Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
Type IIType I
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and all applicable local and national building
and fire codes. Personnel should be aware of general
safety precautions. SMACNA guidelines should be
followed for hanging and supporting the hood. If more
information is needed, contact a licensed professional
engineer before moving forward.
DANGER
Always disconnect power before working on or near
any electrical components in the hood. Lock and tag
the disconnect switch or breaker to prevent accidental
power up.
NOTE
Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), and the
latest edition of the National Fire Protection Agency
Standard for Ventilation Control and Fire Protection
of Commercial Cooking Operations (NFPA 96). Follow
the Canadian Electrical Code (CEC) and ULC-S650 if
installing this product in Canada.
Kitchen Hoods • Type I and Type II1
Receiving
Upon receiving the product, check to ensure all items
are accounted for by referencing the delivery receipt or
packing list. Inspect each crate or carton for shipping
damage before accepting delivery. Alert the carrier
of any damage detected. The customer will make
a notation of damage (or shortage of items) on the
delivery receipt and all copies of the bill of lading which
is countersigned by the delivering carrier. If damaged,
immediately contact your Accurex Representative. Any
physical damage to the unit after acceptance is not the
responsibility of Accurex, LLC.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited
to only items on the bill of lading. Filters are shipped
on a separate skid in their original packaging. Do not
remove factory packaging or install filters until just prior
to commissioning. Remove all other shipping/packing
materials.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or denting.
Damaged finish may reduce ability of unit to resist
corrosion.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage.
The ideal environment for storage of the hood and
accessories is indoors, above grade in a clean, dry
atmosphere that is sealed from the elements. While in
storage, inspect equipment routinely. If any moisture,
dirt or other accumulations are found on the hood or
any of the parts, the source should be located and
eliminated.
Removing from Storage
As equipment is removed from storage to be installed
in their final location, it should be protected and
maintained as outlined in the Handling section above.
Table of Contents
Receiving, Unpacking, Handling and Storage .....2
Removing from Storage .......................2
Canopy Hood Weights ........................3
Proximity Hood Weights .......................4
Supply Plenum
Weights and Dimensions ......................4
Prior to Installation ...........................5
*Hood weight calculations are based on standard selection. Hood height, accessories and material gauge affect overall hood weight.
63 lbs/ft
79 lbs/ft
84 lbs/ft
79 lbs/ft
87 lbs/ft
129.47 kg/m
90 lbs/ft
133.93 kg/m
Kitchen Hoods • Type I and Type II3
Proximity Hood Weights
Hood weight is determined using a simple formula. Select the figures provided in columns A and B (see tables) from
the three respective categories—Hood Width, Filter Type and Hood Height—based on the hood received. Total
the three numbers in column A and the three numbers in column B. Place the sum for column A and the sum for
columnB in the Hood Weight equation where shown and solve for the total Hood Weight.
Prior to installation, check with the Authorities Having
Jurisdiction (AHJ) on clearance requirements to
structures surrounding the hood and other equipment.
Verify there is enough space to safely lift hood up into
its operating position and enough clearance around
the hood for components like fire system connections,
hood lights, hood control components, etc. Consider
access for servicing the equipment and the different
components when locating the hood.
If the hood is a grease hood (Type I), the UL label
located on the end panel on the inside of the hood
will provide pertinent information regarding the hood
installation. Information includes:
• Allowable cooking surface temperatures of the
cooking equipment
• Fire damper fusible link replacement information, if
applicable
With the hood still inside its packing crate, position the
unit beneath its installation location. Carefully remove
the packing crate and place some protective material on
the floor next to the crate to avoid damaging the hood
as it is tipped on its side. Tip the hood carefully onto the
protective material.
Bottom of Hood
Hood Installation Overview
1. If the hood is provided with filler panels, shipped
loose, install them now. See page 7, Filler Panel
Installation. Filler panels may be integral to the
hood, which requires no additional installation.
2. If the hood is equipped with Clearance Reduction
Methods, refer to pages 7 and 8 for special
considerations with hanging the hood.
3. If the hood is provided with hood/duct sensors or
thermostats, install them now. See the Installation
and Operations guide provided with the control
panel.
4. If the hood was provided with either exhaust
collars or supply collars that have shipped loose,
it is recommended that the exhaust and supply
openings are cut and collars are attached now,
prior to hanging the hood. See page 8, Installing
Duct Collars.
5 If the hood is provided with a back supply plenum
(BSP) install it now. See page 9, Installing the Back
Supply Plenum.
6. If possible, connect (weld) exhaust duct to the
hood while on the floor, unless it prohibits the hood
from being raised into place. For information on
ductwork, see page 9, Ductwork.
7. At this point, drill holes in the building structural
support system or utilize uni-strut to match up with
the hanger bracket holes. Then slowly and evenly
raise the hood into position and insert 1/2-inch
(12.7mm) diameter threaded rod (provided by
others) between the hanger brackets and structure.
For Type I hoods, the hood hanging height
requirements are given on the UL label. Typical
canopy hood hanging height will be 80inches
(198.12cm) off the finished floor.
Pallet
Protective Material
NOTE
If the hood is supplied with ceiling enclosures, the
height of the enclosures will typically be the distance
from the ceiling to the top of the hood. Use this
dimension to find the hood’s hanging height off of the
floor.
For questions regarding the supporting structure and
its integrity, either the contractor or structural engineer
needs to be consulted.
Kitchen Hoods • Type I and Type II5
Wall or Single Island Canopy Hoods - continued
NOTE
All hanger brackets MUST be used and the hood must
be properly supported while lifting to prevent damage
or distortion to the hood.
NOTE
The hood MUST be hung evenly. If hung unevenly,
this may cause grease drainage problems. Provide
additional support if necessary so that the hood
doesn’t move in a manner that is acceptable with the
Authorities Having Jurisdiction (AHJ).
WARNING
When mounting the hood or any components against
the hood, never puncture or drill into the canopy. This
will void the hood listing and warranty.
8. If the hood was provided in sections with the
continuous capture option, once each hood
section is hung, install this option now. See page 9,
Continuous Capture Plenum Hoods.
9. If the hood was provided with any front or side
external supply plenums (other than the back
supply plenum), install these now. See page 10,
Installing Front/Side External Supply Plenums.
10. Install the remainder of both the exhaust and
supply ductwork. For further guidelines see page 9,
Ductwork.
11. If the hood is provided with any backsplash/
sidesplash panels, install them now. See page 11,
Installing Backsplash Panels.
12. If the hood is provided with any end skirts, install
them now. See page 12, Installing End Skirts.
13. If the hood is a Type I hood, it will require a fire
suppression system. Once the Type I hood(s)
and ductwork are fully installed, appliances are
in place and walls are complete, the fire system
should be completed. If the hood is provided with
a full factory-coordinated fire suppression system
installation, the certified fire system installer should
be contacted at this time to complete the final
hookups, testing and system certification based
upon manufacturer’s specification and local fire
codes. If the hood is not provided with either prepiping only or no fire suppression system, it is the
responsibility of a certified fire system installer
to install, test and certify the system based upon
manufacturer’s specification and local fire codes.
14. If the hood is provided with a control package,
these will need to be installed and wired by the
jobsite electrician. This typically includes wiring the
hood temperature sensors, hood lights and wiring
the fire suppression micro-switches. For general
hood electrical connections, see page 12, Electrical
Connections. If applicable, see the Installation
and Operations guide provided with the control
package.
15. If the hood is provided with enclosure panels,
install them now. See page 13, Installing Enclosure
Panels.
16. Install the rest of the hood accessories provided.
This may include grease filters or condensate hood
baffles, grease cups, light bulbs (provided by others
unless LED tube style), light globes, and trim strips.
It is recommended that the protective plastic sheeting
remain on the hood until fully installed to better protect
the product from scratching and marking. Once
removed, use stainless steel polish, such as BlueAway
or equivalent, to clean the hood and/or remove marks
or discoloration. Be sure to wipe with the grain and not
against it.
Kitchen Hoods • Type I and Type II6
Filler Panel Installation
Clearance Reduction Methods
1. Uncrate the hood and lay it on the floor with
protective material between the hood and the floor.
2. Bolt the filler panels together with 5/16 in. bolts
provided in the hardware package.
3. Position the filler panels to the hood back, and tackweld them into place.
HOOD
HOOD
HOOD
TACK-WELDED TO
HOOD BACK
5/16 IN. X 3/4 IN. BOLTS
WITH WASHERS & NUTS
RIGHT FILLER PANEL
BOTTOM FILLER PANEL
4. To allow for ease of cleaning, caulk the external
seams with NSF Approved silicone caulk (GE
SCS1009, or its equivalent). The caulk is not
provided.
Clearance reduction methods have been evaluated and
tested and are listed by UL (Underwriters Laboratory).
The method of test was derived from the UL 710 test
standard.
The hood may be installed with zero clearance to
combustible materials if constructed in the following
manner.
1. One inch (2.54 cm) thick layer of insulation of Owens
Corning
®
Type 475, Johns Manville Type 475, IIG®
MinWool-1200® Flexible Batt, or Knauf Insulation
Type EI 475.
2. Insulation must be held securely in place. Pins that
are welded or secured with an adhesive may be
used.
3. A backsplash panel must be attached to the wall
(insulated or uninsulated).
To comply with the UL Listing, the cooking appliances
must be as follows:
• Maximum surface temperature is 700°F (371°C)
• Appliances are located at least 3 in. (7.62 cm) from
the rear wall
• Appliances are at least 40 in. (101.6 cm) below the
bottom front edge of the hood
The hood may be installed with 3 in. (7.62 cm) clearance
to limited combustible materials per NFPA 96 if
constructed in one of the following methods:
• 3 in. (7.62 cm) rear uninsulated stand-off
• 3 in. (7.62 cm) top enclosure panel system
• 3 in. (7.62 cm) end uninsulated stand-off
Top Clearance Reduction Options
One inch (2.54 cm) layer of insulation installed on top
of the hood (optional) meets zero inch requirements for
clearance to combustible surfaces as outlined under the
clearance reductions methods.
Three inches (7.62cm) uninsulated airspace installed on
top of hood (optional) meets NFPA 96 requirements for
clearance to limited combustible surfaces.
Kitchen Hoods • Type I and Type II7
Back and Front Clearance Reduction Options
One inch (2.54 cm) layer of insulation in 3 in. (7.62cm)
back stand-off meets zero inch requirements for
clearance to combustible surfaces as outlined under the
clearance reduction methods.
Three inches (7.62 cm) uninsulated back stand-off
meets NFPA 96 requirements for clearance to limited
combustible surfaces.
One inch (2.54 cm) layer of insulation factory-installed
on the front of the hood (optional) meets zero inch
requirements for clearance to combustible surfaces.
Installing Duct Collars
Exhaust Duct Collars
1. The exhaust duct connection needs to be located
within 48 in. (121.92 cm) from the center of the hood
length to the center of the duct connection and
within shaded area as shown.
Top View of the Hood
Hanger Bracket
Exhaust Plenum
14 in.
Duct cut out area
3 in.
Hood
Width
End Clearance Reduction Options
One inch (2.54 cm) layer of insulation factory-installed
on the end of the hood (optional) meets zero inch
requirements for clearance to combustible surfaces
under the clearance reduction methods.
Three inches (7.62 cm) uninsulated airspace installed on
end of hood (optional). Meets NFPA 96 requirements for
clearance to limited combustible surfaces.
16 in.
8 in.
8 in.
Supply Plenum
Hood Length
Front of hood
Back View of the Hood
8 in.8 in.
1 in.
12 in.
Hood Top
Exhaust Plenum
Duct cut out area
2. The exhaust duct connection is to be a continuous
liquid-tight weld. Weld with a non-ferrous filler wire,
such as silicon bronze or stainless steel filler wire.
Protect all stainless steel areas from weld splatter.
Integral Supply Duct Collars
1. The supply duct connection needs to be located
within the shaded Supply Plenum area as in the
drawing above.
2. The supply duct connection is tack-welded at 1 to
2inch (2.54 to 5.08 cm) intervals or sheet metal
screws at 3 to 6 in. (7.62 to 15.24 cm) spacing to
the hood.
Supply duct connection to be tack
welded with 1 to 2 inch tack or
Supply Duct
Connection
sheet metal screws at 3 to 6 inch
spacing to hood.
3 in.
3. For hoods that are insulated, the edges of the
insulation must be taped after the hole is cut. (The
insulation tape
is provided by
Internal Supply
Chamber
Supply Fire Damper
others).
4. On combination
hoods, make
Hood
certain the
fire damper
is located
over the
internal supply
Insulated
Supply
Plenum
chamber.
Exhaust Capture
Kitchen Hoods • Type I and Type II8
Installing the Back Supply Plenum
BOLT OR WELD
HOOD TOP
HOOD END
SUPPORT ANGLES
CAULK
BOLT
U-CLIP
HOOD
ACORN
NUT
2. RAIS AND
3. FAST
4. FAST
5. CAU
& CAP
1. REM
HOOD FRONT
HOOD FRONT
REMOVE
SUPPORT
ANGLES ON
THE OPEN
END PANEL
Ductwork
Install the Supply Duct Collar
1. Find the center of the back supply plenum.
2. If the back supply plenum is to have
one opening, cut the opening such
that it is centered at L /2 from the
plenum end. (Fig.1)
3. If the back supply plenum is to have
two openings, cut openings such
that they are centered at L /4 from
each end of the plenum.
(Fig. 2)
4. Place the duct
L/4
collar(s) over the
opening(s), fastening
with screws or
tack-welds every
4 to 6 in. (10.16 to
15.24cm). (Fig. 3)
Hang the Plenum
Fig. 2
5. Hang the back
supply plenum
from the ceiling.
The back supply plenum
needs to be mounted 31.25in.
(79.375 cm) above the finished
floor. This is measured from the
lowest rear edge of the back
supply plenum to the finished
floor. (Fig. 4)
Hang using threaded rod
placed through the hanger brackets.
Fig. 1
L (MODULE LENGTH)
L/2
Fig. 3
L (MODULE LENGTH)
L/2
L/2
L/4
Exhaust - As specified in NFPA 96, Ch. 7.5 (latest
edition), exhaust duct systems must be constructed in
the following manner:
Materials: Ducts shall be constructed of and supported
by carbon steel not less than 1.37 mm (0.054 in.) (No.
16 MSG) in thickness, or stainless steel not less than
1.09 mm (0.043 in.) (No. 18 MSG) in thickness.
Installation: All seams, joints, penetrations, and duct to
hood collar connections shall have a liquid-tight external
weld. If you have an automatic fire damper, please refer
to that manual for installation instructions now.
Supply - Supply ductwork (where applicable) should
be connected to the hood in a manner approved by the
local code authorities.
NOTE
For hoods with fire dampers in the exhaust and
supply duct collars, an access panel for cleaning and
inspection shall be provided in the duct. This panel
shall be as close to the hood as possible but should
not exceed 18 in. (45.72 cm).
For proper installation of duct collars when they are
shipped unattached, see page 8.
Continuous Capture Plenum Hoods
1. Remove the support angles
provided for support during
shipping on the open
end panels. Install
and level both
hoods.
FASTENERS HOLDING THE
BACKSUPPLY TO THE WALL
31.25 INCH
CRITICAL
Fig. 4
DIMENSION
6. Fasten the back supply to the wall, going through the
lower back supply wall.
• These fasteners are to help maintain the location of
the back supply, and are not intended to hold the
weight of the back supply unit.
• The fasteners should not interfere with the
removable air diffusers.
2. After leveling, secure the
hoods together by tackwelding and/or bolting the
angles that are located at
the top of the hoods along
its width (Fig. 5).
3. Next, fasten the hoods
together at its inside
plenum profile using
u-clips and bolts (Fig.6).
Caulk this joint with NSF
Approved silicone caulk
(GE SCS1009 or its
equivalent). The caulk is
not provided.
Kitchen Hoods • Type I and Type II9
Fig. 5
Fig. 6
Installing Front/Side External Supply Plenums
Using the Uni-strut
THREADED ROD
SUPPLIED BY OTHERS
UNI-STRUT (U-CHANNEL)
SUPPLIED BY OTHERS
END VIEW
HOOD
The uni-strut (supplied by others) supporting the hood
may be cantilevered over the end of the hood. Utilizing
the external supply plenum’s hanger brackets, securely
fasten to the uni-strut.
THREADED
THREADED
ROD
ROD
UNI-STRUT
UNI-STRUT
(U-CHANNEL)
(U-CHANNEL)
EXTERNAL
SUPPLYPLENUM
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by
others) into hanger brackets on the external supply
plenum top. Raise and hang the external supply
plenum from adequate roof or ceiling supports.
NOTE
Ensure the external supply plenum is installed
flush with the hood front and is plumb and level by
adjusting the threaded rod(s). There should be no gap
between the bottom of the external supply plenum
and the hood after installation and adjustments are
completed.
2. The external supply plenum should be resting
lightly against the hood. The hood is only used to
position the plenum; it is not intended to support the
plenum. All hanger brackets on the external supply
plenum must be used and the plenum must be
properly supported while lifting to prevent damage or
distortion. The external supply plenum must be level
to operate properly.
NOTE
After hanging, secure the external supply plenum to
the hood (or to another external supply plenum) using
the supplied turnbuckle(s). Use caution tensioning the
turnbuckle. Too much tension may cause the bottom
of the external supply plenum to pull away from
the hood or cause the face of the hood to become
deformed.
Air Curtain Supply (ASP)
Horizontal Supply Plenum (HSP)
Variable Supply Plenum (VSP)
Mounted with uni-strut and threaded rod
When using the uni-strut (supplied by others), it must be
bolted to the hood and external supply plenum hanger
brackets.
NOTE
The uni-strut needs to be the full length of the hood
and the external supply plenum.
Using Hanger Brackets and Threaded Rod
Air Curtain
Supply Plenum (ASP)
Horizontal Supply Plenum (HSP)
Variable Supply Plenum (VSP)
TURNBUCKLE
TURNBUCKLE
HOOD HANGER
HOOD HANGER
BRACKET
BRACKET
EXTERNAL
EXTERNAL
SUPPLY PLENUM
SUPPLYPLENUM
HANGER BRACKET
HANGER BRACKET
HOOD
EXTERNAL
SUPPLY
PLENUM
3. It is recommended that caulk be applied at the
mating seams and surfaces of the external supply
plenum, the hood, and the wall. If the external supply
plenum is next to a wall, you will need to caulk
around the surface next to the wall. Caulk the joints
with NSF Approved silicone caulk (GE SCS1009, or
its equivalent). The caulk is not provided.
Installing the Supply Duct Collar to the Plenum
Place the duct collar(s) over the opening, fastening
with tack-welds at 1 to 2 in. (2.54 to 5.08 cm) intervals,
or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm)
intervals.
Kitchen Hoods • Type I and Type II10
Installing Backsplash Panels
Flat Backsplash Panel
Material: Stainless
NOTE
• Backsplash length up to 47.25 inches (1200.15mm)
wide ship in one piece; panel lengths over
47.25inches (1200.15mm) ship in multiple pieces
when panel height is <66 inches (1674.4 mm) or
>80inches (2032mm).
• Backsplash length up to 48 inches (1219.2 mm)
wide ship in one piece; panel lengths over 48inches
(1219.2mm) ship in multiple pieces when panel
height is ≥66 inches (1676.4 mm) or ≤80 inches
(2032 mm).
Insulated Backsplash Panel
Material: Stainless
Insulation: 1 in. (25.4 mm)
1 IN. (25.4 MM)
WALL
HEIGHT
LENGTH
NOTE
Panels up to 45 in. (1143 mm) wide ship in one piece;
over 45 in. (1143 mm) in multiple pieces.
HOOD END PANEL
HOOD FRONT PANEL
1. After hood is hung into position, slide the flat flange
of the backsplash panel behind the back of the
hood. If the hood is provided with flat backsplash
panels, divider bars will be provided. Install divider
bars between panels as shown in the flat backsplash
panel section view.
2. After the backsplash panel and dividers have been
positioned, drill holes in the panel and fasten to
the wall. (Fasteners provided by others). The holes
should be spaced to adequately secure the panel to
the wall.
3. Caulk the joints between the hood and the
backsplash panel with NSF Approved silicone caulk
(GE SCS1009 or its equivalent). Caulk provided by
others.
4. Caulk the joint between the backsplash panels when
multiple panels are required with NSF Approved
(GE SCS1009 or its equivalent). Caulk provided by
others.
SLIDE FLANGE
BEHIND BACK
OF THE HOOD
BACKSPLASH PANEL
SECTION VIEW
OF BACKSPLASH
PANEL OVERLAP
Kitchen Hoods • Type I and Type II11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.