Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage!
General Safety Information
Only qualified personnel should install and maintain this
system. Personnel should have a clear understanding of
these instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
1. Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electrical Code (CEC) in
Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin wheel faster than maximum cataloged
fan RPM. Adjustments to fan speed significantly
affect motor load. If the fan RPM is changed, the
motor current should be checked to make sure it is
not exceeding the motor nameplate amps.
5. Verify that the power source is compatible with the
equipment.
6. Never open access doors to the unit while it is
running.
WARNING
The roof lining contains high voltage wiring. To
prevent electrocution, do not puncture the interior or
exterior panels of the roof.
DANGER
• Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch
or breaker to prevent accidental power up.
• If this unit is equipped with optional gas accessories,
turn off gas supply whenever power is disconnected.
CAUTION
This unit is equipped with a compressed refrigerant
system. If a leak in the system should occur,
immediately evacuate the area. An EPA Certified
Technician must be engaged to make repairs or
corrections. Refrigerant leaks may also cause bodily
harm.
CAUTION
When servicing the unit, the internal components may
be hot enough to cause pain or injury. Allow time for
cooling before servicing.
Packaged Rooftop Ventilator1
Table of Contents
General Safety Information ......................1
This product may have been subject to road salt during
transit. If so, immediately wash off all visible white
reside from all exterior surfaces. Upon receiving the
product, check to ensure all line items are accounted
for by referencing the delivery receipt or packing list.
Inspect each crate or carton for shipping damage before
accepting delivery. Alert the carrier if any damage is
detected, do not refuse shipment. The customer shall
make notation of damage (or shortage of items) on the
delivery receipt and all copies of the bill of lading which
should be countersigned by the delivering carrier. If
damaged, immediately contact your manufacturer’s
representative. Any physical damage to the unit after
acceptance is not the responsibility of the manufacturer.
Handling
Units are to be rigged and moved by the lifting brackets
provided. Location of brackets varies by model and size.
Handle in such a manner as to keep from scratching or
chipping the coating. Damaged finish may reduce ability
of unit to resist corrosion.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
The ideal environment for the storage of units and
accessories is indoors, above grade, in a low humidity
atmosphere which is sealed to prevent the entry of
blowing dust, rain, or snow. Units designed for outdoor
applications may be stored outdoors. All accessories
must be stored indoors in a clean, dry atmosphere.
Indoor
Maintain temperatures evenly to prevent condensation.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To
avoid condensation, allow cold parts to reach room
temperature. Leave coverings loose to permit air
circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off
the floor. Clearance should be provided to permit air
circulation and space for inspection.
Outdoor
The unit should be placed on a level surface to prevent
water from leaking into the unit. The unit should be
elevated so that it is above water and snow levels.
Ensure sufficient support to prevent unit from settling
into soft ground. Locate parts far enough apart to
permit air circulation, sunlight, and space for periodic
inspection. To minimize water accumulation, place all
unit parts on blocking supports so that rain water will
run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Inspection and Maintenance
While in storage, inspect units once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the fan wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Units with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Wipe thoroughly clean
with Tectyl® 506 (Ashland Inc.) or the equivalent. For
hard to reach internal surfaces or for occasional use,
consider using Tectyl® 511M Rust Preventive, WD-40®
or the equivalent.
Removing from Storage
As units are removed from storage to be installed
in their final location, they should be protected and
maintained in a similar fashion until the equipment goes
into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
1. Check all fasteners, set screws on the fan, wheel,
bearings, drive, motor base, and accessories for
tightness.
2. Rotate the fan wheel(s) by hand and assure no parts
are rubbing.
Packaged Rooftop Ventilator3
Product Overview
A horizontally configured High Percentage Outdoor
Air unit designed for installation either indoors or
outdoors. Each unit has multiple options for cooling
and/or heating. The unit is designed to replace air that
is exhausted from the building and also heat and cool,
as needed. The air volume produced by the unit is
constant, but can be optionally modulated to provide a
variable air volume (VAV) and recirculation is also offered
as an option.
Cooling
Units have the following cooling options available:
• Packaged DX
• Split DX
• Chilled water coil
• Air-source heat pump (ASHP)
Units with packaged DX are shipped fully charged with
refrigerant and are ready for operation upon arrival.
Heating
There are three different optional heat sources that can
be ordered for this unit:
• Indirect gas-fired furnace with one or two sets of
heat exchangers
• Electric heat with infinitely variable SCR control
• Hot water coil
• Air-source heat pump (ASHP)
Airflow Arrangement
The unit is capable of Constant Air Volume (CAV),
Variable Air Volume (VAV), 100% Outdoor Air and have
recirculating air options.
Safety Listing
Models are listed per ANSI/UL 1995, Heating and
Cooling Equipment and are ETL Certified.
Models and Capacities
The packaged rooftop ventilator is built on three
different platform sizes.
ModelCooling Capacity
XRV-255 to 15 tons
XRV-4515 to 30 tons
XRV-7025 to 45 tons
Packaged Rooftop Ventilator4
Subassemblies
Blower
Either one or two plenum-type fans. All units are
equipped with a plenum fan for Supply Air and a second
may be selected for Exhaust (Relief) Air.
Each unit having packaged DX will have either one or
two refrigerant compressors. Optionally, one of the
compressors may be a digital scroll type compressor.
Air-source heat pump units will have one inverter
scroll compressor and may contain a second staged
compressor.
Dampers
Motorized outdoor air damper, motorized recirculating
damper. Optional return air damper. Optional gravitytype exhaust damper.
Optional Barometric Relief Damper
Used during economizer mode of the unit when building
pressure increases, relief damper will open due to over
pressurization.
Electric Heater
An SCR controlled electric heater (not shown) is
available on the units. It has its own control panel and
may require a separate power supply. See unit-specific
wiring diagram.supply and has its own control panel.
See unit-specific wiring diagram.
Low Sound Condenser Fans
(optional)
Coils
(optional)
Supply Filters - All housings are available with a filter
bank depth of either 2 or 4-inch.
Indirect Gas-Fired Furnace - Furnace model PVG is
available on XRV-25 and XRV-45. Model XRV-70 uses
furnace model PVF 200-600 or model HMA 700-800.
Packaged DX System - Any unit may be ordered with a
packaged DX system. Housing size XRV-25 will include
either one or two compressors; XRV-45 will include two
compressors; housing size XRV-70 will include four
compressors; a condenser coil(s) and evaporator coil(s)
and all required components. Units that have packaged
DX are charged with R410A refrigerant. Do not use tools
or parts designed for other refrigerants on these units.
Air-Source Heat Pump - Units having an air-source heat
pump will include either one or two compressors, an
indoor and outdoor coil, and all required components.
Air-source heat pump units are charged with R410A
refrigerant. Do not use tools or parts designed for other
refrigerants on these units. Option not available on the
RV-110 and RVE-180.
Split DX
The unit may be ordered with a split DX system for
connection to a building cooling system.
Vestibule
Some units may be ordered with a factory-assembled
vestibule that is to be field-attached to the side of the
unit. See lifting instructions.
Outdoor Air Filters
Weatherhood Filters
(metal mesh)
Condenser Coils
(optional)
Packaged DX
Compressors
(optional)
Furnace Vest Plate
and
Furnace Control Center
(optional)
Main Control
Center
Plenum-Type
Supply Air Blower
Indirect Gas-Fired Furnace
(optional)
Outdoor Air
Damper
Recirculating
Damper
Plenum-Type
Exhaust Air Blower
Packaged Rooftop Ventilator5
Installation
Typical Unit Weights and Dimensions
A
B
1
2
5
4
3
W
7
6
L
H
Component Access
1Optional Inverter Compressor
2Optional Compressor/Electrical
3Optional Gas Furnace/Optional Electric Heater
4Electrical
5Supply Blower
6Coil
7Filters
(A)
Condensing
Section
(B)
Unit
Size
XRV-255-1559.352.598.622.130.12,700
XRV-4515-3072.568.210927.730.14,500
XRV-7020-45906815622/27^306,400
All dimensions are shown in inches. Weight is shown in pounds and includes largest supply and exhaust fans, PDX with reheat, largest indirect-gas
fired furnace, and all dampers. Actual weights will vary based on the unit configuration.
* Only available with powered exhaust ** Only available without barometric relief
+
Only available with barometric relief ^ Above 12,000 cfm
Nominal
tonnage
(tons)
Height
(H)
Width
(W)
Length
(L)
Intake
Nominal
weight
(lbs)
Outdoor
Intake
End
Supply
Discharge
Bottom
or
Side
Return
Intake
Bottom,
End**
or
Side*
Exhaust
Discharge
+
End
or
Side*
Service Clearances
CC End
ACS
Clearance
NA
Clearance
OA End
Unit SizeACSCC End OA End
XRV-25404242241830
XRV-45365842241830
ACS = Access
CC = Control Center
NA = Non-Access
OA = Outdoor Air Weatherhood
Packaged Rooftop Ventilator6
XRV-70365258241830
All dimensions are shown in inches.
*NA from Unit = no condensing section or piping vestibule
**NA from CS = condensing section
***NA from Vest = piping vestibule
*NA
from
Unit
**NA
from
CS
***NA
from
Vest
Installation
Additional Clearances for
Packaged DX Units
Packaged DX units require additional clearance
because they must have unrestricted air movement
around the condenser coil and condenser fans. Hot air
is being discharged from the condenser fans during
operation. Enough clearance must be provided to
avoid recirculation or coil starvation. When equipped
with condenser coils, the unit should never be placed
under an overhang or inside a building. A minimum of
48inches above the condenser fans is acceptable, but
unobstructed is strongly recommended.
Minimum 48 inches clearance
Condenser Fans
Minimum 18 inches
clearance
Condenser Coil
End view of rooftop unit with Packaged DX
Handling Concerns for
Packaged DX or Air-Source Heat Pump
Units with PDX or ASHP have a system that is
pressurized with refrigerant. If damage occurs, the
refrigerant could leak into the atmosphere or cause
bodily harm due to the extreme cold nature of
expanding refrigerant. Use protective equipment such
as gloves and safety glasses to minimize or prevent
injury in case of a system leak during installation.
Before Lifting
Before lifting, be sure that all shipping materials have
been removed from the unit.
Vestibule
Determine whether or not the unit has a vestibule that
must be field-attached to the side of the unit. Vestibules
are shipped assembled but detached from the unit.
They have lifting lugs on them so they can also be lifted
by crane, but the installed location of the unit may make
it preferable to install the vestibule on the unit prior to
lifting.
Field Power Access
Determine where high voltage and low voltage wiring is
to be brought into the cabinet. If wiring is to be brought
into the cabinet through the floor, see Alternate Supply
Entry Locations in this manual. If unit is to be installed
on a roof, cut access openings in the roof deck as
needed.
Additional Clearances for
Air Source Heat Pump
IMPORTANT
Air-source heat pumps are equipped with a defrost
cycle to remove ice from the outdoor coil. During
defrost cycles, melted water may drip from the bottom
of the refrigeration section under the outdoor coil.
In cold climates, proper drainage/heat tape must be
installed under the outdoor coil to prevent the buildup
of ice on the roof.
Air-source heat pump units require additional clearance
because they must have unrestricted air movement
around the outdoor coil and outdoor fans. Enough
clearance must be provided to avoid recirculation or
coil starvation. Air-source heat pump units should
never be placed under an overhang or inside a building.
A minimum of 48-inches above the outdoor fans is
acceptable, but unobstructed is strongly recommended.
Packaged Rooftop Ventilator7
Installation
W
L
L
W
Lifting
1. Ensure that all shipping materials have been
removed from unit.
2. To assist in determining rigging requirements,
weights are provided in the Unit Weights &
Dimensions section of this manual.
3. Unit must be lifted by all lifting lugs provided at top
of unit.
4. Spreader bars must span the unit to prevent
damage to the cabinet by the lift cables.
5. Never rest the spreader bar on the unit.
WARNING
Spreader bars are required to prevent damage to the
cabinet, failure to do so can result in damage that is
the installer’s responsibility.
6. Always test-lift the unit to check for proper balance
and rigging before hoisting to desired location.
7. Never lift unit by weatherhood.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by others)
has been applied to the top of the curb prior to
lifting the unit and setting on the curb.
11. Do not use fork lifts for handling unit.
Roof Curb Mounting
Roof curb details, including duct locations and
dimensions, are to be found in the roof curb assembly
instructions.
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
1. Factory-supplied roof curbs. Roof curbs are model
GKD which are shipped in a knockdown kit (includes
duct adapters) and require field assembly (by others).
Assembly instructions are included with the curb kit.
2. Install curb. Locate curb over roof opening and
fasten in place. Check that the diagonal dimensions are
within ± 1/8inch of each other and adjust as necessary.
For proper coil drainage and unit operation, it is
important that the installation be level. Shim the curb as
required to level. Install gasketing on top surface of curb
(provided by others).
3. Install ductwork. Installation of all ducts should
be done in accordance with SMACNA and AMCA
guidelines. Duct adapters are provided to support ducts
prior to setting the unit.
4. Set the unit. Lift unit to a point directly above the
curb and duct openings. Guide unit while lowering to
align with duct openings. Roof curbs fit inside the unit
base. Make sure the unit is properly seated on the curb
and level.
5. Fasten the unit, Fasten the unit to the curb/
equipment support(s) using appropriate methods. The
installer is responsible for determining appropriate
support and fastening methods to ensure compliance
with all applicable codes.
6. Install vestibule. If unit was ordered with a vestibule
and it has not yet been attached to the unit, caulk and
attach the vestibule at this time.
W
Packaged Rooftop Ventilator8
Typical Unit with Condensing Section and
Factory-Supplied Curb Kit
L
Installation
L
W
Optional Piping Vestibule
If the unit was ordered with the vestibule, the NA (NonAccess side) clearance dimension must be measured
from the vestibule.
L
W
Typical Unit with Piping Vestibule and
Factory-Supplied Curb Kit
Rail Mounting and Layout
• The units may be installed on rails provided and
installed by others. Ensure that rails are designed to
handle the weight of the unit and provide proper load
distribution on building supports.
• Make sure that rail positioning does not interfere with
the openings on the unit.
• Rails should run the width of the unit and extend
beyond the unit a minimum of 12 inches on each side.
• Set unit on rails.
Ductwork Configurations
NOTE
Downblast Discharge Ductwork - whenever
downblast discharge is used, the ductwork directly
beneath the unit must be connected with either a “T”
or an “L” configuration and the area directly beneath
the heat source must not have any openings such
as louvers or grates.
Typical Unit Installed on Rails Supplied by Others
No louvers or grates
Packaged Rooftop Ventilator9
Recommended Electrical and Gas Supply Entry Locations
Manufacturer recommends that electrical service and
gas supply be brought into the cabinet through the
end wall, as shown below. There are three penetrations
into the cabinet that are required; one for high voltage
supply wiring, one for low voltage control wiring and one
for either gas supply or high voltage supply wiring for an
electric heater.
Optional Unit
Disconnect
Indirect
Gas
Supply
Location
Field Wiring
Recommended Gas and Electric Supply Entry Locations
Alternate Supply Entry Locations
Each installation is unique and as a result, alternate
entry locations may be field-located. Before using any
alternate entry location, verify the suitability of the
location and ensure the use of an alternate location
does not interfere with unit wiring, components or
functionality.
WARNING
Never drill holes in the roof of the unit! There is high
voltage wiring located between the inner and outer
roof panels. Damage to the wiring could cause severe
bodily harm or death.
Optional Gas Piping
Units with indirect gas-fired furnaces require fieldsupplied and installed gas supply piping.
Housing
Size
Total Heating
Capacity
(Input in MBH)
Gas
Connection
Size
Max Gas
Pressure
100
150
XRV-25
200
¾” NPT14 in. wg.
250
300
300
XRV-45
¾” NPT14 in. wg.400
500
200
250
300
350
XRV-70
400
¾” NPT14 in. wg.
500
600
700
800
Gas Connections
If this unit is equipped with an indirect gas-fired furnace,
connection to an appropriate gas supply line will be
required. For complete information on installation
procedures for the optional gas furnace, refer the
PVF/PVG Indirect Gas-Fired Heat Module Installation,
Operation, and Maintenance Manual.
Ground
Joint
Gas Cock
From Gas Supply
Bleeder Valve or
1/8 in Plugged Tap
Typical Gas Supply Piping Connection
Packaged Rooftop Ventilator10
Union
8 in. Trap
Gas to
Controls
Piping Installation
Optional Coil Piping
Factory-installed cooling and heating components are
mounted in the coil section of the unit. The coil section
is downstream of the energy wheel on the supply air
side of the unit. Note the coil connection locations on
the picture. Coil connections are located external to the
unit.
Note: DX coil liquid connection is internal to units.
Water Coils
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. When installing couplings,
do not apply undue stress to the connection
extending through the unit. Use a backup pipe
wrench to avoid breaking the weld between coil
connection and header.
2. Connect the water supply to the bottom connection
on the air leaving side and the water return to the
top connection on the air entering side. Connecting
the supply and/or return in any other manner will
result in very poor performance. Be sure to replace
factory-installed grommets around coil connections
if removed for piping. Failure to replace grommets
will result in water leakage into the unit and altered
performance.
3. Water coils are not normally recommended for
use with entering air temperatures below 40°F. No
control system can be depended on to be 100% safe
against freeze-up with water coils. Glycol solutions
or brines are the only safe media for operation of
water coils with low entering air conditions. If glycol
or brine solutions are not used, coils must be drained
when freezing conditions are expected. If required,
vent and drain connections must be fieldpiped, external to the unit.
4. Pipe sizes for the system must be selected on
the basis of the head (pressure) available from the
circulation pump. The velocity should not exceed
6 feet per second and the friction loss should be
approximately 3 feet of water column per 100 feet
of pipe.
5. For chilled water coils, the condensate drain
pipe should be sized adequately to ensure the
condensate drains properly. Refer to Drain Trap
section.
Direct Expansion (DX) Coils (Split DX)
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Undue stress should not
be applied at the connection to coil headers.
2. The condensate drain pipe should be sized
adequately to ensure the condensate drains properly.
Refer to Condensate Drain Trap section.
3. When connecting suction and liquid connections
make sure the coil is free from all foreign material.
Make sure all joints are tight and free of leakage. Be
sure to replace factory-installed grommets around
coil connections if removed for piping.
4. Manufacturer does not supply compressor,
condensing units, or thermal expansion valve (TXV)
with standard models. For further instruction on
DX coil installation and operation contact your
compressor and/or condenser manufacturer.
Condensate Drain Trap
This unit is equipped with a stainless steel condensate
pan with a stainless steel connection. It is important
that the drain connection be fitted with a P trap to
ensure proper drainage of condensate while maintaining
internal static pressures and to prevent migration of
sewer gas back into the unit.
A P trap assembly (kit) is supplied with each unit and is
to be assembled and installed
as local conditions require and
according to the assembly
instructions provided with
the P trap. If local and area
codes permit, the condensate
may be drained back onto the
roof, but a drip pad should be
provided beneath the outlet.
If local and area codes require a permanent drain line,
it should be fabricated and installed in accordance with
Best Practices and all codes.
In some climates, it will be necessary to provide freeze
protection for the P trap and drain line. The P trap
should be kept filled with water or glycol solution at all
times and it should be protected from freezing to protect
the P trap from damage. If severe weather conditions
occur, it may be necessary to fabricate a Ptrap and
drain line of metal and install a heat tape to prevent
freezing.
Condensate Overflow Switch
This unit is equipped with an optional factory-mounted
condensate overflow switch. In the event that a high
level of condensate is detected, a dry contact will be
powered (24 VAC). This dry contact can be used for
field monitoring of condensate levels. All monitoring and
control shall be provided by others.
Packaged Rooftop Ventilator11
Electrical Information
WARNING
The roof lining contains high voltage wiring. To prevent
electrocution, do not puncture the interior or exterior
panels of the roof.
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
For units with a gas furnace, if you turn off the power
supply, turn off the gas.
IMPORTANT
Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached on
the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the latest
edition of the National Electric Code ANSI/NFPA70
and any local codes that may apply. In Canada, wiring
should be done in accordance with the Canadian
Electrical Code.
IMPORTANT
The equipment must be properly grounded and
bonded. Any wiring running through the unit in the
airstream must be protected by metal conduit, metal
clad cable or raceways.
CAUTION
If replacement wire is required, it must have a
temperature rating of at least 105ºC, except for an
energy cut-off or sensor lead wire which must be rated
to 150ºC.
DANGER
High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.
Determine the Size of the Main Power
Lines
The unit’s nameplate states the voltage and the unit’s
MCA. The main power lines to the unit should be sized
accordingly. The nameplate is located on the outside of
the unit on the control panel side.
Determine the Size of Electric Heater
Wiring
An optional electric heater may require a separate
power supply. The power connection should be made
to the factory-provided electric heater disconnect and
must be compatible with the ratings on the nameplate,
supply power voltage, phase and amperage. Consult
ANSI/NFPA 70 and CSA C22.1 for proper conductor
sizing.
Provide the Opening(s) for the Electrical
Connections
Electrical openings vary by unit size and arrangement
and are field-supplied.
Connect the Power Supplies
Connect the main power lines and electric heater power
lines to the disconnect switches or terminal blocks
and main grounding lug(s). Torque field connections to
manufacturer’s recommendations.
Wire the Optional Convenience Outlet
The convenience outlet requires a separate 115V power
supply circuit. The circuit must include short circuit
protection which may need to be supplied by others.
Connect Field-Wired Low Voltage
Components
Most factory-supplied electrical components are
prewired. To determine what electrical accessories
require additional field-wiring, refer to the unit-specific
wiring diagram located on the inside of the control
center access door.
The low voltage control circuit is 24 VAC and control
wiring should not exceed 0.75 ohms.
Control wires should not be run inside the same conduit
as that carrying the supply power. Make sure that
field-supplied conduit does not interfere with access
panel operation. All low voltage wiring should be run in
conduit wherever it may be exposed to the weather.
If wire resistance exceeds 0.75 ohms, an industrialstyle, plug-in relay should be added to the unit control
center and wired in place of the remote switch (typically
between terminal blocks R and G on the terminal strip.
The relay must be rated for at least 5 amps and have a
24 VAC coil. Failure to comply with these guidelines may
cause motor starters to “chatter” or not pull in which
can cause contactor failures and/or motor failures.
Field-Provided Disconnect
If field-installing an additional disconnect switch, it
is recommended that there is at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and size
according to the rating plate.
Packaged Rooftop Ventilator12
Control Center Components
Main Control Center Components
Image represents a typical XRV installation. Components and locations will vary on housing size and configuration.
High Voltage Side
1. Power distribution block; high voltage
supply is terminated here
2. Fuse holders
3. Phase monitor
4. Compressor motor contactors
5. Condensing fan motor contactors
6. Wheel motor contactor
7. Transformer
8. Unit Disconnect
Low Voltage Side
9. Microprocessor controller
10. Monitoring points
11. Low voltage terminal strip
12. Relays
13. Dirty filter switch
14. Outdoor airflow monitor
15. Exhaust airflow monitor
16. Digital scroll controller
10
4
4
13
14
15
9
11
12
LOW VOLTAGE SIDE
Accessible via compressor door
16
HIGH VOLTAGE SIDE
Accessible via control center door
7
3
2
2
2
4
56
8
1
4 5
Optional Indirect Gas-Fired Furnace
Note: In some models, two furnaces are installed to provide greater output. When two furnaces are installed, they are
in parallel and both will operate at the same time and the same output. Both furnaces will have identical controls.
7
1. Single-stage valve
2. Modulating valve
3. PCOE expansion board
4
3
5
4
3
4. Ignition controller
5. Transformer
6. Combustion blower
1
2
1
2
7. Burner manifold
8. Collector box
6
Dual furnaces shown. Available on housing 80 and 120 with furnace capacities 500 MBH or higher.
8
6
For further information on the optional furnace and its control center, see the Indirect Gas-Fired Heat lOM shipped
with the unit.
7
5
8
Packaged Rooftop Ventilator13
Component Operation
Optional Component Operation
Phase Monitor
The unit control circuitry includes a phase monitor that
constantly checks for phase reversal, phase imbalance,
loss of phase or a power brownout. When it detects a
fault, it cuts off the 24 VAC that goes to the low voltage
terminal strip, thereby shutting off all motors.
Variable Frequency Drive (VFD)
If a VFD was provided and installed at the factory, it has
been pre-set to control the speed of the blower motor
for optimum performance. The motor speed needs to be
verified during test and balance of the unit.
If the system was configured for Constant Air Volume
(CAV), the VFD will operate in an ON/OFF fashion
and the speed of the motor will not change. If the
system was configured for Variable Air Volume (VAV),
the microprocessor will constantly monitor operating
conditions and provide a signal to the VFD, changing
the VFD output as needed.
The VFD may alternatively be connected to an external
signal such as provided by a BMS and be operated by a
2-10 VDC or a 4-20 mA input.
Supply Fan VFD Sequence
Optional Room CO2 Sensor: The microprocessor will
modulate the supply fan based on a comparison of the
CO2 set point to the actual CO2 levels reported from
the sensor. Mechanical high static protection cutoffs
must be installed by others to protect the system and
equipment from over-pressurization.
Optional Duct Static Pressure Sensor: The
microprocessor will modulate the supply fan based
on a comparison of the duct static pressure set point
to the actual duct static pressure level reported from
the sensor. Mechanical high static protection cutoffs
must be installed by others to protect the system and
equipment from over-pressurization. The manufacturer
does not assume responsibility for this.
Optional Building Static Pressure Sensor: The
supply fan is modulated based upon the signal from a
building static pressure sensor. The microprocessor will
modulate the supply fan based on a comparison of the
building static pressure set point to the actual building
static pressure level reported from the sensor.
Optional Single Zone VAV: The microprocessor will
use a space mounted temp sensor to vary heating and
cooling capacity and the airflow delivered by the fan to
maintain room-air temp at a desired set point.
Optional 0-10 VDC by others to VFD: Supply fan is
modulated by a 0-10 VDC, field-provided by others.
Exhaust Fan VFD Sequence
Optional Building Static Pressure Sensor: The
exhaust fan is modulated based upon the signal from
a building static pressure sensor. The microprocessor
will modulate the exhaust fan based upon a comparison
of the building static pressure level reported from the
sensor.
Optional Outdoor Air Damper Tracking: The
microprocessor will proportionally modulate the exhaust
fan based upon the outdoor air damper position.
Optional Supply Tracking: The microprocessor will
proportionally modulate the exhaust fan based upon the
supply fan.
Optional 0-10 VDC by Others to VFD: The supply fan
is modulated by a 0-10 VDC provided by others in the
field.
Outdoor Air and Recirculated (Recirc) Air
Damper Sequence
Optional Room CO2 Sensor: The microprocessor
will proportionally modulate the OA/RA dampers based
upon a comparison of the CO2 set point to the actual
CO2 level reported from the sensor. As the CO2 level
rises, the controller will proportionally modulate the
outdoor air damper open, between the minimum and
maximum OA position.
Optional Building Pressure: The OA/RA dampers
will modulate based upon the signal from a building
static pressure sensor. The controller will modulate
the dampers, between the minimum and maximum OA
positions, based upon a comparison of the building
static pressure set point to the actual building static
pressure level reported from the sensor.
Exhaust Fan Only Power
The exhaust fan will have a dedicated power circuit
where in the case of a power outage, the exhaust fan
will still run. A phase monitor will detect an outage or
power loss and open the contact, disconnecting all
power to the unit and controller. An external signal will
need to be sent to a relay to power the exhaust fan,
enabling the fan to run at a maximum speed. This
sequence is NOT to be used for high temperature
exhaust applications.
Vapor Tight Lights
Vapor tight lights provide light to each of the
compartments in the energy recovery unit. The lights
are wired to a junction box mounted on the outside of
the unit. The switch to turn the lights on is located in
the unit control center. The switch requires a separate
power source to allow for power to the lights when the
unit main disconnect is off for servicing.
Packaged Rooftop Ventilator14
Optional Component Operation
Electronically Commutated (EC)
Condenser Fans with Standard Scroll or
Digital Scroll Compressors
The EC condenser fan will
modulate up and down to
maintain the highest liquid
line pressure. The factory
set points are: Set (left
dial): 23 barg; Diff (right
dial): 5 barg.
Fan operation with these
set points are as follows.
The fan will be at max
speed (~1140 rpm) when
the highest liquid line
saturation temperature
is 118°F (410psig, 28
barg). The fan remains at
max speed if the pressure is higher than 410psig (28
barg). The fan will be at min speed (~180rpm) when
the highest liquid line saturation temperature is 105°F
(340 psig, 23 barg). Below this pressure, the fan will be
off. The fan modulates linearly between the min and
max speeds. If unit is selected with inverter compressor
or air-source heat pump, reference the supplemental
Reference Guide for Microprocessor Controller.
Set (left dial): 23 barg;
Diff (right dial): 5 barg
Airflow Monitor
A factory-wired, mounted, and powered airflow
monitoring system is provided in the outdoor and/or
exhaust air streams. The airflow control system offers
the following functionality:
• Display of outdoor and/or exhaust airflow rate in
actual cubic feet per minute (CFM) or actual liters per
second (LPS) on a 16 character LCD display.
• Two configurable analog outputs for transmitting
outdoor and/or exhaust airflow rate, outdoor air
temperature, or a proportional-integral-derivative
(PID) control signal based on an outdoor airflow set
point.
• A configurable digital output that operates based on
an airflow set point or range.
Operation
Outdoor and/or exhaust airflow monitoring is
accomplished using two thermal dispersion sensors
that accurately measure airflow velocity down to zero
feet per minute (fpm). The airflow controller takes the
average measurement for two sensor configurations,
and determines the outdoor airflow rate based on the
effective intake area. Field calibration of the outdoor
airflow monitoring device determines the effective intake
area of the unit.
For additional information on how to navigate through
the airflow controller menus, refer to technical manuals
from GreenTrol® Automation Inc. at www.greentrol.com.
IMPORTANT
For the airflow monitoring device to perform as
intended, field calibration is required. Calibration of
the airflow monitoring device requires an independent
measurement of airflow and should be performed
when the system undergoes test and balance.
Air-Source Heat Pump
IMPORTANT
Air-source heat pumps are equipped with a defrost
cycle to remove ice from the outdoor coil. During
defrost cycles, melted water may drip from the
bottom of the refrigeration section under the outdoor
coil. In cold climates, proper drainage/heat tape must
be installed under the outdoor coil to prevent the
buildup of ice on the roof.
IMPORTANT
Melted water from snow accumulation on the unit
roof can be sucked into outdoor fans, resulting in ice
formation on fan blades under certain conditions.
Remove snow accumulation from the unit roof and
outdoor coil section after snow storms.
Operating Conditions and Limitations
To operate in Cooling mode, the following conditions
must be true:
1. Supply air temperature above minimum low supply
temperature limit (35°F)
2. Outside air temperature above the cooling ambient
lockout (55°F, adj.)
To operate in Heating mode, the following conditions
must be true:
1. Supply air temperature below maximum high supply
temperature limit (120°F)
2. Supply air temperature above 35°F
3. Outside air temperature above the low ambient
lockout (10°F, adj.)
For more information on air-source heat pump
operation, reference the supplemental Reference Guide
for Microprocessor Controller.
Packaged Rooftop Ventilator15
Optional Component Operation
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the
outdoor air filters, exhaust air filters, or both. If the
pressure drop across the filters exceeds the set point,
the sensor will close a set of contacts in the unit control
center. Field-wiring of a light (or other alarm) to these
contacts will notify maintenance personnel when
filters need to be replaced. The switch has not been
set at the factory due to external system losses that
will affect the switch. This switch will need minor field
adjustments after the unit has been installed with all
ductwork complete. The dirty filter switch is mounted in
the exhaust inlet compartment next to the unit control
center or in unit control center.
Microprocessor Control
The microprocessor controller is specifically designed
and programmed to optimize the performance of
the unit with supplemental heating and cooling. This
option ensures that the outdoor air is conditioned to
the desired discharge conditions. The controller and
accompanying sensors are factory-mounted, wired and
programmed. Default settings are pre-programmed, but
are easily field-adjustable.
The microprocessor controller can be interfaced with
a Building Management System through LonWorks®,
BACnet®, or ModBus.
Please refer to the Installation, Operation and
Maintenance manual for detailed information.
Hot Gas Bypass Valve (standard scroll)
On units equipped with hot gas bypass, hot gas
from the compressor is injected into the liquid line of
the evaporator coil after the thermostatic expansion
valve. This process starts to occur when suction gas
temperatures drop below 28°F, which is 32°-34°F coil
surface temperature. Hot gas helps the evaporator coil
from freezing up and the compressor from cycling. The
valve needs to be adjusted to exact specifications once
unit is installed in the field.
Hot Gas Reheat Valve
Units equipped with a reheat coil use a three-way
valve with actuator to control the supply air discharge
temperature of the unit during dehumidification mode.
The unit controller provides a 0-10VDC signal to control
the amount of reheat to meet the supply temperature
set point.
Controls by Others
The reheat coil needs to be purged to ensure adequate
oil return. It is recommended
that every six hours of reheat
compressor run time should
initiate a six minute purge
cycle. During the purge cycle,
the reheat valve should be
modulated to 100% open to
the reheat coil.
Unoccupied Recirculation Damper
The unoccupied recirculation option provides a
recirculation damper from the return air intake to the
supply airstream. If equipped with a room temperature
and/or relative humidity sensor, the unit can cycle on to
maintain unoccupied room set points if there is a call
for unoccupied heating, cooling, or dehumidification.
During the unoccupied mode, the supply and exhaust
(if equipped) fans will be off unless there is a call for
cooling, heating, or dehumidification in the space.
Vapor Tight Lights
Vapor tight lights provide light to each of the
compartments in the energy recovery unit. The lights
are wired to a junction box mounted on the outside of
the unit. The switch to turn the lights on is located in
the unit control center. The switch requires a separate
power source to allow for power to the lights when the
unit main disconnect is off for servicing.
Packaged Rooftop Ventilator16
Factory-Installed Refrigeration System Components
Packaged DX Cooling with Three Way Hot Gas Reheat and Hot Gas Bypass
1. Compressor
2. High Limit Pressure Switch
The switch opens when refrigerant pressure
increases above the set point in the discharge line.
A manual reset is then required.
3. Hot Gas Reheat Valve (optional)
Units equipped with a reheat coil use a threeway valve with actuator to control the supply
air discharge temperature of the unit during
dehumidification mode. The unit controller provides
a 0-10 VDC signal to control the amount of reheat
to meet the supply temperature set point
4. Hot Gas Reheat Coil (Optional)
5. Hot Gas Reheat Check Valve (Optional)
6. Condenser Fans
7. Condensing Coil
8. Liquid Receiver (Optional)
9. Liquid Line Filter Drier
10. Sight Glass
11. Fan Cycle Switch(es)
The switch(es) open or close based on liquid
refrigerant pressure to control the condensing fans
to maintain liquid pressure.
12. Thermostatic Expansion Valve (TXV)
Each unit is equipped with a TXV on each
refrigerant circuit. The valve controls the flow of
liquid refrigerant entering the evaporator coil by
maintaining a constant, factory-set superheat of
10°F. The valve is adjustable and is located on the
side of the evaporator coil and can be accessed
through the coil access panel.
13. Evaporative Coil
14. Low Limit Pressure Switch
The switch is installed on the suction line and
disables the DX system when the suction pressure
drops below the set point. The switch will auto reset
when the pressure rises above the auto-reset set
point.
15. Service Access Ports
16. Hot Gas Bypass Manual Shut Off Valve (Optional)
Used to disable hot gas bypass for service and
troubleshooting procedures.
17. Hot Gas Bypass Valve (Optional)
On units equipped with hot gas bypass, hot gas
from the compressor is injected into the liquid line
of the evaporator coil after the TXV.
Valve Adjustment - To adjust the valve, connect
a pressure gauge to the suction line and block the
entering air to the evaporator coil. The valve should
begin to open when the suction pressure drops to
approximately 115 PSIG for R-410A (the valve will
feel warm to the touch). Adjustments are made by
first removing the cap on the bottom of the valve
and then turning the adjusting stem clockwise to
increase the setting pressure (counterclockwise
to decrease). Allow several minutes between
adjustments for the system to stabilize. When
adjustment is complete, replace the cap on the
valve.
18. Pressure Gauge & Transducer (Optional EC
condenser fans only)
See Optional Electronically Commutated (EC)
Condenser Fans under the component operation.
Packaged Rooftop Ventilator17
Factory-Installed Refrigeration System Components
Air-Source Heat Pump with Three Way Hot Gas Reheat
Outdoor Airflow
EXV
HCV
HRV
HPS
SV
PT
PT
LPS
ACC
Compressor
4WV
Outdoor Coil
SG
Supply
Airflow
SG
Hot Gas Reheat Coil
FDS
Indoor Coil
Outdoor Airflow
4WV
Outdoor Coil
PT
SG
TXV
Supply
Airflow
SG
Indoor Coil
FDS
ACC
LPS
SV
HPS
Compressor
Packaged Rooftop Ventilator18
Factory-Installed Refrigeration System Components
1. Compressor
2. High Limit Pressure Switch
The switch opens when refrigerant pressure
increases above the set point in the discharge line.
A manual reset is then required.
3. Hot Gas Reheat Valve (optional)
Units equipped with a reheat coil use a threeway valve with actuator to control the supply
air discharge temperature of the unit during
dehumidification mode. The unit controller provides
a 0-10 VDC signal to control the amount of reheat
to meet the supply temperature set point
4. Hot Gas Reheat Coil (Optional)
5. Hot Gas Reheat Check Valve (Optional)
6. Outdoor Fans
7. Outdoor Coil
8. Refrigeration Accumulator
9. Liquid Line Filter Drier
10. Sight Glass
11. Four Way Reversing Valve
Each compressor circuit is equipped with a
reversing valve to reverse the direction of refrigerant
flow, switching the unit between heating and
cooling mode.
12. Electronic Expansion Valve (EXV) or
Thermostatic Expansion Valve (TXV)
An expansion valve is provided on each refrigerant
circuit. This valve controls the flow of liquid
refrigerant entering the indoor and outdoor coils
by maintaining a constant superheat. The TXV is
adjustable. Both the EXV and TXV are located on
the side of the outdoor coil and can be accessed
through the refrigeration system access panel.
13. Indoor Coil
14. Low Limit Pressure Switch
The switch is installed on the suction line and
disables the DX system when the suction pressure
drops below the set point. The switch will auto reset
when the pressure rises above the auto-reset set
point.
15. Service Access Ports
Typical port locations are shown. Additional valves
may be present in the system.
16. Refrigerant Pressure Transducers
Packaged Rooftop Ventilator19
Start-Up Unit
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and serious
injury may occur.
CAUTION
Do not operate without the filters and birdscreens
installed. They prevent the entry of foreign objects
such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to
internal components may result and void warranty.
WARNING
• Unit was factory tested. All blowers, fans,
and compressors are set-up to run correctly
when supplied power. If any one fan is running
backwards or the compressor is making loud
noises, immediately turn off the power. Switch two
leads on the incoming power to the disconnect.
This will ensure proper operation of the unit.
Failure to comply may damage the compressors
and void the warranty.
• Do not jumper any safety devices when operating
the unit. This may damage components within or
cause serious injury or death.
• Do not operate compressor when the outdoor
temperature is below 40ºF.
• Do not short-cycle the compressor. Allow
5 minutes between “on” cycles to prevent
compressor damage.
• DX system is charged with refrigerant. Start-up
must be performed by EPA Certified Technician.
WARNING
Prior to starting up the unit, power must be energized
for 24 hours without a call for cool to allow the
compressor crankcase heaters time to boil off any
liquid refrigerant present in the compressor.
Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.
Unit Model No. ___________________________________
Unit Serial No. ____________________________________
Compressor 1 Model No. __________________________
Compressor 2 Model No. __________________________
Compressor 3 Model No. __________________________
Compressor 4 Model No. __________________________
Start-Up Date ____________________________________
Start-Up Personnel Name __________________________
Start-Up Company ________________________________
Phone Number ___________________________________
Packaged Rooftop Ventilator20
Start-Up Unit
Pre-Start-Up Checklist
o Remove any foreign objects that are located in the
unit.
o Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
o Rotate the fan wheels by hand and ensure no parts
are rubbing.
o Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood.
o Verify that non-motorized dampers open and close
properly.
o Check the tightness of all factory wiring
connections.
o Verify proper drain trap installation.
o Check condensing fans for any damage or
misalignment. Spin the blades and make sure they
don’t contact any parts and are free turning without
any resistance.
o Look over the piping system.
o Inspect all coils within the unit. Fins may get
damaged in transit or during construction. Carefully
straighten fins with a fin comb.
Electrical
oDisconnect and lock-out all power switches.
o Verify control wire gauge.
o All field-mounted sensors and instruments are
installed and wired.
o Unit controls are off.
o Electrical service matches unit voltage.
o Electrical field wiring is complete.
o All electrical connections are tightened.
o Compressor and motor breakers or fuses are open
(disabled).
o Main power is wired to the disconnect.
o Discharge air sensor is installed per wiring
instructions.
o Space temperature and humidity sensors are
installed per if selected with unit.
Compressors
o This unit contains an external crankcase heater for
each standard or digital scroll compressor. The
variable speed compressor uses internal stator
heating. Each compressor needs power supplied to
it 24hours prior to start-up. If start-up is scheduled
in 24 hours, unlock the disconnect power and
energize unit.
oCompressor shipping brackets are removed if
provided.
IG Furnace
o If there is an indirect gas-fired furnace in this unit,
refer to the manual provided with this unit for PreStart-Up information.
o Gas piping is complete and gas lines are purged.
o Gas venting is in place.
Hot Water/Chilled Water Coils
o Chilled water piping system is complete.
o Hot water piping system is complete.
o Control valves are installed, wired, and operating
properly.
o Water coils are balanced to design GPM.
o Water system is free of air.
SPECIAL TOOLS REQUIRED
• Voltage Meter (with wire probes)
• Amperage Meter
• Pressure Gauges – (refrigerant)
• Tachometer
• Thermometer
• Incline manometer or equivalent
Start-Up Procedure
The unit will be in operational mode during start-up. Use
necessary precautions to avoid injury. All data must be
collected while the unit is running.
o Make sure Pre-Start-Up checklist is complete.
o Jumper R to G, R to Y1, and R to Y2 (if applicable)
on the control board.
o Turn the disconnect on. After 3 minutes
compressors will come on. Make sure all fans and
compressors are rotating the correct direction.
o Allow the unit to run until the refrigerant system
stabilizes. Approximately 1-2 minutes.
Voltage Imbalance
In a 3-phase system, excessive voltage imbalance
between phases will cause motors to overheat and
eventually fail. Maximum allowable imbalance is 2%.
To determine voltage imbalance, use recorded voltage
measurements in this formula.
Key: V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] /VA
Packaged Rooftop Ventilator21
Start-Up Checklist
Line Voltage. Check at unit disconnect.
L1-L2VoltsL2-L3VoltsL1-L3Volts
Motor Amp Draw
Supply Motor 1 AmpsL1AmpsL2AmpsL3Amps
Supply Motor 2 AmpsL1AmpsL2AmpsL3Amps
Exhaust Motor 1 AmpsL1AmpsL2AmpsL3Amps
Exhaust Motor 2 AmpsL1AmpsL2AmpsL3Amps
Fan RPMCorrect fan rotation direction?
Supply Fan RPMSupply FanYes / No
Exhaust Fan RPMExhaust FanYes / No
Condensing Fans
Condensing Fan 1L1AmpsL2AmpsL3Amps
Condensing Fan 2L1AmpsL2AmpsL3Amps
Condensing Fan 3L1AmpsL2AmpsL3Amps
Condensing Fan 4L1AmpsL2AmpsL3Amps
Compressors
Outdoor Air TemperatureDeg FOutdoor Air Relative Humidity% RH
Return Air TemperatureDeg FReturn Air Relative Humidity% RH
Compressor 1Compressor 2Compressor 3Compressor 4
L1AmpsAmpsAmpsAmps
L2AmpsAmpsAmpsAmps
L3AmpsAmpsAmpsAmps
Crankcase HeaterAmpsAmpsAmpsAmps
Superheat
Should be between 7º and 9ºF
Subcooling
Should be between 10º and 12ºF
Discharge Pressure
Should be between 300 and 500 PSIG
Suction Line Pressure
Should be between 100 and 135 PSIG
Liquid Line Temp.Deg. FDeg. FDeg. FDeg. F
Suction Line Temp.Deg. FDeg. FDeg. FDeg. F
Moisture Indicating Sight Glass
Liquid VisibleYes / NoYes / NoYes / NoYes / No
Color of Center DotPurple / PinkPurple / PinkPurple / PinkPurple / Pink
Hot Gas Bypass OperationalYes / NoNANANA
Deg. FDeg. FDeg. FDeg. F
Deg. FDeg. FDeg. FDeg. F
PSIGPSIGPSIGPSIG
PSIGPSIGPSIGPSIG
Packaged Rooftop Ventilator22
Start-Up Checklist - Packaged Direct Expansion (DX)
Compressor 1Compressor 2Compressor 3Compressor 4
L1AmpsAmpsAmpsAmps
L2AmpsAmpsAmpsAmps
L3AmpsAmpsAmpsAmps
Crankcase Heater
Not present on inverter compressor
Superheat
Should be between 8º and 12ºF
Subcooling
Should be between 8º and 12ºF
Discharge Pressure
Should be between 300 and 500 PSIG
Suction Line Pressure
Should be between 100 and 135 PSIG
Liquid Line Temp.Deg. FDeg. FDeg. FDeg. F
Suction Line Temp.Deg. FDeg. FDeg. FDeg. F
Moisture Indicating Sight Glass
Liquid VisibleYes / NoYes / NoYes / NoYes / No
Color of Center DotPurple / PinkPurple / PinkPurple / PinkPurple / Pink
Hot Gas Bypass OperationalYes / No / NANANANA
AmpsAmpsAmpsAmps
Deg. FDeg. FDeg. FDeg. F
Deg. FDeg. FDeg. FDeg. F
PSIGPSIGPSIGPSIG
PSIGPSIGPSIGPSIG
Packaged Rooftop Ventilator23
Start-Up Checklist - Air-Source Heat Pump (ASHP)
Compressor 1Compressor 2
Compressors
L1AmpsAmps
L2AmpsAmps
L3AmpsAmps
Crankcase Heater NAAmps
Cooling
Superheat
Should be between 10º and 20ºF (0% reheat) or
should be between 10º and 30ºF (100% reheat)
Subcooling
Should be between 10º and 15ºF (0% reheat) or
should be between 2º and 10ºF (100% reheat)
Discharge Pressure
Should be between 250 and 500 PSIG
Suction Line Pressure
Should be between 96 and 155 PSIG
Liquid Line TempDeg. FDeg. F
Suction Line TempDeg. FDeg. F
Moisture Indicating Sight Glass
Liquid VisibleYes / NoYes / No
Color of Center DotPurple / PinkPurple / Pink
Heating
Superheat
Should be between 10º and 20ºF
Subcooling
Should be between 10º and 20ºF
Discharge Pressure
Should be between 250 and 500 PSIG
Suction Line Pressure
Should be between 96 and 155 PSIG
Liquid Line TempDeg. FDeg. F
Suction Line TempDeg. FDeg. F
Moisture Indicating Sight Glass
Liquid VisibleYes / NoYes / No
Color of Center DotPurple / PinkPurple / Pink
Note: Unit may not run at 100% heating mode in ambient temperatures over 70°F (21°C). Modulate compressor as necessary to
keep unit running.
Deg. FDeg. F
Deg. FDeg. F
PSIGPSIG
PSIGPSIG
Deg. FDeg. F
Deg. FDeg. F
PSIGPSIG
PSIGPSIG
Packaged Rooftop Ventilator24
Start-Up Components
Fan
The fan should be checked for free rotation. If any
binding occurs, check for concealed damage and
foreign objects in the fan housing.
CAUTION
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.), consult
manufacturer to determine if the unit can operate
safely at the new conditions.
Supply Fan (Plenum Type)
The unit contains one plenum supply fan located on
the end of the unit opposite the outdoor air intake and
may optionally have a relief air blower which is referred
to as an exhaust blower in this document. Efficient fan
performance can be maintained by having the correct
offset.
Offset: Proper offset, or overlap, is
adjusted by loosening the wheel hub
from the shaft and moving the wheel
to the desired position along the shaft.
The transition between the inlet cone
and the wheel should
be as shown; there is
a smooth feel to the
profile when moving
one component to the
other.
Tolerance
(inches)
Fan Size
Wheel
Offset
Inlet
Cone
Offset
(inches)
ER35C5/32± 1/32
ER45C3/16± 1/32
ER50C13/64± 1/32
ER56C1/4± 1/32
Refer to the respective Installation, Operation and
Maintenance Manual shipped with this unit for additional
start-up and maintenance information regarding the
plenum fan.
Fan Wheel Rotation Direction
Check for proper wheel rotation by momentarily
energizing the fan. Rotation is determined by viewing
the wheel from the drive side and should match the
rotation decal affixed to the fan housing.
If the wheel is rotating the wrong way, direction can be
reversed by interchanging any two of the three electrical
leads. Check for unusual noise, vibration or overheating
of the bearings. Refer to the Troubleshooting portion of
this manual if a problem develops.
Supply/Exhaust Fan
The optional exhaust fan is a direct-drive plenum type.
Fan speed is controlled by a VFD which, in turn, is
controlled by the microprocessor controller or by an
external signal. Motor speed will be set on the VFD
during the unit Test and Balance, but after that, the
VFD will not normally be changed. Always check the
motor amperage rating shown on the motor nameplate
when changing the fan RPM. All access doors must be
installed except the control center door.
Vibration
Vibration Causes
Off axis or loose components
Drive component unbalance
Poor inlet / outlet conditions
Foundation stiffness
including structural and/or component failure. The most
common sources of vibration are listed.
Many of these conditions can be discovered by careful
observation. Refer to the Troubleshooting section of
this manual for corrective actions. If observation cannot
locate the source of vibration, a qualified technician
using vibration analysis equipment should be consulted.
Generally, fan vibration and noise is transmitted to other
parts of the building by the ductwork. To eliminate this
undesirable effect, the use of flexible connectors is
recommended.
Excessive vibration may
be experienced during
initial start-up. Left
unchecked, excessive
vibration can cause a
multitude of problems,
Discharge Air Temperature Sensor
Units are supplied with a Discharge Air Temperature
Sensor that is to be field-installed prior to unit startup. The sensor is to be installed at least three duct
diameters downstream of the heat exchanger.
The sensor must be connected directly to the
microprocessor controller. All other sensors and
low voltage devices are to be
connected to the low voltage
terminal strip in the control center.
The discharge air sensor is
shipped loose and can be found
in the unit’s control center. See
the unit-specific wiring diagram
for connection locations.
Typical Discharge Air
Temperature Sensor
Optional Hot Gas Bypass Valve
(standard scroll)
To adjust, connect a pressure gauge to the suction line
and block the entering air to the evaporator coil. The
valve should begin to open when the suction pressure
drops to approximately 115 PSIG for R-410A (the valve
will feel warm to the touch). Adjustments are made by
first removing the cap on the bottom of the valve and
then turning the adjusting stem clockwise to increase
the setting pressure (counterclockwise to decrease).
Allow several minutes between adjustments for the
system to stabilize. When adjustment is complete,
replace the cap on the valve.
Packaged Rooftop Ventilator25
Start-Up Components
Airflow Monitor
For additional information on how to navigate through
the airflow controller menus, refer to technical manuals
GF-2200A from GreenTrol® Automation Inc. at
www.greentrol.com.
Field calibration procedure:
1. Turn off power to the unit using the power
disconnect(s).
2. Remove the cover from the GreenTrol airflow
monitoring controller.
3. Install a jumper wire between terminals R and G on
the unit’s terminal board if one isn’t present.
4. When safe, turn the power back on to the unit
using the power disconnect(s).
If no microprocessor controller, skip to step 8.
Steps 5 thru 7 are for microprocessor only.
5. Look at the unit’s microprocessor controller screen
and view the status of the unit. If the displayed
status is “System Off” continue with step 6,
otherwise go to step 7.
6. Adjust the unit on/off priorities on the unit’s
microprocessor controller so that the unit will run
for calibration.
a. Push the “Prg” button on the microprocessor
controller.
b. Use the up and down arrows to get to the “On/
Off Unit” menu.
c. Push the enter button to view the current unit
on/off priorities.
d. Push the down arrow to display the Unit ON/
OFF Control screen.
e. Record the settings below so they can be
changed back when calibration is complete.
By digit input: ___________
By BMS: ___________
By Scheduler: ___________
f. Use the enter button to navigate between the
different settings on the page, use the up and
down arrows to change the values so that “By
digit input” is the only setting with “Yes”.
7. Enter the service override menu to control the
damper position.
a. At the Home Screen push the “Prg” button. (If
you’re not at the home screen push the escape
button until you get there).
b. Use the up and down arrows to get to the
“Service” menu, then push the enter button.
c. If you’re asked for a password, enter “1000”
for the password and push enter.
d. Use the up and down arrows to get to the
“Overrides” screen, then push enter.
e. Use the arrow buttons to get the supply
override.
8. Measure the supply airflow rate of the unit using an
approved test and balance method.
9. Without making any changes to the system,
calibrate the airflow monitoring controller so it
reads the airflow measured in step 8 by using the
Field Calibration Wizard.
a. The field calibration lasts for two minutes. Any
significant changes in airflow will affect the
accuracy of the reading.
b. To enter the Field Calibration Wizard, hold the
Down and Enter buttons simultaneously on the
airflow controller, then release the buttons.
c. Push the enter button to go to Wizard 1.
d. Push the enter button twice and change Wiz1
Enable to YES.
e. When asked for the number of calibration
points (Cal Points), set the value to 1.
f. Push the enter button when the display says
“Set Flow 1”.
g. After completing the steps above, set the
FLOW1 value to the airflow measured in
step 8, then push the enter button to begin
calibration.
10. After the calibration is completed, measure the
supply airflow rate again and compare with the
value on the airflow controller’s display
a. If the values are within 5% of each other the
device has been successfully calibrated.
b. If the values are not within 5% of each other
repeat the field calibration process.
11. If you had to change the On/Off priorities on the
microprocessor unit controller, change them back
to the values that were written down in part 6.
12. Turn off power to the unit using the power
disconnect(s) and wait one minute for the variable
frequency drive(s) to lose backup power.
13. Replace the cover to the GreenTrol airflow
monitoring station.
14. If you added a jumper between terminals R and
G in step 3 remove it at this time. If a jumper was
already in place, leave it in place.
15. When safe, turn the power back on to the unit
using the power disconnect(s).
a. Recycling of the power resets the manual
override values that were set during the
calibration.
Packaged Rooftop Ventilator26
Troubleshooting – Alarms
Several of the electronic controls in the unit monitor the
system for faults and will go into alarm, shutting down
the unit or a single function within the unit.
Microprocessor Controller
Check the screen on the microprocessor for an alarm
condition. If the microprocessor is in an alarm condition,
a message will show on the microprocessor controller
screen.
The microprocessor is located in the main control
center. If the microprocessor is in alarm condition,
the Alarm button will blink red. Press the Alarm
button to see the specific condition or to reset the
microprocessor. Refer to the microprocessor IOM for
detailed information on fault codes and see the unitspecific wiring diagram.
Phase Monitor
The phase monitor has two LED indicator lights, one
red and one green. Green indicates proper operational
status, red indicates the unit has detected a fault and is
in alarm condition. The alarm LED will blink to show the
specific fault and there is a chart printed on the monitor
that shows the code for the blinking light. The phase
monitor is self-resetting once the alarm condition is
corrected. It is located in the main control center.
Variable Frequency Drive (VFD)
Variable frequency drives have a display screen that will
show an alarm condition. If a fault such as a voltage
spike occurs, the VFD will go into alarm and will not
reset until a hard restart is performed. See the unitspecific manufacturer’s manual supplied with the unit.
VFDs are located in the main control center.
Optional Digital Scroll Compressor
Controller
Present only if packaged DX with digital scroll option is
selected. The controller has
three LED indicator lights.
One is green, indicating that
it has power, one is an alarm
indicator that will flash a code
for various alarm conditions
and the third indicates
whether the compressor
is operating in a loaded or unloaded condition. See
the manufacturer’s unit-specific manual for further
information.
See the Fault Code chart below. The Fault Code chart
is also printed on the back of the controller. Note that
if the controller generates either a Code 2 or a Code 4
Lockout, a manual reset must be performed. Manual
Reset is accomplished by shutting off main power to the
unit and then turning it back on.
Digital Scroll Compressor
Controller Fault Codes
Alert Code
Code 2*
Code 3
Code 4*Locked RotorBlinks 4 TimesLockout
Code 5
Code 6
Code 7FutureN/AN/A
Code 8
Code 9Low VoltageBlinks 9 TimesTrip Compressor
System
Condition
High Discharge
Temperature Trip
Compressor
Protector Trip
Demand Signal
Loss
Discharge
Thermistor Fault
Welded
Contactor
*Protective faults that require manual reset.
Diagnostic
Alert Light
Blinks 2 TimesLockout
Blinks 3 TimesLockout
Blinks 5 TimesLockout
Blinks 6 Times
Blinks 8 Times
Action
Reduce
Capacity
Unload
Compressor
Packaged Rooftop Ventilator27
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Blown fuse or open circuit breaker.Replace fuse or reset circuit breaker and check amps.
Blower fails
to operate
Motor
starters
“chatter” or
do not pull in
Motor over
amps
Low airflow
(cfm)
High airflow
(cfm)
Excessive
noise or
vibration
Defective motor or capacitor.Replace.
Motor overloaded.Reset VFD and check amps.
Electrical.
Control power (24 VAC) wiring run is too
long. (Resistance should not
exceed 0.75 ohms).
Incoming supply power is less than
anticipated. Voltage supplied to starter
coil must be within +10% / -15% of
nominal voltage stated on the coil.
Static pressures are higher than design.Check for dirty filters. Improve ductwork.
Motor voltage incorrect.
Motor horsepower too low.
Shorted windings in motor.Replace motor.
Unit damper not fully open.Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.
Fan wheels are operating backwards.
Dirty filter.
Leaks in ductwork.Repair.
Elbows or other obstructions may be
obstructing fan outlet.
Motor base or blower loose.Tighten mounting bolts.
Noise being transmitted by duct.
Check for On/Off switches. Check for correct supply
voltage. Check Control wiring.
Shorten wiring run to mechanical room or install a relay
to turn unit on/off. Consult factory for relay information.
Increase wire gauge size so that resistance is 0.75 ohms
or less.
Need to increase supply power or use a special control
transformer which is sized for the actual supply power.
Check motor wiring. Check motor nameplate versus
supplied voltage.
See specifications and catalog for fan curves to
determine if horsepower is sufficient.
Improve ductwork to eliminate losses using good duct
practices.
Check maximum motor RPM and compare with catalog
data. Verify that external control wiring is in place if
required.
For 3-phase, see Direction of Fan Wheel Rotation
Direction in Start-Up, Components section.
Replace filters or follow cleaning procedures in Routine
Maintenance section of this manual.
Correct or improve ductwork.
Check for correct maximum fan RPM. Decrease
maximum fan speed if necessary in the VFD.
Induce Ps into system ductwork. Make sure grilles
and access doors are installed. Decrease fan speed if
necessary.
Adjust wheel and/or inlet cone. Tighten wheel hub or
bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings. Tighten
collars and fasteners.
Make sure ductwork is supported properly. Make sure
ductwork metal thickness is sized for proper stiffness.
Check duct size at discharge to ensure that air velocities
are not too high.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information.
Packaged Rooftop Ventilator28
Troubleshooting – Refrigeration Circuit
TROUBLESHOOTING NOTE
IMPORTANT
Do not release refrigerant to the atmosphere! If
Before any components are changed on the
refrigeration system, the cause of the failure must be
identified. Further problems will exist unless the true
cause or problem is identified and corrected.
required service procedures include the adding or
removing of refrigerant, the service technician must
comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by a qualified EPA Certified Technician.
NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical
supply.
The first step in troubleshooting a refrigeration circuit is to examine the microprocessor controller and digital scroll
compressor controller (if present) and see if there is a fault code. The next step is to check airflow conditions
(e.g. improper ductwork, atypical wet bulb / dry bulb, etc.). After these steps have been eliminated, proceed with
troubleshooting by following this guide.
SymptomPossible CauseCorrective Action
Open disconnect switch or circuit
breaker.
Compressor contactor not closing.
Blown fuse or tripped breaker.
Close switch and/or breaker.
Check voltage to contactor coil, transformer, slave relay,
system. Replace parts as necessary.
Check for reason and repair. Replace fuse after correcting
problem.
Compressor
will not run
or does not
start
Compressor
starts but
cuts out on
low pressure
Low pressure
switch cuts
out at
50 PSIG (PDX)
or 25 PSIG
(ASHP)
Low line voltage.
Check line voltage. If more than 10% from compressor
marking, correcting is necessary.
Motor thermal protector automatically resets. Allow time
Compressor motor protector open.
(2 hours) for compressor to cool down so protector will
reset. Restart and check for reason overheat occurred.
Check motor for open circuit, short circuit, grounded
Compressor defective.
windings, or burn out. Compressor may be seized; check
refrigerant. If necessary, replace compressor.
High pressure switch open
or defective.
Low pressure switch open
or defective.
Open room thermostat or control.
(No cooling required).
If manual reset (high pressure), reset switch. (Switch
opens at 610 psi and will not reset above 420 psi for
R-410A). Replace if defective.
See switch label for setpoint.
Check room temperature. If temperature is proper, wait
for thermostat to close.
Loose wiring.Check all wire terminals and tighten as necessary.
Low or loss of refrigerant charge.
Check refrigerant pressures and temperatures
(subcooling.)
Check for dirty evaporator coil, dirty filters, dampers
Check equalized high side pressure with equivalent
outdoor temperature.
Clear restriction upstream of point of frosting. (Note:
liquid line frosting in normal on ASHP units).
Check airflow, check filters, check VFD control signal for
proper operation.
Check bulb of thermal expansion valve.
Check valve. If defective, replace.
Open valve.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information.
Packaged Rooftop Ventilator32
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to the unit to
OFF at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
This unit requires minimal maintenance to operate
properly. Maintenance requirements for this model
vary for each installation and depend greatly on how
much the system is used and the cleanliness of the air.
Proper maintenance will both increase the life of the
system and maintain its efficiency. Maintenance must
be performed by experienced technicians and in the
case of refrigeration systems, must be done by an EPA
certified technician.
Maintenance frequency is based on a presumed
nominal use of the system. If the system is being
run constantly, the frequency should be adjusted
accordingly. If there is seasonal debris in the air which
can be drawn into the filters and the coils, they should
be checked more frequently. If the system is being
used for only a few hours per day, the frequency may
be reduced. Use the maintenance log at the end of
this manual to record each maintenance session
and observations and then establish a maintenance
schedule that is appropriate for the installation. The
following is provided as a guideline.
Annually
It is recommended that the annual inspection and
maintenance occur at the start of the cooling season.
After completing the checklist, follow the unit start-up
checklist provided in the manual to ensure the
refrigeration system operates in the intended matter.
1. Lubrication
Apply lubricant where required
2. Dampers
Check for unobstructed operation
3. Blower Wheel and Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
4. Door Seal
Check if intact and pliable
5. Wiring Connections
Check all connections for tightness
6. Cabinet
Check entire cabinet, inside and out, for dirt
buildup or corrosion. Remove accumulated dirt,
remove any surface corrosion and coat the area
with appropriate finish.
Adjust replacement schedule for MERV 13 and
MERV 14 or other filters as inspection requires.
Semiannually
1. Check motor and motor bearings
Check for excessive heat, vibration or noise.
Lubricate bearings in accordance with the
motor manufacturer’s recommendations.
2. Condensate Drain (if applicable)
Inspect and clean – refill with water
3. Heat Transfer Coils (if applicable)
Inspect for cleanliness – clean as required
4. Outdoor Fan Blades and Motor (if applicable)
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
Packaged Rooftop Ventilator33
Maintenance Procedures:
Filter
Lubrication - Check all moving components for
proper lubrication. Apply lubricant where required.
Any components showing excessive wear should be
replaced to maintain the integrity of the unit and ensure
proper operation.
Dampers - Check all dampers to ensure they open and
close properly and without binding. Backdraft dampers
can be checked by hand to determine if blades open
and close freely. Apply power to motorized dampers to
ensure the actuator opens and closes the damper as
designed.
Gas Furnace - Maintain furnace in accordance with
instructions in the Indirect Gas-Fired Heat IOM shipped
with this unit.
Fan Motors - Motor maintenance is generally limited
to cleaning and lubrication. Cleaning should be limited
to exterior surfaces only. Removing dust and grease
buildup on the motor housing assists proper cooling.
Never wash-down the motor with high pressure
spray. Greasing of motors is only intended when
fittings are provided. Fan motors typically have two
grease fittings. Each motor manufacturer has different
lubrication schedules for different models. Go to the
motor manufacturer’s website and download their
maintenance requirements. Do not over-lubricate motors or use an incompatible grease. Many
fractional motors are permanently lubricated for life and
require no further lubrication.
Fan Wheel and Fasteners - Wheels require very little
attention when moving clean air. Occasionally oil and
dust may accumulate on the wheel causing imbalance.
When this occurs, the wheel and housing should be
cleaned to assure smooth and safe operation. Inspect
fan impeller and housing for fatigue, corrosion, or wear.
Routinely check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness. A proper maintenance
program will help preserve the performance and
reliability designed into the fan.
Internal Filter Maintenance - The unit will typically be
provided with 2-inch thick pleated paper filters in the
airstream. These filters should be checked according
to a routine maintenance schedule and replaced as
necessary to ensure proper airflow through the unit.
Replacement filters shall be of same performance and
quality as factory installed filters. Filter must be pleated
design with integral metal grid. Two acceptable filter
replacements are Aerostat Series400 or Farr 30/30®.
Filters upstream of the coil should be checked regularly.
If the filters are dirty, they should be cleaned or
replaced. It is important the filters stay clean to maintain
desired airflow.
WARNING
REFER TO GENERAL SAFETY INFORMATION
Do not operate this unit without the filters and
birdscreen installed. They prevent the entry of foreign
objects such as leaves, birds, etc.
Do not remove access panels or other unit
components while standing on a ladder or other
unsteady base. Access panels and unit components
are heavy and serious injury may occur.
thick filters are located in the supply weatherhood (if
the weatherhood option was purchased). These filters
should be checked and
cleaned on a regular basis
for best efficiency. The
frequency of cleaning
depends upon the
cleanliness of the incoming
air. These filters should be
cleaned by rinsing with
a mild detergent in warm
water prior to start-up.
Outdoor Air Intake Hood
Mesh Filter Access
Coil Maintenance- Coils must be cleaned to maintain
maximum performance. Check coils once per year
under normal operating conditions and if dirty, brush
or vacuum clean. Soiled fins reduce the capacity of the
coil, demand more energy from the fan and create an
environment for odor and bacteria to grow and spread
through the conditioned zone. High pressure water
(700 psi or less) may be used to clean coils with a fin
thickness over 0.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil to determine
if the fins will withstand the spray pressure.
For coils with fragile fins or high fin density, foaming
chemical sprays and washes are available. Many coil
cleaners use harsh chemicals, so they must be used
with caution by qualified personnel only. Care must be
taken not to damage the coils, including the fins, while
cleaning. Caution: Fin edges are sharp!
WARNING
Biological hazard. May cause disease. Cleaning
should be performed by qualified personnel.
Drain pans in any air conditioning unit will have some
moisture in them, therefore, algae and other organisms
will grow due to airborne spores and bacteria. Periodic
cleaning is necessary to prevent this buildup from
plugging the drain and causing the drain pan to
overflow. Inspect twice a year to avoid the possibility
of overflow. Also, drain pans should be kept clean to
prevent the spread of disease. Cleaning should be
performed by qualified personnel.
As a result of our commitment to continuous improvement, Accurex reserves the right to change specifications
without notice.
Product warranties can be found online at accurex.com, either on the specific product page or in the Warranty
section of the website at Accurex.com/Resources/Warranty.