Quick Start Technical Support (800) 726-8663 61200335L1-13B
TOTAL ACCESS® 4303 DC POWER SUPPLY
October 2001
Copyri ght © 2001 ADTRAN All rights rese rved
CLEI: SLPOCD0C_ _
DC SUPPLY
1200335L1
POWER
TEMP
fa
FACEPLATE LEDS
POWER LED Description
Off Both –48V fuses blown, power not supplied to
the shelf, or incorrect polarity on the voltage
supplied to the shelf.
Green Power supplied is the correct voltage and
polarity; backplane and hot insertion voltages
correct.
Red –48V input present; no backplane voltage and
no hot insertion voltage.
Amber –48V input and hot insertion voltage present;
no backplane voltage.
TEMP LED Description
Off Normal
Red Over-temperature condition
FUNCTIONALITY
The Total Access 4303 DC Power Supply furnishes the voltages
necessary for proper backplane operation. The DC Power Supply
also provides the voltages that enable hot insertion of the option
cards and SCUs. The D C P ower S upply does not, however, provide the voltages necessary to power individual option cards or the
SCUs as each card has its own DC-DC supply.
In addition, the DC Power Supply in slot PS-A provides alarm relay
output functional ity . If only one DC Power Supply is used, place
the DC Power Supply in PS-A to provide alarm relay facilities. The
DC Power Supply, as well as all Total Access 430 3 o ption modules and SCUs, has protection against the wrong voltage polarity
being applied to the shelf.
INSTALLATION INFORMATION
• Insert the module into either slot PS-A or PS-B (hot insertion
permissible).
• When power is supplied to the shelf, v erify that the Power LED is
green.
• If power is supplied to the shelf and the Power LED does not
illuminate, remove power and verify polarity.
• To v erify one or both -48V supply v oltages, use the SCU terminal
menus (see SCU Quick Start, 61200334L1-13A) and navigate
the following path:
System Status/System Ala rms/–48V Bus.
.
SPECIFICATIONS
Input voltage –42 to –54 VDC
Operating temperature
Storage temperature
Over-temperature Indication
o
C to 50oC
0
o
C to 70oC
–40
o
C + 10oC
90
Relative humidity 0% to 95% noncondensing
–48V short circuit protection Fused (1 amp)
Backplane voltage short
Self-mending
circuit protection
Compliance FCC Part 15, UL 60950,
NEBS Level 3
Warranty 10 years
Quick Start Technical Support (800) 726-8663 61200335L1-13B
TOTAL ACCESS® 4303 DC POWER SUPPLY
October 2001
Copyri ght © 2001 ADTRAN All rights rese rved
AUD. ALARM OUTPUTS
CRI - A MAJ - A MIN - A
NO COM NC NO COM NC NO COM NC
A MISC B
TRS ABABA BAB
TRS
ACO RMT
(-)
VIS. ALARM
OUTPUTS
CRI - V MAJ - V MIN - V
NO COM NC NO COM NC NO COM NC
TX 4
RX 4
AUX1 AUX2
AUX1 AUX2
NOCOM NC
10-15A Fuse
ADTRAN 1999 © COPYRIGHT
TA 4303
Backplane
NOCOM NC
Minimum 12 AWG wire
Minimum 12 AWG wire
(+)
E - NET B E - NET A
ADMIN
Minimum
10 AWG wire
Chassis
Ground
EXT STA CLK
P50 P52 P51
+_s
+_s+_s
TX 3
5200330-1B
NTWK MGMT
RX 3
A - IN A - OUT B - IN
-48 VDC PRI
-48 VDC RET
P53
+_s
B - OUT
TX 2
RX 2
-48 VDC SEC
-48 VDC RET
TX 1
RX 1
Minimum 12 AWG wire
Minimum 12 AWG wire
10-15A Fuse
(-)
(+)
Primary 48V Supply
Note: Only one of the above supplies is necessary for proper operation.
Chassis
Ground
Secondary 48V Supply
Chassis
Ground