ADTRAN OPTI-T200 User Manual

TOTAL ACCESS®OPTI-T200
JOBAID
61184400L1-22A
0309
OPTI-T200
CLEI: SOI4JN6D_ _
LED STATUS
STATUSOff No power to unit
Green Power up and initialization OK
Yellow Unit is in Out-of-Service – Unassigned modeFlashing Yellow Unit is in Out-of-Service – Maintenance mode
Red Unit has an equipment failure
OPTICS Green Normal Operation
Yellow Soft failure (e.g. RDI)Flashing Yellow Unit in Test (e.g. Loopback)
Red LOS, LOL, or other hard alarms on optical
interface
Flashing Red Unit in Test (e.g. Loopback) with an alarm present
on the Optical Interface
DS3 Off DS3 disabled
Green DS3 normal operation
Yellow Soft failure (e.g. RDI)Flashing Yellow Unit in Test (e.g. Loopback)
Red LOS, LOL, or other hard alarms on DS3 interfaceFlashing Red Unit in Test (e.g. Loopback) with an alarm present
on the DS3 Interface
CRAFT INTERFACE
Connect to terminal using a serial cable with a male DB-9 connector.
Set VT100 terminal emulation to 9600 bps, 8 Data Bits, No Parity, 1 Stop Bit,
and No Flow Control.
Baud rate is configurable at 9600, 19,200, 38,400 or 115,200 bps.
DESCRIPTION
The OPTI-T200 is designed to work in a back-to-back mode of operation, OPTI-T200 to OPTI-T200. It uses a standard 1310 nm OC3 signal to interface between the systems and provides a single DS3 signal to the loop. The OPTI-T200 provides DCC communication with TL1 support. A craft port and an Ethernet port are available on the front panel for management. The OPTI-T200 is a T200 mechanics card, which will fit standard T200 and T400 enclosures.
Compliant with SONET standards, the OPTI-T200 functions as a terminal multiplexer, detecting standard optical, SONET, and DS3 related alarms and conditions. The OPTI-T200 is easily managed with TL1 or TCP/IP commands, or Telnet sessions separately to each system or via the craft interface.
C A U T I O N
For a complete Installation and Maintenance Practice (P/N 61184400L1-5): 877-457-5007, Faxback Document 918. Please have your fax number ready.
INSTALLATION
The OPTI-T200 is a T200 mechanics card which will fit standard T200 and T400 enclosures. Ensure the appropriate chassis is installed before proceeding with the installation.
Carefully insert the OPTI-T200 halfway into the selected slot. Route the fiber cables to the front panel and approximately 4 inches past the SC receptacles (to create slack). Gently but firmly push the OPTI-T200 all the way into the slot, being careful not to pinch the fibers between the front panel and the shelf.
WARNING: Once fully inserted into the chassis, the module will be powered (provided power
is connected to the chassis).
When the OPTI-T200 powers up, it performs a self-test. The front panel LEDs illuminate for approximately 8 seconds. The self-test is complete once the STATUS LED illuminates Green.
ALARM CONTACT DEFINITION
Lead Assignment Contact (functionally) * Contact Rating
T (pin 7) Failure detected on optical facility Normally Open 60 VDC R (pin 13) 0.2 A T1 (pin 41) Failure detected on coax facility Normally Open 1M cycles (min) R1 (pin 47) 40ºC to +65ºC (temp)
NOTE: Simultaneous T/R & T1/R1 contact closures used to indicate internal unit failure, loss
of OC-3/DS-3 inputs, or loss of power.
POWER: –48VR = Pin 17, –48VDC = Pin 35, Frame-GND = Pin27.
1
2
C A U T I O N
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
!
TOTAL ACCESS OPTI-T200
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
www.adtran.com
61184400L1-22A
ACCOUNT PROVISIONING
1. Account 1 a) User Name – User Defined, up to 15 characters b) Password – User Defined, up to 15 characters c) Permission Level – Disabled, Read Only, Read-Write, Administrator d) Delete Account
2. Account 2 – Same options as Account 1
3. Account 3 – Same options as Account 1
4. Account 4 – Same options as Account 1
5. Account 5 – Same options as Account 1
6. Account 6 – Same options as Account 1
7. Account 7 – Same options as Account 1
8. Account 8 – Same options as Account 1
9. Account 9 – Same options as Account 1
10. Account 10 – Same options as Account 1
SOFTWARE UPGRADE
Software download for the local OPTI-T200 is provided using XModem or YModem via the craft port or TFTP, XModem or YModem via Ethernet. Software download to a remote OPTI-T200 is accomplished either from the CO OPTI-T200 craft port or its Ethernet port. The download is carried over the DCC channel. TFTP is supported from only the Ethernet interface, and both systems would require IP addresses.
COMPLIANCE
This product intended for use in Restricted Access Areas only, and is intended to be installed in a Type “B” or “E” enclosure. This product complies with UL 60950.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Changes or modifications not expressly approved by ADTRAN could void the user’s authority to operate this equipment.
WARRANTY
ADTRAN will replace or repair this product within the warranty period if it does not meet its published specifications or fails while in service. Warranty information can be found at www.adtran.com/warranty. U.S. and Canada customer Faxback: 877-457-5007, Document 414.
Code Input Output
Power Code (PC) F C Telecommunication Code (TC) – Installation Code (IC) A
PROVISIONING OPTIONS
Upon initial installation, the OPTI-T200 uses factory default settings. To provision the OPTI-T200, connect a terminal emulator via the RS-232 (DB-9) connector on the front panel. The terminal must be VT100 compatible and set for 9600 bps, 8 data bits, no parity and 1 stop bit. The following table lists the provisioning settings and their default values. The settings are retained in a nonvolatile memory device in case of power loss to the OPTI-T200.
Options Settings (Default in Bold)
Service State In Service, Out Of Service-Unassigned, Out Of Service-Maintenance
DS3 Provisioning
DS3 Interface Enable, Disable DS3 Line Build Out Short, Long
Signal Fail (SF) Thresh 1x10-3, 1x10-4, 1x10
-5
Signal Degrade (SD) Thresh 1x10-5, 1x10-6, 1x10-7, 1x10-8, 1x10
-9
Clock Source (TX) 1. Receive OC-3
2. Free Run CLLI Code User definable up to 20 characters
Network Provisioning
IP Address User Defined
Format = x.x.x.x where x = 0–255
Subnet Mask User Defined
Format = x.x.x.x where x = 0–255
Default Gateway User Defined
Format = x.x.x.x where x = 0–255 Telnet Menu Port User defined = 0–65535 (23) Telnet (TL-1) Port User defined = 0–65535 (2001)
Time and Date User Defined Mount Location Central Office, Remote Account Provisioning See the Account Provisioning section to the right of this table. Restore Factory Defaults Software Upgrade TFTP, XModem, YModem
NOTE: To navigate through the menus, select the desired entry and press Enter. To work
backward in the menus, press the Escape key. Some entries can be changed in only the Out-of-Service – Maintenance mode.