Accurex XQEI Operator’s Manual

Document 481883
Model XQEI
Mixed Flow
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
General Safety Information
Only qualified personnel should install this fan. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC) and the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be free to rotate without striking or rubbing any stationary objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than max cataloged fan rpm. Adjustments to fan speed significantly effects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to a duct while the fan is running.
DANGER
Always disconnect, lock and tag power source before installing or servicing. Failure to disconnect power source can result in fire, shock or serious injury.
CAUTION
When servicing the fan, motor may be hot enough to cause pain or injury. Allow motor to cool before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
DANGER
Pour écarter les risques d’incendie, de choc électrique ou de blessure grave, veiller à toujours débrancher, verrouiller et étiqueter la source de courant avant l’installation ou l’entretien.
ATTENTION
Lors de toute intervention sur la soufflante, le moteur peut être suffisamment chaud pour provoquer une douleur voire une blessure. Laisser le moteur refroidir avant toute maintenance.
ATTENTION
Faire preuve de précaution dans les atmosphères explosives.
Mixed Flow 1
Receiving
Upon receiving the product check to make sure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier of any damage detected. The customer will make a notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which is countersigned by the delivering carrier. If damaged, immediately contact your Accurex Representatives. Any physical damage to the unit after acceptance is not the responsibility of Accurex, LLC.
Remove any accumulations of dirt, water, ice or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection.
The unit should be stored at least 3½ inches (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Handling
Fans are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce the ability of the fan to resist corrosion.
Fans should never be lifted by the shaft, fan housing, motor, belt guard, windband or accessories.
Storage
Fans are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the fan and accessories while in storage. The manufacturer will not be responsible for damage during storage. The following suggestions are provided solely as a convenience to the user.
INDOOR - The ideal environment for the storage of fans and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should be evenly maintained between 30°F (-1°C) and 110°F (43°C) (wide temperature swings may cause condensation and “sweating” of metal parts). All accessories must be stored indoors in a clean, dry atmosphere.
OUTDOOR
hauling equipment are needed. The fan should be placed on a level surface to prevent
water from leaking into the fan. The fan should be elevated on an adequate number of wooden blocks so that it is above water and snow levels and has enough blocking to prevent it from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all fan parts on blocking supports so that rain water will run off.
The use of a tarp to cover the unit will aid in keeping it clean and dry. Avoid using a black plastic tarp as it will promote condensation.
Fan wheels should be blocked to prevent spinning caused by strong winds.
- Roads or aisles for portable cranes and
Inspection & Maintenance During Storage
While in storage, inspect fans once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the wheel by hand ten to fifteen revolutions to distribute lubricant on motor. If paint deterioration begins, consideration should be given to touch-up or repainting. Fans with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe clean thoroughly with Tectyl hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40® or the equivalent.
®
506 (Ashland Inc.) or the equivalent. For
Mixed Flow2
Removing From Storage
As fans are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the fan equipment goes into operation.
Prior to fully assembling and installing the fan and system components, inspect the fan assembly to make sure it is in working order.
1. Check all fasteners, set screws, wheel, bearings, drive, motor base and accessories for tightness.
2. Rotate the fan wheel by hand and assure no parts are rubbing. Access to the wheel is obtained through an access panel located on the side of the fan housing.
3. Ensure proper wheel settings for radial gap and alignment. See Unit Start-Up section.
Table of Contents
General Safety Information . . . . . . . . . . . . . . 1
Receiving, Unpacking, Handling . . . . . . . . . . . . 2
Storage - Indoor / Outdoor . . . . . . . . . . . . . . 2
Inspection and Maintenance During Storage . . . . . 2
Removing from Storage . . . . . . . . . . . . . . . . 3
Installation
Ducted Installations . . . . . . . . . . . . . . . . . 4
Non-Ducted Installations . . . . . . . . . . . . . . 4
Duct Connections . . . . . . . . . . . . . . . . . . 4
Mounting Configurations
Universal Mounting . . . . . . . . . . . . . . . . . 5
Mounting Rails (Optional) . . . . . . . . . . . . . 5-6
Ceiling Hung - Horizontal or Vertical . . . . . . . 6
Base Mount - Horizontal or Vertical . . . . . . . . 6
Installation for UL 762 Restaurant Exhaust
Installation Overview . . . . . . . . . . . . . . . 6-7
Cleaning, Maintenance, Repair . . . . . . . . . . . 7
Unit Start-Up . . . . . . . . . . . . . . . . . . . . . . 8
Radial Gap and Alignment . . . . . . . . . . . . . 8
Vibration . . . . . . . . . . . . . . . . . . . . . . . 8
Maintenance
V-Belt Drive . . . . . . . . . . . . . . . . . . . . . 9
V-Belt Replacement . . . . . . . . . . . . . . . . . 9
Motors . . . . . . . . . . . . . . . . . . . . . . . .10
Fan Bearing Replacement . . . . . . . . . . . . . .10
Fan Bearing Lubrication . . . . . . . . . . . . . . .10
Troubleshooting . . . . . . . . . . . . . . . . . . . .11
Our Commitment. . . . . . . . . . . . . . . Backcover
Mixed Flow 3
Installation
1 Fan Wheel
Dia.
Installations with poor inlet or discharge configurations may result in reduced fan performance.
Ducted Installations
Inlet Duct Turns – Installation of a duct turn or elbow
too close to the fan inlet reduces fan performance. Restricted or unstable flow at the fan inlet can cause pre-rotation of incoming air or uneven loading of the fan wheel, yielding large system losses and increased sound levels. To achieve full fan performance, there should be at least one fan wheel diameter between the turn or elbow and the fan inlet.
PoorGood
1 Fan
Wheel
Dia.
Turning Vanes
Discharge Duct Turns – Fan performance is reduced when duct turns are made immediately off the fan discharge. To achieve cataloged fan performance there should be at least three equivalent duct diameters of straight ductwork between the fan discharge and any duct turns.
Poor
Duct Connections
It is highly recommended to use a flexible sleeve connection instead of a rigid duct connection. This will reduce vibration transmission through the ductwork.
Slip-Fit End Connection
Directly attach the flexible sleeve to the duct and fan. No additional parts are required.
Flexible Sleeve
Fan Duct
Flanged End Connection
Optional companion flanges are bolted to the fan to provide a slip-fit connection for a flexible sleeve.
Flexible Sleeve
Fan Duct
Companion Flange
Note: Flexible sleeve & attachment hardware not provided.
Length of
Straight Duct
Good
Non-Ducted Installation
Inlet Clearance
Installation of a fan with an open inlet too close to a wall or bulkhead will cause reduced fan performance. It is desirable to have a minimum of one fan wheel diameter between the fan inlet and the wall.
Free Discharge
Free or abrupt discharge into a plenum results in a reduction in fan performance. The effect of discharge static regain is not realized, and performance is reduced.
Mixed Flow4