ADTRAN Power Supply-Battery Charger User Manual

0 (0)
ADTRAN Power Supply-Battery Charger User Manual

AC/DC POWER SUPPLY AND BATTERY CHARGER

JOBAID

61175044L2-22A

0002

AC/DC POWER

SUPPLY AND BATTERY CHARGER

CLEI:SIMPAAAARA

C A U T I O N !

SUBJECT TO ELECTROSTATIC DAMAGE

OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

MOUNTING INSTRUCTIONS

1Remove the TA 750/850 AC Power Supply (ADTRAN part # 1175043LX) from the box and inspect for damage. If damage is apparent, contact your carrier or supplier.

Place the power supply with the power cord oriented 2downward.

3Use four #6 x 3/8" machine screws (supplied) to mount the power supply to either side of the TA 750/850 shelf.

Note: Threaded mounting holes are provided on both sides of the shelf.

Note: For battery backup installations, it is recommended to mount the power supply on the left side of the TA 750/850 shelf, next to the battery cover hinge.

Note: Alternatively, the power supply can be mounted to the backboard with four #6 x 1" wood screws (not supplied).

STATUS LEDS

AC Power Operation (AC power only) Battery Operation (AC power supply or battery backup)

GREEN

OK

GREEN

OK (charging)

YELLOW

Power Fail

YELLOW

Discharging

RED

Power Fail

RED

Low (<40 V)

OFF

Power Fail

OFF

Disconnected

RELAYS

Alarm Relay

Provided for customer use

Condition

Alarm Relay

Normal

Open

AC Power Failure/

Cycles open/closed once per second if AC voltage <88 Vrms at

Battery Backup engaged

full load and battery backup is connected

Battery voltage <45V

Stays closed if voltage <45 VDC to indicate that battery is

 

becoming depleted

Battery Disconnect Relay

Disconnects battery pack from the system if the battery voltage falls below 40 VDC

Prevents damage to batteries

CIRCUIT BREAKER

The device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:

(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Changes or modifications not expressly approved by ADTRAN could void the user’s authority to operate this equipment.

WARRANTY

Warranty for Carrier Network products manufactured by ADTRAN and supplied under Buyer’s order for use in the U.S. is ten (10) years. For a complete copy of ADTRAN’s U.S. Carrier Network Equipment Warranty: (877) 457-5007, Document 414.

3-amp circuit breaker

Protects unit from over-current

Rocker button extends out from front panel when tripped

Reset by pushing in on the rocker button

GROUNDING

18 AWG or larger ground wire recommended to connect additional ground connector to 'ground bus' in customer equipment room

ELECTRICAL SPECIFICATIONS

AC input: 115 V nominal

Range: 90 to 132 VAC

DC output: -54 V, 60 W average, 100 W peak

Battery charging: 16 hr nominal, 24 hr maximum

Battery discharge: Up to 8 hours

TELECOMMUNICATIONS CODES

Code

Input

Output

IC

F

C

TC

PC

R

For a complete I&M Practice: 877.457.5007, Document # 422. Please have fax number available.