY WATER INLET
ANALYZER
PORT
EXHAST
MANIFOLD
CHAPTER 6 – SAFETY DEVICE TESTING
AIR INLET
DRAIN VALVE
CONDENSATE DRAIN
Figure 6-4: Boiler Rear View Showing Air Inlet Location

6.9 SSOV PROOF OF CLOSURE SWITCH

The SSOV shown in Figure 6-1 contains the proof of closure switch. The proof of closure switch circuit is checked as follows:
SSOV Proof of Closure Switch
1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in Manual Mode and set the valve position between 25% and 30%
3. Refer to Figure 6-1 and locate the SSOV.
4. Remove the cover from the SSOV by loosening the screw shown in Figure 6-5. Lift off the cover to access the terminal wiring connections.
5. Disconnect wire #148 from the SSOV to “open” the proof of closure switch circuit.
6. The unit should fault and display SSOV SWITCH OPEN.
7. Replace wire #148 and press the CLEAR button.
8. Set the ON/OFF switch to the ON position to start the unit.
9. Remove the wire again when the unit reaches the purge cycle and PURGING is
displayed.
10. The unit should shut down and display SSOV FAULT DURING PURGE.
11. Replace the wire on the SSOV and press the CLEAR button. The unit should restart.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 87 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 88
Benchmark 1500DF - 2000DF Boilers
SSOV
ACTUATOR
CHAPTER 6 – SAFETY DEVICE TESTING
ACTUATOR
COVER
Figure 6-5: SSOV Actuator Cover Location

6.10 PURGE SWITCH OPEN DURING PURGE

The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. To check the switch, proceed as follows:
COVER SCREW
Purge Switch Open During Purge
1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and
set the valve position between 25% and 30%.
2. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it (see Figure 6-6).
3. Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 6-6).
4. Initiate a unit start sequence.
5. The unit should begin its start sequence, then shut down and display PRG SWITCH OPEN DURING PURGE.
6. Replace the wire on the Purge Switch and depress the CLEAR button. The unit should restart.
Page 88 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 89
Benchmark 1500DF - 2000DF Boilers
BLOCKED
BLOWER
CHAPTER 6 – SAFETY DEVICE TESTING

6.11 IGNITION SWITCH OPEN DURING IGNITION

The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the switch, proceed as follows:
Ignition Switch Open During Ignition
1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in Manual Mode and set the valve position between 25% and 30%.
3. Remove the Air/Fuel Valve cover (Figure 6-6) by rotating the cover counterclockwise to unlock and lift up to remove.
4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-7).
5. Initiate a unit start sequence.
6. The unit should begin its start sequence and then shut down and display IGN SWITCH OPEN DURING IGNITION.
7. Replace the wire on the Ignition Switch and press the CLEAR button. The unit should
restart.
PROOF
SWITCH
AIR/FUEL VALVE COVER
(Rotate Counter-Clock-Wise
to Remove)
Figure 6-6: Air/Fuel Valve Cover Location
AIR/FUEL VALVE
INLET SWITCH
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 89 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 90
Benchmark 1500DF - 2000DF Boilers
172
171
170
169
Ignition
Purge
AIR IN
TO BLOWER
VALVE
DIAL
AIR/FUEL VALVE
BREAKOUT
CHAPTER 6 – SAFETY DEVICE TESTING
Position
Switch
POSITION
SWITCH WIRING
Position
Switch
Figure 6-7: Air/Fuel Valve Purge and Ignition Switch Locations

6.12 SAFETY PRESSURE REL IEF VALVE TEST

Test the safety Pressure Relief Valve in accordance with ASME Boiler and Pressure Vessel Code, Section VI.
Page 90 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 91
Benchmark 1500DF - 2000DF Boilers
Labor
Time
Igniter-Injector
(66013)
Flame Detector
(66020)
O2 Sensor
(61026)
Combustion
Calibration
Testing of Safety
Devices
See ASME CSD-1
Chart
7.6
Burner
Inspect
2 hrs.
Condensate
Drain Trap
Inspect, Clean &
Replace Gaskets
Inspect, Clean &
Replace Gaskets
7.8
WARNING
CHAPTER 7 – MAINTENANCE

CHAPTER 7. MAINTENANCE

7.1 MAINTENANCE SCHEDULE

The unit requires regular routine maintenance to keep up efficiency and reliability. For best operation and life of the unit, the following routine maintenance procedures should be performed in the time periods specified in Table 7-1. For a complete inspection check list see ASME CSD­1 chart.
In order to perform the maintenance tasks specified in Table 7-1, the following maintenance kits are available through your local AERCO Sales Representative:
12 Month Maintenance Kit, Part No. 58025-01
24-Month Waterside/Fireside Inspection Kit, Part No. 58025-13 (See NOTE below)
NOTE:
The 24-Month Waterside/Fireside Inspection Kit also includes the items contained in the Annual Maintenance Kit (58025-01). Therefore, only Kit Part No. 58025-13 is required when performing the waterside/fireside inspections. Refer to Appendix L for recommended spare
TO AVOID PERSONAL INJURY, PRIOR TO SERVICING ENSURE THAT THE FOLLOWING GUIDELINES ARE STRICTLY OBSERVED:
DISCONNECT THE AC SUPPLY BY TURNING OFF THE SERVICE SWITCH AND AC SUPPLY CIRCUIT BREAKER.
SHUT OFF THE GAS SUPPLY AT THE MANUAL SHUT-OFF VALVE PROVIDED WITH THE UNIT
ALLOW THE UNIT TO COOL TO A SAFE WATER TEMPERATURE TO PREVENT BURNING OR SCALDING
Table 7-1: Maintenance Schedule
Section Item 6 Mos. 12 Mos. 24 Mos.
7.2
7.3
7.4
4.3
*Inspect Inspect Replace 15 mins.
*Inspect Inspect Replace 15 mins.
*Inspect Inspect 15 mins.
*Check Check 1 hr.
* Only performed after initial 6 month period after initial startup.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 91 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
7.5
7.7
*Inspect
Air Filter (59138) Clean Replace 15 mins.
45 mins.
30 mins.
Page 92
Benchmark 1500DF - 2000DF Boilers
IGNITOR-
FLAME DETECTOR
BURNER
PLENUM
FLAME
AIR/FUEL VALVE
BLOWER
A/F VALVE
CHAPTER 7 – MAINTENANCE

7.2 IGNITER-INJECTOR

The igniter-injector (part no. 66026) is located on the burner plate at the top of the boiler. In addition to providing the ignition spark required to light the burner, the igniter-injector also contains a gas injector tube which connects to the staged ignition assembly. Figure 7-1 shows the complete burner assembly removed from the boiler and indicates the location of the igniter­injector flame detector and other related components.
BLOWER
BLOWER
PLENUM
INJECTOR
ASSEMBLY
PLENUM
O2 SENSOR
FLANGE/ BURNER
TOP PLATE
The igniter-injector may be hot, therefore, care should be exercised to avoid burns. It is easier to remove the igniter-injector from the unit after the unit has cooled to room temperature. To inspect/replace the Igniter:
1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power
PROOF
SWITCH
OBSERVATION PORT
Figure 7-1: Benchmark 1500/2000 Burner Assembl y (Rem oved f ro m Boil er)
Igniter-Injector Maint enance Procedures
from the unit
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up.
This will disengage the shroud from the four (4) pins in the side panels.
3. Disconnect the cable from the igniter-injector (Figure 7-1).
Page 92 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 93
Benchmark 1500DF - 2000DF Boilers
STAGED
FLAME
FLAME
INJECTOR-
O2 SENSOR
FLEX GAS
COMPRESSION FITTING & ELBOW
BLOWER PLENUM
CHAPTER 7 – MAINTENANCE
Igniter-Injector Maintenance Procedures – Continued
4. Refer to the partial exploded view in Figure 7-2. Using a 7/16” open-end wrench,
disconnect the compression nut securing the gas injector tube of the igniter-injector to the elbow of the staged ignition assembly. Disconnect the staged ignition assembly from the igniter-injector.
5. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end
wrench.
6. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence
of substantial erosion or carbon build-up, the igniter-injector should be replaced. If carbon build-up is present, clean the component using fine emery cloth. Repeated carbon build­up is an indication that the combustion settings of the unit should be checked. Refer to Chapter 4 for combustion calibration procedures.
HOSE
NIPPLE
IGNITION
SOLENOID
IGNITOR
ASSY WITH
INDEXING
(CLOCKING)
WASHERS
(0-3 as
needed)
& WASHER
BURNER PLATE
FLANGE
OBSER­VATION PORT
DETECTOR & GASKET
Figure 7-2: Igniter-Injector & Flame Detector Mounting Details
7. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end
wrench.
8. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence
of substantial erosion or carbon build-up, the igniter-injector should be replaced. If carbon build-up is present, clean the component using fine emery cloth. Repeated carbon build­up is an indication that the combustion settings of the unit should be checked. Refer to Chapter 4 for combustion calibration procedures.
9. Prior to reinstalling the igniter-injector, a high temperature, conductive, anti-seize com-
pound must be applied to the threads.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 93 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 94
Benchmark 1500DF - 2000DF Boilers
O2 SENSOR
BLOWER PLENUM
IGNITER-
FLAME ANGLE OF GAS
120°
FLAME
CHAPTER 7 – MAINTENANCE
IGNITER-INJECTOR MAINTENANCE PROCEDURES – Continued
NOTE
If a replacement igniter-injector (part no. 66026) is being installed, a compression nut containing a built-in ferrule will be included with the replacement part. If needed, 3 indexing washers are also included These washers may be needed to properly position the gas injector tube of the igniter-injector within the 120° angle range shown in Figure 7-3.
INJECTOR
INJECTOR TUBE
OBSERVATION PORT
ROD
Figure 7-3: Igniter-Injector Orientation (Viewed Looking Down from Above)
10. Reinstall the igniter-injector in the burner plate. Torque to 170 - 180 in-lbs. DO NOT over
tighten.
11. Connect the staged ignition assembly to the gas injector tube of the igniter-injector by
securing the compression nut to the elbow of the staged ignition assembly.
12. Reconnect the igniter-injector cable.
13. Reinstall the shroud on the unit.

7.3 FLAME DETECTOR

The flame detector (part no. 66020) is located on the burner plate at the top of the unit (see Figures 7-1 and 7-2). The flame detector may be hot. Allow the unit to cool sufficiently before removing the flame detector. Inspect or replace the flame detector as follows:
1. Set the control panel ON/OFF switch to the OFF position. Disconnect AC power from the
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up.
Page 94 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Flame Detector Maintenance
unit.
This will disengage the shroud from the four (4) pins in the side panels.
Page 95
Benchmark 1500DF - 2000DF Boilers
CHAPTER 7 – MAINTENANCE
Flame Detector Maintenance – Continued
3. Disconnect the flame detector lead wire.
4. Remove the two (2) screws securing the flame detector to the plate (Figure 7-2). The
flame detector is secured to the burner plate with one #10-32 screw and one #8-32 screw.
5. Remove the flame detector and gasket from the burner plate.
6. Thoroughly inspect the flame detector. If eroded, the detector should be replaced.
Otherwise clean the detector with a fine emery cloth.
7. Reinstall the flame detector and flame detector gasket.
8. Reconnect the flame detector lead wire.
9. Reinstall the shroud on the unit.

7.4 O2 SENSOR

The O2 sensor (part no. 61026) is located on the burner plate at the top of the unit (see Figures 7-1 and 7-2). The sensor may be hot. Allow the unit to cool sufficiently before removing or replacing the O
sensor.
2
O2 Sensor Maintenance Procedures
1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power
from the unit.
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up.
This will disengage the shroud from the four (4) pins in the side panels.
3. Disconnect the O
sensor lead wire by pushing in on the release tab and pulling apart the
2
connector.
4. Next, loosen and remove the O
sensor and crush washer from the burner plate using a
2
15/16" open-end wrench.
5. Thoroughly inspect the O
sensor. If eroded, the sensor should be replaced. Otherwise
2
clean the sensor with a fine emery cloth.
6. Reinstall the O
sensor and crush washer on the burner plate.
2
7. Reconnect the sensor lead wire.
8. Reinstall the shroud on the unit.

7.5 SAFETY DEVICE TESTING

Systematic and thorough tests of the operating and safety devices should be performed to ensure that they are operating as designed. Certain code requirements, such as ASME CSD-1, require that these tests be performed on a scheduled basis. Test schedules must conform to local jurisdictions. The results of the tests should be recorded in a log book. See Chapter 6­Safety Device Testing Procedures.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 95 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 96
Benchmark 1500DF - 2000DF Boilers
Part No.
Description
88183
Burner Upper Release Gasket (1 each)
81166
Burner Gasket (1 each)
81186
Burner Lower Release Gasket (1 each)
81048
Flame Detector Gasket (1 each)
CHAPTER 7 – MAINTENANCE

7.6 BURNER ASSEMBLY INSPECTION

The burner assembly is located at the top of the unit's heat exchanger. The burner assembly may be hot. Therefore, allow the unit to cool sufficiently before removing the burner assembly.
NOTE
In order to do this procedure most efficiently with a minimum of steps, a simple support rig has been designed to hold up the blower and Air/Fuel Valve assembly while the blower plenum is removed to allow the burner assembly to be removed for maintenance. Using this support will relieve the blower’s weight from bearing down upon the connection to the gas train. This support rig prevents having to dismantle the entire blower and A/V Valve assembly from the gas train. The support rig is available as an after-market part.
The following parts will be required for reassembly after burner inspection:
To inspect or replace the burner assembly, proceed as follows:
Burner Assembly Inspection and Maintenance Procedures
1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power
from the unit and turn off the gas supply.
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up.
This will disengage the shroud from the four (4) pins in the side panels.
3. Disconnect the lead wire from the flame detector installed on the burner plate. See Figure
7-2.
4. Remove the two (2) screws securing the flame detector to the plate. The flame detector is
secured to the burner plate with one (1) #10-32 screw and one (1) #8-32 screw.
5. Remove the flame detector and gasket from the burner plate.
6. Disconnect the cable from the igniter-injector.
7. Using a 7/16” open-end wrench, disconnect the compression nut securing the gas injector
tube of the igniter-injector to the elbow of the staged ignition assembly (see Figure 7-2). Disconnect the staged ignition assembly from the igniter-injector.
8. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end
wrench.
9. Retrieve the blower support rig and attach it to the blower and unit as described in the
instructions provided with the rig.
10. Loosen and remove the four 5/16x1-3/4” bolts, washers, and nuts from the burner plenum
where it is attached to the blower (see Figure 7-4a & 7-4b).
Page 96 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 97
Benchmark 1500DF - 2000DF Boilers
CHAPTER 7 – MAINTENANCE
Burner Assembly Inspection and Maintenance Procedures (Cont.)
11. Remove the eight (8) 3/8-16 nuts, using a 9/16” wrench, attaching the blower plenum to
the burner beneath (see Figure 7-4a & 7-4b).
12. Remove the blower plenum from between the blower and the burner and set aside for
later reassembly. O2 sensor and flame observation port remain assembled to the plenum flange.
NOTE
The burner assembly is heavy, weighing approximately 65 lbs.
13. Remove the burner by pulling straight up.
14. Remove and replace the burner gasket(s) (see Figure 7-5).
IMPORTANT!
ALL THREE gaskets provided for maintenance MUST be installed during this procedure, as shown in Figure 7-5, even if there is only one existing gasket being replaced. Note that the LOWER RELEASE GASKET has tabs, which the others do not.
NOTE
During reassembly, apply a light coating of high-temperature, anti­seize lubricant to the threads of the igniter-injector and grounding screw. Also, ensure that the igniter-injector is properly positioned as indicated in Figure 7-3. Torque the igniter-injector to 170 - 180 in-lbs.
15. Beginning with the burner assembly, reinstall all the components in the reverse order that
they were removed. When reinstalling the blower plenum (removed in step 11), tighten the 3/8-16 nuts using a typical torque pattern (for example, loosely tighten one nut, then loosely tighten a second nut on the opposite side, a third at 90 degrees to the first two, and a fourth opposite the third, and then repeat this pattern with the remaining four nuts. Repeat the entire pattern a second time to partially tighten all eight nuts, and then repeat a third time until all eight nuts are fully torqued to 22 ft. lbs).
16. Ensure that the igniter-injector and flame detector cutouts in the burner plate are properly
aligned with the heat exchanger top flange.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 97 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Page 98
Benchmark 1500DF - 2000DF Boilers
5/16” x 1-3/4”
(4 each)
BLOWER PLENUM
GAS TRAIN
A/F VALVE BLOWER
BURNER
3/8”-16
(8 each)
AIR/FUEL
IGNITER-
1/2” NUTS
CHAPTER 7 – MAINTENANCE
Burner Assembly Inspection and Maintenance Procedure (Cont.)
BOLTS, 5/16” WASHERS &
INJECTOR
ASSEMBLY
HEX NUTS
PLATE
NYLOCK NUTS
PLENUM
VALVE FILTER
& BOLTS (4 each)
Figure 7-4a: Burner Assembly Mounting Details
AIR FILTER
Page 98 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Page 99
Benchmark 1500DF - 2000DF Boilers
BARE
is only one existing gasket being replaced.
NOTE
four tabs around its periphery.
NATURAL GAS INLET
PROPANE INLET
5/16” x 1-3/4” BOLTS,
3/8”-16
(8 each)
CHAPTER 7 – MAINTENANCE
Burner Assembly Inspection and M aintenance Procedure – Continued
5/16” WASHERS &
NYLOCK NUTS
(4 each)
BLOWER
HEX NUTS
A/F VALVE
PLENUM
BLOWER
PROOF
SWITCH
AIR/FUEL
VALVE
BLOCKED
INLET
SWITCH
AIR
FILTER
Figure 7-4b: Burner Assembly Mounting Details
The LOWER RELEASE
GASKET (P/N 81186) features
81183 – UPPER RELEASE GASKET 81166 – MIDDLE BURNER GASKET 81186 – LOWER RELEASE GASKET
MANUAL SHUT-OFF VALVE
Use ALL THREE gaskets provided, even if there
IMPORTANT!
BURNER
INSTALLED
IN HEAT
EXCHANGER
ASSY.
OMM-0098_0A AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 99 of 196
GF-144 Ph.: 800-526-0288 04/01/2014
Figure 7-5: Bare Burner and Replacement Gaskets Location
Page 100
Benchmark 1500DF - 2000DF Boilers
THUMB SCREWS
COVER
GASKET
FLOAT FLOAT
CONDENSATE
(P/N 24060)
OUTLET
INLET
Thumb Screws
Condensate
Float
Float Guide
O-Rings
3/4" NPT Port
3/4" NPT Port
Adapter
Opening
CHAPTER 7 – MAINTENANCE

7.7 CONDENSATE DRAIN TRAP

Benchmark boilers contains a condensate trap as shown in Chapter 2, Figure 2-5. The trap is located external to the unit and attached to the drain pipe from the exhaust manifold. This trap should be inspected and cleaned in accordance with the maintenance schedule shown in Table 7-1 to ensure proper operation. To inspect and clean the trap, proceed as follows:
Condensate Drain Trap Maint enance Procedure
1. Disconnect the external condensate trap by loosening the union pipe connection between
the trap and the exhaust manifold drain pipe.
2. Remove the connections on the inlet and outlet sides of the condensate trap shown in
Figure 7-6.
3. Loosen the four (4) thumbscrews securing the cover on the condensate trap. Remove the
cover.
4. Remove the float from the condensate trap.
5. Remove the O-ring and orifice gaskets from the trap. AERCO recommends that these
items be replaced annually.
6. Thoroughly clean the trap and float. Also inspect the drain piping for blockage. If the trap
cannot be thoroughly cleaned, replace the trap.
7. After the above items have been inspected and thoroughly cleaned, replace the O-ring
(84017) and orifice gasket (81092) with new parts.
8. Reassemble all piping and hose connections to the condensate trap inlet and outlet.
Reconnect trap to exhaust manifold drain.
NOTE
There are two slightly different types of condensate traps that may be used in
your configuration; an older style with a separate inlet adapter, and a newer style with a built-in adapter (see Figure 11). Maintenance is the same, except that the newer style does not need an orifice gasket (Step 6).
9.
(4)
GUIDE
Trap O-Ring
TRAP
(2)
Figure 7-6: External Conden sat e Trap: Cu t aw ay and Exploded Views
Page 100 of 196 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
Loading...