AERCO BMK 1.5 LN User Manual May 2009

Page 1
AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA
Instruction
No.
Installation, Operation
& Maintenance Instructions
Benchmark 1.5LN Series Gas Fired Low NOx Boiler System
Condensing, Modulating
Forced Draft, Hot Water Boiler
1,500,000 BTU/H Input
Printed in U.S.A. REVISED MAY, 2009
Page 2
Telephone Support
Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday):
1-800-526-0288
AERCO International, Inc. 159 Paris Avenue Northvale, NJ 07647-0128
www.aerco,com
© AERCO International, Inc., 2009
The information contained in this installation, operation and mainte­nance manual is subject to change without notice from AERCO International, Inc.
AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
Page 3
CONTENTS
GF-120 - AERCO BENCHMARK 1.5LN GAS FIRED LOW NOx BOILER
Operating & Maintenance Instructions
FOREWARD A
Chapter 1 – SAFETY PRECAUTIONS 1-1
Para. Subject Page
1-1 Warnings & Cautions 1-1 1-2 Emergency Shutdown 1-2
Chapter 2 – INSTALLATION 2-1
Para. Subject Page
2.1 Introduction 2-1
2.2 Receiving the Unit 2-1
2.3 Unpacking 2-1
2.4 Site Preparation 2-1
2.5 Supply and Return Piping 2-3
2.6 Condensate Drains 2-3
2.7 Gas Supply Piping 2-4
2.8 AC Electrical Power Wiring 2-5
Para. Subject Page
1-3 Prolonged Shutdown 1-2
Para. Subject Page
2.9 Modes of Operation and Field Control Wiring
2.10 I/O Box Connections 2-7
2.11 Auxiliary Relay Contacts 2-9
2.12 Flue Gas Vent Installation 2-9
2.13 Combustion Air 2-9
2-5
Chapter 3 – CONTROL PANEL COMPONENTS AND OPERATING PROCEDURES 3-1
Para. Subject Page
3.1 Introduction 3-1
3.2 Control Panel Description 3-1
3.3 Control Panel Menus 3-4
3.4 Operating Menu 3-5
3.5 Setup Menu 3-5
Para. Subject Page
3.6 Configuration Menu 3-6
3.7 Tuning Menu 3-7
3.8 Start Sequence 3-7
3.9 Start/Stop Levels 3-9
Chapter 4 – INITIAL START-UP 4-1
Para. Subject Page
4.1 Initial Startup Requirements 4-1
4.2 Tools and Instruments for Combustion Calibration
4.3 Natural Gas Combustion Calibration
4-1
4-2
Para. Subject Page
4.4 Unit Reassembly 4-5
4.5 Over-Temperature Limit Switches
4-5
i
Page 4
CONTENTS
Chapter 5 – MODE OF OPERATION 5-1
Para. Subject Page
5.1 Introduction 5-1
5.2 Indoor/Outdoor Reset Mode 5-1
5.3 Constant Setpoint Mode 5-2
5.4 Remote Setpoint Mode 5-2
5.5 Direct Drive Modes 5-3
Para. Subject Page
5.6 Boiler Management System (BMS)
5.7 Combination Control System (CCS)
5-4
5-5
Chapter 6 – SAFETY DEVICE TESTING PROCEDURES 6-1
Para. Subject Page
6.1 Testing of Safety Devices 6-1
6.2 Low Gas Pressure Fault Test 6-1
6.3 High Gas Pressure Test 6-2
6.4 Low Water Level Fault Test 6-2
6.5 Water Temperature Fault Test 6-2
6.6 Interlock Tests 6-3
6.7 Flame Fault Test 6-4
Para. Subject Page
6.8 Air Flow Fault Test 6-4
6.9 SSOV Proof of Closure Switch 6-4
6.10 Purge Switch Open During Purge
6.11 Ignition Switch Open During Ignition
6.12 Safety Pressure Relief Valve Test
6-5
6-5
6-6
Chapter 7 – MAINTENANCE REQUIREMENTS 7-1
Para. Subject Page
7.1 Maintenance Schedule 7-1
7.2 Spark Ignitor 7-1
7.3 Flame Detector 7-2
7.4 Combustion Calibration 7-2
7.5 Safety Device Testing 7-3
7.6 Burner Assembly 7-3
Para. Subject Page
7.7 Condensate Drain Trap 7-4
7.8 Shutting the Boiler Down For An Extended Period of Time
7.9 Placing The Boiler Back In Service After A Prolonged Shutdown
7-4
7-4
Chapter 8 – TROUBLESHOOTING GUIDE 8-1
Para. Subject Page
8.1 Introduction 8-1
Para. Subject Page
ii
Page 5
CONTENTS
APPENDICES
App Subject Page
A Boiler Menu Item Descriptions A-1 B Startup, Status and Fault
Messages
C Temperature Sensor Resistance
Chart
D Indoor/Outdoor Reset Ratio
Charts
B-1
C-1
D-1
WARRANTIES W-1
App Subject Page
E Boiler Default Settings E-1 F Dimensional and Part Drawings F-1 G Piping Drawings G-1 H Wiring Schematics H-1 I Recommended Periodic Testing
Checklist
J Benchmark Control Panel Views J-1
I-1
iii
Page 6
Page 7

FOREWORD

Foreword
The AERCO Benchmark 1. 5LN Boiler is a m odulating unit. It represents a true industry advance that meets the needs of today's ener gy and environmental concerns. Designed for application in any closed loop hydronic system, the Benchmark's modulating capability relates energ y input directly to fluctuating system loads. The Benchmark 1.5, with its 20:1 turn down ratio and condensing capability, provides extremely high efficiencies and makes it ideally suited for modern low temperature, as well as, conventional heating systems.
The Benchmark 1.5 operates at inputs ranging from 75, 000 BTU/hr. to 1,500,000 BTU/hr. The output of the boiler is a f unction of the unit’s firing rate and return water temperat ure. Output ranges from 74,250 BT U/hr. to 1,450,000 BTU/hr . , depending on operating conditions.
When installed and operated in accordance with this Instruction Manual, the Benchmark 1.5 Boiler complies with the NOx emission standards outlined in:
South Coast Air Quality Management District (SCAQMD), Rule 1146.2
Whether used in singular or modular arrangements, the Benchmark 1.5 offers the maximum flexibility in venting with minimum installation space requirements. The Benchmark 's advanced electronics are available in several selectable modes of operation offering the most efficient operating methods and energy manag em ent system integration.
For service or parts, contact your local sales represent at ive or AERCO I NTERNATIONAL.
NAME: ORGANIZATION: ADDRESS: TELEPHONE: INSTALLATION DATE: _____________________________________________
A
Page 8
Page 9
SAFETY PRECAUTIONS
CHAPTER 1 SAFETY PRECAUTIONS
1.1 WARNINGS & CAUTIONS
Installers and operating personnel MUST, at all times, observe all safety regulations. The following warnings and cautions are general and must be given the same attention as specific precautions included in these instructions. In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-
54). Where ASME CSD-1 is required by local jurisdiction, the installation must conform to CSD-1.
Where applicable, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CGA B149, and applicable Provincial regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
IMPORTANT
This Instruction Manual is an integral part of the product and must be maintained in legible condition. It must be given to the user by the installer and kept in a safe place for future reference.
WARNINGS!
MUST BE OBSERVED TO PREVENT SERIOUS INJURY.
WARNING!
BEFORE ATTEMPTING TO PER­FORM ANY MAINTENANCE ON THE UNIT, SHUT OFF ALL GAS AND ELECTRICAL INPUTS TO THE UNIT.
WARNING
DO NOT USE MATCHES, CANDLES, FLAMES, OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS.
WARNING!
FLUIDS UNDER PRESSURE MAY CAUSE INJURY TO PERSONNEL OR DAMAGE TO EQUIPMENT WHEN RELEASED. BE SURE TO SHUT OFF ALL INCOMING AND OUTGOING WATER SHUTOFF VALVES. CAREFULLY DECREASE ALL TRAPPED PRESSURES TO ZERO BEFORE PERFORMING MAINTENANCE.
WARNING!
ELECTRICAL VOLTAGES UP TO 120 VAC MAY BE USED IN THIS EQUIPMENT. THEREFORE THE COVER ON THE UNIT’S POWER BOX (LOCATED BEHIND THE FRONT PANEL DOOR) MUST BE INSTALLED AT ALL TIMES, EXCEPT DURING MAINTENANCE AND SERVICING.
CAUTIONS!
Must be observed to prevent equipment damage or loss of operating effectiveness.
CAUTION!
Many soaps used for gas pipe leak testing are corrosive to metals. The piping must clean water after leak checks have been completed.
be rinsed thoroughly with
WARNING!
THE EXHAUST VENT PIPE OF THE UNIT OPERATES UNDER A POSITIVE PRESSURE AND THERE­FORE MUST BE COMPLETELY SEALED TO PREVENT LEAKAGE OF COMBUSTION PRODUCTS INTO LIVING SPACES.
CAUTION!
DO NOT use this boiler if any part has been under water. Call a qualified service technician to inspect and replace any part that has been under water.
1-1
Page 10
SAFETY PRECAUTIONS
1.2 EMERGENCY SHUTDOWN
If overheating occurs or the gas supply fails to shut off, close the manual gas shutoff valve (Figure 1-1) located external to the unit.
IMPORTANT
The Installer must identify and indicate the location of the emergency shutdown manual gas valve to operating personnel.
1.3 PROLONGED SHUTDOWN
After prolonged shutdown, it is recommended that the startup procedures in Chapter 4 and the safety device test procedures in Chapter 6 of this manual be performed, to verify all system­operating parameters. If there is an emergency, turn off the electrical power supply to the AERCO boiler and close the manual gas valve located upstream the unit. The installer is to identify the emergency shut-off device.
Figure 1-1
Manual Gas Shutoff Valve
1-2
Page 11
INSTALLATION
CHAPTER 2 INSTALLATION
2.1 INTRODUCTION
This Chapter provides the descriptions and procedures necessary to unpack, inspect and install the AERCO Bench mark 1.5 Boiler. Brief descriptions are also pr ovided f or each avai lable mode of operation. Detailed procedures for implementing these modes are provided in Chapter 5.
2.2 RECEIVING THE UNIT
Each Benchmark 1.5 System is shipped as a single crated unit. The shipping weight is approximately 1551 pounds. The unit must be moved with the proper rigging equipment for safety and to avoid equipment dam age. The unit should be complete ly inspected for evidence of shipping damage and ship ment com pleteness at the time of receipt from the carrier and before the bill of lading is signed.
NOTE
AERCO is not responsible for lost or damaged freight.
Each unit has a Tip-N-Tell indicator on the outside of the crate. T his indic ates if the un it has been turned on its side during shipment. If the Tip-N-Tell indicat or is trip ped, do not s ign for the shipment. Note the information on the carrier’s paperwork and request a freight claim and inspection by a claims adjuster before proceeding. Any other visual damage to the packaging materials s hould also be made clear to the delivering carrier.
2.3 UNPACKING
Carefully unpack the unit taking care not to damage the unit enclosure when cutting away packaging materials
A close inspection of the unit s hould be made to ensure that there is no evidence of dam age not indicated by the T ip-N-Tell indicator. The f reight carrier should be notified immediately if any damage is detected.
The following accessories come standard with each unit and are either packed separately within the unit’s pack ing container or are fac tory installed on the boiler:
Pressure/Temperature Gauge
Spare Spark Igniter
Spare Flame Detector
ASME Pressure Relief Valve
Condensate Drain Trap
1-1/2” Gas Supply Shutoff Valve
When ordered, optional accessories may be packed separately, packed within the boiler shipping container, or may be installed on the boiler. Any standard or optional accessories shipped loose should b e identified and s tored in a safe place until ready for installation or use.
2.4 SITE PREPARATION.
Ensure that the site selected for installation of the Benchmark 1.5 Boiler includes:
Access to AC Input Power at 120 VAC, 1-
Phase, 60 Hz @ 20
Access to Natural Gas line at a minimum
pressure of 4 inches W.C.
2.4.1 Installation Clearances
The unit must be installed with the prescribed clearances for service as shown in Figure 2-1. The minimum AERCO, are listed below. However, if Local Building Codes require additional clearances, these codes shall supersede AERCO’s requirements. Minimum acceptable clearances required are:
Sides: 24 inches
Front : 24 inches
Rear: 30 inches
Top: 18 inches
All gas piping, water piping and el ec tric al c on du it or cable must be arranged so that they do not interfere with the removal of any panels, or inhibit service or maintenance of the unit.
clearance dimens ions , requir ed by
2-1
Page 12
INSTALLATION
Figure 2-1 Benchmark 1.5 Boiler Clearances
WARNING
KEEP THE UNIT AREA CLEAR AND FREE FROM ALL COMBUSTIBLE MATERIALS AND FLAMMABLE VAPORS OR LIQUIDS
.
CAUTION
While packaged in the shipping container, the boiler must be moved by pallet jack or forklift from the FRONT ONLY.
2.4.2 Setting the Unit
The unit must be installed on a 4 inch to 6 inch housekeeping pad to e nsure proper conde nsate drainage. If anchoring the unit, refer to the dimensional drawings in Appendix F for anchor locations. Two lifting t abs ar e provided a t the top of the heat exchanger as shown in Figure 2-2. USE THE TABS SHOWN IN FIGURE 2-2 TO LIFT AND MOVE THE UNIT . Remove the front top panel from the unit to prov ide access to the lifting tabs. Remove the four (4) lag screws securing the unit to the shipping skid. Lift the unit off the shipping sk id and position it on the 4 inch to 6 inch housekeeping concrete pad (required) in the desired location.
BLOWER
LIFTING
TAB
AIR/FUEL
VALVE
FRONT
LIFTING
Figure 2-2
Partial Top View Showing Lifting Tab
Locations
In multiple unit installations, it is important to plan the position of each unit in advance. Sufficient space for piping connections and future service/maintenance requirements must also be taken into cons ider ation. All pipin g m ust include ample provisions for expansion.
TAB
2-2
Page 13
If installing a Combina tion Control Panel (CCP) system, it is important to identify the Combination Mode B oilers in adv ance and plac e them in the proper physical location. Refer to Chapter 5 for inform ation on Combination Mode Boilers.
2.5 SUPPLY AND RETURN PIPING
The Benchmark 1.5 Boiler utilizes 3” 150# flanges for the water system supply and return piping connectio ns. The physical location of the supply and return p iping connections are on the rear of the unit as shown in Figure 2-3. Ref er to Appendix F, Drawing AP-A-832 for additional dimensional data.
INSTALLATION
Figure 2-4
Condensate Drain Connection Location
2.6.1 Exhaust Manifold Condensate
Drain
The exhaust manifold drain pipe connection shown in Figure 2-4, must be connected to a condensate drain trap external to th e unit. Refer to Figure 2-5 and install the trap as follows:
Figure 2-3
Supply and Return Locations
2.6 CONDENSATE DRAIN
The Benchmark 1.5 Boiler is designed to condense water vapor from the flue products. Therefore, the insta llation must have provisions for suitable condensate drainage or collection.
The drain pipe located on the exhaust manifold must be connected to a c ondensate trap which is packed separately within the unit’s shipping container.
1. Position the supplied condensate trap (part
no. 24060) on the floor at the rear of the unit.
2. Install 3/4” NPT nipples in the tapped inlet
and outlet of the condensate trap.
3. Attach a length of 1” I.D. hose between t he
exhaust manifold drain pipe and the inlet side of the condensate trap (Figure 2-5). Secure both ends of the hose with clamps.
4. Connect a second length of 1” I.D. h ose to
the outlet side of the condensate trap and route it to a nearby floor drain.
If a floor drain is not available, a condensate pump can be used to remove the condens ate to drain. The max imum condensate flow rate is 2 0 GPH. The condensate drain trap, associated fittings and drain lines must be removable for routine maintenance. Therefore, DO NOT hard pipe.
The procedure to install and connect the condensate drain is provided in paragraph 2.6.1.
2-3
Page 14
INSTALLATION
Figure 2-5
Condensate Trap Installation
2.7 GAS SUPPLY PIPING
The AERCO Benchmark 1.5 Gas Components and Supply Design Guide, GF-4030 must be consulted prior to des ignin g or installi ng an y gas supply piping.
A suitable piping compound, approved for use with natural gas, should be used. Any excess must be wiped off to prevent clogging of components.
To avoid unit damage whe n pres sur e tes ting gas piping, isolate the unit from the gas supply piping. At no time should the gas pressure applied to the unit exceed 2 psi. Leak test all external piping thoroughly using a soap and water solution or suitable equivalent. The gas piping used must meet all applicable codes.
2.7.1 Gas Supply Specifications.
The gas supply input specifications to the unit for Natural Gas are as follows:
The maximum static pressure to the unit must not exceed 2 psi. The minimum operating gas pressure for natural gas is 4 inches W.C. for both FM and IRI gas trains when the unit is firing at maximum input. The gas supply pressure to the unit must be of suff icient capacity to provide 1500 cfh while maintain ing the gas press ure at 4 inches W.C. for FM or IRI gas trains.
WARNING
NEVER USE MATCHES, CANDLES, FLAMES OR OTHER SOURCES OF IGNITION TO CHECK FOR GAS LEAKS
Many soaps used for gas pipe leak testing are corrosive to metals. There­fore, piping must be rinsed thoroughly with clean water after leak checks have been completed.
All gas piping m ust be arranged so that it does not interfere with removal of any covers, inhibit service/maintenance, or restrict access between the unit and walls, or another unit.
A 1-1/2 inch gas inlet connection is located on the rear of the unit as shown in Figure 2-3.
.
CAUTION
NOTE
2.7.2 Manual Gas Shutoff Valve
A manual shut-off valve must be installed in th e gas supply line upstream of the Boiler as shown in Figure 2-6. M aximum allowable gas pressure to the Boiler is 2 psi
NATURAL
GAS
SUPPLY
1-½” MANUAL
GAS SHUTOFF
VALVE
DIRT
TRAP
Prior to installation, all pipes should be de­burred and internally clear ed of any scale, m etal chips or other foreign particles. Do Not install any flexible connectors or unapproved gas fittings. Piping must be s upported from the floor, ceiling or walls onl y and must not be supported by the unit.
2-4
Figure 2-6
Manual Gas Shut-Off Valve Location
Page 15
INSTALLATION
2.7.3 IRI Gas Train Kit
The IRI gas train is an optional gas train configuration which is r e qui red i n s ome areas for code compliance or for insurance purposes. The IRI gas train is factor y pre-piped and wired. See Appendix F, Drawing AP- A-830 f or details.
2.8 AC ELECTRICAL POWER WIRING
The AERCO Benchmark 1.5 Electrical Power Wiring Guide, GF-40 60, must be co nsulted prior to connecting any AC power wiring to the unit. External AC power connect ions are made to the unit inside the Power Box on the front panel of the unit. Remove the front door of the unit to access the Power Box mounted directly above the Control Box. Loosen the four Power Box cover screws and remove cover to access the AC terminal connections inside the Power Box (Figure 2-7).
NOTE
All electrical conduit and hardware must be installed so that it does not interfere with the removal of any un it cover s, inh ibit service/maintenance, or prevent access between the unit and walls or another unit.
2.8.1 Electrical Power Requirements
The AERCO Benchmark 1.5 Boiler accepts 120 VAC, single-phase, 60 Hz @ 20 A. The Power Box contains a terminal block as shown in Figure 2-8. In addition, a wiring diagr am showing the required AC power connections is provided on the front cover of the Power Box.
Each Benchmark 1.5 Boil er must be connected to a dedicated electrical circuit. NO OTHER DEVICES SHOULD BE ON THE SAME ELECTRICAL CIRCUIT AS THE BENCHMARK BOILER. A means for disconnecting AC power from the unit (such as a ser vice switch) mus t be installed near th e unit for normal operation and maintenance. All electrical connections should be made in accordance with the National Electrical Code and/ or with any applicable local codes.
For electrical power wiring diagrams, see the AERCO Benchmark 1.5 Electrical Power W iring Guide, (GF-4060).
Figure 2-7
AC Input Terminal Block Location
Figure 2-8
AC Terminal Block Configurations
2.9 MODES OF OPERATION AND FIELD
CONTROL WIRING
The Benchmark 1.5 B oiler is available in severa l different modes of operation. W hile each unit is factory configured and wired for its intended mode, some additional field wiring may be required to complete th e installation. This wir ing is typically connected to the Input/Output (I/O) Box located on the lower por tion of the unit fr ont panel (Figure 2-9) behind the removable front door.
2-5
Page 16
INSTALLATION
To access the I/O Box terminal strips shown in Figure 2-10, loosen the four cover screws and remove the cover. All field wiring is installed from the rear of the panel by routing the wires through one of the four bushings provided.
Refer to the wiring diagram provided on the cover of the I/O Box (Figur e 2-10) when making all wiring connections.
In addition to the term inal strips s hown in Figure 2-9, the I/O Box also contains a pre-wired temperature transmitter which receives inlet air temperature sensor readings and transmits this signal to the variable frequency drive (VFD) contained in the Benchm ark 1.5 Boil er. T he VFD utilizes this input signal to adjust the rotation speed of the blower.
Brief descriptions of each mode of operation, and their wiring requirements, are provided in the following paragr aphs. Additional information concerning field wiring is prov ided in paragr aphs
2.9.1 through 2.9.9. Refer to Chapter 5 for detailed information on the available modes of operation.
Figure 2-9.
Input/Output (I/O) Box Location
Figure 2-10. I/O Box Terminal Strip
2-6
Page 17
INSTALLATION
2.9.1 Constant Setpoint Mode
The Constant Setpoi nt Mode is used when it is desired to have a fixed setpoint that does not deviate. No wiring connections, other than AC electrical power connections, are required for this mode. However, if desired, fault monitor ing or enable/disable in terlock wiring c an be utilized (see paragraphs 2.9.9.1 and 2.9.10).
2.9.2 Indoor/Outdoor Reset Mode
This mode of operation increases supply water temperature as outdoor te mperatures decrease. An outside air temperatur e sensor (AERCO Part No. 122790) is requ ired. The sensor MUST BE wired to the I/O Box wiring term inals (see Figure 2-10). Refer to paragraph 2.10.1 for additional information on outside air temperature sensor installation.
2.9.3 Boiler Management System Mode
When using an AERCO Boiler Management System (BMS), the field wiring is connected between the BMS Panel and each Boiler’s I/O Box terminal strip (Figure 2-10). Twisted shielded pair wire f rom 18 to 22 AWG must be utilized for the connections. The BMS Mode can utilize either pulse width modulation (PWM) signaling, or RS485 Modbu s s ignaling. F or PWM signaling, connections are made from the AERCO Boiler Management System to the B.M.S. (PWM) IN terminals on the I/O Box terminal strip. For RS485 Modus signaling, connections are made from the BMS to the RS485 COMM term inals on the I/O Box ter minal strip. Polarity m ust be maintain ed and the shie ld must be connected only at the AERCO BMS. The boiler end of the shi eld m ust be left f loating. For additional instructions, refer to Chapter 5, paragraph 5.6 in t his manual. Also, ref er to GF­108M, BMS -Operations Guide.
2.9.4 Remote Setpoint and Direct Drive Modes
The Benchmark 1.5 Boiler can accept several types of signal formats from an Energy Management System (EMS), Building Automation System (BAS) or other source, to control either the setpoint (Remote Setpoint Mode) or firing rate (Direct Drive Mode) of the Boiler. These formats are:
4 to 20 mA/1 to 5 VDC
0 to 20 mA/0 to 5 VDC
PWM – (Pulse W idth Modulated signal. See
para. 2.10.4)
Network (RS485 Modbus. See para. 2.10.7)
While it is possible to c ontrol a boiler or boilers using one of the previously described m odes of operation, it ma y not be the method best suited for the application. Prior to selecting one of these modes of operation, it is recommended that you consult with your local AERCO representative or the factory for the mode of operation that will work best with your application. For m ore information on wir ing the 4 to 20 mA / 1to 5VDC or the 0 to 20 m A / 0 to 5 VDC, see paragraph 2.9.3.
2.9.5 Combination Mode
With a Combination Mode unit, field wiring is between the unit’s I/O Box wiring terminals, the CCP (Combination Contr ol Panel), an d the BMS (Boiler Management System). The wiring must be accomplished using twisted-shielded pair wire from 18 to 22 AWG. Polarity must be maintained. For further instructions and wiring diagrams, refer to the GF-108 Boiler Management System Operations Guide and the CCP-1 data sheet.
2.10 I/O BOX CONNECTIONS
The types of input and output signals and devices to be connecte d to the I/O Box terminals shown in Figure 2-10 are described in the following paragraphs.
CAUTION
DO NOT make any connections to the I/O Box terminals labeled “NOT USED”. Attempting to do so may cause equipment damage.
2.10.1 OUTDOOR SENSOR IN
An outdoor air temperature sensor (AERCO Part No. 122790) will be required primarily for the Indoor/Outdoor reset m ode of operation. It can also be used with anoth er m ode if it is desired to use the outdoor sensor enable/disable feature. This feature allows the boiler to be enabled or disabled based on the outdoor air temperature.
The factory default for the outdoor sensor is DISABLED. To enable the sensor and/or select an enable/disable o utdoor temperature, see the Configuration menu in Chapter 3.
The outdoor sensor m ay be wired up t o 200 feet from the boiler. It is connected to the OUTDOOR SENSOR IN and SENSOR COMMON terminals in the I/O Box (see Figures 2-9 and 2-10). Wire the sensor using a twisted shielded pair wire fr om 18 to 22 AWG. There is no polarity to observe when terminating these wires. The shield is to be c onnected only to the
2-7
Page 18
INSTALLATION
terminals labeled SHIELD in the I/O Box. The sensor end of the shield must be left free and ungrounded.
When mounting the sensor, it must be located on the North side of the building where an average outside air temperature is expected. The sensor must be shield ed f r om dir ect sunli ght as well as impingement by the elements. If a shield is used, it must allow for free air circulation.
2.10.2 AUX SENSOR IN
The AUX SENSOR IN terminals can b e used to add an additional temperature sensor for monitoring purposes. This input is always enabled and is a view-only input that can be seen in the Operating Menu. The sensor must be wired to the AUX S ENSOR IN and SENSOR COMMON terminals and must be similar to AERCO BALCO wire se nsor Part No. 124 49. A resistance chart for this sensor is provided in Appendix C.
2.10.3 ANALOG IN
The ANALOG IN + and – terminals are used when an external signal is used to drive the firing rate (Direct Drive Mode) or change the setpoint (Remote Setpoint Mode) of the Boiler.
Either a 4 to 20 mA /1 to 5 VDC or a 0 t o 20 mA / 0 to 5 VDC signal may be used to vary the setpoint or firing rate. T he factory def ault setting is for 4 to 20 mA / 1 to 5 VDC, howev er this m a y be changed to 0 to 20 mA / 0 to 5 VDC usi ng the Configuration Menu described in Chapter 3. If voltage rather than current is selected as the drive signal, a DIP switch must be set on the CPU Board located inside the Control Box. Contact the AERCO factory for information on setting DIP switches.
All of the supplied signals must be floating (ungrounded) signals . Connectio ns bet ween the signal source and the Boiler’s I/O Box must be made using twiste d shiel ded pa ir wire fr om 18 to 22 AWG, such as Belden 9841 (see Figure 2-10). Polarity mu st be maintained. The shi eld must be connected only at the source end and must be left floating (not connected) at the Boiler’s I/O Box.
Regardless of whether volt age or curr ent is used for the drive signal, the y are linearly mapped to a 40°F to 240°F setpoint or a 0% to 100% f iring rate. No scaling for these signals is provided
2.10.4 B.M.S. (PWM) IN
These terminals are used to connect the AERCO Boiler Management System (BMS) to the unit. The BMS utilizes a 12 millisecond, ON/OFF duty cycle. This duty cycle is Pulse Width Modulated (PW M) to control f iring rate. A 0% firing rate = a 5% ON pulse and a 100% firing rate = a 95% ON pulse.
2.10.5 SHIELD
The SHIELD terminals are us ed to terminate any shields used on sensor wires connected to the unit. Only shields m ust be connected to these terminals.
2.10.6 mA OUT
These terminals provide a 4 to 20 mA output to the VFD to control the rotational speed of the blower. This function is enabled in the Configuration Menu (Chapter 3, Table 3.4).
2.10.7 RS-485 COMM
These terminals are used for RS-485 MODBUS serial communication between the unit and an external “Master” suc h as a Boiler Management System (BMS), Energy Management System (EMS), Building Automation System (BAS) or other suitable device.
2.10.8 EXHAUST SWITCH IN
These terminals permit an external exhaust switch to be connected to the exhaust manifold of the boiler. The exhaust switch should be a normally open t ype s witc h (such as AERCO Par t No. 123463) that closes (trips) at 500°F.
2.10.9 INTERLOCKS
The unit offers two interlock circuits for interfacing with Energy Management Systems and auxiliary equipment such as pumps or louvers. These interlock s are called the Rem ote Interlock and Delayed Interlock (Figure 2-10). The wiring terminals for these interlocks are located inside the I/O Box on the unit front panel. The I/O Box cover contains a wiring diagram which s hows th e ter m inal str ip locat ions for these interlocks (REMOTE INTL’K IN and DELAYED INTL’K IN). Both interlocks, described below, are fac tory wired in the closed position.
NOTE
Both the Delayed Interlock and Remote Interlock MUST be in the closed position to allow the unit to fire.
2-8
Page 19
INSTALLATION
2.10.9.1 REMOTE INTERLOCK IN
The remote interlock circuit is provided to remotely start (enable) and stop (disable) the Boiler, if desired. The circuit is labeled REMOTE INTL’K IN and is loc ate d i nsid e th e I/O Box on the front panel. The circuit is 24 VAC and is factory pre-wired in the c losed (jum pered) position.
2.10.9.2 DELAYED INTERLOCK IN
The delayed interlock is typically used in conjunction with the aux iliary relay described in paragraph 2.10. This interlock circuit is located in the purge section of the start string. It can be connected to the proving device (end switch, flow switch etc.) of an auxiliary piece of equipment started b y the Boiler’s a uxiliary rela y. The delayed interlock must be closed for the boiler to fire.
If the delayed interl ock is connec ted t o a pr oving device that requir es tim e to clos e (mak e), a tim e delay (Aux Start On Dly) that holds the start sequence of the boiler lon g enoug h for a proving switch to make can be progr amm ed. Should the proving switch not prove within the programm ed time frame, the boiler will shut down. The Aux Start On Dly can be progr ammed from 0 to 120 seconds. This option is locate in the Configuration Menu (Chapter 3, Table 3-4).
2.12 FLUE GAS VENT INSTALLATION
The minimum allowable vent diameter for a single Benchmark 1.5 Boiler is 6 inches.
The AERCO Benchmark Venting and Combustion Air Guide, GF-4050, must be consulted before any flue gas vent or inlet air venting is designed or installed. U/L listed, positive pressure, watertight vent materials as specified in AERCO’s GF-4050, must be used for safety and code com pliance. S ince the u nit is capable of dischar ging low temperature ex haust gases, horizontal sections of the flue vent system must be pitched back to the unit a minimum of 1/4 inch per foot to avoid condensate pooling and allow for proper drainage.
The combined pressure drop of vent and combustion air systems must not exceed 140 equivalent feet of 6 inc h ducting. Fittings as we ll as pipe lengths must be calculate d as part of the equivalent length.
For a natural draf t installation the draf t must not exceed ±0.25 inch W .C. These factors must be planned into the vent installation. If the maximum allowabl e equivalent lengt hs of piping are exceeded, the unit will not operate properly or reliably.
2.10.10 FAULT RELAY
The fault relay is a single pole double throw (SPDT) relay having a normally open and normally closed set of relay contacts that are rated for 5 amps at 12 0 VAC and 5 amps at 30 VDC. The relay energizes when any fault condition occurs and remains energized until the fault is cleared and the CLEAR button is depressed. The fault relay connections are shown in Figure 2-10.
2.11 AUXILIARY RELAY CONTACTS
Each Boiler is equipped with a single pole double throw (SPDT) relay that is energized when there is a demand for heat and de­energized after the dem and for heat is satisf ied. The relay is prov ided for the control of auxiliary equipment, such as pumps and louvers, or can be used as a Boiler status indictor (firing or n ot firing). Its contacts are r ated for 120 VAC @ 5 amps. Refer to Figure 2- 10 to locate the AUX RELAY terminals for wiring connections.
2.13 COMBUSTION AIR
The AERCO Benchmark Venting and Combustion Air Guide, GF-4050 MUST be consulted before any flue or com bustion supply air venting is designed or implemented. Combustion air supp ly is a direct r equirem ent of ANSI 223.1, NFPA-54, and local codes. These codes should be consulted before a permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons, or other chemicals that can become ha zardous when used in gas­fired equipment. Common sources of these compounds are swimming pools, degreasing compounds, plastic proc essing and refrigerants. Whenever the env ironment c ontains thes e t ypes of chemicals, combustion air must be supplied from a clean area outdoors for the protection and longevity of the equipment.
2-9
Page 20
INSTALLATION
The AERCO Benchm ark 1.5 Boiler is UL listed for 100% sealed combustion. It can also be installed using room air, provided there is an adequate supply. (See paragraph 2.13.3 for more information conc erning sealed com bustion air). If the sealed combustion air option is not being used, an inlet screen will be attached at the air inlet on the top of the unit
The more common methods of supplying combustion air are outlined below. For more information concerning combustion air, consult the AERCO Benchmark Venting and Combustion Air Guide, GF-4050.
2.13.1 Combustion Air From Outside the Building
Air supplied from outside the building must be provided through two perm anent openings. Each opening must have a free area of not less than one square inch for each 4000 BTU/H boiler input. The free area must take into account restrictions such as louvers and bird screens.
2.13.2 Combustion Air From Inside The
Building
When combustion air is provided f rom within the building, it must be supplied through two permanent openings in an interior wall. Each opening must have a free area of not less than one square inch per 1000 BTU/H of total boiler input. The free area must take into ac count any restrictions such as louvers.
2.13.3 Sealed Combustion
The AERCO Benchm ark 1.5 Boiler is UL listed for 100%-sealed combustion. For sealed combustion installations, the screen on the air inlet duct of the unit m ust be removed. T he inlet air ductwork must then be attached directly to the unit’s air inlet.
In a sealed combustion air application, the combustion air ducting pre ssure losses must be taken into account when calculating the total maximum allowable venting run. See the AERCO Benchmark Venting and Combustion Air Guide, GF-40 50. When using the bo iler in a sealed combustion air configuration, each unit must have a minimum 8 inch diameter connection at the unit.
2-10
Page 21
CONTROL PANEL OPERATING PROCEDURES
CHAPTER 3 CONTROL PANEL OPERATING PROCEDURES
3.1 INTRODUCTION
The information in this Chapter provides a guide to the operation of the Benchmark 1.5 Boiler using the Control Panel mounted on the front of the unit. It is imperative that the initial startup of this unit be performed by factory trained personnel. Operation prior to initial startup by factory trained personnel will void the equipment warranty. In addition, the following WARNINGS and CAUTIONS must be observed at all times.
CAUTION
All of the installation procedures in Chapter 2 must be completed before attempting to start the unit.
WARNING
ELECTRICAL VOLTAGES IN THIS SYSTEM MAY INCLUDE 460, 208 AND 24 VOLTS AC. IT MUST BE SERVICED ONLY BY FACTORY CERTIFIED SERVICE TECHNICIANS
WARNING
DO NOT ATTEMPT TO DRY FIRE THE BOILER. STARTING THE UNIT WITHOUT A FULL WATER LEVEL CAN SERIOUSLY DAMAGE THE UNIT AND MAY RESULT IN INJURY TO PERSONNEL OR PROPERTY DAMAGE. THIS SITUATION WILL VOID ANY WARRANTY.
3.2 CONTROL PANEL DESCRIPTIO N
The Benchmark 1.5 Control Panel shown in Figure 3-1 contains all of the controls, indicators and displays necessary to operate, adjust and troubleshoot the Benchmark 1.5 Boiler. These operating controls, indicators and displays are listed and described in Table 3-1. Additional information on these items are provided in the individual operating procedures provided in this Chapter.
Figure 3-1.
Control Panel Front View
3-1
Page 22
CONTROL PANEL OPERATING PROCEDURES
Table 3-1 Operating Controls, Indicators and Displays
ITEM
NO.
CONTROL, INDICATOR
OR DISPLAY
1 LED Status Indicators Four Status LEDs indicate the current operating status as
follows:
COMM
MANUAL
REMOTE
DEMAND
OUTLET
2
TEMPERATURE
Display
3 VFD Display Vacuum Fluorescent Display (VFD) consists of 2 lines each
Lights when RS-232 communication is occurring
Lights when the unit is being controlled using the front panel keypad.
Lights when the unit is being controlled by an external signal from an Energy Management System
Lights when there is a demand for heat.
3–Digit, 7–Segment LED display continuously displays the
outlet water temperature. The °F or °C LED next to the
display lights to indicate whether the displayed temperature is in degrees Fahrenheit or degrees Celsius.
capable of displaying up to 16 alphanumeric characters. The information displayed includes:
Startup Messages
Fault Messages
Operating Status Messages
FUNCTION
Menu Selection
RS-232 Port
4
FAULT Indicator Red FAULT LED indicator lights when a boiler alarm
5
CLEAR Key Turns off the FAULT indicator and clears the alarm message
6
READY Indicator
7
ON/OFF Switch
8
LOW WATER LEVEL
9
TEST/RESET Switches
Port permits a Laptop Computer or External Modem to be connected to the unit’s Control Panel.
condition occurs. An alarm message will appear in the VFD.
if the alarm is no longer valid. Lockout type alarms will be latched and cannot be cleared by simply pressing this key. Troubleshooting may be required to clear these types of alarms.
Lights ON/OFF switch is set to ON and all Pre-Purge
conditions have been satisfied.
Enables and disables boiler operation.
Allows operator to test operation of the water level monitor.
Pressing TEST opens the water level probe circuit and
simulates a Low Water Level alarm.
Pressing RESET resets the water level monitor circuit. Pressing the CLEAR key (item 6) resets the display.
3-2
Page 23
CONTROL PANEL OPERATING PROCEDURES
Table 3-1 Operating Controls, Indicators and Displays – Continued
ITEM
NO.
10 MENU Keypad Consists of 6 keys which provide the following functions for
CONTROL, INDICATOR
OR DISPLAY
the Control Panel Menus:
MENU
BACK
▲ (UP) Arrow When in one of the main menu categories (Figure 3-2),
▼ (DOWN) Arrow When in one of the main menu categories (Figure 3-2),
CHANGE
Steps through the main menu categories shown in Figure 3-
2. The Menu categories wrap around in the order shown.
Allows you to go back to the previous menu level without changing any information. Continuously pressing this key will bring you back to the default status display in the VFD. Also, this key allows you to go back to the top of a main menu category.
pressing the arrow key will select the displayed menu
category. If the CHANGE key was pressed and the menu
item is flashing, pressing the arrow key will increment the selected setting.
pressing this key will select the displayed menu category. If
the CHANGE key was pressed and the menu item is
flashing, pressing the arrow key will decrement the selected setting.
Permits a setting to be changed (edited). When the
CHANGE key is pressed, the displayed menu item will begin
to flash. Pressing the or arrow key when the item is flashing will increment or decrement the displayed setting.
FUNCTION
11
12
ENTER
AUTO/MAN Switch
FIRE RATE Bargraph
Saves the modified menu settings in memory. The display will stop flashing.
This switch toggles the boiler between the Automatic and
Manual modes of operation. When in the Manual (MAN)
mode, the front panel controls are enabled and the
MANUAL status LED lights. When in the Automatic (AUTO) mode, the MANUAL status
LED will be off and the front panel controls disabled.
20 segment red LED bargraph continuously shows the Fire Rate in 5% increments from 0 to 100%
3-3
Page 24
CONTROL PANEL OPERATING PROCEDURES
3.3 CONTROL PANEL MENUS
The Control Panel incorporates an extensive menu structure which permits the operator to set up, and configure the unit. The menu structure consists of four major menu categories as shown in Figure 3-2. Each of the menus shown, contain options which permit operating parameters to be viewed or changed. The menus are protected by a password to prevent unauthorized use.
Prior to entering the correct password, the options contained in the Operating, Setup, Configuration and Tuning Menu categories can be viewed. However, with the exception of Internal Setpoint Temperature (Configuration Menu), none of the viewable menu options can be changed.
Once the valid password (159) is entered, the options listed in the Setup. Configuration and Tuning Menus can be viewed and changed, if desired.
3.3.1 Menu Processing Procedure
Accessing and initiating each menu and option is accomplished using the Menu Keys shown in Figure 3-1. Therefore, it is imperative that you be thoroughly familiar with the following basic steps before attempting to perform specific menu procedures.
around after the first or last available option is reached.
6. To change the value or setting of a
displayed menu option, press the CHANGE
key. The displayed option will begin to flash. Press the or arrow key to scroll through the available menu option choices for the option to be changed. The menu option choices do not wrap around.
7. To select and store a changed menu item,
press the ENTER key.
1. The Control Panel will normally be in the Operating Menu and the VFD will display the current unit status. Pressing the or arrow key will display the other available data items in the Operating Menu.
2. Press the MENU key. The display will show
the Setup Menu, which is the next menu category shown in Figure 3-2. This menu contains the Password option which must be entered if other menu options will be changed.
3. Continue pressing the MENU key until the
desired menu is displayed.
4. With the desired menu displayed, press the or arrow key. The first option in the selected menu will be displayed.
5. Continue to press the or arrow key until the desired menu option is displayed. Pressing the arrow key will display the available menu options in the Top-Down sequence. Pressing the arrow key will display the options in the Bottom-Up sequence. The menu options will wrap-
Figure 3-2. Menu Structure
NOTE
The following paragraphs provide brief descriptions of the options contained in each menu. Refer to Appendix A for detailed descriptions of each menu option. Refer to Appendix B for listings and descriptions of displayed startup, status and error messages.
3-4
Page 25
CONTROL PANEL OPERATING PROCEDURES
3.4 OPERATING M ENU
The Operating Menu displays a number of key operating parameters for the unit as listed in Table 3-2. This menu is “Read-Only” and does not allow personnel to change or adjust any displayed items. Since this menu is “Read-Only”, it can be viewed at any time without entering a password. Pressing the arrow key to display the menu items in the order listed (Top-Down). Pressing the arrow key will display the menu items in reverse order (Bottom-Up).
3.5 SETUP MENU
The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is required to change the menu options. To prevent unauthorized use, the password will
Table 3-2. Operating Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Status Message
time-out after 1 hour. Therefore, the correct password must be reentered when required. In addition to permitting password entries, the Setup Menu is also used to enter date and time, units of temperature measurements and entries required for external communication and control of the unit via the RS-232 port. A view-only software version display is also provided to indicate the current Control Box software version.
NOTE
The Outdoor Temp display item shown with an asterisk in Table 3-2 will not be displayed unless the Outdoor Sensor function has been enabled in the Configuration Menu (Table 3-4).
Active Setpoint 40°F 240°F
Aux Temp 30°F 245°F
Outdoor Temp* -70°F 130°F
Fire Rate In 0% Max Fire Rate
Flame Strength 0% 100%
Run Cycles 0 999,999
Run Hours 0 999,999
Fault Log 0 9 0
Table 3-3. Setup Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Passsword 0 9999 0
Language English English
Time 12:00 am 11:59 pm
Date 01/01/00 12/31/99
Unit of Temp Fahrenheit or Celsius Fahrenheit
Comm Address 0 127 0
Baud Rate 2400, 4800, 9600, 19.2K 9600
Software Ver 0.00 Ver 9.99
3-5
Page 26
CONTROL PANEL OPERATING PROCEDURES
3.6 CONFIGURATION MENU
The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt) temperature regardless of whether the valid password has been entered. Setpt is required for operation in the Constant Setpoint mode. The remaining options in this menu require the valid password to be entered, prior to changing existing entries. This menu contains a number of other configuration settings which may or may not be displayed, depending on the current operating mode setting.
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Internal Setpt Lo Temp Limit Hi Temp Limit 130°F
Unit Type Boiler or Water Heater Boiler
Unit Size 0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
2.5 MBTU, 3.0 MBTU
Boiler Mode Constant Setpoint,
Remote Setpoint,
Combination
Outdoor Reset
NOTE
The Configuration Menu settings shown in Table 3-4 are Factory-Set in accordance with the requirements specified for each individual order. Therefore, under normal operating conditions, no changes will be required.
1.0 MBTU
Constant
Setpoint
Direct Drive
Remote Signal (If Mode = Remote Setpoint, Direct Drive or Combination)
Bldg Ref Temp (If Mode = Outdoor Reset)
Reset Ratio (If Mode = Outdoor Reset)
Outdoor Sensor Enabled or Disabled Disabled
System Start Tmp (If Outdoor Sensor = Enabled)
Setpt Lo Limit 40°F Setpt Hi Limit 60°F
Setpt Hi Limit Setpt Lo Limit 220°F 200°F
Temp Hi Limit 40°F 240°F 210°F
Max Fire Rate 40% 100% 100%
Pump Delay Timer 0 min. 30 min. 0 min.
Aux Start On Dly 0 sec. 120 sec. 0 sec.
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
40°F 230°F 70°F
0.1 9.9 1.2
30°F 100°F 60°F
4 – 20 mA,
1-5V
3-6
Page 27
CONTROL PANEL OPERATING PROCEDURES
Table 3-4. Configuration Menu - Continued
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Failsafe Mode Shutdown or Constant Setpt Shutdown
*mA Output
(See CAUTION)
Low Fire Timer 2 sec. 120 sec. 2 sec.
Setpt Limiting Enabled or Disabled Disabled
Setpt Limit Band 0°F 10°F 5°F
*CAUTION: DO NOT CHANGE mA Output Menu Item from its Default setting.
Setpoint, Outlet Temp,
Fire Rate Out, Off
*Fire Rate
Out
3.7 TUNING MENU
The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change these menu entries unless specifically requested to do so by Factory-Trained personnel.
Table 3-5. Tuning Menu
Available Choices or Limits
Menu Item Display Minimum Maximum Default
Prop Band 1°F 120°F 70°F
Integral Gain 0.00 2.00 1.00
Derivative Time 0.0 min 2.00 min 0.00 min
Reset Defaults? Yes
No
Are You Sure?
No
3.8 START SEQUENCE
When the Control Box ON/OFF switch is set to
the ON position, it checks all pre-purge safety switches to ensure they are closed. These switches include:
Safety Shut-Off Valve Proof of Closure
(POC) switch
Low Water Level switch
High Water Temperature switch
High Gas Pressure switch
Low Gas Pressure switch
Blower Proof switch
If all of the above switches are closed, the
READY light above the ON/OFF switch will light
and the unit will be in the Standby mode.
When there is a demand for heat, the following events will occur:
NOTE
If any of the Pre-Purge safety device switches are open, the appropriate fault message will be displayed. Also, the appropriate fault messages will be displayed throughout the start sequence, if the required conditions are not observed.
1. The DEMAND LED status indicator will light.
2. The unit checks to ensure that the Proof of Closure (POC) switch in the downstream Safety Shut-Off Valve (SSOV) is closed. See Figure 3-3 for SSOV locations.
3-7
Page 28
CONTROL PANEL OPERATING PROCEDURES
STEPPER
Figure 3-3.
SSOV Locations
MOTOR
DIAL (DETAIL “A”)
100
3. With all required safety device switches closed, a purge cycle will be initiated and the following events will occur:
(a) The Blower relay energizes and turns
on blower.
(b) The Air/Fuel Valve rotates to the full-
open purge position and closes purge position switch. The dial on the Air/Fuel Valve (Figure 3-4) will read 100 to indicate that it is full-open (100%).
(c) The FIRE RATE bargraph will show
100%.
4. Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display will
show Purging and indicate the elapsed time
of the purge cycle in seconds. The normal (default) time for the purge cycle is 7 seconds.
5. Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the following events occur:
(a) The Air/Fuel Valve rotates to the low-
fire ignition position and closes the ignition switch. The dial on the Air/Fuel Valve (Figure 3-6) will read between 25 and 35 to indicate that the valve is in the low-fire position.
(b) The igniter relay is activated and
provides ignition spark.
(c) The gas Safety Shut-Off Valve (SSOV)
is energized (opened) allowing gas to flow into the Air/Fuel Valve.
DETAIL “A”
Figure 3-4.
Air/Fuel Valve In Purge Position
Figure 3-5.
Blower Proof Switch
6. Up to 7 seconds will be allowed for ignition to be detected. The igniter relay will be turned off one second after flame is detected.
7. After 2 seconds of continuous flame, Flame Proven will be displayed and the flame
strength will be indicated. After 5 seconds, the current date and time will be displayed in place of the flame strength.
3-8
Page 29
CONTROL PANEL OPERATING PROCEDURES
8. With the unit firing properly, it will be controlled by the temperature controller
circuitry. The boiler’s FIRE RATE will be
continuously displayed on the front panel bargraph.
Once the demand for heat has been satisfied, the Control Box will turn off the dual SSOV gas valves. The blower relay will be deactivated and
the Air/Fuel Valve will be closed. Standby will
be displayed.
DIAL (DETAIL “A”)
3.9 START/STOP LEVELS
The start and stop levels are the fire rate percentages that start and stop the unit, based on load. These levels are Factory preset as follows:
Start Level: 20%
Stop Level: 16%
Normally, these settings should not require adjustment.
Note that the energy input of the boiler is not linearly related to the fire rate percentage (Air/Fuel Valve position). Refer to Table 3-6 on the following page for the relationship between the energy input and fire rate percentage for a unit running on natural gas.
STEPPER
MOTOR
5
2
DETAIL “A”
Figure 3-6.
Air/Fuel Valve In Ignition
3-9
Page 30
CONTROL PANEL OPERATING PROCEDURES
Table 3-6.
Relationship Between Air/Fuel Valve Position and Energy Input For Unit Running On Natural Gas
Fire Rate,
Air/Fuel Valve
Position
(% Open)
0% 0 0
10% 0 0
16 %
(Stop Level)
20% 157,000 10%
30% 310,000 21%
40% 534,000 36%
50% 783,000 52%
60% 970,000 65%
70% 1,140,000 76%
80% 1,240,000 83%
90% 1,370,000 91%
100% 1,500,000 100%
Energy Input
(BTU/Hr)
75,000 5.0%
Boiler Energy Input (% of Full Capacity)
3-10
Page 31
CHAPTER 4 INITIAL START-UP
INITIAL START-UP
4.1 INITIAL START-UP REQUIREMENTS
The requirements for the initial start-up of the Benchmark 1.5 Boiler consists of the following:
Complete installation
Perform combustion calibration
Set proper controls and limits
Set up mode of operation (see Chapter 5)
Test safety devices (see Chapter 6)
Installation should be fully completed before performing initial start-up; and the start-up must be complete prior to putting the unit into service. Starting a unit without the proper piping, venting, or electrical systems can be dangerous and may void the product warranty. The following start-up instructions should be followed precisely in order to operate the unit safely and at a high thermal efficiency, with low flue gas emissions.
Initial unit start-up is to be performed ONLY by AERCO factory trained start-up and service personnel. After following the steps in this chapter, it will be necessary to perform the Mode of Operation settings in Chapter 5, and the Safety Device Testing procedures in Chapter 6 to complete the initial unit start-up.
An AERCO Gas Fired Startup Sheet, included with each Benchmark Boiler, must be completed for each unit for warranty validation and a copy must be returned promptly to AERCO at:
AERCO International, Inc.
159 Paris Ave. Northvale, NJ 07647
CAUTION
All applicable installation procedures in Chapter 2 must be completed before attempting to start the unit.
4.2 TOOLS AND INSTRUMENTATION FOR COMBUSTION CALIBRATION
To properly perform combustion calibration, the proper instruments and tools must be used and correctly attached to the unit. The following paragraphs outline the necessary tools and instrumentation as well as their installation.
4.2.1 Required Tools & Instrumentation
The following tools and instrumentation are necessary to perform combustion calibration of the unit:
Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and Nitrogen Oxide (NOx) resolution to 1PPM.
16 inch W.C. manometer or equivalent gauge and plastic tubing.
1/8 inch NPT-to-barbed fittings for use with gas supply manometer or gauge.
Small and large flat blade screwdrivers.
Tube of silicone adhesive
4.2.2 Installing Gas Supply Manometer
The gas supply manometer is installed in the gas train as follows:
1. Close the main manual gas supply shut-off valve upstream of the unit.
WARNING
DO NOT ATTEMPT TO DRY FIRE THE BOILER. STARTING THE UNIT WITHOUT A FULL WATER LEVEL CAN SERIOUSLY DAMAGE THE UNIT AND MAY RESULT IN INJURY TO PERSONNEL OR PROPERTY DAMAGE. THIS SITUATION WILL VOID ANY WARRANTY.
2. Remove the front door and left side panels from the boiler to access the gas train components.
3. Remove the 1/8 inch NPT pipe plug from the leak detection ball valve on the downstream side of the Safety Shut Off Valve (SSOV) No. 1 as shown in Figure 4-1.
4. Install a NPT-to-barbed fitting into the tapped plug port.
4-1
Page 32
INITIAL START-UP
5. Attach one end of the plastic tubing to the barbed fitting and the other end to the 16 inch W.C. manometer.
Figure 4-1.
1/8 Inch Gas Plug Location
4.2.3 Accessing the Vent Probe Port
The unit contains NPT plug on the exhaust manifold at the rear of the unit as shown in Figure 4-2. Prepare the port for the combustion analyzer probe as follows:
1. Remove the plug from the probe port on the
right side of the exhaust manifold.
left or
2. If necessary, adjust the stop on the combustion analyzer probe so that it will extend mid-way into the flue gas flow. DO NOT install the probe at this time.
4.3 NATURAL GAS COMBUSTION CALIBRATION
The Benchmark 1.5LN Boiler is combustion calibrated at the factory prior to shipping. However, recalibration as part of initial start-up is necessary due to changes in the local altitude, gas BTU content, gas supply piping and supply regulators. Factory Test Data sheets are shipped with each unit. These sheets must be filled out and returned to AERCO for proper Warranty Validation.
It is important to perform the following procedure as outlined. This will keep readjustments to a minimum and provide optimum performance.
1. Open the water supply and return valves to the unit and ensure that the system pumps are running.
2. Open the natural gas supply valve(s) to the unit.
3. Set the control panel ON/OFF switch to the OFF position.
4. Turn on external AC power to the unit. The
display will show LOSS OF POWER and the
time and date.
5. Set the unit to the Manual Mode by pressing
the AUTO/MAN key. A flashing Manual Fire Rate message will be displayed with the present rate in %. Also, the MANUAL LED
will light.
6. Adjust the fire rate to 0% by pressing the arrow key.
7. Ensure that the leak detection ball valve down-stream of SSOV No. 2 is open.
8. Set the ON/OFF switch to the ON position.
9. Change the fire rate to 29% using the arrow key. The unit should begin its start sequence and fire.
4-2
Figure 4.2
Analyzer Probe Hole Location
10. Next, verify that the gas pressure downstream of the SSOV is 3” W.C. for both FM and IRI gas trains. If gas pressure adjustment is required, remove the brass hex nut on the downstream SSOV actuator (IRI gas train) containing the gas pressure regulator (Figure 4-3). Make gas regulator adjustments using a flat-tip screwdriver to obtain 3” W.C.
Page 33
AIR/FUEL
VALVE
INITIAL START-UP
AIR INLET
Figure 4-3
Regulator Adjustment Screw Location
11. Raise the firing rate to 100% and verify that the gas pressure downstream of the SSOV remains at 3” W.C. Readjust pressure if necessary.
12. With the firing rate at 100%, insert the combustion analyzer probe into the flue probe opening and allow enough time for the combustion analyzer to settle.
13. Compare the measured oxygen level to the oxygen range for the inlet air temperature shown in Table 4-1. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-1
Combustion Oxygen Levels for a 100%
Firing Rate
Inlet Air
Temp
>100°F 4.8 % <100 ppm <30 ppm
90°F 5.0 % <100 ppm <30 ppm 80°F 5.2 % <100 ppm <30 ppm
<70°F 5.3 % <100 ppm <30 ppm
14. If necessary, adjust the iris air damper shown in Figure 4-4 until the oxygen level is within the range specified in Table 4-1.
Oxygen %
± 0.2
Carbon
Monoxide NOx
A
USE 1/2" WRENCH TO INCREASE (CW) OR DECREASE (CCW) INLET AIR
IRIS ADJUSTMENT
VIEW A - A
A
IRIS AIR
DAMPER
FRONT
Figure 4-4
Iris Air Damper Location/Adjustment
NOTE
The remaining combustion calibration steps utilize the Variable Frequency Drive (VFD) located behind the front door of the unit. The VFD controls will be used to adjust the oxygen level (%) at firing rates of 80%, 60%, 45%, 30% and 12% as described in the following steps. These steps assume that the inlet air temperature is within the range of 50°F to 100°F.
16. Locate the Variable Frequency Drive (VFD) behind the front door of the unit. Refer to the VFD operating controls shown in Figure 4-5.
15. Once the oxygen level is within the specified range at 100%, lower the firing rate to 80%.
4-3
Page 34
INITIAL START-UP
Figure 4-5
VFD Controls and Displays
17. Press the M (Menu) programming key on
the VFD.
18. Using the up () arrow key, select VFD
parameter 65. The selected parameter will
appear in the left part of the display and the voltage frequency (Hz) will appear in the right part of the display. This is thee frequency of the AC voltage sent to the blower.
19. With the selected VFD parameter display
flashing, press the M key. Code will be
displayed, requesting the valid code to be
entered. Enter code 59 using the arrow
keys.
20. Press the M key again and observe the
frequency shown in the right part of the display. The oxygen level at the 80% firing rate should be as shown in the following tabular listing. Also, ensure that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Combustion Oxygen Level at
80% Firing Rate
Oxygen %
± 0.2
6.0 % <100 ppm <30 ppm
21. If the oxygen level is not within the specified range, adjust the level using the up () and down () arrow keys on the VFD. Using the up () arrow key will increase oxygen level and the down () arrow key will decrease the oxygen level.
Carbon
Monoxide
NOx
22. Once the oxygen level is within the specified range at 80%, lower the firing rate to 60%
and select VFD parameter 64. The oxygen
level at the 60% firing rate should be as shown below.
Combustion Oxygen Level at
60% Firing Rate
Oxygen %
± 0.2
6.3 % <50 ppm <30 ppm
23. Adjust the oxygen level as necessary to obtain the required reading at the 60% firing rate.
24. Next, set the firing rate to 45% and select
VFD parameter 63. The oxygen level at the
45% firing rate should be as shown below.
Carbon
Monoxide
NOx
Combustion Oxygen Level at
45% Firing Rate
Oxygen %
± 0.2
7.0 % <50 ppm <30 ppm
25. Adjust the oxygen level as necessary to obtain the required reading at the 45% firing rate.
26. Next, set the firing rate to 30% and select
VFD parameter 62. The oxygen level at the
30% firing rate should be as follows:
Carbon
Monoxide
NOx
Combustion Oxygen Level at
30% Firing Rate
Oxygen %
± 0.2
7.0 % <50 ppm <30 ppm
27. Adjust the oxygen level as necessary to obtain the required reading at the 30% firing rate.
28. Finally, reduce the firing rate to 16% and
select VFD parameter 61. The oxygen level
at the 16% firing rate should be as shown in the following tabular listing:
Carbon
Monoxide
NOx
NOTE
At a 16% fire rate, if parameter 61 is
above 326, the VFD software will use 326 by default. 326 corresponds to a voltage of 3.26 volts.
4-4
Page 35
INITIAL START-UP
Combustion Oxygen Level at
16% Firing Rate
Oxygen %
± 0.2
8.0 % <50 ppm <30 ppm
29. Adjust the oxygen level as necessary to obtain the required reading at the 16% firing rate.
30. This completes the Natural Gas combustion calibration procedures.
Carbon
Monoxide
NOx
4.4 UNIT REASSEMBLY
Once the combustion calibration adjustments are properly set, the unit can be reassembled for service operation.
1. Set the ON/OFF switch in the OFF position.
2. Disconnect AC power from the unit.
3. Shut off the gas supply to the unit.
4. Remove the manometer and barbed fittings and reinstall the NPT plug using a suitable pipe thread compound.
5. Remove the combustion analyzer probe from the vent hole. Replace the NPT plug in the vent hole using a suitable pipe joint compound.
6. Replace the unit’s side panels and front door.
4.5 OVER- TEMPER ATURE LIMIT
SWITCHES
The unit contains both automatic and manual reset over-temperature limit switches. These switches are mounted on a plate next to the VFD as shown in Figure 4-6. The switches can be accessed by opening the front panel door of the unit. The manual reset switch is not adjustable and is permanently fixed at 210°F. This switch will shut down and lock out the boiler if the water temperature exceeds 210°F. Following an over-temperature condition, it must be manually reset by pressing the RESET button before the boiler can be restarted. The automatic reset over-temperature switch is adjustable and allows the boiler to restart, once the temperature drops below its temperature setting. Set the automatic over-temperature switch to the desired setting.
Figure 4-6
Over Temperature Limit Switch
Locations
4-5
Page 36
Page 37
MODE OF OPERATION
CHAPTER 5 MODE OF OPERATION
5.1 INTRODUCTION
The Benchmark 1.5 Boiler is capable of being operated in any one of six different modes. The following paragraphs in this Chapter provide descriptions of each of these operating modes. Each Benchmark 1.5 Boiler is shipped from the factory tested and configured for the ordered mode of operation. All temperature related parameters are at their factory default values which work well in most applications. However, it may be necessary to change certain parameters to customize the unit to the system environment. A complete listing and descriptions of the temperature related parameters are included in Appendix A. Factory defaults are listed in Appendix E. After reading this chapter, parameters can be customized to suit the needs of the specific application.
5.2 INDOOR/OUTDOOR RESET MODE
This mode of operation is based on outside air temperatures. As the outside air temperature decreases, the supply header temperature will increase and vice versa. For this mode, it is necessary to install an outside air sensor as well as select a building reference temperature and a reset ratio.
5.2.1 Reset Ratio
Reset ratio is an adjustable number from 0.1 to
9.9. Once adjusted, the supply header
temperature will increase by that number for each degree that the outside air temperature decreases. For instance, if a reset ratio of 1.6 is used, for each degree that outside air temperature decreases the supply header temperature will increase by 1.6 degrees.
5.2.3 Outdoor Air Temperature Sensor Installation
The outdoor air temperature sensor must be mounted on the North side of the building in an area where the average outside air temperature is expected. The sensor must be shielded from the sun's direct rays, as well as direct impingement by the elements. If a cover or shield is used, it must allow free air circulation. The sensor may be mounted up to two hundred feet from the unit. Sensor connections are made at the Input/Output (I/O) Box on the front of the Benchmark 1.5 Boiler. Connections are made at the terminals labeled OUTDOOR SENSOR IN and SENSOR COMMON inside the I/O Box. Use shielded 18 to 22 AWG wire for connections. A wiring diagram is provided on the cover of the I/O Box. Refer to Chapter 2, paragraph 2.9.1 for additional wiring information.
5.2.4 Indoor/ Outdoor Startup
Startup in the Indoor/Outdoor Reset Mode is accomplished as follows:
1. Refer to the Indoor/Outdoor reset ratio charts in Appendix D.
2. Choose the chart corresponding to the desired Building Reference Temperature.
3. Go down the left column of the chart to the coldest design outdoor air temperature expected in your area.
NOTE
A design engineer typically provides design outdoor air temperature and
header temperature data
supply
5.2.2 Building Reference Temperature
This is a temperature from 40°F to 230°F. Once selected, it is the temperature that the system references to begin increasing its temperature. For instance, if a reset ratio of 1.6 is used, and we select a building reference temperature of 70°F, then at an outside temperature of 69°F, the supply header temperature will increase by
1.6° to 71.6°F.
4. Once the design outdoor air temperature is chosen, go across the chart to the desired supply header temperature for the design temperature chosen in step 3.
5. Next, go up that column to the Reset Ratio row to find the corresponding reset ratio.
6. Access the Configuration Menu and scroll through it until the display shows Bldg Ref Temp. (Building Reference Temperature).
5-1
Page 38
MODE OF OPERATION
7. Press the CHANGE key. The display will begin to flash.
8. Use the ▲ and ▼ arrow keys to select the desired Building Reference Temperature.
9. Press ENTER to save any changes.
10. Next, scroll through the Configuration Menu until the display shows Reset Ratio.
11. Press the CHANGE key. The display will begin to flash.
12. Use the ▲ and ▼ arrow keys to select the Reset Ratio determined in step 5.
13. Press ENTER to save the change.
Refer to paragraph 3.3 for detailed instructions on menu changing.
5.3 CONSTANT SETPOINT MODE
The Constant Setpoint mode is used when a fixed header temperature is desired. Common uses of this mode of operation include water source heat pump loops, and indirect heat exchangers for potable hot water systems or processes.
5.4 REMOTE SETPOINT MODES
The unit’s setpoint can be remotely controlled by an Energy Management System (EMS) or Building Automation System (BAS). The Remote Setpoint can be driven by a current or voltage signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Remote Setpoint mode is 4 - 20 mA/1 - 5 Vdc. With this setting, a 4 to 20 mA/1 to 5 Vdc signal, sent by an EMS or BAS, is used to change the unit's setpoint. The 4 mA/1V signal is equal to a 40°F setpoint while a 20 mA /5V signal is equal to a 240°F setpoint. When a 0 to 20 mA/0 to 5 Vdc signal is used, 0 mA is equal to a 40°F setpoint.
In addition to the current and voltage signals described above, the Remote Setpoint mode can also driven by a RS485 Modbus Network signal from an EMS or BAS.
The Remote Setpoint modes of operation can be used to drive single as well as multiple units.
No external sensors are required to operate in this mode. While it is necessary to set the desired setpoint temperature, it is not necessary to change any other temperature-related functions. The unit is factory preset with settings that work well in most applications. Prior to changing any temperature-related parameters, other than the setpoint, it is suggested that an AERCO representative be contacted. For descriptions of temperature-related functions and their factory defaults, see Appendices A and E.
5.3.1 Setting the Setpoint
The setpoint temperature of the unit is adjustable from 40°F to 240°F. To set the unit for operation in the Constant Setpoint Mode, the following menu settings must be made in the Configuration Menu:
MENU OPTION SETTING
Boiler Mode Constant Setpoint
Internal Setpt Select desired setpoint
using and arrow keys (40°F to 240°F)
NOTE
If a voltage, rather than current signal is used to control the remote setpoint, a DIP switch adjustment must be made on the
PMC Board located in the Control Panel
Assembly. Contact your local AERCO representative for details.
In order to enable the Remote Setpoint Mode, the following menu setting must be made in the Configuration Menu:
MENU OPTION SETTING
Boiler Mode Remote Setpoint
Remote Signal 4-20mA/1-5V,
0-20mA/0-5V, or
Network
Refer to paragraph 3.3 for detailed instructions on changing menu options.
Refer to paragraph 3.3 for detailed instructions on changing menu options.
5-2
Page 39
MODE OF OPERATION
If the Network setting is selected for RS485 Modbus operation, a valid Comm Address must be entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional information.
While it is possible to change the settings of temperature related functions, the unit is factory preset with settings that work well in most applications. It is suggested that an AERCO representative be contacted, prior to changing any temperature related function settings. For descriptions of temperature-related functions and their factory defaults, refer to Appendices A and E.
5.4.1 Remote Setpoint Field Wiring
The only wiring connections necessary for the Remote Setpoint mode are connection of the remote signal leads from the source to the unit’s I/O Box. The I/O Box is located on the front panel of the Benchmark 1.5 Boiler. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the connections are made at the ANALOG IN terminals in the I/O Box. For a Network setting, the connections are made at the RS-485 COMM terminals in the I/O Box. The signal must be floating, (ungrounded) at the I/O Box and the wire used must be a two wire shielded pair from 18 to 22 AWG. Polarity must be observed. The source end of the shield must be connected at the source. When driving multiple units, each unit’s wiring must conform to the above.
5.4.2 Remote Setpoint Startup
Since this mode of operation is factory preset and the setpoint is being externally controlled, no startup instructions are necessary. In this mode, the REMOTE LED will light when the external signal is present.
To operate the unit in the Manual mode, press the AUTO/MAN switch. The REMOTE LED will go off and the MANUAL LED will light.
To change back to the Remote Setpoint mode, simply press the AUTO/MAN switch. The REMOTE LED will again light and the MANUAL LED will go off.
5.5 DIRECT DRIVE MODES
The unit’s fire rate can be changed by a remote signal which is typically sent from an Energy Management System (EMS) or from a Building Automation System (BAS). The Direct Drive mode can be driven by a current or voltage signal within the following ranges:
4-20 mA/1-5 Vdc
0-20 mA/0-5 Vdc
The factory default setting for the Direct Drive mode is 4-20 mA/1-5 Vdc. With this setting, a 4 to 20 mA signal, sent by an EMS or BAS is used to change the unit’s fire rate from 0% to 100%. A 4 mA/1V signal is equal to a 0% fire rate, while a 20 mA /5V signal is equal to a 100% fire rate. When a 0-20 mA/0-5 Vdc signal is used, zero is equal to a 0% fire rate.
In addition to the current and voltage signals described above, the Direct Drive mode can also driven by a RS485 Modbus Network signal from an EMS or BAS.
When in a Direct Drive mode, the unit is a slave to the EMS or BAS and does not have a role in temperature control. Direct Drive can be used to drive single, or multiple units.
NOTE
If a voltage, rather than current signal is used to control the remote setpoint, a DIP switch adjustment must be made on the
PMC Board located in the Control Box
Assembly. Contact your local AERCO representative for details.
To enable the Direct Drive Mode, the following menu setting must be made in the Configuration Menu:
MENU OPTION SETTING
Boiler Mode Direct Drive
Remote Signal 4-20mA/1-5V,
0-20mA/0-5V, or
Network
Refer to paragraph 3.3 for instructions on changing menu options.
5-3
Page 40
MODE OF OPERATION
If the Network setting is selected for RS485 Modbus operation, a valid Comm Address must be entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional information.
5.5.1 Direct Drive Field Wiring
The only wiring connections necessary for Direct Drive mode are connection of the remote signal leads from the source to the unit’s I/O Box. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the connections are made at the ANALOG IN terminals in the I/O Box. For a Network setting, the connections are made at the RS-485 COMM terminals in the I/O Box. The signal must be floating, (ungrounded) at the I/O Box and the wire used must be a two wire shielded pair from 18 to 22 AWG. Polarity must be observed. The source end of the shield must be connected at the source. When driving multiple units, each unit’s wiring must conform to the above.
5.5.2 Direct Drive Startup
Since this mode of operation is factory preset and the fire rate is being externally controlled, no startup instructions are necessary. In this mode, the REMOTE LED will light when the signal is present.
To operate the unit in manual mode, press the AUTO/MAN switch. The REMOTE LED will go off and the MANUAL LED will light.
To change back to the Direct Drive mode, simply press the AUTO/MAN switch. The REMOTE LED will again light and the MANUAL LED will go off.
5.6 BOILER MANAGEMENT SYSTEM
(BMS)
and operation, see GF-108M (BMS Model 168) and GF-124 (BMS II Model 5R5-384), BMS Operations Guides. For operation via an RS485 Modbus network, refer to Modbus Communication Manual GF-114.
To enable the BMS Mode, the following menu settings must be made in the Configuration Menu:
MENU OPTION SETTING
Boiler Mode Direct Drive
Remote Signal BMS (PWM Input)
or Network (RS485)
Refer to paragraph 3.3 for instructions on changing menu options.
5.6.1 BMS External Field Wiring
Wiring connections for BMS control using PWM signaling are made between connector JP2 on the BMS panel (boilers 1 through 8), and the B.M.S. (PWM) IN terminals in the I/O Box on the front of the Benchmark 1.5 Boilers. Refer to the wiring diagram provided on the cover of the I/O Box.
Wiring connections for RS485 Modbus control are made between connector JP11 on the BMS (boilers 9 through 40) and the RS485 COMM terminals in the I/O Box on the front of the Benchmark 1.5 Boilers.
Wire the units using shielded twisted pair wire between 18 and 22 AWG. Observe the proper polarity for the B.M.S. (PWM) IN and/or RS485 COMM wiring connections. Shields should be terminated only at the BMS and the boiler end must be left floating. Each unit’s wiring must conform to the above.
NOTE
BMS Model 168 can utilize either pulse width modulation (PWM) or RS485 Modbus signaling to the Boiler. BMS II Model 5R5-384 can utilize only RS485 signaling to the Boiler.
The BMS mode of operation is used in conjunction with an AERCO Boiler Management System. The BMS mode is used when it is desired to operate multiple units in the most efficient manner possible. The BMS can control up to 40 boilers; 8 via pulse width modulation (PWM) and up to 32 via Modbus (RS485) network communication. For BMS programming
5-4
5.6.2 BMS Setup and Startup
This mode of operation is factory preset and the AERCO BMS controls the firing rate. There are no setup instructions for each individual unit.
To operate the unit in manual mode, press the AUTO/MAN switch. The REMOTE LED will go off and the MANUAL LED will light
To change back to the BMS mode, simply press the AUTO/MAN switch. The REMOTE LED will again light and the MANUAL LED will go off.
Page 41
MODE OF OPERATION
5.7 COMBINATION CONTROL SYSTEM
(CCS)
NOTE
Only BMS Model 168 can be utilized for the Combination Mode, not the BMS II (Model 5R5-384).
A Combination Control System (CCS) is one that uses multiple boilers to cover both space­heating and domestic hot water needs. An AERCO Boiler Management System (BMS) Model 168 and a Combination Control Panel (CCP) are necessary to configure this system. Typically, an adequate number of boilers are installed to cover the space-heating load on the design day, however one or more units are used for the domestic hot water load.
The theory behind this type of system is that the maximum space-heating load and the maximum domestic hot water load do not occur simul­taneously.+ Therefore, boilers used for the domestic hot water are capable of switching between constant setpoint and BMS modes of operation. These boilers are the combination units and are referred to as the combo boilers. The combo boilers heat water to a constant setpoint temperature. That water is then circulated through a heat exchanger in a domestic hot water storage tank.
When the space-heating load is such that all the space-heating boilers are at 100% firing rate, the BMS will then ask the Combination Control Panel for the domestic boilers to become space­heating boilers. Provided the domestic hot water load is satisfied, the combo (hot water) boilers will then become space-heating boilers. If the domestic hot water load is not satisfied, the combo boiler(s) remain on the domestic hot water load. If the combo boilers switch over to space heating, but there is a call for domestic hot water, the CCP switches the combo units back to the domestic load.
When the combo units are satisfying the domestic load they are in constant setpoint mode of operation. When the combo units switch over to space heating, their mode of operation changes to the BMS mode. For more information concerning the operation of the Combination Control Panel see the AERCO CCP-1 literature.
5.7.1 Combination Control System Field Wiring
Wiring for this system is between the BMS Model 168 panel, the CCP and the B.M.S. (PWM) IN terminals in the I/O Box. Wire the units using a shielded twisted pair of 18 to 22 AWG wire. When wiring multiple units, each unit’s wiring must conform to the above. For a complete CCP system-wiring diagram see the AERCO CCP-1 literature.
5.7.2 Combination Control System Setup and Startup
Setup for the Combination Mode requires entries to be made in the Configuration Menu for boiler mode, remote signal type and setpoint. The setpoint is adjustable from 40°F to 240°F.
Enter the following settings in the Configuration Menu:
MENU OPTION SETTING
Boiler Mode Combination
Remote Signal BMS (PWM Input)
Internal Setpt 40°F to 240°F
Refer to paragraph 3.3 for instructions on changing menu options.
While it is possible to change other temperature­related functions for combination mode, thes functions are preset to their factory default values. These default settings work well in most applications. It is suggested that AERCO be contacted prior to changing settings other than the unit’s setpoint. For a complete listing of temperature related function defaults, see Appendix E.
To set the unit to the manual mode, press the AUTO/MAN switch. The MANUAL LED will light.
To set the unit back to the auto mode, press the AUTO/MAN switch. The MANUAL LED will go off and the REMOTE LED will light.
When the boiler is switched to BMS mode, the AERCO BMS controls the firing rate. There are no setup requirements to the boiler(s) in this mode.
5-5
Page 42
Page 43
SAFETY DEVICE TESTING
CHAPTER 6 SAFETY DEVICE TESTING
6.1 TESTING OF SAFETY DEVICES
Periodic safety device testing is required to ensure that the control system and safety devices are operating properly. The Benchmark
1.5LN control system comprehensively monitors
all combustion-related safety devices before, during and after the start sequence. The following tests check to ensure that the system is operating as designed.
Operating controls and safety devices should be tested on a regular basis or following service or replacement. All testing must conform to local codes such as ASME CSD-1.
NOTE
MANUAL and AUTO modes of operation are required to perform the following tests. For a complete explanation of these modes, see Chapter 3.
NOTE
It will be necessary to remove the front door and side panels from the unit to perform the following tests.
WARNING
ELECTRICAL VOLTAGES IN THIS SYSTEM MAY INCLUDE 120 AND 24 VOLTS AC. POWER MUST BE RE­MOVED PRIOR TO PERFORMING WIRE REMOVAL OR OTHER TEST PROCEDURES THAT CAN RESULT IN ELECTRICAL SHOCK.
4. Place the unit in Manual Mode and adjust the firing rate between 25 and 30%.
5. While the unit is firing, slowly external manual gas shut-off valve.
6. The unit should shut down and display a LOW GAS PRESSURE fault message at approximately 2.6” W.C. The FAUL cator shou
ld also start flashing.
close the
T indi-
Figure 6-1
Low & High Gas Pressure Testing
7. Fully open the external manual gas shut-off valve and press the CLEAR button on the Control Box.
8. The fault message should clear and the FAULT indicator should go off. The unit should restart.
6.2 LOW GAS PRESSURE FAULT TEST
Refer to Figure 6-1 and ensure that the leak detection ball valve located at the high gas pressure switch is closed.
1. Remove the 1/8 “ plug from the ball valve at the low gas pressure switch shown in the lower portion of Figure 6-1.
2. Install a 0 – 16 “ W.C. manometer or a W.C. gauge where the 1/8" plug was removed.
3. Slowly open the ball valve near the low gas pressure switch.
9. Upon test completion, close the ball valve and remove the manometer. Replace the 1/8 “ plug removed in step 1.
6-1
Page 44
SAFETY DEVICE TESTING
6.3 HIGH GAS PRESSURE TEST
To simulate a high gas pressure fault, refer to Figure 6-1 and proceed as follows:
1. Remove the 1/8“ plug from the leak detection ball valve shown in Figure 6-1.
2. Install a 0 – 16” W.C. manometer (or W.C. gauge) where the 1/8” plug was removed.
3. Slowly open the leak detection ball valve
4. Start the unit in Manual mode at a firing rate between 25 and 30%.
5. Slowly increase the gas pressure using the adjustment screw on the SSOV.
6. The unit should shut down and display a HIGH GAS PRESSURE fault message when the gas pressure exceeds 4.7” W.C. The FAULT indicator should also start flashing.
7. Reduce the gas pressure back to 3.0” W.C.
8. Press the CLEAR button on the Control Box to clear the fault.
shut the unit off immediately and refer fault to qualified service personnel.
7. Close the drain and pressure relief valve used in draining the unit.
8. Open the water shut-off valve in the return piping to the unit.
9. Open the water supply shut-off valve to the unit to refill.
10. After the shell is full, press the LOW WATER LEVEL RESET button to reset the low water cutoff.
11. Press the CLEAR button to reset the FAULT LED and clear the displayed error message.
12. Set the ON/OFF switch to the ON position. The unit is now ready for operation.
6.5 WATER TEMPERATURE FAULT
TEST
A high water temperature fault is simulated by adjusting the automatic over-temperature switch. This switch is accessible from the front of the unit as shown in Figure 6-2.
9. The fault message should clear and the FAULT indicator should go off. The unit should restart.
10. Upon test completion, close the ball valve and remove the manometer. Replace the 1/8“ plug removed in step 1.
6.4 LOW WATER LEVEL FAULT TEST
To simulate a low water level fault:
1. Set the ON/OFF switch to the OFF position
2. Close the water shut-off valves in the supply and return piping to the unit.
3. Slowly open the drain valve on the rear of the unit. If necessary the unit’s relief valve may be opened to aid in draining.
4. Continue draining the unit until a LOW WATER LEVEL fault message is displayed and the FAULT indicator flashes.
5. Place the unit in the Manual Mode and raise the firing rate above 30%.
1. Start the unit in the normal operating mode. Allow the unit to stabilize at its setpoint.
2. Lower the adjustable over-temperature switch setting to match the displayed OUTLET TEMPERATURE.
3. Once the adjustable over-temperature switch setting is approximately at, or just below, the actual outlet water temperature, the unit should shut down. The FAULT indicator should start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should be displayed. It should not be possible to restart the unit.
4. Reset the adjustable over-temperature switch to its original setting.
5. The unit should start once the adjustable temperature limit switch setting is above the actual outlet water temperature.
6. Set the ON/OFF switch to the ON position. The READY light should remain off and the unit should not start. If the unit does start,
6-2
Page 45
SEE
DETAIL “A”
FRONT VIEW
SAFETY DEVICE TESTING
6.6 INTERLOCK TESTS
The unit is equipped with two interlock circuits called the Remote Interlock and Delayed Interlock. Terminal connections for these circuits are located in the I/O Box (Figure 2-9) and are labeled REMOTE INTL’K IN and DELAYED INTL’K IN. These circuits can shut down the unit in the event that an interlock is opened. These interlocks are shipped from the factory jumpered (closed). However, each of these interlocks may be utilized in the field as a remote stop and start, an emergency cut-off, or to prove that a device such as a pump, gas booster, or louver is operational.
6.6.1 REMOTE INTERLOCK
1. Remove the cover from the I/O Box and locate the REMOTE INTL’K IN terminals.
2. Start the unit in the Manual Mode and set the firing rate between 25% and 30%.
RESET BUTTON FOR
MANUAL RESET
TEMPERATURE
LIMIT SWITCH
MOUNTING
PLATE
DETAIL “A”
ADJUSTABLE
TEMPERATURE
LIMIT SWITCH
VFD
Figure 6-2
Temperature Limit Switch Setting
6. Once the adjustable over-temperature switch setting is approximately at, or just below, the actual outlet water temperature, the unit should shut down. The FAULT indicator should start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should be displayed. It should not be possible to restart the unit.
7. Reset the adjustable over-temperature switch to its original setting.
8. The unit should start once the adjustable temperature limit switch setting is above the actual outlet water temperature.
3. If there is a jumper across the REMOTE INTL’K IN terminals, remove one side of the jumper. If the interlock is being controlled by an external device, either open the interlock via the external device or disconnect one of the wires leading to the external device.
4. The unit should shut down and display INTERLOCK OPEN.
5. Once the interlock connection is reconnected, the INTERLOCK OPEN message should automatically clear and the unit should restart.
6.6.2 DELAYED INTERLOCK
1. Remove the cover from the I/O Box and locate the DELAYED INTL’K IN terminals.
2. Start the unit in the Manual Mode at a firing rate between 25% and 30%.
3. If there is a jumper across the DELAYED INTL’K IN terminals, remove one side of the jumper. If the interlock is connected to a proving switch of an external device, disconnect one of the wires leading to the proving switch.
4. The unit should shut down and display a DELAYED INTERLOCK OPEN fault message. The FAULT LED should be flashing.
5. Reconnect the wire or jumper removed in step 3 to restore the interlock.
6-3
Page 46
SAFETY DEVICE TESTING
6. Press the CLEAR button to reset the fault
7. The unit should start.
6.7 FLAME FAULT TESTS
Flame faults can occur during ignition or while the unit is already running. To simulate each of these fault conditions, proceed as follows:
1. Set the ON/OFF switch to the OFF position.
2. Place the unit in the Manual Mode and set the firing rate between 25% and 30%.
3. Close the manual gas shutoff valve located between the Safety Shut-Off Valve (SSOV) and the Air/Fuel Valve (see Figure 6-3).
4. Set the ON/OFF switch to the ON position to start the unit.
5. The unit should shut down after reaching the Ignition cycle and display FLAME LOSS
DURING IGN.
6. Open the valve previously closed in step 3 and press the CLEAR button.
7. Restart the unit and allow it to prove flame.
8. Once flame is proven, close the manual gas valve located between the SSOV and the Air/Fuel Valve.
9. The unit should shut down and display FLAME LOSS DURING RUN.
10. Open the valve previously closed in step 8.
11. Press the CLEAR button. The unit should restart and fire.
6.8 AIR FLOW FAULT TESTS
These tests check the operation of the Blower Proof Switch and Blocked Inlet Switch shown in Figure 6-3.
1. Start the unit in the Manual Mode at a firing rate between 25% and 30%.
2. Once the unit has proved flame, remove the memory stick from the Variable Frequency Drive (VFD).
3. The Blower Proof Switch will open and the blower should stop. The unit should shut down and display AIRFLOW FAULT DURING RUN.
4. Replace the memory stick in the VFD.
5. Press the CLEAR button. The unit should restart.
6. Next, check the Blocked Inlet Switch by closing the Iris Air Damper to position 8.
7. .The unit should shut down and again display AIRFLOW FAULT DURING RUN.
8. Return the Iris Air Damper to its previous setting.
9. Press the CLEAR button. The unit should restart.
6.9 SSOV PROOF OF CLOSURE SWITCH
The SSOV shown in Figure 6-1 contains the proof of closure switch. The proof of closure switch circuit is checked as follows:
Figure 6-3
Manual Gas Shut-Off Valve Location
6-4
1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in Manual Mode and set the firing rate between 25% and 30%
3. Refer to Figure 6-1 and locate the SSOV.
4. Remove the cover from the SSOV by loosening the screw shown in Figure 6-4. Lift off the cover to access the terminal wiring connections.
5. Disconnect wire #148 from the SSOV to “open” the proof of closure switch circuit.
6. The unit should fault and display SSOV SWITCH OPEN.
7. Replace wire #148 and press the CLEAR button.
Page 47
SAFETY DEVICE TESTING
8. Set the ON/OFF switch to ON to start the unit.
9. Remove the wire again when the unit reaches the purge cycle and PURGING is displayed.
10. The unit should shut down and display SSOV FAULT DURING PURGE.
11. Replace the wire on the SSOV and press the CLEAR button. The unit should restart.
Figure 6-4
SSOV Actuator Cover Location
6.11 IGNITION SWITCH OPEN DURING IGNITION
The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the switch, proceed as follows:
1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in Manual Mode and set the firing rate between 25% and 30%.
3. Remove the Air/Fuel Valve cover (Figure 6-5) by rotating the cover counterclockwise to unlock and lift up to remove.
4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-6).
5. Initiate a unit start sequence.
6. The unit should begin it’s start sequence and then shut down and display IGN SWITCH OPEN DURING IGNITION.
7. Replace the wire on the Ignition Switch and press the CLEAR button. The unit should restart.
6.10 PURGE SWITCH OPEN DURING PURGE
The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. To check the switch, proceed as follows:
1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and set the fire rate between 25% and 30%.
2. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it and then lift up (see Figure 6-5).
3. Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 6-6).
4. Initiate a unit start sequence.
5. The unit should begin it’s start sequence, then shut down and display PRG SWITCH OPEN DURING PURGE.
6. Replace the wire on the Purge Switch and depress the CLEAR button. The unit should restart.
Figure 6-5
Air/Fuel Valve Cover Location
6-5
Page 48
SAFETY DEVICE TESTING
9
6
1
1
7
2
Figure 6-6
Air/Fuel Valve Purge and Ignition Switch
Locations
6.12 SAFETY PRESSURE RELIEF
VALVE TEST
Test the safety Pressure Relief Valve in accordance with ASME Boiler and Pressure Vessel Code, Section VI.
6-6
Page 49
MAINTENANCE
CHAPTER 7 MAINTENANCE
7.1 MAINTENANCE SCHEDULE
The unit requires regular routine maintena nce to keep up efficiency and reliability. For best operation and life of the unit, the following routine maintenance procedures should be carried out in the tim e periods spec ified in T able 7-1. See Appendix I for a complete CSD-1 inspection check list.
WARNING
TO AVOID PERSONAL, PRIOR TO SERVICING:
DISCONNECT THE AC SUPPLY BY TURNING OFF THE SERVICE SWITCH AND AC SUPPLY CIRCUIT BREAKER.
SHUT OFF THE GAS SUPPLY AT THE MANUAL SHUT-OFF VALVE PROVIDED WITH THE U NIT
ALLOW THE UNIT T O COOL TO A SAFE WATER TEMPERATURE TO
PREVENT BURNING OR SCALDING
5. The igniter is gapped at 1/8-inch. If there is a substantial erosion of the spark gap or ground electrode, the igniter should be replaced. If carbon buil d-up is pres ent, clean the igniter using fine emery cloth. Repeate d carbon build-up on the igniter is an indication that a check of the combustion settings is required (see Chapter 4 for combustion calibration.
6. Prior to reinstalling the igniter, a high temperature anti-seize compound must applied to the igniter threads.
7. Reinstall the igniter. Do not over tig hten the igniter. A slight snugging up is sufficient. Reconnect the igniter cable.
8. Reinstall the side and top panels on the unit.
be
7.2 SPARK IGNITER
The spark igniter (part no. GP-122435-S) is located in the bod y of the burner (see Figure 7-
1). The igniter may be HOT. Care should be exercised. It is easier to re move the igniter from the unit after the unit has cooled to room temperature.
To inspect/replace the Igniter:
1. Set the ON/OFF switch on the control pa nel, to the OFF position. Disconnect AC power from the unit
2. Remove the side and top panels from the unit.
3. Disconnect the igniter cable from the igniter.
4. Using a 15/16” wrench, unscrew the igniter from the burner head. Remove the igniter from the burner shell, by grasping the contact end of the igniter.
Figure 7-1
Spark Igniter and Flame Detector
Location – Top View
7-1
Page 50
MAINTENANCE
Table 7-1 - Maintenance Schedule
PARAGRAPH ITEM 6 Mos. 12 Mos. 24 Mos.
7.2
7.3
7.4
7.5
7.6 Burner Inspect 2 hrs.
7.7
* Only performed after initial 6 month period after initial startup.
7.3 FLAME DETECTOR
The flame detector (par t no. 66006)is loca ted in the body of the burner (see Fig. 7-1) . The flame detector may be HOT. Allow the unit to cool sufficiently before removing the flame detector.
To inspect or replace the flame detector:
Spark Igniter (GP-122435-S) Flame Detector
(66006)
Combustion
Calibration
Testing of
Safety Devices
Condensate Drain Traps
*Inspect Inspect Replace 15 mins. *Inspect Inspect Replace 15 mins.
*Check Check 1 hr.
See CSD-1
Chart in
20 mins.
Appendix I
*Inspect
Inspect &
Clean
1 hr.
Labor
Time
1. Set the ON/O FF s witch on the c ontrol panel , to the OFF position. Disconnect AC power from the unit.
2. Remove the top panels from the unit.
3. Disconnect the flame detector lead wire. Unscrew the flame detector and remove it. (See Fig 7-2)
4. Inspect the detector thoroughly. If eroded, the detector should be replac ed. Otherwise clean the detector with a fine emery cloth.
5. Reinstall the flame detector and flame detector gasket, if removed.
6. Reconnect the flame detector lead wire.
7. Reinstall the side and top panels on the unit.
7.4 COMBUSTION CALIBRATION
Combustion settings must be checked at the intervals shown in Table 1 as part of the maintenance requirem ents. Refer to Chapter 4 for combustion calibration instructions.
Figure 7-2
Burner Assembly Spark Igniter and
Flame Detector Location
7-2
Page 51
7.5 SAFETY DEVICE TESTING
Systematic and thorough tests of the operating and safety devices should be performed to ensure that they are operating as designed. Certain code requirements, such as ASME CSD-1, require that t hese tests be perform ed on a scheduled basis. Test schedules must conform to local jurisdictions. The results of the tests should be recorded in a log book. See Chapter 6-Safety Device Testing Procedures.
7.6 BURNER ASSEMBLY
The burner assem bly (part no. 24012) is loc ated at the top of the unit. T he burner assembl y may be HOT. Allow the un it to c ool suf ficiently bef ore removing the burner assembly.
It should be noted that the complete burner assembly also includes the blower and air/fuel valve in addition t o the Benchm ark 1.5 low NOx burner. It can be removed as one complete assembly.
The following parts will be necessary for reassembly after inspection :
Part No. Description
81063 Burner Gaskets (Qty=2) 81047 Gas Injector Gasket (Qty=1) 81064 Blower Gasket
To inspect or replace the burner assembly:
MAINTENANCE
8. Remove the eight (8) 3/8-16 nuts from the burner flange (Figure 7-3) using a 9/16” wrench.
NOTE
The burner assembly is heavy, weighing approximately 25 pounds.
9. Remove the burner assembly from burner flange by pulling straight up.
10. Remove the grounding screw.
11. Remove and replace the burner gaskets.
12. Beginning with the burner assembly removed in step 9, reinstall all the components in the reverse order that they were removed.
13. Make sure to align the S/I and F/R slots in the burner with the heat exchanger top head.
14. Check to ensure that the ground ing screw is reinstalled.
AIR/FUEL
VALVE
FLAME
DETECTOR
3/8-16
NUTS (8)
BLOWER
1. Set the ON/OFF switch on the con trol pa nel, to the OFF position. Disconnect AC power from the unit and turn off the gas supply.
2. Remove the side and top panels from the unit.
3. Disconnect the lead wire from the flame detector. Unscrew the flame detector.
4. Disconnect the igniter cabl e from the igniter contactor. Unscrew the igniter.
5. Remove the two (2) 10-32 screws sec uring the gas injector to the burner. Sep arate the gas injector and gasket from the burner.
6. Disconnect the gas train from the air/fuel valve by removing the four 1/2” screws.
7. Disconnect the flex hose from the air/fuel valve by loosening the hose clamp.
BURNER
PLATE
SPARK
IGNITER
STAGED
IGNITION
ASSEMBLY
PARTIAL TOP VIEW
Figure 7-3
Burner Disassembly Diagram
GAS
TRAIN
7-3
Page 52
MAINTENANCE
7.7 CONDENSATE DRAIN TRAP
The Benchmark 1.5 Boiler contains a condensate trap as shown in Figure 2-5. The trap is located external to t he unit and attached to the drain pipe fr om the exhaus t m anifold. T his traps should be inspected and, if necessary, cleaned to ensure proper operation. To inspect and clean the trap, proceed as follows:
1. Disconnect the external condensate trap b y loosening the hose c lam ps between the trap and the exhaust manifold drain pipe.
2. Remove the connections on the inlet and outlet sides of the condensate tr ap shown in Figure 7-4.
3. Loosen the four (4) thumbscrews securing the cover on the condensate trap. Remove the cover.
4. Remove the float from the condensate trap.
5. Remove the orifice gasket from the trap.
6. Thoroughly clean the trap, f loat and gasket. Also inspect the drain pipin g for blockage. If the trap cannot be thoroughly cleaned, replace the trap.
7. After the above items have been inspected and thoroughly cleaned, replace the orifice gasket and float in the condensat e trap and replace the trap cover.
8. Reassemble all piping and hose connections to the condensate trap inlet and outlet. Reconnect trap to exhaust manifold drain pipe.
7.8 SHUTTING THE BOILER DOWN FOR AN EXTENDED PERIOD OF TIME
If the boiler is to be taken out of s ervice for an extended period of tim e (one year or more), the following instructions must be followed.
1. Set ON/OFF sw itch on the f ront panel to the OFF position to shut down the boiler’s operating controls.
2. Dis c onnect AC po wer fr om the unit.
3. Close the water supply and return valv es to isolate boiler.
4. Close external gas supply valve.
5. O pen relief valve to vent water pressure.
7.9 PLACING THE BOILER BACK IN
SERVICE AFTER A PROLONGED SHUTDOWN
After a prolonged shutdo wn (one year or more), the following procedures must be followed:
1. Review installation requirements inc luded in Chapter 2.
2. Inspect all piping and connections to the unit.
3. Inspect exhaust vent, air duct (if applicable).
4. Perform initial startup per Chapter 4.
5. Perform safety device testing and the scheduled maintenance procedures per Chapters 6 and 7 of this manual.
7-4
Figure 7-4
External Condensate Trap
Page 53
TROUBLESHOOTING

Chapter 8- TROUBLESHOOTING GUIDE

8.1 INTRODUCTION
This troubleshooting guide is intended to aid service/maintenance personnel in isolating the cause of a fault in a Benchm ark 1.5 Boiler. The troubleshooting procedures contained her ein are presented in tabular form on the f ollowing pages. These tables are comprised of three columns labeled: Fault Indication, Probable Cause and Corrective Action. The numbered items in the Probable Cause and Corrective Ac tion columns correspond to each other. For example, Probable Cause No. 1 corresponds to Corrective Action No. 1, etc.
When a fault occurs in the Benchmark Boiler, proceed as follows to isolate and correct the fault:
1. Observe the fault m essages dis played in the Control Box display.
2. Refer to the Fault Indication column in Troubleshooting Table 8-1 which f ollows and locate the Fault that best describes the existing conditions.
3. Proceed to the Probable Cause column and start with the first item (1) lis ted for the Fault Indication.
4. Perform the c hecks and procedures listed in the Corrective Action column for the first Probable Cause candidate.
5. Continue checking each additional Probable Cause for the existing fault until the fault is corrected.
6. Paragraph 8.2 and Table 8-2 contain additional troubleshooting information which may apply when no fault message is displayed.
7. If the fault cannot be corrected using the information provided in the Troubleshooting Tables, contact your local AERCO Representative.
8-1
Page 54
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
AIRFLOW FAULT
DURING IGNITION
1. Blower stopped running due to thermal or current overload
2. Blocked Blower inlet or inlet ductwork
3. Blocked Blower proof switch
4. Blocked blocked-air inlet switch
5. Defective Blower proof switch
6. Defective blocked-air inlet switch
7. Loose temperature transmitter to VFD’s analog input wire connection
8. Loose temperature sensor to temperature transmitter wire connection.
9. Defective temperature transmitter
10. Defective temperature sensor
11. Loose wire connection between the 4­20 mA signal from I/O box to VFD analog input
12. Defective I/O box
13. Wrong 4-20 mA output selection on the control box
14. Defective air-fuel valve potentiometer
15. Defective or missing VFD’s logic stick
16. Defective program on the logic stick or Defective VFD.
1. Check combustion blower for signs of excessive heat or high current drain that may trip thermal or current overload devices.
2. Inspect the inlet to the combustion blower including any ductwork leading up to the combustion blower for signs of blockage.
3. Remove the Blower proof switch and inspect for signs of blockage, clean or replace as necessary.
4. Remove the blocked-air inlet switch and inspect for signs of blockage, clean or replace as necessary.
5. Measure the Blower proof switch for continuity with the combustion blower running. If there is an erratic resistance reading or the resistance reading is greater than zero ohms, replace the switch.
6. Measure the blocked-air inlet switch for continuity with the combustion blower running. If there is an erratic resistance reading or the resistance reading is greater than zero ohms, replace the switch.
7. Check the actual inlet air temperature and measure voltage at temperature transmitter and VFD analog input. Verify that the voltage conforms to Table 8-3 for the inlet air temperature.
8. Refer to CORRECTIVE ACTION 7 and verify that the resistance conforms to Table 8-3.
9. See CORRECTIVE ACTION 7.
10. See CORRECTIVE ACTION 8.
11. Measure amperage at the I/O box output and VFD analog input, 4mA equates to 0% fire rate and 20 mA equates to 100% fire rate
12. See CORRECTIVE ACTION 11.
13. Check C-More configuration menu, mA OUT – Fire Rate should be selected
14. Check air fuel valve position at 0%, 50% and 100% fire rates,
the position on the c-more barograph should match the valve
15. Confirm that the logic stick is securely mounted on the VFD
16. Check the following VFD parameters: Max Hz = 67, Min Hz = 0,
parameter 59 & 60 should be set to 2.
8
-2
Page 55
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
AIRFLOW FAULT
DURING PURGE
AIRFLOW FAULT
DURING RUN
1. Blower not running or running too slow
2. Defective Air Flow Switch
3. Blocked Air flow Switch
4. Blocked Blower inlet or inlet ductwork.
5. No voltage to switch from control box.
PROBABLE CAUSES from 3 to 16
6. for AIRFLOW FAULT DURING IGNITION applies for this fault
1. Blower stopped running due to thermal or current overload
2. Blocked Blower inlet or inlet ductwork
3. Blocked airflow switch
4. Defective airflow switch
5. Combustion oscillations
PROBABLE CAUSES from 3 to 16
6. for AIRFLOW FAULT DURING IGNITION applies for this fault
1. Start the unit. If the blower does not run check the blower solid state relay for input and output voltage. If the relay is okay, check the blower.
2. Start the unit. If the blower runs, check the airflow switch for continuity. Replace the switch if there is no continuity.
3. Remove the air flow switch and inspect for signs of blockage, clean or replace as necessary.
4. Inspect the inlet to the combustion blower including any ductwork leading up to the combustion blower for signs of blockage.
5. Measure for 24 VAC during start sequence from eac h side of the switch to ground. If 24VAC is not present refer to qualified service personnel.
6. See
1. Check combustion blower for signs of excessive heat or high
2. Inspect the inlet to the combustion blower including any ductwork
3. Remove the airflow switch and inspect for signs of blockage,
4. Measure the airflow switch for continuity with the combustion
5. Run unit to full fire. If the unit rumbles or runs rough, perform
6.
CORRECTIVE ACTION from 3 to 16 for AIRFLOW
FAULT DURING IGNITION
current draw that may trip thermal or current overload devices.
leading up to the combustion blower for signs of blockage.
clean or replace as necessary.
blower running. If there is an erratic resistance reading or the resistance reading is greater than zero ohms, replace the switch.
combustion calibration.
PROBABLE CAUSES from 3 to 16 for AIRFLOW FAULT
DURING IGNITION applies for this fault
8-3
Page 56
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
DELAYED
INTERLOCK OPEN
DIRECT DRIVE SIGNAL FAULT
FLAME LOSS
DURING IGN
1. Delayed Interlock Jumper not installed or removed.
2. Device proving switch hooked to interlocks is not closed
1. Direct drive signal is not present: Not yet installed. Wrong polarity. Signal defective at source. Broken or loose wiring.
2. Signal is not isolated (floating).
3. Control Box signal type selection switches not set for correct signal type (voltage or current).
1. Burner Ground Screw not installed or loose.
2. Worn flame detector
3. No spark from Spark Plug
4. Defective Ignition Transformer
5. Defective Ignition/Stepper (IGST) Board
6. Defective SSOV
1. Check for a jumper properly installed across the delayed interlock terminals in the I/O box.
2. If there are 2 external wires on these terminals, check to see if an end switch for a device such as a pump, louver, etc. is tied these interlocks. Ensure that the device and or its end switch are functional. (jumper may be temporarily installed to test interlock)
1. Check I/O Box to ensure signal is hooked up. Hook up if not installed. If installed, check polarity. Measure signal level. Check continuity of wiring between source and boiler.
2. Check signal at source to ensure it is isolated.
3. Check DIP switch on PMC board to ensure it is set correctly for the type of signal being sent. Check control signal type set in Configuration Menu.
1. Inspect and install/retighten Burner Ground Screw.
2. Remove and inspect the flame detector for signs of wear. Replace if necessary.
3. Close the internal gas valve in the boiler. Install and arc a spark ignitor outside the unit.
4. If there is no spark, check for 120VAC at the primary side to the ignition transformer during the ignition cycle.
5. If 120VAC is not present, the IGST Board in the Control Box may be defective. Refer fault to qualified service personnel.
6. While externally arcing the spark ignitor, observe the open/close indicator in the Safety Shut-Off Valve to ensure it is opening. If the valve does not open, check for 120VAC at the valves input terminals. If 120VAC is not present, the IGST board in the Control Box may be defective. Refer fault to qualified service personnel.
8-4
Page 57
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
(continued) 7. Carbon or other debris on Burner.
8. Staged ignition ball valve closed.
FLAME LOSS
DURING RUN
HEAT DEMAND
FAILURE
HIGH EXHAUST TEMPERATURE
HIGH GAS
PRESSURE
1. Worn Flame Detector or cracked ceramic.
2. Defective Differential Regulator.
3. Poor combustion calibration.
4. Debris on burner.
5. Blocked condensate drain.
1. The Heat Demand Relays on the Ignition/Stepper board failed to activate when commanded
2. Relay is activated when not in Demand
1. Defective exhaust sensor.
2. Carboned heat exchanger due to incorrect combustion calibration
1. Incorrect supply gas pressure.
2. Defective SSOV Supply Regulator.
7. Remove the burner and inspect for any carbon or debris. Clean and reinstall.
8. Open ball valve downstream of SSOV (see Figure 8-1).
1. Remove and inspect the Flame Detector for signs of wear or cracked ceramic. Replace if necessary.
2. Check gas pressure readings using a gauge or manometer into and out of the Air/Fuel Valve to ensure that the gas pressure into and out of the valve is correct.
3. Check combustion calibration. Adjust as necessary.
4. Remove the burner and inspect for any carbon or debris. Clean and reinstall.
5. Remove blockage in condensate drain.
1. Press CLEAR button and restart the unit. If the f ault persists, replace Ignition/Stepper (IGST) Board.
2. Defective relay. Replace IGST Board.
1. Measure the actual exhaust temperature and continuity of the exhaust sensor. If the exhaust temperature is less than 475 and the exhaust sensor shows continuity replace the sensor.
2. If exhaust temperature is greater than 500 combustion calibration. Calibrate or repair as necessary.
1. Check to ensure gas pressure at inlet of SSOV is 2 psig maximum.
2. If gas supply pressure downstream of SSOV cannot be lowered, to 1.5” W.C. (see para. 4.3, step 10), the SSOV Supply Regulator may be defective.
o
F, check
o
F
8-5
Page 58
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
continued 3. Defective High Gas Pressure Switch
4. Gas pressure snubber not installed.
HIGH WATER TEMP
SWITCH OPEN
HIGH WATER
TEMPERATURE
IGN BOARD
COMM FAULT
1. Faulty Water temperature switch.
2. Incorrect PID settings.
3. Faulty shell temperature sensor.
4. Unit in Manual mode
5. Unit setpoint is greater than Over Temperature Switch setpoint.
6. Boiler Management System PID or other settings not correctly setup.
7. No interlock to boiler or BMS to disable boiler(s) in event that system pumps have failed.
8. System flow rate changes are occurring faster than boilers can respond.
1. See HIGH WATER TEMPERATURE SWITCH OPEN.
2. Temp HI Limit setting is too low.
1. Communication fault has occurred between the PMC board and Ignition/Stepper (IGST) board
3. Remove the leads from the high gas pressure switch and measure continuity across the common and normally closed terminals with the unit not firing. Replace the switch if it does not show continuity.
4. See Figure 8-1. Ensure that the gas pressure snubber is installed at the high gas pressure switch.
1. Test the temperature switch to insure it trips at its actual water temperature setting.
2. Check PID settings against Menu Default settings in the Appendix. If the settings have been changed, record the current readings then reset them to the default values.
3. Using the resistance charts in the Appendix C, Measure the resistance of Shell sensor and BTU sensor at a known water temperature.
4. If unit is in Manual Mode switch to Auto Mode.
5. Check setpoint of unit and setpoint of Temperature Switch; Ensure that the temperature switch is set higher than the unit’s setpoint.
6. Check the BMS for changes to PID default values, correct as necessary.
7. If system pump is controlled by Energy Management System other than BMS or pumps are individually controlled by boiler, check to see if there are flow switches interlocked to the BMS or boiler.
8. If the system is a variable flow system, monitor system flow changes to ensure that the rate of flow change is not faster than what the boilers can respond to.
1. See HIGH WATER TEMPERATURE SWITCH OPEN.
2. Check Temp HI Limit setting.
1. Press CLEAR button and restart unit. If fault persists, contact qualified Service Personnel.
8-6
Page 59
TROUBLESHOOTING
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
IGN SWTCH CLOSED
DURING PURGE
IGN SWTCH OPEN
DURING IGNITION
INTERLOCK
OPEN
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
1. Air/Fuel Valve not rotating
2. Defective or shorted switch
3. Switch wired incorrectly
4. Defective Power Supply Board or fuse
5. Defective IGST Board
1. Air/Fuel Valve not rotating to ignition position.
2. Defective ignition switch
3. Defective Power Supply Board or fuse
4. Defective IGST Board
1. Interlock jumper not installed or removed
2. Energy Management System does not have boiler enabled.
1. Start the unit. The Air/Fuel Valve should rotate to the purge (open) position. If the valve does not rotate at all or does not rotate fully open, check the Air/Fuel Valve calibration. If calibration is okay, the problem may be in the Air-Fuel Valve or the Control Box. Refer to qualified service personnel
2. . If the Air/Fuel Valve does rotate to purge, check the ignition switch for continuity between the N.O. and COM terminals. If the switch shows continuity when not in contact with the cam replace the switch.
3. Check to ensure that the switch is wired correctly (correct wire numbers on the normally open terminals). If the switch is wired correctly, replace the switch
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board
1. Start the unit. The Air/Fuel Valve should rotate to the purge (open) position, then back to ignition position (towards closed) during the ignition cycle. If the valve does not rotate back to the ignition position, check the Air/Fuel Valve calibration. If calibration is okay, the problem m ay be in the Air/Fuel Valve or the Control Box. Refer fault to qualified service personnel.
2. If the Air/Fuel Valve does rotate to the ignition position, check the ignition position switch for continuity between the N.O. and COM terminals when in contact with the cam.
3. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
4. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board.
1. Check for a jumper properly installed across the interlock terminals in the I/O box
2. If there are two external wires on these terminals check any Energy Management system to see if they have the units disabled (a jumper may be temporarily installed to see if the interlock circuit is functioning).
8-7
Page 60
TROUBLESHOOTING
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
continued 3. Device proving switch hooked to
LINE VOLTAGE
OUT OF PHASE
LOW GAS
PRESSURE
LOW WATER
LEVEL
MODBUS COMM
FAULT
PRG SWTCH CLOSED
DURING IGNITION
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
3. Check that proving switch for any device hooked to the interlock
interlocks is not closed.
1. Line and Neutral switched in AC Power Box.
2. Incorrect power supply transformer wiring.
1. Incorrect supply gas pressure.
2. Defective Low Pressure Gas Switch
1. Insufficient water level in system
2. Defective water level circuitry.
3. Defective water level probe.
1. Boiler not seeing information from modbus network
1. A/F Valve rotated open to purge and did not rotate to ignition position
2. Defective or shorted switch.
3. Switch wired incorrectly.
4. Defective Power Supply Board or fuse
5. Defective IGST Board
circuit is closing and that the device is operational.
1. Check hot and neutral in AC Power Box to ensure they are not reversed
2. Check transformer wiring, in AC Power Box, against the power box transformer wiring diagram to ensure it is wired correctly
1. Measure gas pressure upstream of the supply gas regulator with the unit firing. Ensure it is between 4” W.C. and 2 psig (see para.
2.7.1).
2. Measure gas pressure at the low gas pressure switch. If it is greater than 2.6” W.C., measure continuity across the switch and replace if necessary.
1. Check system for sufficient water level.
2. Test water level circuitry using the Control Box front panel LOW WATER TEST and RESET buttons. Replace water level circuitry if it does not respond.
3. Check continuity of probe end to the shell, change probe if there is no continuity.
1. Check network connections. If fault persists, contact qualified Service Personnel.
1. Start the unit. The Air/Fuel Valve should rotate to the purge (open) position, then back to ignition position (towards closed) during the ignition cycle. If the valve does not rotate back to the ignition position, check the Air/Fuel Valve calibration. If calibration is okay, the problem m ay be in the Air/Fuel Valve or the Control Box. Refer fault to qualified service personnel.
2. If the Air/Fuel Valve does rotate to the ignition position, check the purge switch for continuity between the N.O. and COM terminals. If the switch shows c ontinuity when not in contact with the cam, check to ensure that the switch is wired correctly (correct wire numbers on the normally open terminals).
3. If the switch is wired correctly, replace the switch.
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and ver ify it is blinking ON & OFF every second. If not, replace IGST Board.
8-8
Page 61
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
PRG SWTCH OPEN
DURING PURGE
OUTDOOR TEMP
SENSOR FAULT
REMOTE SETPT
SIGNAL FAULT
RESIDUAL
FLAME
1. Defective purge switch.
2. No voltage present at switch.
3. Switch wired incorrectly.
4. Defective Power Supply Board or fuse
5. Defective IGST Board
1. Loose or broken wiring.
2. Defective Sensor.
3. Incorrect Sensor.
1. Remote setpoint signal not present: Not yet installed. Wrong polarity. Signal defective at source. Broken or loose wiring.
2. Signal is not isolated (floating) if 4 to 20 mA.
3. Control Box signal type selection switches not set for correct signal type (voltage or current).
1. SSOV not fully closed. 1. Check open/close indicator window of Safety Shut-Off Valve
1. If the air-fuel valve does rotate, check the purge switch for continuity when closing. Replace switch if continuity does not exist.
2. Measure for 24 VAC f rom each side of the switch to ground. If 24VAC is not present, refer fault to qualified service personnel.
3. Check to ensure that the switch is wired correctly (correct wire numbers on the normally open terminals).
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and ver ify it is blinking ON & OFF every second. If not, replace IGST Board.
1. Inspect Outdoor Temperature sensor for loose or broken wiring.
2. Check resistance of sensor to determine if it is within specification.
3. Ensure that the correct sensor is installed.
1. Check I/O Box to ensure signal is hooked up. Hook up if not installed. If installed, check polarity. Measure signal level. Check continuity of wiring between source and boiler.
2. Check signal at source to ensure it is isolated.
3. Check DIP switch on PMC board to ensure it is set correctly for the type of signal being sent. Check control signal type set in Configuration Menu.
(SSOV) and ensure that the SSOV is fully closed. If not fully closed, replace the valve and or actuator.
Close gas shut-off valve downstream of SSOV. Install a manometer or gauge in a gas test port between the SSOV and the gas shut off valve. If a gas pressure reading is observed replace the SSOV valve and or actuator.
8-9
Page 62
TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
FAULT INDICATION PROBABLE CAUSES CORRECTIVE ACTION
(continued) 2. Defective Flame Detector
SSOV FAULT
DURING PURGE
SSOV FAULT DURING RUN SSOV RELAY
FAILURE
SSOV
SWITCH OPEN
STEPPER MOTOR
FAILURE
3. See SSOV SWITCH OPEN
1. SSOV switch closed for 15 seconds during run.
1. SSOV relay failed on board. 1. Press CLEAR button and restart unit. If fault persists, replace
1. Actuator not allowing for full closure of gas valve
2. SSOV powered when it should not be
3. Defective Switch or Actuator
4. Incorrectly wired switch.
1. Air/Fuel Valve out of calibration.
2. Air/Fuel Valve unplugged.
3. Loose wiring connection to the stepper motor.
4. Defective Air/Fuel Valve stepper motor.
5. Defective Power Supply Board or fuse
6. Defective IGST Board
2. Replace Flame Detector.
1. Replace or adjust microswitch in SSOV actuator. If fault persists, replace actuator.
Ignition/Stepper (IGST) Board.
1. Observe operation of the Safety Shut-Off Valve (SSOV) through indicator on the Valve actuator and ensure that the valve is fully and not partially closing.
2. If the SSOV never closes, it may be powered continuously. Close the gas supply and remove power from the unit. Refer fault to qualified service personnel.
3. Remove the electrical cover from the SSOV and check switch continuity. If the switch does not show continuity with the gas valve closed, either adjust or replace the switch or actuator.
4. Ensure that the SSOV Proof of Closure switch is correctly wired.
1. Refer to GF-112 and perform Stepper Test (para. 6.3.5) to ensure stepper motor rotates properly between the 0% (fully closed) and 100% (fully open) positions. Verify that the FIRE RATE bargraph and the dial on the Air/Fuel Valve track each other to indicate proper operation. If operation is not correct, perform the Stepper Feedback Calibration (GF-112, para. 6.2.1).
2. Check that the Air/Fuel Valve is connected to the Control Box.
3. .Inspect for loose connections between the Air/Fuel Valve motor and the wiring harness.
4. Replace stepper motor.
5. Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board.
6. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board.
8-10
Page 63
TROUBLESHOOTING
8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES
Refer to Table 8-2 to troubleshoot faults which may occur without a specific fault message being displayed.
TABLE 8-2. BOILER TROUBLESHOOTING WITH NO FAULT MESSAGE DISPLAYED
OBSERVED INCIDENT PROBABLE CAUSES CORRECTIVE ACTION
Hard Light-Off 1. Staged Ignition Ball Valve closed.
2. Clogged/damaged Gas Injector (Figure 8-2).
3. Defective Staged Ignition Solenoid (Figure 8-2)
Fluctuating Gas Pressure 1. Gas pressure going into unit is
fluctuating.
2. Damping Orifice not installed.
Air/Fuel Valve “hunting” at 80%
Firing Rate
1. IGST and Power Supply Boards in Control Box are outdated.
1. Open the 1/4” Ball Valve downstream of the SSOV (Fig. 8-1).
2. Remove and inspect Gas Injector to ensure it is not clogged or damaged.
3. Close the 2” and the 1/4” Ball Valve downstream of the SSOV (Fig. 8-1). Start the unit and listen for a “clicking” sound that the Staged Ignition Solenoid makes during Ignition Trial. If “clicking” sound is not heard after 2 or 3 attempts, replace the Staged Ignition Solenoid.
1. Stabilize gas pressure going into unit. If necessary, troubleshoot Building Supply Regulator.
2. Check to ensure that the Damping Orifice is installed in the downstream SSOV/Regulator Actuator (Figure 8-3).
1. Check to ensure that the IGST and Power Supply Boards are Rev. E or higher.
8-11
Page 64
TROUBLESHOOTING
Figure 8-2
Staged Ignition Solenoid Location
8-12
Figure 8-1
High Pressure Gas Switch & Snubber Locations
Figure 8-3
Damping Orifice Location
Page 65
TROUBLESHOOTING
Table 8-3
BMK 1.5 LN (3.3 K) Temperature Sensor and Temperature
Transmitter Outputs
TEMP
ºC
-40 -40 111177 0.289 28 82.4 2915 6.16
-30 -22 58443 0.523 29 84.2 2787 6.31
-20 -4 32814 0.904 30 86 2659 6.470
-10 14 18200 1.560 31 87.8 2549 6.610
-5 23 13972 1.972 32 89.6 2443 6.760 0 32 10775 2.459 33 91.4 2343 6.900 1 33.8 10240 2.564 34 93.2 2247 7.040 2 35.6 9735 2.680 35 95 2156 7.180 3 37.4 9256 2.791 36 96.8 2068 7.320 4 39.2 8806 2.906 37 98.6 1984 7.460 5 41 8380 3.022 38 100.4 1905 7.600 6 42.8 7977 3.143 39 102.2 1830 7.730 7 44.6 7595 3.267 40 104 1758 7.860 8 46.4 7234 3.387 41 105.8 1688 8.000 9 48.2 6891 3.514 42 107.6 1622 8.130
10 50 6566 3.643 43 109.4 1559 8.250 11 51.8 6260 3.772 44 111.2 1499 8.490 12 53.6 5969 3.900 45 113 1441 8.510 13 55.4 5692 4.040 46 114.8 1386 8.630 14 57.2 5432 4.170 47 116.6 1334 8.750 15 59 5184 4.310 48 118.4 1283 8.960 16 60.8 4972 4.440 49 120.2 1234 8.980 17 62.6 4759 4.570 50 122 1189 9.100 18 64.4 4547 4.710 51 123.8 1145 9.210 19 66.2 4334 4.860 52 125.6 1102 9.320 20 68 4122 5.020 53 127.4 1061 9.430 21 69.8 3958 5.150 54 129.2 1023 9.530 22 71.6 3793 5.290 55 131 986 9.640 23 73.4 3629 5.520 56 132.8 950 9.740 24 75.2 3464 5.580 57 134.6 916 9.840 25 77 3300 5.740 58 136.4 883 9.920 26 78.8 3172 5.870 59 138.2 852 10.030 27 80.6 3044 6.010 60 140 821 10.120
TEMP
ºF
UA33
Resistance
Ohm
Volts
outputs
UA33
TEMP
ºC
TEMP
ºF
UA33
Resistance
Ohm
Volts
outputs
UA33
8-13
Page 66
Page 67

APPENDIX A - BOILER MENU ITEM DESCRIPTIONS

MENU LEVEL & OPTION DESCRIPTION
OPERATING MENU Active Setpoint This is the setpoint temperature to which the
control is set when operating in the Constant Setpoint, Remote Setpoint or Outdoor Reset Mode. When in the Constant Setpoint Mode, this value is equal to the Internal Setpoint setting in the Configuration Menu. When in the Remote Setpoint Mode, this value is the setpoint equivalent to the remote analog signal supplied to the unit. When in the Outdoor Reset Mode, this is the derived value from the charts in Appendix D.
Aux Temp For monitoring purposes only
APPENDIX A
Outdoor Temp Displayed only if outdoor sensor is installed and
enabled.
Fire Rate In Desired input fire rate. This would normally be the
same as the fire rate shown on the bar-graph (fire
rate out) when the boiler is operating. Flame Strength Displays flame strength from 0% to 100%. Run Cycles Displays the total number of run cycles from 0 to
999,999. Run Hours Displays total run time of unit in hours from 0 to
9,999,999. Fault Log Displays information on the last 9 faults.
A-1
Page 68
APPENDIX A
APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
SETUP MENU
Password Allows password to be entered.
Once the valid password (159) is entered, options in the Setup, Configuration and Tuning Menus can be modified.
Language Permits selection of English, Spanish or French for
displayed messages. Default is English. Time Displays time from 12:00 am to 11:59 pm. Date Displays dates from 01/01/00 to 12/31/99 Unit of Temp Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). Default is
°F. Comm Address For RS-485 communications (0 to 127). Default
address is 0. RS-232 should have its own
(programmable) password. Baud Rate Allows communications Baud Rate to be set (2400
to 19.2K). Default is 9600. Software Version Identifies the current software version of the control
box (Ver 0.0 to Ver 9.9). CONFIGURATION MENU Internal Setpoint Allo ws inter nal setpoint to be set . Default is 130°F. Unit Type Allows selection of Boiler or Water Heater. Unit Size Sets unit size from 0.5 to 3.0 MBTUs. Default is 1.0
MBTU. Boiler Mode It allows selection of: Constant Setpoint, Remote
Setpoint, Direct Drive, Combination, or Outdoor
Reset Mode. Default is Constant Setpoint Mode. Remote Signal Used to set the type of external signal which will be
used when operating in the Remote Setpoint, Direct
Drive or Combination Mode. The factory default is
4-20 mA/1-5V. Bldg Ref Temp
Allows the building reference temperature to be set
when operating a boiler in the Outdoor Reset Mode.
Default is 70°F.
A-2
Page 69
APPENDIX A
APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
Reset Ratio Permits setting of Reset Ratio when operating boiler
in the Outdoor Reset Mode. Reset Ratio is
adjustable from 0.1 to 9.9. Default is 1.2. Outdoor Sensor Allows outdoor sensor function to be enabled or
disabled. Default is disabled. System Start Tmp If outdoor sensor is enabled, this menu item allows
the system start temperature to be set from 30 to
100°F. Default is 60°F. Setpoint Lo Limit Used to set the minimum allowable setpoint (40°F to
Setpoint Hi Limit). Default is 60°F Setpoint Hi Limit Used to set the maximum allowable setpoint
(Setpoint Lo Limit to 240°F). Default is 200°F. Temp Hi Limit This is the maximum allowable outlet temperature
(40 to 240°F). Any temperature above this setting
will turn off the unit. The temperature must then drop
5° below this setting to allow the unit to run. Default
Hi Limit is 210°F. Max Fire Rate Sets the maximum allowable fire rate for the unit
(40% to 100%). Default is 100%. Pump Delay Timer Specifies the amount of time (0 to 30 min.) to keep
the pump running after the unit turns off. Default is
zero. Aux Start On Dly Specif ies th e amount of time to wait (0 to 120 sec.)
between activating the Aux Relay (due to a demand)
and checking the pre-purge string to start the boiler.
Default is 0 sec. Failsafe Mode Allows the Failsafe mode to be set to either
Constant Setpoint or Shutdown. Default is
Shutdown. mA Output Must be set to Fire Rate Out for Benchmark 1.5LN. Lo Fire Timer Specifies how long (2 to 600 sec.) to remain in the
low fire position after ignition, before going to the
desired output. Default is 2 sec.
A-3
Page 70
APPENDIX A
APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
TUNING MENU
Prop Band G ener ates a fire rate based on the error that exists
between the setpoint temperature and the actual
outlet temperature. If the actual error is less than
the proportional band setting (1 to 120°F), the fire
rate will be less than 100%. If the error is equal to
or greater than the proportional band setting, the fire
rate will be 100%. Integral Gain This sets the fraction of the output, due to setpoint
error, to add or subtract from the output each minute
to move towards the setpoint. Gain is adjustable
from 0.00 to 1.00 (Default is 0.10). Derivative Time This value (0.0 to 20.0 min.) responds to the rate of
change of the setpoint error. This is the time that
this action advances the output. Reset Defaults? Allows Tuning Menu options to be reset to their
Factory Default values.
A-4
Page 71

APPENDIX B - STARTUP, STATUS AND FAULT MESSAGES

MESSAGE DESCRIPTION
DISABLED
HH:MM pm MM/DD/YY
STANDBY Displayed when ON/OFF switch is in the ON position, but
DEMAND DELAY
XX sec
PURGING
XX sec
IGNITION TRIAL
XX sec
FLAME PROVEN
WARMUP
XX sec
WAIT Prompts the operator to wait.
APPENDIX B
TABLE B-1. STARTUP AND STATUS MESSAGES
Displayed if ON/OFF switch is set to OFF. The display also shows the time and date that the unit was disabled.
there is no demand for heat. The time and date are also displayed. Displayed if Demand Delay is active.
Displayed during the purge cycle during startup. The duration of the purge cycle counts up in seconds. Displayed during ignition trial of startup sequence. The duration of cycle counts up in seconds. Displayed after flame has been detected for a period of 2 seconds. Initially, the flame strength is shown in %. After 5 seconds has elapsed, the time and date are shown in place of flame strength. Displayed for 2 minutes during the initial warmup only.
B-1
Page 72
APPENDIX B
FAULT MESSAGE FAULT DESCRIPTION
HIGH WATER TEMP
SWITCH OPEN
LOW WATER
LEVEL
LOW GAS
PRESSURE
HIGH GAS
PRESSURE
INTERLOCK
OPEN
DELAYED
INTERLOCK OPEN
AIRFLOW FAULT DURING PURGE
PRG SWTCH OPEN
DURING PURGE
IGN SWTCH OPEN
DURING IGNITION
IGN SWTCH CLOSED
DURING PURGE
PRG SWTCH CLOSED
DURING IGNITION
AIRFLOW FAULT
DURING IGN
AIRFLOW FAULT
DURING RUN
SSOV
SWITCH OPEN
SSOV FAULT
DURING PURGE
SSOV FAULT
DURING IGN
SSOV FAULT
DURING RUN
SSOV RELAY
FAILURE
FLAME LOSS
DURING IGN
FLAME LOSS
DURING RUN HIGH EXHAUST TEMPERATURE
LOSS OF POWER
TABLE B-2. FAULT MESSAGES
The High Water Temperature Limit Switch is open.
The Water Level Control board is indicating low water level.
The Low Gas Pressure Limit Switch is open.
The High Gas Pressure Limit Switch is open.
The Remote Interlock is open.
The Delayed Interlock is open.
The Blower Proof Switch opened during purge, or air inlet is blocked. The Purge Position Limit switch on the air/fuel valve opened during purge. The Ignition Position Limit switch on the air/fuel valve opened during ignition. The Ignition Position Limit switch on the air/fuel valve closed during purge. The Purge Position Limit switch on the air/fuel valve closed during ignition. The Blower Proof Switch opened during ignition.
The Blower Proof Switch opened during run.
The SSOV switch opened during standby.
The SSOV switch opened during purge.
The SSOV switch closed or failed to open during ignition.
The SSOV switch closed for more than 15 seconds during run. A failure has been detected in one of the relays that control the SSOV. The Flame signal was not seen during ignition or lost within 5 seconds after ignition. The Flame signal was lost during run.
The High Exhaust Temperature Limit Switch is closed.
A power loss had occurred. The time and date when power was restored is displayed.
B-2
Page 73
APPENDIX B
TABLE B-2. FAULT MESSAGES - Continued
FAULT MESSAGE FAULT DESCRIPTION
RESIDUAL
FLAME
HEAT DEMAND
FAILURE
IGN BOARD
COMM FAULT DIRECT DRIVE SIGNAL FAULT
REMOTE SETPT
SIGNAL FAULT
OUTDOOR TEMP
SENSOR FAULT
OUTLET TEMP
SENSOR FAULT
FFWD TEMP
SENSOR FAULT
HIGH WATER
TEMPERATURE
LINE VOLTAGE
OUT OF PHASE
STEPPER MOTOR
FAILURE
NETWORK COMM
FAULT
The Flame signal was seen for more than 60 seconds during standby. The Heat Demand Relays on the Ignition board failed to activate when commanded.
A communication fault has occurred between the PMC board
and Ignition board. The direct drive signal is not present or is out of range.
The remote setpoint signal is not present or is out of range.
The temperature measured by the Outdoor Air Sensor is out of range. The temperature measured by the Outlet Sensor is out of range. The temperature measured by the FFWD Sensor is out of range. The temperature measured by the Outlet Sensor exceeded the Temp Hi Limit setting. The High AC voltage is out of phase from the low AC voltage.
The stepper motor failed to move the valve to the desired position. The RS-485 network information is not present or is corrupted.
B-3
Page 74
Page 75
TEMPERATURE SENSOR RESISTANCE CHART
(BALCO)
TEMPERATURE SENSOR AERCO PART NO. 123449
R = RESISTANCE (OHMS) T = TEMPERATURE (°F)
R=.00161T^2+1.961T+854.841
APPENDIX C
TEMP (°F) RES. (OHMS)
-40 779.0
-30 797.5
-20 816.3
-10 835.4 0 854.8
10 874.6 20 894.7 30 915.1 40 935.9 50 956.9 60 978.3 70 1000.0 80 1022.0
90 1044.4 100 1067.0 110 1090.0 120 1113.3 130 1137.0 140 1160.9 150 1185.2 160 1209.5 170 1234.7 180 1260.0 190 1285.6 200 1311.4 210 1337.7 220 1364.2 230 1391.0 240 1418.2 250 1445.7
C-1
Page 76
Page 77
Air
Temp
50F 45F 40F 35F 30F 25F 20F 15F 10F
5F 0F
-5F
-10F
-15F
-20F
Air
Temp
60F 55F 50F 45F 40F 35F 30F 25F 20F 15F 10F
5F 0F
-5F
-10F
-15F
-20F
APPENDIX D
APPENDIX D. - INDOOR/OUTDOOR RESET RATIO CHARTS
Table D-1. Header Temperature for a Building Reference Temperature of 50F
RESET RATIO
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
50 50 50 50 50 50 50 50 50 50 53 54 55 56 57 58 59 60 60 62 56 58 60 62 64 66 68 70 72 74 59 62 65 68 71 74 77 80 83 86 62 66 70 74 78 82 86 90 94 98 65 70 75 80 85 90 95 100 105 110 68 74 80 86 92 98 104 110 116 122 71 78 85 92 99 106 113 120 127 134 74 82 90 98 106 114 122 130 138 146 77 86 95 104 113 122 131 140 149 158 80 90 100 110 120 130 140 150 160 170 83 94 105 116 127 138 149 160 171 182 86 98 110 122 134 146 158 170 182 194 89 102 115 128 141 154 167 180 193 206 92 106 120 134 148 162 176 190 204 218
Table D-2. Header Temperature for a Building Reference Temperatrure of 60F
RESET RATIO
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
60 60 60 60 60 60 60 60 60 60 63 64 65 66 67 68 69 70 71 72 66 68 70 72 74 76 78 80 82 84 69 72 75 78 81 84 87 90 93 96 72 76 80 84 88 92 96 100 104 108 75 80 85 90 95 100 105 110 115 120 78 84 90 96 102 108 114 120 126 132 81 88 95 102 109 116 123 130 137 144 84 92 100 108 116 124 132 140 148 156 87 96 105 114 123 132 141 150 159 168 90 100 110 120 130 140 150 160 170 180 93 104 115 126 137 148 159 170 181 192 96 108 120 132 144 156 168 180 192 204
99 112 125 138 151 164 177 190 203 216 102 116 130 144 158 172 186 200 214 105 120 135 150 165 180 195 210 108 124 140 156 172 188 204
D-1
Page 78
APPENDIX D
Table D-3. Header Temperature for a Building Reference Temperature of 65F
Air
Temp
65 60 55 50 45 40 35 30 25 20 15 10
5 0
-5
-10
-15
-20
Air
Temp
70F 65F 60F 55F 50F 45F 40F 35F 30F 25F 20F 15F 10F
5F 0F
-5F
-10F
-15F
-20F
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
65 65 65 65 65 65 65 65 65 65 68 69 70 71 72 73 74 75 76 77 71 73 75 77 79 81 83 85 87 89 74 77 80 83 86 89 92 95 98 101 77 81 85 89 93 97 101 105 109 113 80 85 90 95 100 105 110 115 120 125 83 89 95 101 107 113 119 125 131 137 86 93 100 107 114 121 128 135 142 149 89 97 105 113 121 129 137 145 153 161 92 101 110 119 128 137 146 155 164 173 95 105 115 125 135 145 155 165 175 185
98 109 120 131 142 153 164 175 186 197 101 113 125 137 149 161 173 185 197 209 104 117 130 143 156 169 182 195 208 107 121 135 149 163 177 191 205 219 110 125 140 155 170 185 200 215 113 129 145 161 177 193 209 116 133 150 167 201 218
Table D-4. Header Temperature for a Building Reference Temperature of 70F
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
70 70 70 70 70 70 70 70 70 70
73 74 75 76 77 78 79 80 81 82
76 78 80 82 84 86 88 90 92 94
79 82 85 88 91 94 97 100 103 106
82 86 90 94 98 102 106 110 114 118
85 90 95 100 105 110 115 120 125 130
88 94 100 106 112 118 124 130 136 142
91 98 105 112 119 126 133 140 147 154
94 102 110 118 126 134 142 150 158 166
97 106 115 124 133 142 151 160 169 178 100 110 120 130 140 150 160 170 180 190 103 114 125 136 147 158 169 180 191 202 106 118 130 142 154 166 178 190 202 214 109 122 135 148 161 174 187 200 213 112 126 140 154 168 182 196 210 115 130 145 160 175 190 205 118 134 150 166 182 198 214 121 138 155 172 189 206 124 142 160 178 196 214
RESET RATIO
RESET RATIO
D-2
Page 79
APPENDIX D
Table D-5. Header Temperature for a Building Reference Temperature of 75F
RESET RATIO
Air
Temp
75F 70F 65F 60F 55F 50F 45F 40F 35F 30F 25F 20F 15F 10F
5F 0F
-5F
-10F
-15F
Air
Temp
80F 80 80 80 80 80 80 80 80 80 80 75F 83 84 85 86 87 88 89 90 91 92 70F 86 88 90 92 94 96 98 100 102 104 65F 89 92 95 98 101 104 107 110 113 116 60F 92 96 100 104 108 112 116 120 124 128 55F 95 100 105 110 115 120 125 130 135 140 50F 98 104 110 116 122 128 134 140 146 152 45F 101 108 115 122 129 136 143 150 157 164 40F 104 112 120 128 136 144 152 160 168 176 35F 107 116 125 134 143 152 161 170 179 188 30F 110 120 130 140 150 160 170 180 190 200 25F 113 124 135 146 157 168 174 190 201 212 20F 116 128 140 152 164 176 188 200 212 15F 119 132 145 158 171 184 197 210 10F 122 136 150 164 178 192 206
5F 125 140 155 170 185 200 215 0F 128 144 160 176 192 208
-5F 131 148 165 182 199 216
-10F 134 152 170 188 206
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
75 75 75 75 75 75 75 75 75 75 78 79 80 81 82 83 84 85 86 87 81 83 85 87 89 91 93 95 97 99 84 87 90 93 96 99 102 105 108 111 87 91 95 99 103 107 111 115 119 123 90 95 100 105 110 115 120 125 130 135 93 99 105 111 117 123 129 135 141 17 96 103 110 117 124 131 138 145 152 159
99 107 115 123 131 139 147 155 163 171 102 111 120 129 138 147 156 165 174 183 105 115 125 135 145 155 165 175 185 195 108 119 130 141 152 163 174 185 196 207 111 123 135 147 159 171 183 195 207 219 114 127 140 153 166 179 192 205 218 117 131 145 159 173 187 201 215 120 135 150 165 180 195 210 123 139 155 171 187 203 219 126 143 160 177 194 211 129 147 165 183 201 219
Table D-6. Header Temperature for a Building Reference Temperature of 80F
RESET RATIO
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
D-3
Page 80
APPENDIX D
Table D-7. Header Temperature for a Building Reference Temperature of 90F
RESET RATIO
Air
Temp
90F 85F 80F 75F 70F 65F 60F 55F 50F 45F 40F 35F 30F 25F 20F 15F 10F
5F 0F
0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
90 90 90 90 90 90 90 90 90 90
93 94 95 96 97 98 99 100 101 102
96 98 100 102 104 106 108 110 112 114
99 102 105 108 111 114 117 120 123 126 102 106 110 114 118 122 126 130 134 138 105 110 115 120 125 130 135 140 145 150 108 114 120 126 132 138 144 150 156 162 111 118 125 132 139 146 153 160 167 174 114 122 130 138 146 154 162 170 178 186 117 126 135 144 153 162 171 180 189 198 120 130 140 150 160 170 180 190 200 210 123 134 145 156 167 178 189 200 126 138 150 162 174 186 198 210 129 142 155 168 181 194 207 132 146 160 174 188 202 216 135 150 165 180 195 210 138 154 170 186 202 218 141 158 175 192 209 144 162 180 198 216
D-4
Page 81
APPENDIX E
MENU & OPTION FACTORY DEFAULT
BOILER DEFAULT SETTINGS
Setup Menu
Password 0
Language English
Unit of Temp Fahrenheit
Comm Address 0
Baud Rate 9600
Configuration Menu
Internal Setpt 130°F
Unit Type Boiler
Unit Size 1.5 MBTU
Boiler Mode Constant Setpoint
Remote Signal (If Mode = Remote Setpoint, Direct Drive or Combination)
Bldg Ref Temp (If Boiler Mode = Outdoor Reset)
4 – 20 mA / 1-5V
70°F
Reset Ratio (If Boiler Mode = Outdoor Reset)
Outdoor Sensor Disabled
System Start Tmp (If Outdoor Sensor = Enabled)
Setpt Lo Limit 60°F
Setpt Hi Limit 200°F
Temp Hi Limit
Max Fire Rate 100%
Pump Delay Timer 0 min
Aux Start On Dly 0 sec
Failsafe Mode Shutdown
mA Output Fire Rate Out
CAUTION: DO NOT Change
Lo Fire Timer 2 sec
Setpt Limit Band (If Setpt Limiting = Enabled) 5°F
1.2
60°F
215°F
Tuning Menu
Prop Band 70°F
Integral Gain 1.00
Derivative Time 0.0 min
E-1
Page 82
Page 83
APPENDIX F
F-1
Page 84
APPENDIX F
A
REV
REAR
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
GAS FIRED BOILER
AERCO
BENCHMARK 1.5 LOW NOx
SD -A -730
*NOT TO SCALE*
ANCHOR BOLT LOCATION
DRWN BY: SJD
DATE: 10/12/07
F-2
FRONT
1) ALL HOLES ARE FLUSH WITH THE BOTTOM SURFACE OF
THE FRAME
2) ALL DIMENSIONS SHOWN ARE IN INCHES (CENTIMETERS)
NOTES:
Page 85
APPENDIX F
F-3
Page 86
APPENDIX F
A
REV
24"
42"*
24"
28"
24"
FRONT
REAR
1) REAR CLEARANCE MAY BE REDUCED TO 30" DEPENDENT UPON
NOTES:
AND LOCAL CODE REQUIREMENTS
PIPING AND VENTING COMPONENT SELECTION, ARRANGEMENT,
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 LOW NOx
AERCO
GAS FIRED BOILER
INSTALLATION CLEARANCES
DRWN BY: SJD
SD - A - 731
*NOT TO SCALE*
DATE: 10/12/07
SIDE VIEW TOP VIEW
18"
44.5"
101"
79"
LEFT & RIGHT SIDES: 24"
FRONT: 24"
REAR: 42" *
CEILING HIEGHT: 101"
F-4
INSTALLATION CLEARANCES:
1) THIS APPLIANCE MAY BE INSTALLED ON COMBUSTIBLE FLOORING
2) MINIMUM CLEARANCES TO ADJACENT CONSTRUCTION ARE AS
FOLLOWS:
Page 87
APPENDIX F
B
REV
TO AIR-FUEL
VALVE ASSY
AP - A - 829
INTERNATIONAL, INC.
1.5" NPT P/N: 92006-7
FULL PORT BALL VALVE
TEST COCK
NORTHVALE, NJ 07647
FM GAS TRAIN
SAFETY SHUT-OFF VALVE
ACTUATOR W/REGULATOR
BENCHMARK 1.5 LOW NOx
AERCO
P/N 64048
VALVE P/N: 124150
1.5" SAFETY SHUT-OFF
1.5" - SCH.40 PIPE
DRWN BY: SJD
*NOT TO SCALE*
DATE: 12/18/07
HIGH GAS PRESS
SWITCH P/N: 61002-12
1/8" NPT PLUG
(INSTALL MANOMETER HERE)
LOW GAS PRESS
SWITCH P/N: 61002-1
ENTIRE BMK1.5 LN FM
GAS TRAIN P/N: 22039-1
F-5
Page 88
APPENDIX F
1.5" FULL
PORT BALL
VALVE
P/N: 92006-7
B
REV
TEST
COCK
LOW GAS PRESSURE
HERE)
SWITCH P/N: 61002-1
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
1/8" NPT PLUG
(INSTALL MANOMETER
AP -A -830
IRI GAS TRAIN
*NOT TO SCALE*
BENCHMARK 1.5 LOW NOx
VENT TO ATMOSPHERE
PER ANSI Z223.1 (NFPA54)
P/N: 124178
HIGH GAS PRESSURE
SWITCH P/N: 61002-12
CONNECTING FLANGE
1.5" DOUBLE BODY SSOV
1.5" SCH.40 PIPE
3/4" SCH.40 PIPE
DRWN BY: SJD
DATE: 10/11/07
F-6
SAFETY SHUT-OFF VALVE ACTUATOR
W/ REGULATOR P/N: 64048
1.5" DOUBLE BODY
SSOV P/N: 124137
ENTIRE BMK 1.5 LN IRI GAS
TRAIN P/N: 22039-2
NORMALLY OPEN
VENT VALVE
P/N: 122774
SAFETY SHUT OFF VALVE ACTUATOR WITHOUT
PROOF OF CLOSURE SWITCH P/N: 69038
Page 89
APPENDIX F
B
REV
PL -A -156
INTERNATIONAL INC.
23
159 PARIS AVE, NORTHVALE, N.J.
BMK1.5 LOW NOX
*DRAWING NOT TO SCALE*
BLOWER, BURNER, & AIR /FUEL
VALVE ACCESSORIES
DRWN. BY: SJD DATE: 102907
9
18
13 21
10
16
19
15
1 1 42048 PLATE, BURNER
2 1 81063 GASKET, BURNER
4 1 46015 BURNER, BMK 1.5 LOW NOX
3 1 81063 GASKET, BURNER
5 1 81064 GASKET, BLOWER
6 1 24111 BLOWER, AMETEK 8.9"
7 1 59072 OBSERVATION PORT 1/2 NPT
8 1 122435-s SPARK IGNITOR, BMK BOILER
9 1 24113 STAGED IGNITION ASSY, BMK 1.5 LOW NOX
10 1 66006 FLAME ROD, BMK 2.0 LOW NOX
11 1 42049 ADAPTOR, BLOWER-A/F VALVE
24 1 24010-2 A/F VALVE ASSY 1.5 MM
13 1 81057 GASKET, BLOWER
14 1 88004 O-RING #2-244 BUNA-N
15 1 81047 GASKET, GAS INJECTOR
16 1 81048 GASKET, FLAME ROD LOW NOX
17 2 54016 SCREW, MACH #10-32 X .50 LG
18 1 122377 SCREW, MACH #10-32 X 3/8 LG
19 1 54015 SCREW, MACH #8-32 X 3/8 LG
20 6 54027 SCREW, SOC HD CAP M8x1.25 X 16 MM LG
21 6 122544 BOLT, HEX HD 1/4-20 X .75 LG
22 4 54028 SCREW, HEX HD SERRATED 5/16-18
ITEM NO. QTY PART NUMBER DESCRIPTION
23 1 88003 O-RING #2-339
17
11 2420
17
14
6
2
7
5
22
1
4
3
8
APPLY HI TEMP
PRIOR TO ASSY
CONDUCTIVE ANTI -SIEZE
F-7
Page 90
EXHAUST MANIFOLD
APPENDIX F
F-8
DESCRIPTIONQTYPART NO.ITEM
1 2
EXHAUST MANIFOLD143045
EXHAUST MANIFOLD SEAL184020
3
GAS TRAIN ASSEMBLY
ITEM PART NO. QTY DESCRIPTION
STD FM GAS TRAIN ASSEMBLY
IRI GAS TRAIN ASSEMBLY
1
DUAL FUEL FM GAS TRAIN
DUAL FUEL IRI GAS TRAIN
(3)
4
22039-1 22039-2 22039-3 22039-4
BURNER & AIR/FUEL VALVE
DESCRIPTIONQTYPART NO.ITEM
BLOWER, BURNER, & A/F
240125
1
VALVE ASSEMBLY
(SEE PL-A-156)
A/F VALVE ASSEMBLY124010-26
HOSES,GASKETS, & INSULATION
ITEM PART NO. QTY DESCRIPTION
22 88003
1
O-RING #2-339 (A/F VALVE) 23 59041 1 HOSE ASSEMBLY, 4" 24 88004 1
O-RING #2-244 BUNA - N (BLOWER)
25 62005 1 CORD GRIP 26
1241137
2810638
IGNITION ASSY.
(PART OF BURNER ASSY.)
BURNER GASKET
(PART OF BURNER ASS'Y)
9
HEAT EXCHANGER
DESCRIPTIONQTYPART NO.ITEM
BMK1.5LN STAGED
18003610 18003511 12801712
HEAT EXCHANGER
UPPER INSULATION
HEAT EXCHANGER
LOWER INSULATION
HEAT EXCHANGER
13
BLOWER
ITEM PART NO. QTY DESCRIPTION
14 24111 1 BLOWER ASSEMBLY 15 123815 1 IRIS AIR DAMPER 16 81064
1BLOWER GASKET 17 39054 1 ADAPTOR, AIR INLET 18 39059 1 19 97004-18
CAP, SCREENED, AIR INLET 6"
1 HOSE, FLEXIBLE 6" I.D. - A/F 20 123583 3 CLAMP HOSE SAE #96 21 81057 1 BLOWER GASKET (A/F)
AERCO
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 LOW NOx
BOILER PARTS LIST
DRAWN BY: DATE: 12/08/08
*NOT TO SCALE*
SJD
PL - A - 157
(SHEET 1 OF 7)
B
Page 91
CONTROLS
APPENDIX F
F-9
ITEM PART NO. QTY DESCRIPTION
27 123966 1 OVER TEMP SWITCH AUTO 28 123552 1 OVER TEMP SWITCH MANUAL 29 61002-5 1 30 61014 1
BLOCKED INLET SWITCH
BLOWER PROOF SWITCH
31 161560 1 I /O WIRING BOX 32 181197 1 C-MORE CONTROL BOX
GP-122464
33
1 IGNITION TRANSFORMER
34 33048 1 VFD MOUNTING BRACKET 35 64034 1 VFD (120 V)
(1)
36 61012 1 AIR TEMP SENSOR 37 64018 1 TEMPERATURE TRANSMITTER
(1) (1)
(1)
GP-122569
38
1 IGNITION CABLE ASSY.
39 63016 1 BMK1.5LN SHELL HARNESS 40 63038 1
24065-4
41
24065-5
1
BLOWER HARNESS
PROGRAMMED LOGICSTICK
(NON DUAL FUEL) DUAL FUEL, NAT. GAS - STICK DUAL FUEL, PROPANE - STICK24065-6
42 64031 1 120V POWER WIRING BOX
(1)
(5)
44
122843 1 LOW WATER CUT-OFF
BMK1.5LN GAS TRAIN WIRING
116145043
HARNESS
45 123449 1 SHELL TEMP. SENSOR 46 161521 1
(6)
47 61002-1 1
61002-12
(7)(5)
48
61002-12
61002-3
THERMOWELL, DUAL AQUASTAT BULB
LOW GAS PRESSURE SWITCH
HIGH GAS PRESSURE SWITCH
(NON DUAL FUEL)
1
DUAL FUEL HGPS - NAT. GAS DUAL FUEL HGPS - PROPANE
49
OTHER DUAL FUEL COMPONENTS
ITEM PART NO. QTY
(4)(1) (4)(1) (5)(4)(1)
58
63032
(4)
59
(4)
(1)
(4) (4)(1)
62
1
13303660
FUEL SELECTOR SWITCH LABEL
17203061
DUAL FUEL WIRING HARNESS163034
DESCRIPTION "PROPANE" LABEL17203156 "NAT. GAS" LABEL17203257
DOUBLE GAS TRAIN WIRING
HARNESS
FUEL SELECTOR SWITCH165024
FUEL SELECTOR SWITCH
MOUNTINGBRACKET
63
SHEET METAL / PANEL ASSEMBLY
ITEM PART NO QTY DESCRIPTION
64 37017 1 LEFT REAR PANEL 65 37018 1 RIGHT REAR PANEL 66 49064 2 TOP RAIL 67 201233 1 MOUNTING PANEL
68 201113 1
FRONT PANEL
ENCLOSURE
69 201120 1 FRONT DOOR ASSY.
GP-122620
70 71
4 HANDLE
TOP PANEL237019
SIDE PANEL43700272
BMK1.5LN LOGO17400373
OTHER PARTS
ITEM PART NO QTY DESCRIPTION
74 99017 1 75 59050 1 LOGICSTICK LANYARD
GAS PRESSURE SNUBBER -
PART OF GAS TRAIN
PART NO.ITEM
(2)
(1)
SEE SD-A-751
51
(1)(6)
52
(1) (5) (1)
OTHER ACCESORIES / PARTS
DESCRIPTIONQTY
PRESS./TEMP. GAUGE169087- 50
1 PRESSURE RELIEF VALVE
EXT. MANUAL SHUT-OFF VALVE
192006-7
1" DRAIN HOSE, 60" LG19103053 1-1/2" NPT BALL VALVE192006-754
12406055
COND. TRAP ASSEMBLY
NOTES:
NOT SHOWN IN DRAWING
(1) (2)
-5 (30 AND 50 PSI RELIEF VALVE SETTING)
-6 (60,75,100 & 125 PSI RELIEF VALVE SETTING)
-7 (150 PSI RELIEF VALVE SETTING)
(3)
FOR PICTORAL PURPOSES ONLY, FM GAS TRAIN (NON DUAL FUEL) IS SHOWN
(4)
ONLY NEEDED ON DUAL FUEL
(5)
PART OF GAS TRAIN ASSY.
(6)
TWO (2) REQUIRED FOR DUAL FUEL BMK1.5 LN
(7)
SEE DRAWING AP-A-833 FOR DUAL FUEL DETAILS
AERCO
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 LOW NOx
BOILER PARTS LIST
DRAWN BY: DATE 12/08/08
*NOT TO SCALE*
SJD
PL - A - 157
(SHEET 2 OF 7)
B
Page 92
23
APPENDIX F
F-10
7
45
51
35
10
11
A
12
5 20
18
17 15
19
4
DETAIL A
1
AERCO
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 LOW NOx
2
DRWN BY: SJD DATE: 12/08/08
BOILER PARTS LIST
PL - A - 157
*NOT TO SCALE*
(SHEET 3 OF 7)
REV
B
Page 93
16
APPENDIX F
F-11
25
47
14
46
44
B
24 21
22
30
6
29 54
8
48
DETAIL B
AERCO
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 LOW NOx
BOILER PARTS LIST
12/08/08
DATE:
*NOT TO SCALE*
SJDDRWN BY:
PL - A - 157
(SHEET 4 OF 7)
REV
B
Page 94
42
APPENDIX F
F-12
32
284127
35
C
31
37
48
74
75
DETAIL C
34
FUEL SELECTOR SWITCH
(DUAL FUEL ONLY)
61
59
47
AERCO
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 LOW NOx
BOILER PARTS LIST
DRWN BY: DATE:
SJD
12/08/08
*NOT TO SCALE*
PL - A - 157
(SHEET 5 OF 7)
REV
B
Page 95
67
APPENDIX F
F-13
66
68
64 65
AERCO
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 LOW NOx
BOILER PARTS LIST
DRWN BY:
SJD
12/08/08DATE:
*NOT TO SCALE*
PL - A - 157
(SHEET 6 OF 7)
REV
B
Page 96
73
APPENDIX F
F-14
69
71
72
70
AERCO
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 LOW NOx
BOILER PARTS LIST
DRWN BY:
SJD
12/08/08DATE:
*NOT TO SCALE*
PL - A - 157
(SHEET 7 OF 7)
REV
B
Page 97
APPENDIX G
G-1
Page 98
APPENDIX G
LEGEND
UNION
BALANCING VALVE
ISOLATION VALVE
Y STRAINER
PRESSURE &
P&T
TEMPERATURE GAUGE
C
REV
GAS SUPPLY
* 1-1/2" MANUAL
SHUTOFF
VALVE
AT MAXIMUM BTU/HR INPUT,
MAINTAIN MINIMUM GAS
PRESSURE AT 4.0" W.C.
(FM GAS TRAIN); 4.2" W.C.(IRI).
MAX. GAS PRESSURE=2.0 PSIG.
(SEE NOTE 6)
P&T
DRIP TRAP
SYSTEM
RETURN
HEATING
INTERNATIONAL, INC.
NORTHVALE, NJ 07647
BENCHMARK 1.5 MIL. BTU LOW NOx
AERCO
SD-A-735
102307
GAS FIRED BOILER
DATE
DATE
MULTIPLE UNIT INSTALLATION
JK
NTS
APPD.
DWN.BY
SCALE
RELIEF
VALVE (TYP.)
P&T
AUTOMATIC
AIR VENT
AIR
SEPARATOR
DRAIN TRAP
* CONDENSATE
SYSTEM
PUMP
CHECK
VALVE
(TYP.)
1-1/2" NPT
DRAIN CONN.
EXPANSION TANK
DIAPHRAGM TYPE
GAS SUPPLY
DRIP TRAP
G-2
LINE
SIZE
BACKFLOW PREVENTER
BYPASS
SUPPLY
SYSTEM
HEATING
WATER
SUPPLY
PRESSURE
REDUCING
FILL VALVE
(SEE N OTE 7)
Diagram 1
MAINTAIN A REGULATED
4.0" W.C. (FM), 4.2 W.C. (IRI)
GAS PRESSURE AT MAX
BTU/HR INPUT
* 1-1/2" MANUAL
SHUTOFF
VALVE
(TO BOILER)
NOTES:
CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT 18'' ABOVE FLOOR.
2) SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN FREELY, BY GRAVITY, TO A
1) FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE DIMENSIONAL DRAWING (AP-A-739).
3) ALL (*) ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY.
ELECTRIC CONNECTIONS (SERVICE SWITCHES, COND UIT BOXES) SHOULD LIKEWISE BE 6" AWAY FROM SIDE PANELS.
FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND
4) LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6'' FROM BOILER
5) THIS IS A TYPICAL INSTALLATION DRAWING. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED.
SEE DIAGRAM 1
DOWNSTREAM OF THE 2" MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO 2.0 PSIG.
7) A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSAC HUSETTS, REGARDLESS OF SUPPLY PRESSURE.
6) WHEN AVAILABLE GAS PRESSURE IS GREATER THAN 2.0 PSIG, A LOCK-UP STYLE REGULATOR MUST BE INSTALLED
Page 99
APPENDIX G
G-3
Page 100
APPENDIX G
G-4
Loading...