Accurex Kitchen Hood Operators Manual

Page 1
Document 470399
Kitchen Hoods
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Type IIType I
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and all applicable local and national building and fire codes. Personnel should be aware of general safety precautions. SMACNA guidelines should be followed for hanging and supporting the hood. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near any electrical components in the hood. Lock and tag the disconnect switch or breaker to prevent accidental power up.
NOTE
Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), and the latest edition of the National Fire Protection Agency Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations (NFPA 96). Follow the Canadian Electrical Code (CEC) and ULC-S650 if installing this product in Canada.
Kitchen Hoods • Type I and Type II 1
Page 2
Receiving
Upon receiving the product, check to ensure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier of any damage detected. The customer will make a notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which is countersigned by the delivering carrier. If damaged, immediately contact your Accurex Representative. Any physical damage to the unit after acceptance is not the responsibility of Accurex, LLC.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading. Filters are shipped on a separate skid in their original packaging. Do not remove factory packaging or install filters until just prior to commissioning. Remove all other shipping/packing materials.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or denting. Damaged finish may reduce ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage.
The ideal environment for storage of the hood and accessories is indoors, above grade in a clean, dry atmosphere that is sealed from the elements. While in storage, inspect equipment routinely. If any moisture, dirt or other accumulations are found on the hood or any of the parts, the source should be located and eliminated.
Removing from Storage
As equipment is removed from storage to be installed in their final location, it should be protected and maintained as outlined in the Handling section above.
Table of Contents
Receiving, Unpacking, Handling and Storage .....2
Removing from Storage .......................2
Canopy Hood Weights ........................3
Proximity Hood Weights .......................4
Supply Plenum
Weights and Dimensions ......................4
Prior to Installation ...........................5
Wall or Single Island Canopy Hoods
Hood Installation Overview ................... 5-6
Filler Panel Installation ........................7
Clearance Reduction Methods
Top, Back, Front and End .................... 7-8
Installing Duct Collars
Exhaust Duct Collars .........................8
Integral Supply Duct Collars ....................8
Installing the Back Supply Plenum
Install the Supply Duct Collar ...................9
Hang the Plenum ............................9
Ductwork ...................................9
Continuous Capture Plenum Hoods .............9
Installing Front/Side External Supply Plenums
Using the Uni-strut ..........................10
Using Hanger Brackets and Threaded Rod .......10
Installing the Supply Duct Collar to the Plenum ....10
Installing Backsplash Panels
Flat Backsplash Panels .......................11
Insulated Backsplash Panels ..................11
Installing End Skirts .........................12
Electrical Connections
Hood Lights / Fan and/or Thermal (Tempering) Switches / Keypads or Touchscreens (Vari-Flow). . . 12
Installing Enclosure Panels ...................13
Double Island Canopy Style Hoods
Installing U-Channel Strips ....................13
Proximity (Backshelf) Hoods ..................14
Plate Shelf with Duct Enclosure Installation .......14
Balancing the Kitchen Exhaust System .........15
Testing Hood Air Volume - Procedures
with Baffle Filters (GH Series) .............. 16-17
with High Velocity Cartridge Filters (GK Series) 18-19 with High Efficiency Filters (GX and GG Series) 20-21
Perforated Face Supply ......................22
Short Circuit Hoods .........................23
Exhaust Air Balancing Baffles .................24
Wiring Diagrams
Amerex® Wiring Plan View ....................25
Ansul® Wiring Plan View .....................26
Wiring Plan View for Kitchen Systems ...........27
Wiring for Switch Panels and Circuit Diagrams ....28
Maintenance
Daily, Weekly, Periodic .......................29
Condensate Hood Baffle and Air Diffusers ........29
Grease Grabber™ Filters Installation & Cleaning 29-30
Filter Washing Frequency Guide ................31
Troubleshooting .......................... 32-33
Replacement Parts ..........................34
Maintenance Log ............................35
Our Commitment ............................36
Kitchen Hoods • Type I and Type II2
Page 3
Canopy Hood Weights
Hood Model
2 ft
.609 m
2.5 ft
.762 m
3 ft
.914 m
Hood Depth (Multiply by Length) for Hood Weight*
3.5 ft
1.067 m
4 ft
1.219 m
4.5 ft
1.372 m
5 ft
1.524 m
5.5 ft
1.676 m
6 ft
1.829 m
6.5 ft
1.981 m
7 ft
2.134 m
7.5 ft
2.286 m
XB, XK,
XX, XTEW
XB, XK,
XX, XTDW
XB, XK, XXFW
XB, XK, XXCW
XB, XK, XXSW
XGEW
XGDW
XGFW
XGCW
XGSW
30 lbs/ft
44.64 kg/m
36 lbs/ft
53.57 kg/m
39 lbs/ft
58.04 kg/m
45 lbs/ft
66.97 kg/m
32 lbs/ft
47.62 kg/m
38 lbs/ft
56.55 kg/m
40 lbs/ft
59.53 kg/m
48 lbs/ft
71.43 kg/m
44 lbs/ft
65.48 kg/m
41 lbs/ft
61.01 kg/m
47 lbs/ft
69.94 kg/m
49 lbs/ft
72.92 kg/m
57 lbs/ft
84.83 kg/m
53 lbs/ft
78.87 kg/m
35 lbs/ft
52.09 kg/m
41 lbs/ft
61.01 kg/m
44 lbs/ft
65.48 kg/m
51 lbs/ft
75.90 kg/m
48 lbs/ft
71.43 kg/m
44 lbs/ft
65.48 kg/m
50 lbs/ft
74.41 kg/m
53 lbs/ft
78.87 kg/m
60 lb/ft
89.29 kg/m
57 lbs/ft
84.83 kg/m
38 lbs/ft
56.55 kg/m
44 lbs/ft
65.48 kg/m
48 lbs/ft
71.43 kg/m
54 lbs/ft
80.36 kg/m
52 lbs/ft
77.38 kg/m
47 lbs/ft
69.94 kg/m
53 lbs/ft
78.87 kg/m
57 lbs/ft
84.83 kg/m
63 lbs/ft
93.75 kg/m
61 lbs/ft
90.78 kg/m
40 lbs/ft
59.53 kg/m
46 lbs/ft
68.46 kg/m
52 lbs/ft
77.38 kg/m
57 lbs/ft
84.83 kg/m
56 lbs/ft
83.34 kg/m
49 lbs/ft
72.92 kg/m
55 lbs/ft
81.85 kg/m
61 lbs/ft
90.78 kg/m
66 lbs/ft
98.22 kg/m
65 lbs/ft
96.73 kg/m
XB, XK, XXEV
XB, XK, XXFV
XB, XK, XXCV
XB, XK, XXSV
XO/XD1
XD2
XD3
20 lbs/ft
29.76 kg/m
24 lbs/ft
35.72 kg/m
28 lbs/ft
41.67 kg/m
43 lbs/ft
63.99 kg/m
58 lbs/ft
86.31 kg/m
32 lbs/ft
47.62 kg/m
48 lbs/ft
71.43 kg/m
64 lbs/ft
95.24 kg/m
52 lbs/ft
77.38 kg/m
61 lbs/ft
90.78 kg/m
36 lbs/ft
53.57 kg/m
53 lbs/ft
78.87 kg/m
70 lbs/ft
104.17 kg/m
54 lbs/ft
80.36 kg/m
66 lbs/ft
98.22 kg/m
66 lbs/ft
98.22 kg/m
40 lbs/ft
59.52 kg/m
58 lbs/ft
86.31 kg/m
76 lbs/ft
113.10 kg/m
56 lbs/ft
83.34 kg/m
68 lbs/ft
101.20 kg/m
69 lbs/ft
102.68 kg/m
44 lbs/ft
65.48 kg/m
63 lbs/ft
93.75 kg/m
82 lbs/ft
122.03 kg/m
58 lbs/ft
86.31 kg/m
72 lbs/ft
107.15 kg/m
72 lbs/ft
107.15 kg/m
48 lbs/ft
71.43 kg/m
68 lbs/ft
101.20 kg/m
88 lbs/ft
130.96 kg/m
61 lbs/ft
90.78 kg/m
75 lbs/ft
111.61 kg/m
81 lbs/ft
120.54 kg/m
76 lbs/ft
113.10 kg/m
52 lbs/ft
77.38 kg/m
73 lbs/ft
108.64 kg/m
94 lbs/ft
139.89 kg/m
93.75 kg/m
117.56 kg/m
125.01 kg/m
117.56 kg/m
*Hood weight calculations are based on standard selection. Hood height, accessories and material gauge affect overall hood weight.
63 lbs/ft
79 lbs/ft
84 lbs/ft
79 lbs/ft
87 lbs/ft
129.47 kg/m
90 lbs/ft
133.93 kg/m
Kitchen Hoods • Type I and Type II 3
Page 4
Proximity Hood Weights
Hood weight is determined using a simple formula. Select the figures provided in columns A and B (see tables) from the three respective categories—Hood Width, Filter Type and Hood Height—based on the hood received. Total the three numbers in column A and the three numbers in column B. Place the sum for column A and the sum for columnB in the Hood Weight equation where shown and solve for the total Hood Weight.
IMPERIAL AB
Category 1: Hood Width (in.)
23 - 25 1.3 28 26 - 28 1.35 30 29 - 32 1.4 31.5 33 - 36 1.45 33.5
Category 2: Filter Type
Baffle 0.3 0
Grease-X-Tractor™
or Cartridge
Grease Grabber™ 1 0
Category 3: Hood Height (in.)
24 - 27 0 0 28 - 33 0.08 5 34 - 38 0.16 10 39 - 42 0.24 15
Example: A B
Category 1: Hood Width 23 - 25 1.3 28
Category 2: Filter Type Baffle 0.3 0
Category 3: Hood Height 24 - 27 0 0
0.4 0
Total: 1.6 28
METRIC AB
Category 1: Hood Width (cm)
58.42 - 63.50 0.232 12.68
66.04 - 71.12 0.241 13.59
73.66 - 81.28 0.250 14.27
83.82 - 91.44 0.259 15.18
Category 2: Filter Type
Baffle 0.054 0
Grease-X-Tractor™
or Cartridge
Grease Grabber™ 0.178 0
Category 3: Hood Height (cm)
60.96 - 68.58 0.000 0
71.12 - 83.82 0.014 2.27
86.36 - 96.52 0.029 4.53
99.06 - 106.68 0.043 6.80
Example: A B
Category 1: Hood Width 58.42 - 63.50 0.232 12.68
Category 2: Filter Type Baffle 0.054 0
Category 3: Hood Height 60.96 - 68.58 0 0
0.071 0
Total: 1.6 28
Hood Weight Equation (lb.)
A x Length (in.) + B = Weight (lb.)
1.6 x 48 + 28 = 104.8 lb.
Hood Weight Equation (kg.)
A x Length (cm.) + B = Weight (kg.)
0.286 x 121.92 + 12.68 = 47.5 kg.
Supply Plenum - Weights and Dimensions
External Supply
Plenum Type
Air Curtain Supply (ASP)
Split Air Curtain Supply (Split ASP)
Back Supply (BSP) 35.0 52.09 6 152.4 Variable Variable 3 to 16 .91 to 4.88
Horizontal Supply (HSP) 14.0 20.83 12 304.8 18 457.2 3 to 16 .91 to 4.88
Variable Supply (VSP) 16.0 23.81 12 304.8 18 457.2 3 to 16 .91 to 4.88
Weight
lbs/ft 8.3 8.6 8.9 9.2 9.5 9.8 10.1 10.4 10.7 11.1 11.3 11.6 11.9 12.2 12.5
kg/m 12.35 12.80 13.24 13.69 14.14 14.58 15.03 15.48 15.92 16.52 16.82 17.26 17.71 18.16 18.60
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
lbs/ft kg/m in. mm in. mm ft. m
Refer to Air Curtain
Supply Plenum
Weight Table
15.5 23.07 24 609.6 10 254.0 3 to 16 .91 to 4.88
Weight Width Height Length per section
Refer Air Curtain
Supply Plenum
Weight Table
Air Curtain Supply Plenum Width (inches)
10 to 24 254.0 to 609.6 10 254.0 3 to 16 .91 to 4.88
Kitchen Hoods • Type I and Type II4
Page 5
Prior to Installation
Wall or Single Island Canopy Hoods
Prior to installation, check with the Authorities Having Jurisdiction (AHJ) on clearance requirements to structures surrounding the hood and other equipment. Verify there is enough space to safely lift hood up into its operating position and enough clearance around the hood for components like fire system connections, hood lights, hood control components, etc. Consider access for servicing the equipment and the different components when locating the hood.
If the hood is a grease hood (Type I), the UL label located on the end panel on the inside of the hood will provide pertinent information regarding the hood installation. Information includes:
• Allowable cooking surface temperatures of the cooking equipment
• Front and side overhang/underhang requirements
• Minimum exhaust (and possibly supply) airflow requirements
• Hood lighting load information and restrictions
• Filter information
• Fire damper fusible link replacement information, if applicable
With the hood still inside its packing crate, position the unit beneath its installation location. Carefully remove the packing crate and place some protective material on the floor next to the crate to avoid damaging the hood as it is tipped on its side. Tip the hood carefully onto the protective material.
Bottom of Hood
Hood Installation Overview
1. If the hood is provided with filler panels, shipped loose, install them now. See page 7, Filler Panel Installation. Filler panels may be integral to the hood, which requires no additional installation.
2. If the hood is equipped with Clearance Reduction Methods, refer to pages 7 and 8 for special considerations with hanging the hood.
3. If the hood is provided with hood/duct sensors or thermostats, install them now. See the Installation and Operations guide provided with the control panel.
4. If the hood was provided with either exhaust collars or supply collars that have shipped loose, it is recommended that the exhaust and supply openings are cut and collars are attached now, prior to hanging the hood. See page 8, Installing Duct Collars.
5 If the hood is provided with a back supply plenum
(BSP) install it now. See page 9, Installing the Back Supply Plenum.
6. If possible, connect (weld) exhaust duct to the hood while on the floor, unless it prohibits the hood from being raised into place. For information on ductwork, see page 9, Ductwork.
7. At this point, drill holes in the building structural support system or utilize uni-strut to match up with the hanger bracket holes. Then slowly and evenly raise the hood into position and insert 1/2-inch (12.7mm) diameter threaded rod (provided by others) between the hanger brackets and structure.
For Type I hoods, the hood hanging height
requirements are given on the UL label. Typical canopy hood hanging height will be 80inches (198.12cm) off the finished floor.
Pallet
Protective Material
NOTE
If the hood is supplied with ceiling enclosures, the height of the enclosures will typically be the distance from the ceiling to the top of the hood. Use this dimension to find the hood’s hanging height off of the floor.
For questions regarding the supporting structure and its integrity, either the contractor or structural engineer needs to be consulted.
Kitchen Hoods • Type I and Type II 5
Page 6
Wall or Single Island Canopy Hoods - continued
NOTE
All hanger brackets MUST be used and the hood must be properly supported while lifting to prevent damage or distortion to the hood.
NOTE
The hood MUST be hung evenly. If hung unevenly, this may cause grease drainage problems. Provide additional support if necessary so that the hood doesn’t move in a manner that is acceptable with the Authorities Having Jurisdiction (AHJ).
WARNING
When mounting the hood or any components against the hood, never puncture or drill into the canopy. This will void the hood listing and warranty.
8. If the hood was provided in sections with the continuous capture option, once each hood section is hung, install this option now. See page 9, Continuous Capture Plenum Hoods.
9. If the hood was provided with any front or side external supply plenums (other than the back supply plenum), install these now. See page 10, Installing Front/Side External Supply Plenums.
10. Install the remainder of both the exhaust and supply ductwork. For further guidelines see page 9, Ductwork.
11. If the hood is provided with any backsplash/ sidesplash panels, install them now. See page 11, Installing Backsplash Panels.
12. If the hood is provided with any end skirts, install them now. See page 12, Installing End Skirts.
13. If the hood is a Type I hood, it will require a fire suppression system. Once the Type I hood(s) and ductwork are fully installed, appliances are in place and walls are complete, the fire system should be completed. If the hood is provided with a full factory-coordinated fire suppression system installation, the certified fire system installer should be contacted at this time to complete the final hookups, testing and system certification based upon manufacturer’s specification and local fire codes. If the hood is not provided with either pre­piping only or no fire suppression system, it is the responsibility of a certified fire system installer to install, test and certify the system based upon manufacturer’s specification and local fire codes.
14. If the hood is provided with a control package, these will need to be installed and wired by the jobsite electrician. This typically includes wiring the hood temperature sensors, hood lights and wiring the fire suppression micro-switches. For general hood electrical connections, see page 12, Electrical Connections. If applicable, see the Installation and Operations guide provided with the control package.
15. If the hood is provided with enclosure panels, install them now. See page 13, Installing Enclosure Panels.
16. Install the rest of the hood accessories provided. This may include grease filters or condensate hood baffles, grease cups, light bulbs (provided by others unless LED tube style), light globes, and trim strips.
It is recommended that the protective plastic sheeting remain on the hood until fully installed to better protect the product from scratching and marking. Once removed, use stainless steel polish, such as BlueAway or equivalent, to clean the hood and/or remove marks or discoloration. Be sure to wipe with the grain and not against it.
Kitchen Hoods • Type I and Type II6
Page 7
Filler Panel Installation
Clearance Reduction Methods
1. Uncrate the hood and lay it on the floor with protective material between the hood and the floor.
2. Bolt the filler panels together with 5/16 in. bolts provided in the hardware package.
3. Position the filler panels to the hood back, and tack­weld them into place.
HOOD
HOOD
HOOD
TACK-WELDED TO HOOD BACK
5/16 IN. X 3/4 IN. BOLTS WITH WASHERS & NUTS
RIGHT FILLER PANEL
BOTTOM FILLER PANEL
4. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
Clearance reduction methods have been evaluated and tested and are listed by UL (Underwriters Laboratory). The method of test was derived from the UL 710 test standard.
The hood may be installed with zero clearance to combustible materials if constructed in the following manner.
1. One inch (2.54 cm) thick layer of insulation of Owens Corning
®
Type 475, Johns Manville Type 475, IIG® MinWool-1200® Flexible Batt, or Knauf Insulation Type EI 475.
2. Insulation must be held securely in place. Pins that are welded or secured with an adhesive may be used.
3. A backsplash panel must be attached to the wall (insulated or uninsulated).
To comply with the UL Listing, the cooking appliances must be as follows:
• Maximum surface temperature is 700°F (371°C)
• Appliances are located at least 3 in. (7.62 cm) from the rear wall
• Appliances are at least 40 in. (101.6 cm) below the bottom front edge of the hood
The hood may be installed with 3 in. (7.62 cm) clearance to limited combustible materials per NFPA 96 if constructed in one of the following methods:
• 3 in. (7.62 cm) rear uninsulated stand-off
• 3 in. (7.62 cm) top enclosure panel system
• 3 in. (7.62 cm) end uninsulated stand-off
Top Clearance Reduction Options
One inch (2.54 cm) layer of insulation installed on top of the hood (optional) meets zero inch requirements for clearance to combustible surfaces as outlined under the clearance reductions methods.
Three inches (7.62cm) uninsulated airspace installed on top of hood (optional) meets NFPA 96 requirements for clearance to limited combustible surfaces.
Kitchen Hoods • Type I and Type II 7
Page 8
Back and Front Clearance Reduction Options
One inch (2.54 cm) layer of insulation in 3 in. (7.62cm) back stand-off meets zero inch requirements for clearance to combustible surfaces as outlined under the clearance reduction methods.
Three inches (7.62 cm) uninsulated back stand-off meets NFPA 96 requirements for clearance to limited combustible surfaces.
One inch (2.54 cm) layer of insulation factory-installed on the front of the hood (optional) meets zero inch requirements for clearance to combustible surfaces.
Installing Duct Collars
Exhaust Duct Collars
1. The exhaust duct connection needs to be located within 48 in. (121.92 cm) from the center of the hood length to the center of the duct connection and within shaded area as shown.
Top View of the Hood
Hanger Bracket
Exhaust Plenum
14 in.
Duct cut out area
3 in.
Hood Width
End Clearance Reduction Options
One inch (2.54 cm) layer of insulation factory-installed on the end of the hood (optional) meets zero inch requirements for clearance to combustible surfaces under the clearance reduction methods.
Three inches (7.62 cm) uninsulated airspace installed on end of hood (optional). Meets NFPA 96 requirements for clearance to limited combustible surfaces.
16 in.
8 in.
8 in.
Supply Plenum
Hood Length
Front of hood
Back View of the Hood
8 in. 8 in.
1 in.
12 in.
Hood Top
Exhaust Plenum
Duct cut out area
2. The exhaust duct connection is to be a continuous liquid-tight weld. Weld with a non-ferrous filler wire, such as silicon bronze or stainless steel filler wire. Protect all stainless steel areas from weld splatter.
Integral Supply Duct Collars
1. The supply duct connection needs to be located within the shaded Supply Plenum area as in the drawing above.
2. The supply duct connection is tack-welded at 1 to 2inch (2.54 to 5.08 cm) intervals or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm) spacing to the hood.
Supply duct connection to be tack welded with 1 to 2 inch tack or
Supply Duct
Connection
sheet metal screws at 3 to 6 inch spacing to hood.
3 in.
3. For hoods that are insulated, the edges of the insulation must be taped after the hole is cut. (The insulation tape is provided by
Internal Supply Chamber
Supply Fire Damper
others).
4. On combination hoods, make
Hood
certain the fire damper is located over the internal supply
Insulated Supply Plenum
chamber.
Exhaust Capture
Kitchen Hoods • Type I and Type II8
Page 9
Installing the Back Supply Plenum
BOLT OR WELD
HOOD TOP
HOOD END
SUPPORT ANGLES
CAULK
BOLT
U-CLIP
HOOD
ACORN NUT
2. RAIS AND
3. FAST
4. FAST
5. CAU
& CAP
1. REM
HOOD FRONT
HOOD FRONT
REMOVE SUPPORT ANGLES ON THE OPEN END PANEL
Ductwork
Install the Supply Duct Collar
1. Find the center of the back supply plenum.
2. If the back supply plenum is to have one opening, cut the opening such that it is centered at L /2 from the plenum end. (Fig.1)
3. If the back supply plenum is to have two openings, cut openings such that they are centered at L /4 from each end of the plenum. (Fig. 2)
4. Place the duct
L/4
collar(s) over the opening(s), fastening with screws or tack-welds every 4 to 6 in. (10.16 to
15.24cm). (Fig. 3)
Hang the Plenum
Fig. 2
5. Hang the back
supply plenum from the ceiling.
The back supply plenum
needs to be mounted 31.25in. (79.375 cm) above the finished floor. This is measured from the lowest rear edge of the back supply plenum to the finished floor. (Fig. 4)
Hang using threaded rod
placed through the hanger brackets.
Fig. 1
L (MODULE LENGTH)
L/2
Fig. 3
L (MODULE LENGTH)
L/2
L/2
L/4
Exhaust - As specified in NFPA 96, Ch. 7.5 (latest
edition), exhaust duct systems must be constructed in the following manner:
Materials: Ducts shall be constructed of and supported by carbon steel not less than 1.37 mm (0.054 in.) (No. 16 MSG) in thickness, or stainless steel not less than
1.09 mm (0.043 in.) (No. 18 MSG) in thickness.
Installation: All seams, joints, penetrations, and duct to hood collar connections shall have a liquid-tight external weld. If you have an automatic fire damper, please refer to that manual for installation instructions now.
Supply - Supply ductwork (where applicable) should
be connected to the hood in a manner approved by the local code authorities.
NOTE
For hoods with fire dampers in the exhaust and supply duct collars, an access panel for cleaning and inspection shall be provided in the duct. This panel shall be as close to the hood as possible but should not exceed 18 in. (45.72 cm).
For proper installation of duct collars when they are shipped unattached, see page 8.
Continuous Capture Plenum Hoods
1. Remove the support angles provided for support during shipping on the open end panels. Install and level both hoods.
FASTENERS HOLDING THE
BACKSUPPLY TO THE WALL
31.25 INCH CRITICAL
Fig. 4
DIMENSION
6. Fasten the back supply to the wall, going through the lower back supply wall.
These fasteners are to help maintain the location of
the back supply, and are not intended to hold the weight of the back supply unit.
The fasteners should not interfere with the
removable air diffusers.
2. After leveling, secure the hoods together by tack­welding and/or bolting the angles that are located at the top of the hoods along its width (Fig. 5).
3. Next, fasten the hoods together at its inside plenum profile using u-clips and bolts (Fig.6). Caulk this joint with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
Kitchen Hoods • Type I and Type II 9
Fig. 5
Fig. 6
Page 10
Installing Front/Side External Supply Plenums
Using the Uni-strut
THREADED ROD
SUPPLIED BY OTHERS
UNI-STRUT (U-CHANNEL)
SUPPLIED BY OTHERS
END VIEW
HOOD
The uni-strut (supplied by others) supporting the hood may be cantilevered over the end of the hood. Utilizing the external supply plenum’s hanger brackets, securely fasten to the uni-strut.
THREADED
THREADED
ROD
ROD
UNI-STRUT
UNI-STRUT
(U-CHANNEL)
(U-CHANNEL)
EXTERNAL
SUPPLY PLENUM
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by others) into hanger brackets on the external supply plenum top. Raise and hang the external supply plenum from adequate roof or ceiling supports.
NOTE
Ensure the external supply plenum is installed flush with the hood front and is plumb and level by adjusting the threaded rod(s). There should be no gap between the bottom of the external supply plenum and the hood after installation and adjustments are completed.
2. The external supply plenum should be resting lightly against the hood. The hood is only used to position the plenum; it is not intended to support the plenum. All hanger brackets on the external supply plenum must be used and the plenum must be properly supported while lifting to prevent damage or distortion. The external supply plenum must be level to operate properly.
NOTE
After hanging, secure the external supply plenum to the hood (or to another external supply plenum) using the supplied turnbuckle(s). Use caution tensioning the turnbuckle. Too much tension may cause the bottom of the external supply plenum to pull away from the hood or cause the face of the hood to become deformed.
Air Curtain Supply (ASP)
Horizontal Supply Plenum (HSP)
Variable Supply Plenum (VSP)
Mounted with uni-strut and threaded rod
When using the uni-strut (supplied by others), it must be bolted to the hood and external supply plenum hanger brackets.
NOTE
The uni-strut needs to be the full length of the hood and the external supply plenum.
Using Hanger Brackets and Threaded Rod
Air Curtain
Supply Plenum (ASP)
Horizontal Supply Plenum (HSP)
Variable Supply Plenum (VSP)
TURNBUCKLE
TURNBUCKLE
HOOD HANGER
HOOD HANGER
BRACKET
BRACKET
EXTERNAL
EXTERNAL
SUPPLY PLENUM
SUPPLY PLENUM
HANGER BRACKET
HANGER BRACKET
HOOD
EXTERNAL
SUPPLY PLENUM
3. It is recommended that caulk be applied at the mating seams and surfaces of the external supply plenum, the hood, and the wall. If the external supply plenum is next to a wall, you will need to caulk around the surface next to the wall. Caulk the joints with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
Installing the Supply Duct Collar to the Plenum
Place the duct collar(s) over the opening, fastening with tack-welds at 1 to 2 in. (2.54 to 5.08 cm) intervals, or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm) intervals.
Kitchen Hoods • Type I and Type II10
Page 11
Installing Backsplash Panels
Flat Backsplash Panel
Material: Stainless
NOTE
• Backsplash length up to 47.25 inches (1200.15mm) wide ship in one piece; panel lengths over
47.25inches (1200.15mm) ship in multiple pieces when panel height is <66 inches (1674.4 mm) or >80inches (2032mm).
• Backsplash length up to 48 inches (1219.2 mm) wide ship in one piece; panel lengths over 48inches (1219.2mm) ship in multiple pieces when panel height is ≥66 inches (1676.4 mm) or ≤80 inches (2032 mm).
Insulated Backsplash Panel
Material: Stainless Insulation: 1 in. (25.4 mm)
1 IN. (25.4 MM)
WALL
HEIGHT
LENGTH
NOTE
Panels up to 45 in. (1143 mm) wide ship in one piece; over 45 in. (1143 mm) in multiple pieces.
HOOD END PANEL
HOOD FRONT PANEL
1. After hood is hung into position, slide the flat flange of the backsplash panel behind the back of the hood. If the hood is provided with flat backsplash panels, divider bars will be provided. Install divider bars between panels as shown in the flat backsplash panel section view.
2. After the backsplash panel and dividers have been positioned, drill holes in the panel and fasten to the wall. (Fasteners provided by others). The holes should be spaced to adequately secure the panel to the wall.
3. Caulk the joints between the hood and the backsplash panel with NSF Approved silicone caulk (GE SCS1009 or its equivalent). Caulk provided by others.
4. Caulk the joint between the backsplash panels when multiple panels are required with NSF Approved (GE SCS1009 or its equivalent). Caulk provided by others.
SLIDE FLANGE BEHIND BACK OF THE HOOD
BACKSPLASH PANEL
SECTION VIEW OF BACKSPLASH PANEL OVERLAP
Kitchen Hoods • Type I and Type II 11
Page 12
Installing End Skirts
Electrical Connections
1. After the hood is hung in position, line up the top of the end skirt with the end panels of the hood.
2. Drill a hole in the hood end panel to line up with the hole in the end skirt. Attach the end skirt with a 1/4in. bolt and cap nut to the inside of the hood, or tack-weld the end skirt to the hood.
3. Position the end skirt against the wall and attach. The method depends on the wall construction. (Fasteners provided by others).
4. Caulk the internal joint formed by the end skirt and the hood end panel with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
5. To allow for ease in cleaning, also caulk all the external seams.
HOLE DRILLED BY INSTALLER
1/4 INCH BOLT AND CAP NUT SUPPLIED BY MANUFACTURER
See pages 25-28 for more wiring details regarding the fire system, fan control and switches.
Hood Lights
If the hood is provided with lights, a junction box will be located on top of the hood for field connections. Use minimum 14 AWG copper wire. Light bulbs will not be provided (unless equipped with LED tube style fixtures). For incandescent or compact fixtures, standard light bulbs up to 100 watts may be used.
CAUTION
For multiple hood systems that have more than 14 lights total, incandescent or fluorescent, the hood lights must be wired to multiple circuits. Each circuit must have less than 14 lights total.
WARNING
All 120 VAC field wiring (or higher) must be high temperature rated and must be routed through hard or flex conduit. All low voltage field wiring should be plenum rated if not routed through conduit. All wiring should not come in contact with the surface of the hood.
FULL END SKIRT
ATTACH TO WALL
FASTENERS BY OTHERS
HEMMED EDGE
Hood Light, Fan and/or Thermal (Tempering) Switches
If the hood is provided with hood light, fan and/or thermal (tempering) switches and the switches are located on a hood mounted utility cabinet or on the face of the hood, a junction box will be located on top of the hood for field connections and must be connected in the field (unless factory-wired). Use minimum 14 AWG copper wire for all 120 VAC field connections. Standard switches will be rated for 15 amps. Higher amperage switches are available upon request.
Keypads or Touchscreens (Vari-Flow)
If the hood system is equipped with a Vari-Flow control panel, it may be equipped with either a keypad or touchscreen that can be mounted on a hood-mounted utility cabinet or mounted on the face of the hood. The keypad/touchscreen may be factory connected and wired to a female-to-female connector on top of the hood where the field will have to run factory-provided cabling from this connector back to the control panel. See the Vari-Flow wiring schematic and Installation and Operation Manual for more details.
Plenum LED Puck Lights
If the hood is provided with plenums equipped with 120VAC LED puck lights, a junction box will be located on top of the plenum for field connections. Use minimum 14 AWG copper wire for field connections. Each light uses 3.5 watts.
Kitchen Hoods • Type I and Type II12
Page 13
DOUBLE ISLAND CLIP
Installing Enclosure Panels
Double Island Canopy Style Hoods
Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork attached and all fire system and electrical connections completed.
1. Position the end enclosure panels on the hood, and clamp into place with clamps provided or tack-weld the panels into place.
2. Fasten the end enclosure panels to the wall; method depends on wall construction. (Fasteners provided by others).
If the hood is a double island, bolt the end enclosure
panels together. (Fasteners provided by others).
3. Position the front enclosure panel(s) on the hood, and bolt to the end enclosure panels with the 5/16 in. bolts provided in the hardware package.
4. Tack-weld or clamp the front enclosure panel(s) to the hood. If clamps are used, they must be positioned 4in. (10.16 cm) from the ends and in the center of the front enclosure panel.
5. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
NOTE
Before hanging the hoods, please verify the hood marks to ensure the correct hood is hung on the correct side.
A double island hood is created by installing two wall style hoods back to back. Use the installation procedure described for single island canopy hoods; install and level both hoods. After leveling, secure the hoods together by tack-welding and/or bolting the rear mounting brackets together. Double island hoods may also be provided with a U-Channel to seal the seam between the two hoods.
Installing U-Channel Strip
1. After the hood is hung in position and leveled, apply caulk to the inside edge of the double island clip.
2. Position and install the clip by tapping into position along clip (friction fit).
3. Caulk edges to seal out grease and allow for ease of cleaning. Caulk with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
NOTE
Installation instructions may not be applicable for concrete ceilings.
BOLT PANELS TOGETHER WITH 5/16 INCH BOLTS SUPPLIED BY MANUFACTURER
CLAMP PANELS TO HOOD STANDING SEAM WITH HARDWARE SUPPLIED BY MANUFACTURER
END ENSLOSURE PANEL
HOOD TOP
FRONT ENCLOSURE PANEL
END ENSLOSURE PANEL
ITEM-1B
ITEM-1A
HOOD FRONT
HOOD-1A
HOOD-1B
SILICONE CAULK (GE SCS1009)
DOUBLE ISLAND CLIP
HOOD BACK
ATTACH TO WALL FASTENERS BY OTHERS
Kitchen Hoods • Type I and Type II 13
Page 14
Proximity (Backshelf) Hoods
A proximity style hood is designed to be mounted close to the cooking appliance and typically incorporates underhang instead of overhang as utilized with canopy style hoods.
UL Vertical Distance
Above Cooking Surface
The proximity design, in addition to the hanger brackets, may include a back mounting flange. Therefore, hanging the hood differs slightly from that of a wall or single island canopy hood.
1. Locate the studs in the wall.
2. Drill 1/2 inch (13 mm) diameter holes in the hood mounting flange. Be sure to align to wall studs.
3. Lift hood into a level position and lag bolt hood to wall (fasteners by others).
4. Bolt 1/2 inch threaded rod into the remaining hanging brackets.
5. Fasten threaded rod to the ceiling supports, then level the hood.
Plate Shelf with Duct Enclosure Installation
If the proximity hood is provided with a plate shelf, this will be factory mounted to the hood (shown loose in figure below). Similar to the standard enclosure panel installation procedures, make sure the hood is hung in position with all the ductwork attached and fire system and electrical connections completed before attaching the enclosures.
1. Tack-weld or clamp end enclosure panels into place (clamps provided).
2. Attach the end enclosure panels to the wall (fasteners are not provided).
3. Position the front enclosure panel(s) on the hood and bolt to the end enclosure with the 5/16 inch bolts provided.
4. Tack-weld or clamp the front enclosure panel(s) to the hood. If clamps are used, they must be positioned 4inches (100 mm) from the ends and in the center of the front enclosure panel.
5. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
Mounting Flange
Hanger Brackets
If the proximity hood was provided with a back supply plenum, the hood mounting flange may be fastened to the back supply using sheet metal screws (by others). Pilot holes are recommended.
NOTE
Installation instructions may not be applicable for concrete ceilings.
End Enclosure Panels
Front Enclosure
Plate Shelf
Standing
Seam
Kitchen Hoods • Type I and Type II14
Page 15
Balancing the Kitchen Exhaust System
To determine the proper dining room air balance:
1. Refer to engineering drawings to determine total exhaust CFM from dining areas. (exhaust fans, heating and air conditioning units, rest rooms, etc.)
2. Determine the total CFM of make-up air supplied to dining area.
3. Subtract #1 from #2 above. If the result is a negative number, a negative pressure is present in the dining area. In this case, kitchen exhaust odors could be drawn from the kitchen to the dining area. Therefore, exhaust or supply air should be adjusted to provide a slight positive pressure in the dining area.
To determine proper kitchen air balance:
1. Refer to engineering drawings to determine total exhaust from the kitchen area. (exhaust hoods, dishwasher hoods, etc.)
2. Determine total CFM of make-up air supplied to kitchen area. (make-up air hoods, heating and air conditioning units, etc.)
3. Subtract #1 from #2 above. The result should be a negative number. If the result is a positive number, a positive pressure is present in the kitchen area. Kitchen odors could be forced into the dining area. Also, a positively balanced kitchen area can adversely affect the performance of the exhaust hood.
CAUTION
According to NFPA 96, Ch. 8-3 Replacement Air: Replacement air quantity shall be adequate to prevent negative pressures in the commercial cooking area(s) from exceeding 4.98 Pa (0.02 in. wg).
NOTE
The airflow rates were established under controlled laboratory conditions.
NOTE
Greater exhaust and/or lesser supply air may be required for complete vapor and smoke control in specific installations.
Kitchen Hoods • Type I and Type II 15
Page 16
Testing Hood Air Volume
Baffle Filter - Rotating Vane Method
With all the filters in place, determine the total hood exhaust volume with a rotating vane anemometer as follows:
1. All cooking equipment should be on.
2. Measure the velocities. Velocity measurements should be taken at five locations per filter. These must be over a filter slot as in Fig. 7.
the anemometer at the 2 in. (50.8 mm) distance and parallel to the filter. Both squareness and distance are very important for accuracy.
Rotating Vane Anemometer
Airflow
2 in.
(50.8 mm)
Fig. 7
Calculate the average velocity for the filter.
3. Determine the filter’s conversion factor from the
4. Calculate the filter’s volume in CFM (m
5. Calculate the hood’s volume by repeating the
X
X
X
L
Nominal Filter Size
H/4
X
H
X
H/2
H/4
Measure and record the velocity of each location.
A digital 2.75 in. (69.85 mm) rotating vane anemometer or equivalent is suggested. The center of the anemometer should be held 2 in. (50.8 mm) from the face of the filters. It is helpful to make a bracket to keep
Example: Exhaust only hood with three 20 x 16 filters
Measured velocities in ft/min. for one 20 x 16 filter
Average Velocity =
Sum of Velocity Readings
Number of Readings
table.
3
/hr) by multiplying the average velocity by the conversion factor.
process for the remaining filters and summing the individual filter volumes.
Nominal Filter Size (H x L) Imperial
Inches Millimeters
16 x 16 400 x 400 1.63 .157
16 x 20 500 x 400 2.13 .198
20 x 16 400 x 500 1.90 .177
20 x 20 500 x 500 2.48 .230
Conversion
255
(4663.44 m/h)
248
(4535.42 m/h)
Factor
256
(4681.73 m/h)
Metric
Conversion
Factor
250
(4572 m/h)
240
(4389.12 m/h)
(Imperial)
(Metric)
255 + 250 + 256 + 248 + 240
=
4663 + 4572 + 4681 + 4535 + 4389
=
5
5
249.8 ft/min.
=
=
4568 m/hr
For a nominal filter size of 20 x 16, the conversion factor is 1.90 Imperial (.177 Metric)
Volume for one filter = Conversion Factor x Average Velocity
(Imperial)
(Metric)
= 1.90 x 249.8 ft/min. = 474.6 cfm
= .177 x 4568 m/hr = 809 m3/hr
Total hood volume = (Filter 1 Volume) + (Filter 2 Volume) + (Filter 3 Volume)
(Imperial)
(Metric)
Kitchen Hoods • Type I and Type II16
= 474.6 + 455.4 + 470.1 = 1400.1 cfm
= 809 + 880 + 799 = 2488 m3/hr
Page 17
Baffle Filter - Shortridge Method
With all the filters in place, determine the total hood exhaust volume with a Shortridge meter as follows:
1. All cooking equipment should be on. If the hood has internal short circuit make-up air, it should be turned off.
2. Measure velocities
• Set up the Shortridge meter.
For 20 in. (500 mm) wide filters, position the
grid as shown in Fig. 8 and 9. Average the two measurements.
For 16 in. (400 mm) wide filters, position the grid as
shown in Fig. 10.
Take velocity readings for each filter.
3. Calculate each filter’s volumetric flow rate as follows:
Calculate each filter’s average velocity by summing
the velocity readings and dividing by the number of readings for each filter.
Multiply the average velocity by the conversion factor
to obtain the volumetric flow rate for each filter.
4. Calculate the hood’s total volumetric flow rate by summing the volumetric flow rate of each individual filter in the hood as calculated in Step 3.
Place standoff spacers against face of outlet or inlet grill, filter, coil, etc.
Maintain 1½ inch (38.1 mm) margin
Swivel bracket
Tubing connectors
Extension rods
Pushbutton handle and plug
Handle bracket
Captive knob screws
Edge of outlet/inlet active face area
Maintain 1½ inch (38.1 mm) margin
Tubing harness
Pressure input ports
External read jack
Neckstrap
NOTE
For best accuracy multiply the velocity of each filter by its conversion factor and sum the flow rates. Averaging the velocity measured for all filters may cause error.
Nominal Filter Size (H x L)
Inches Millimeters
16 x 16 400 x 400 1.66 .154
16 x 20 400 x 500 2.10 .195
20 x 16 500 x 400 1.96 .182
20 x 20 500 x 500 2.40 .223
Example: Measured velocities for a 20 x 20 filter = 185 and 189 ft/min.
Average Velocity =
(Imperial)
(Metric)
Flow rate for one filter =
(Imperial)
(Metric)
Total hood flow rate = (Filter 1 Flow Rate) + + (Filter x Flow Rate)
(Imperial)
(Metric)
Sum of Velocity Readings
Number of Readings
185 + 189
=
3383 + 3456
=
2
2
Conversion
Factor
= 187.0 ft/min.
3420 m/hr
=
Average
x
Velocity
= 2.40 x 187.0 ft/min. = 448.8 cfm
= .223 x 3420 m/hr = 763 m3/hr
= 448.8 + 457.8 + 437.5 + 444.8 = 1788.9 cfm
= 763 + 778 + 743 + 756 = 3040 m3/hr
Fig. 8
Fig. 9
Fig. 10
Imperial
Conversion
Factor
17.25 in.
17.25 in.
(2978.15 mm)
(2978.15 mm)
(355.6 mm)
(355.6 mm)
Metric
Conversion
Factor
14 in.
14 in.
(355.6 mm)
(355.6 mm)
2.75 in.
2.75 in.
(69.85 mm)
(69.85 mm)
6 in.
6 in.
(152.4 mm)
(152.4 mm)
14 in.
14 in.
2.75 in.
2.75 in.
(69.85 mm)
(69.85 mm)
10 in.
10 in.
(254 mm)
(254 mm)
10 in.
10 in.
(254 mm)
(254 mm)
10 in.
10 in.
(254 mm)
(254 mm)
Kitchen Hoods • Type I and Type II 17
Page 18
High Velocity Cartridge Filters - Rotating Vane
A
Method
With all the filters in place, determine the total hood exhaust volume with a rotating vane anemometer as follows:
1. All cooking equipment should be on. If the hood has internal short circuit make-up air, it should be turned off.
2. Measure velocities.
Velocity measurements should be taken at three
locations per filter. These must be over the inlet opening as shown in Fig. 11.
Measure the velocity of each location. A digital
2.75 in. (69.85 mm) rotating vane anemometer or its equivalent is suggested. The center of the anemometer should be held 2 in. (50.8 mm) from the face of the filters as in Fig. 12. It is helpful to make brackets to keep the anemometer at the 2 in. (50.8 mm) distance and parallel to the filter. Both squareness and distance are important for accuracy.
3. Calculate the average slot velocity.
4. Calculate the CFM per linear foot by dividing the average velocity by a conversion factor listed in the following table.
5. Calculate each filter’s volumetric flow rate in CFM by multiplying the average velocity for each filter by the conversion factor.
Fig. 11
1/4 Width
Fig. 12
Rotation Vane
nemometer
2 in.
(50.8 mm)
1/2 Width
Cartridge Filter Size
16 in. (400 mm) high with 4 in. (100 mm) high inlet
20 in. (500 mm) high with 4 in. (100 mm) high inlet
16 in. (400 mm) high with 7 in. (120 mm) high inlet
20 in. (500 mm) high with 7 in. (120 mm) high inlet
1/4 Width
Imperial
Conversion
Factor
3
ft
1.63 1/
3
ft
2.15 1/
3
ft
1.24 1/
3
ft
1.58 1/
1/2 Height
Inlet
Height
Filter
Height
Metric
Conversion
Factor
5.35 1/m
7.05 1/m
4.07 1/m
5.18 1/m
3
3
3
3
Example:
Measure the slot velocities in ft/min. for a 9 ft. (2.74 m) hood with four 20 x 20 in. (500 x 500 mm) filters with the standard 4 in. (101.6 mm) opening, three readings per filter.
Average Velocity =
(Imperial)
(Metric)
CFM per linear foot =
(Imperial)
(Metric)
Hood exhaust volume = CFM/linear foot (m3/hr / m) x Hood Length
(Imperial)
(Metric)
Sum of Velocity Readings
Number of Readings
5330
=
12
97474
=
12
=
= 8123 m/hr
Average Slot Velocity
Conversion Factor
444.2 ft/min.
=
=
2.15
8123 m/hr
7.05
444.2 ft/min.
= 206.6 cfm/linear ft.
= 1152 m3/hr
Filter Readings (ft/min.)
470 440 425
482 430 453
455 431 441
399 439 465
Filter Readings (m/hr)
8595 8047 7772
8815 7864 8284
8321 7882 8065
7297 8028 8504
= 206.6 x 9 ft. = 1859.4 cfm
= 1152 x 2.74 m = 3156 m3/hr
Kitchen Hoods • Type I and Type II18
Page 19
High Velocity Cartridge Filters - Shortridge Meter
With all the filters in place, determine the total hood exhaust volume with a Shortridge meter as follows:
1. All cooking equipment should be on. If the hood has internal short circuit make-up air, it should be turned off.
2. Measure velocities
Set up the Shortridge meter. Leave all holes of
VelGrid open. Do NOT tape over holes that are not over openings. The conversion factor takes this into account.
Position the grid over each filter. Refer to Fig. 13
• Take velocity readings for each filter.
3. Calculate each filter’s volumetric flow rate as follows:
Calculate each filter’s average velocity by summing
the velocity readings and dividing by the number of readings for each filter.
Multiply the average velocity by the conversion factor
to obtain the volumetric flow rate for each filter.
4. Calculate the hood’s total volumetric flow rate by summing the volumetric flow rate of each individual filter in the hood as calculated in Step 3.
NOTE
For best accuracy multiply the velocity of each filter by its conversion factor and sum the flow rates. Averaging the velocity measured for all filters may cause error.
Place standoff spacers against face of outlet or inlet grill, filter, coil, etc.
Maintain 1½ inch (38.1 mm) margin
Swivel bracket
Tubing connectors
Extension rods
Nominal Filter Size
(H x L)
Inches Millimeters
16 x 16 400 x 400
16 x 20 400 x 500
20 x 16 500 x 400
20 x 20 500 x 500
Pushbutton handle and plug
Handle bracket
Captive knob screws
Imperial
Conversion
Factor
Edge of outlet/inlet active face area
External read jack
2
ft
1.22
2
ft
1.67
2
ft
1.21
2
ft
1.50
Maintain 1½ inch (38.1 mm) margin
Tubing harness
Pressure input ports
Neckstrap
Metric
Conversion
Factor
2
.113 m
2
.155 m
2
.112 m
2
.139 m
Example:
Measured velocities for 20 x 20 filter = 282 ft/min. (5157 m/hr)
Flow rate for one filter =
(Imperial)
(Metric)
Conversion
Factor
= 1.50 x 282 ft/min. = 423.0 cfm
= .139 x 5157 m/hr = 717 m3/hr
Total hood flow rate = (Filter 1 Flow Rate) + + (Filter X Flow Rate)
(Imperial)
(Metric)
= 423.0 + 421.8 + 420.7 + 418.2 = 1683.7 cfm
= 717 + 717 + 715 + 711 = 2860 m3/hr
x
Average
Velocity
Fig. 13
1/2 width
1/2 height
Kitchen Hoods • Type I and Type II 19
Page 20
Grease-X-Tractor™ High Efficiency Filters or Grease Grabber™ Multi-Filtration System Rotating Vane Method
With all the filters in place, determine the total hood exhaust volume with a rotating vane anemometer as follows:
1. All cooking equipment should be off. If the hood has internal short circuit make-up air, it should be turned off.
2. Measure velocities
Measurement should be taken at six locations per
filter. They must be over the inlet opening as shown in Fig. 14.
Measure the velocity of each location. A digital
2.75 in. (69.85 mm) rotating vane anemometer or its equivalent is suggested. The center of the anemometer should be held 2 in. (50.8 mm) from the face of the filters as in Fig. 15. It is helpful to make brackets to keep the anemometer at the 2 in. (50.8 mm) distance and parallel to the filter. Both squareness and distance are important for accuracy.
3. Calculate the average velocity for the filter.
4. Determine the filter’s conversion factor from the table.
5. Calculate each filter’s volumetric flow rate in CFM by multiplying the average velocity for each filter by the conversion factor.
Fig. 14
1/4 Width
Nominal Filter Size (H x L)
Inches Millimeters
16 x 16 400 x 400
16 x 20 400 x 500
20 x 16 500 x 400
20 x 20 500 x 500
1/2 Width
Rotating Vane Anemometer
Fig. 15
Imperial
Conversion
Factor
1.31
1.65
1.23
1.65
1/4 Width
1/2 Height
2
ft
2
ft
2
ft
2
ft
2 in.
(50.8 mm)
Metric
Conversion
Factor
2
.122 m
2
.153 m
2
.114 m
2
.153 m
Example: (Imperial)
Hood Length: 7 feet 0 inches with four 20 x 20 filters.
Measure the velocities in ft/min. for each 20 x 20 filter (six readings per filter)
Filter 1
Filter 2
Filter 3
Filter 4
Average slot velocity for Filter 1 =
(repeat for each filter)
For a nominal filter size of 20 x 20, the conversion factor is 1.65
Volume for Filter 1 = Conversion Factor x Average Velocity
Total hood volume
Filter 1
=
Volume
= 346.0 + 377.6 + 386.9 + 378.1 =
225 201 187 210 238 197 228 222 226 237 240 220 230 245 240 250 223 219 225 265 219 245 221 200
= 1.65 ft =
346.0 cfm (repeat for each filter)
+
Filter 2 Volume
+
Filter 3
Volume
Sum of Velocity Readings Number of Readings 1258
=
2
+
6
Filter 4
Volume
= 209.7 ft/min.
x 209.7 ft/min.
1488.6 cfm
Example: (Metric)
Hood Length: 2.13 meters, with four 500 x 500 mm filters.
Measure the velocities in m/hr for each 500 x 500 mm filter (six readings per filter)
Filter 1
Filter 2
Filter 3
Filter 4
Average slot velocity for Filter 1 =
(repeat for each filter)
For a nominal filter size of 500 x 500, the conversion factor is .153
Volume for Filter 1 = Conversion Factor x Average Velocity
Total hood volume
Filter 1
=
Volume
= 587 + 642 + 657 + 642 =
4114.80 3675.88 3419.86
3840.48 4352.54 3602.74
4169.66 4059.94 4133.08
4334.26 4389.21 4023.36
4420.12 4480.56 4389.12
4572.00 4078.22 4005.07
4114.80 4846.52 4005.07
4480.56 4041.65 3657.60
=
2
+
+
= .153 m =
Filter 2
Volume
586.7 m3/hr (repeat for each filter)
Filter 3
+
Volume
Sum of Velocity Readings Number of Readings 23006 6
Filter 4
Volume
= 3834 m/hr
x 3834 m/hr
2528 m3/hr
Kitchen Hoods • Type I and Type II20
Page 21
Grease-X-Tractor™ High Efficiency Filters or Grease Grabber™ Multi-Filtration System Shortridge Method
With all the filters in place, determine the total hood exhaust volume with a Shortridge meter as follows:
1. All cooking equipment should be on. If the hood has internal short circuit make-up air, it should be turned off.
2. Measure velocities
Set up the Shortridge meter. Leave all holes of
VelGrid open. Do NOT tape over holes that are not over openings. The conversion factor takes this into account.
For 20 in. (500 mm) high filters, position the grid
as shown in Fig. 16 and 17. Average the two measurements.
For 16 in. (400 mm) high filters position the grid as
shown in Fig. 18.
For 20 in. (500 mm) wide filters, position the grid
over the left and right side of the filter. Average the two measurements.
• Take velocity readings for each filter.
3. Calculate each filter’s volumetric flow rate as follows:
Calculate each filter’s average velocity by summing
the velocity readings and dividing by the number of readings for each filter.
Multiply the average velocity by the conversion factor
to obtain the volumetric flow rate for each filter.
4. Calculate the hood’s total volumetric flow rate by summing the volumetric flow rate of each individual filter in the hood as calculated in Step 3.
Nominal Filter Size (H x L)
Inches Millimeters
16 x 16 400 x 400
16 x 20 400 x 500
20 x 16 500 x 400
20 x 20 500 x 500
Imperial
Conversion
Factor
2
ft
1.53
2
ft
2.00
2
ft
2.25
2
ft
3.00
Metric
Conversion
Factor
.142 m .185 m .209 m .279 m
NOTE
For best accuracy multiply the velocity of each filter by its conversion factor and sum the flow rates. Averaging the velocity measured for all filters may cause error.
Place standoff spacers against face of outlet or inlet grill, filter, coil, etc.
Maintain 1½ inch (38.1 mm) margin
Swivel bracket
Tubing connectors
Extension rods
Pushbutton handle and plug
Handle bracket
Captive knob screws
Edge of outlet/inlet active face area
Maintain 1½ inch (38.1 mm) margin
Tubing harness
Pressure input ports
External read jack
Neckstrap
2
2
2
2
Example: Measured velocities for 20 x 20 in. (500 x 500 mm) filter.
Average Slot Velocity =
(Imperial)
(Metric)
Flow rate for one filter =
(Imperial)
(Metric)
Total hood flow rate = (Filter 1 Flow Rate) + + (Filter x Flow Rate)
(Imperial)
(Metric)
Sum of Velocity Readings
Number of Readings
198 + 205
=
3021 + 3749
=
Conversion
2
2
Factor
= 201.5 ft/min.
=
3385 m/hr
Average
x
Velocity
= 3.0 x 201.5 ft/min. = 604.5 cfm
= .279 x 3385 m/hr = 944 m3/hr
= 604.5 + 600.3 + 592.4 + 613.3 = 2410.5 cfm
= 944 + 1020 + 1006 + 1042 = 4012 m3/hr
Fig. 16
Fig. 17
(63.5 mm)
(63.5 mm)
Fig. 18
2.5 in.
2.5 in.
14.25 in. (361.95 mm)14.25 in. (361.95 mm)
2.75 in.
2.75 in.
(69.85 mm)
(69.85 mm)
3.25 in. (82.55 mm)3.25 in. (82.55 mm)
14.75 in. (374.65 mm)14.75 in. (374.65 mm)
14.25 in. (361.95 mm)14.25 in. (361.95 mm)
2.75 in.
2.75 in.
(69.85 mm)
(69.85 mm)
2.75 in.
2.75 in.
(69.85 mm)
(69.85 mm)
2.75 in.
2.75 in.
(69.85 mm)
(69.85 mm)
Kitchen Hoods • Type I and Type II 21
Page 22
Perforated Face Supply - Rotating Vane Method
1. Hood set up.
If the make-up air unit has a temperature control, it
should be used to keep the supply air at the desired room discharge air temperature.
2. Measure velocities.
Divide the perforated face panel into a grid of equal
areas, each approximately 4 in. (101.6 mm) square.
Measure the velocity at the center of each grid
area. A digital 2.75 in. (69.85 mm) rotating vane anemometer or equivalent is suggested. The center of the anemometer should be held tight to the face of the panel and parallel to the filter. Both squareness and distance are important for accuracy. Calculate the average velocity of the panel.
3. Measure the length and height of the perforated face panel.
4. Calculate the perforated face panel volume using the following formula:
CFM = avg. velocity x length (in.) x height (in.) x 0.005
m/hr = avg. velocity x length (m) x height (m) x 0.72
5. Calculate the system’s volume by repeating the process for the remaining panels and adding the individual panel volumes together.
Filter Readings (ft/min.)
260 250 255 260 250 255 265
270 275 270 280 265 265 270
290 285 280 280 275 290 295
285 275 280 260 270 265 260
Filter Readings (m/hr)
4755 4572 4663 4755 4572 4663 4846
4938 5029 4938 5121 4846 4846 4938
5304 5212 5121 5121 5029 5304 5395
5212 5029 5121 4755 4938 4846 4755
Example: Face supply hood with three 28 inch (.711 m) perforated panels
Measured velocities in ft/min. for one perforated panel
Average Velocity =
(Imperial)
(Metric)
=
=
Sum of Velocity Readings
Number of Readings
260 + 250 + ... + 265 + 260
28
4755 + 4572 + ... + 4846 + 4755
28
= 270.7 ft/min.
= 4951 m/hr
Measure length and height. 28 inches (.711 m) long perforated panel by 16 inches (.406 m) high
Volume for one panel = Conversion Factor x Average Velocity x Length x Height
(Imperial)
(Metric)
= 0.005 x 270.7 ft/min. x 28 x 16 = 606.4 cfm
= 0.72 x 4951 m/hr x .711 x .406 = 1029 m3/hr
Total system volume = (Panel 1 Volume) + (Panel 2 Volume) + (Panel 3 Volume)
(Imperial)
(Metric)
= 606.4 + 614.3 + 593.8 = 1814.5 cfm
= 1029 + 1044 + 1009 = 3082 m3/hr
Kitchen Hoods • Type I and Type II22
Page 23
Short Circuit Hood Supply - Rotating Vane Method
All cooking equipment should be off. The hood exhaust should also be off.
1. Measure Velocities
Velocity measurements should be made with a digital
2.75 in. (69.85 mm) rotating vane anemometer or its equivalent.
One velocity measurement should be taken for
every 8 in. (203.2 mm) of short circuit opening length, starting tight against one edge of the opening, and finishing tight against the other edge. The anemometer should be placed at the bottom edge of the opening, flush with the bottom lip. Both squareness and placement are important for accuracy.
2. Calculate the average slot velocity.
3. Calculate the volumetric flow rate per linear foot by dividing the average velocity by a conversion factor of 5.52 per ft. If metric units are used, divide the average velocity by a conversion factor of 1.68 per meter.
4. Calculate the hoods supply volume by multiplying the CFM per linear foot by the total hood length.
Example: 4 ft. (1.22 m) short circuit hood (36 inch (.914 m) short circuit opening
Number of readings = 36 in. / 8 in. => 6 readings (.914 m / .2 m => 6 readings)
Average Velocity =
(Imperial)
(Metric)
=
1335 + 1529 + 1913 + 1780 + 1888 + 1894
=
CFM per linear foot =
(Imperial)
(Metric)
1014.3 ft/min.
=
=
Hood supply volume = CFM/linear foot (m
(Imperial)
(Metric)
= 183.8 x 4 ft. = 735.2 cfm
= 1026 x 1.22 m = 1252 m3/hr
Sum of Velocity Readings
Number of Readings
786 + 900 + 1126 + 1048 + 1111 + 1115
6
6
Average Slot Velocity
Conversion Factor
5.52
1723 m/hr
1.68
= 183.8 cfm/linear ft.
= 1026 m3/hr
3
/hr / m) x Hood Length
=
=
6086
6
10339
6
= 1014.3 ft/min.
= 1723 m/hr
For all air volume testing pertaining to energy recovery filters,
refer to Energy Recovery Installation, Operation and Maintenance Manual.
Kitchen Hoods • Type I and Type II 23
Page 24
Exhaust Air Balancing Baffles
This is a guide to assist in determining if multiple hoods on one fan can be balanced to have equal static pressure. For multiple hoods on one fan to achieve their designed exhaust flow, all of the hoods must have equal static pressure at their designed exhaust flow.
The laws of physics force the static pressure for each branch of a duct system on one fan to always be equal. This will happen by the flow rate increasing in low static branches and decreasing in high static branches until the static pressure is equal in all branches.
Checking for Balance
Every hood with exhaust air balancing baffles (EABB) has a range for its static pressure. The low static pressure number (when EABB is open) in this range is given by the standard calculation for hood static and is printed on the CAPS submittal page for that hood. The high static pressure number (when EABB is closed) in this range can be found by calculating the maximum potential increase of static and adding that value to the low static pressure number.
High static pressure number = low static pressure number + maximum increase
The maximum potential increase in static is given in the graph, or can be calculated from the following formula:
Maximum Increase = 0.00000036 x (Duct velocity)
Maximum Increase in Static Pressure for Exhaust Air Balancing Baffle
4.5
4
3.5
3
2.5
2
1.5
1
Increase in Collar Staitc Pressure
0.5
0
500 1000 1500 2000 2500 3000 3500
(Fully Closed)
Duct Velocity FPM
2
Refer to the examples.
Example 1:
Hood 1: Ps = 0.58 in. wg Duct Velocity = 1900 ft/min.
Hood 2: Ps = 0.44 in. wg Duct Velocity = 1800 ft/min.
Hood 2 has the lower Ps, at 1800 ft/min. the maximum increase in Ps is 1.17. The range for Hood 2 is 0.44 to
1.61. Hood 1 is less than 1.61 so these hoods can be balanced.
Example 2:
Hood 3: Ps = 2.00 in. wg Duct Velocity = 2000 ft/min.
Hood 4: Ps = 0.44 in. wg Duct Velocity = 1500 ft/min.
Hood 4 has the lower Ps, at 1500 ft/min. the maximum increase in Ps is .81. The range for Hood 4 is 0.44 to
1.25. Hood 3 is higher than 1.25, so these hoods cannot be balanced.
NOTE
For many systems, exhaust air balancing baffles may not be needed on the hood that has the highest static pressure. The exception to this is if the individual ductwork has uneven static pressures.
NOTE
When sizing the fan, use the static pressure from the highest hood and sum the CFM from all the hoods.
Step 1: Find the hood with the lowest static pressure as shown on the CAPS submittal pages.
Step 2: Calculate the high static pressure number for this hood as instructed above.
Step 3: Compare this high static pressure number to the low static pressure number of the remaining hoods. If the remaining hood’s low static pressure number is lower than the high static pressure number calculated, then the system can be balanced; if the low static pressure number is higher than the calculated high static pressure number, then the system cannot be balanced.
Kitchen Hoods • Type I and Type II24
Page 25
Wiring Diagrams
Amerex Wiring Plan View
PRM
MICROSWITCH
INSTALLER PROVIDED JUNCTION BOXES
BASIC WIRING DIAGRAM
RED (COMMON)
YELLOW (N.O)
POWER SOURCE
POWER SOURCE
BLACK (N.C.)
MANUAL RESET RELAY
ELECTRIC GAS VALVE
MANUAL RESET
RELAY
MICROSWITCH
NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.
BASIC WIRING DIAGRAM
MANUAL RESET RELAY
RED (COMMON)
YELLOW (N.O)
MICROSWITCH
NOTES:
1. DENOTES FIELD INSTALLATION
2. DENOTES FACTORY INSTALLATION
3. GAS VALVE: UL LISTED ELEC TRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871, 12872, 12873, 12874, 12875 AND 12876.
4. K1a AND K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.
120V/60HZ
BLACK (N.C.)
L1
L2
K1b
GAS VALVE
K1
Ka
CURRENT DRAW MAX: 8A RESISTIVE 8A INDUCTIVE 120VAC
PUSHBUTTON SWITCH
GAS VALVE
SEE NOTE 3
Kitchen Hoods • Type I and Type II 25
Page 26
Ansul Wiring Plan View
Snap-Action Switches may be wired as shown. Typical examples shown.
Equipment
NO
120 VAC
N
NC
Electric gas valve - If reset relay is used, see option A or B at right. Mechanical gas shut off valve does not require electrical connection.
Alarms
NO
NC
NO
Input
NC
Fans
NO
120 VAC N
NC
Input
Power to cooking equipment
Shunt Trip Breaker
Input
Voltage Free Contacts for Building Alarm(s)
Power to fan(s)
Fan Starter
Manual Reset Relay Part No. 426151
Black
GND
Red
Brown
5
4
3
2
1
Gas Valve See Note 3
Reset
AB
Relay Coil
6 9 3
4 7 1
Electrical Rating 1/3 HP, 10 AMP, 120 VAC 1/2 HP, 10 AMP, 240 VAC 13 AMP, 28 VDC
Note:
1. Denotes field installation.
2. Denotes factory installation.
3. Gas Valves: “UL Listed electrically-operated safety valve for natural or LP gas as needed, of appropriate pressure and temperature rating, 110V/60Hz” or Ansul gas valves.
4. Do not use black wire on snap-action switch in normal installation. Black wire may only be used for extraneous alarm, light circuits, etc.
Power
Indicator
Screw
Ansul Snap-Action Switch Part No. 423878
Switch contacts shown with Ansul Automan in the cocked position
110 VAC/60Hz
L2 Neutral L1 Hot
Manual Switch
If prohibited by local codes, do not shut down exhaust fans with this method of wiring.
Kitchen Hoods • Type I and Type II26
Page 27
Overall Wiring Plan View for Kitchen Systems with Make-Up Air Control Centers
In this arrangement, single-point power to the make-up air (MUA) unit is fed to each individual exhaust fan disconnect from exhaust fan starters within the MUA control center. This arrangement can be used for constant volume systems only. The diagram below is generic. To see your job specific wiring requirements, refer to the wiring diagrams provided with the package.
TYPICAL MUA FAN
DISCONNECT
SWITCH IN CONTROL
CENTER
WITH CONTROL CENTER
M1
M2
TYPICAL
EXHAUST
FAN
OPTIONAL
DISCONNECT
(FIELD OR FACTORY
INSTALLED)
TYPICAL
EXHAUST
FAN
M3
Fan power feeds
to be field wired to
respective exhaust starters
located in MUA control center.
120 VAC
FOR LIGHTS
(1400W MAX)
D. UDS E. Hood F. WWCP
N
H
LIGHT SWITCH
LABEL DESCRIPTION
M XFCC UDS WWCP
FACTORY WIRING FIELD WIRING
Motor Kitchen Fan Control Center Utility Distribution System Water Wash Control Panel
FROM CIRCUIT BREAKER FOR EXHAUST AND MUA FANS
FROM 120VAC 15A CIRCUIT BREAKER FOR LIGHTS
FROM 120VAC 15A CIRCUIT BREAKER FOR CONTROLS
These components may
be mounted in a hood
mounted cabinet or
on a wall near the hood.
Any other components that need electrical signals during a
fire (shunt trips, alarms, etc.) will require connections to fire
suppression micro-switches/contacts. The fire suppression
system control is not an electrically-rated box, and
therefore no electrical connection can be made inside.
TEMP
INTERLOCK
(STAND ALONE)
24VAC MUA CONTROL WIRE
FIRE
SUPPRESSION
SYSTEM
CONTROL
TYPICAL HOOD
Typical Light and Fan Switch Locations:
A. XFCC
B. Utility Cabinet
C. Wall (Shipped Loose)
Overall Wiring Plan View for Kitchen Systems with Kitchen Fan Control Centers
This arrangement requires individual power connections for each supply and exhaust fan from remote circuit breakers through the fan starters in the Kitchen Fan Control Center (XFCC) or variable frequency drives in the Variable Volume Control Package. This arrangement can be used for either constant volume or variable volume systems. The diagram below is generic. To see your job specific wiring requirements, refer to the wiring diagrams provided with the package.
TYPICAL MUA FAN
WITH CONTROL CENTER
NOTE:
Make-Up Air fan will
typicallly have starters in MUA
only. Control wiring must be run
to Kitchen Fan Control Center
or VAV System.
M3
M1
TYPICAL
EXHAUST
FAN
OPTIONAL
DISCONNECT
(FIELD OR FACTORY
INSTALLED)
TYPICAL SUPPLY FAN
M2
DISCONNECT
SWITCH IN CONTROL
CENTER
FROM CIRCUIT BREAKER FOR MUA
FROM CIRCUIT BREAKER FOR SUPPLY FAN
FROM CIRCUIT BREAKER FOR EXHAUST FAN
FROM 120VAC 15A CIRCUIT BREAKER FOR CONTROLS
FROM 120VAC 15A CIRCUIT BREAKER FOR LIGHTS
These components may
be mounted in a hood
mounted cabinet or
on a wall near the hood.
TO APPLIANCE SHUNT TRIP BREAKER (OPTIONAL)
TO ELECTRIC GAS VALVE/RESET RELAY (IF APPLICABLE)
TO BUILDING ALARM (IF APPLICABLE)
AUTO FAN CONTROL
CENTER OR VAV SYSTEM
FIRE
SUPPRESSION
SYSTEM
CONTROL
TYPICAL HOOD
Typical Light and Fan Switch Locations:
A. AFCC B. Utility Cabinet C. Wall (Shipped Loose)
D. UDS E. Hood F. WWCP
24VAC MUA CONTROL WIRE
FACTORY WIRING FIELD WIRING
LABEL DESCRIPTION
M
Motor Auto Fan Control Center
AFCC
Utility Distribution System
UDS
Water Wash Control Panel
WWCP
Kitchen Hoods • Type I and Type II 27
Page 28
Overall Wiring Plan View for Switch Panels
The diagrams below show typical wiring for combined exhaust and supply switching when the switches are shipped loose for remote mounting, and for hood mounted switches.
The diagram shows how to wire the exhaust and supply fan starters to the switches and fire suppression contact. Typically, supply fans will be turned off and exhaust fans will be turned on (or continue to run) in the
Shipped Loose Hood Mounted
TYPICAL WIRING FOR COMBINED EXHAUST & SUPPLY SWITCHING (SHIPPED LOOSE)
FACTORY WIRING FIELD WIRING
LABEL DESCRIPTION
Normally-open
NO
Normally-closed
NC
Common
COM
Motor Starter
STR
Overload
OL
FAN STARTERS PROVIDED
BY OTHERS
VOLTAGE FOR LIGHTS
J-BOX ON
TOP OF
HOOD
N
120 VAC
WHITE
BLACK
H
CONTROL VOLTA GE
N
H
SUP FAN STR
NC
NO
OL
OL
EXH FAN STR
FIRE SUPPRESSION
COM
MICRO-SWITCH/CONTACTS
SUPPLY FAN
CONTACT
CONTROL VOLTA GE
H
SUP
SUP
HTR
COOL
N
CTRL
CTRL
event the fire system is activated. The fire suppression micro-switch is provided as part of the fire suppression system and is normally mounted in the fire system control box.
Wiring examples for use when a control panel is not provided as part of the kitchen package.
TYPICAL WIRING FOR COMBINED
EXHAUST & SUPPLY SWITCHING (HOOD MOUNTED)
FACTORY WIRING FIELD WIRING
LABEL DESCRIPTION
NO
Normally-open Normally-closed
NC
Common
COM
Motor Starter
STR
Overload
OL
FAN STARTERS PROVIDED
BY OTHERS
VOLTAGE FOR LIGHTS
J-BOX ON
TOP OF
HOOD
N
WHITE
120 VAC
BLACK
NOTE
NC
NO
OL
CONTROL VOLTA GE
H
OL
SUP
EXH
FAN
FAN
N
H
STR
STR
BLACK
BLACK
FIRE SUPPRESSION
COM
MICRO-SWITCH/CONTACTS
SUPPLY FAN
CONTACT
CONTROL VOLTAGE
H
RED
BROWN
ORANGE
SUP
SUP
HTR
COOL
N
CTRL
CTRL
J-BOX ON TOP OF HOOD
PURPLE
YELLOW
HOOD LIGHTS
Circuit Diagrams
Single Throw
Double Throw
Double Throw
Center Off
Single Pole
OFF ON
ON (NC)
ON (NO)
ON
OFF
ON
Series Circuit
FANSLIGHTS
SWITCHES
OFF ON
ON (NC)
ON (NO)
HEAT/COOL
HOOD LIGHTS
Double Pole
OFF ON
OFF ON ON
ON (NC) ON (NC)
ON (NO) ON (NC)
ON (NO) ON
OFF
ON ON
OFF
ON
OFF ON
OFF
ON (NO)
ON (NC)
ON (NO)
Parallel Circuit
FANSLIGHTS
SWITCHES
HEAT/COOL
Normally
Open
Contacts
Normally
Closed
Contacts
Kitchen Hoods • Type I and Type II28
Off if both are not activated
Off if either are not activated
On if both are activated
On if both are not activated
Off if either are not activated
Off if both are activated
Off if both are not activated
On if either is activated
On if both are activated
On if either is activated
Off if either not activated
Off if both are activated
Page 29
Maintenance
FIG. 17
REMOVABLE AIR DIFFUSERS
Daily Maintenance
1. Wipe grease from exposed metal surfaces on the hood interior using a clean, dry cloth.
2. Visually inspect the filters or cartridges for grease accumulation.
3. Remove grease cup, empty contents and replace cup.
Weekly Maintenance
1. Remove the grease filters or cartridges and wash in dishwasher or pot sink.
Note: Filters installed over heavy grease
producing equipment may require more frequent cleaning. See Filter Washing Frequency Guide, page 31.
2. Before replacing filters, clean the interior plenum surfaces of any residual grease accumulations.
Periodic Maintenance
1. Painted hood exterior surfaces should be cleaned with a mild detergent solution.
2. Stainless steel hood exterior surfaces should be cleaned with a mild detergent and then polished with a good grade stainless steel polish to preserve the original luster.
Note: Never use abrasive cleaners or chemicals
on hood surfaces. Never use chlorine based cleaners or iron wool pads to clean the hood. They may scratch or mar the material. Always rub with the grain of the stainless.
3. To maintain optimum performance of your hood and fan, duct cleaning should be performed as often as the application and code requires.
4. Recaulk the hoods with an NSF Approved silicone caulk, (GE SCS1009 or its equivalent) as needed.
5. Inspect the supply air discharge portion on external supply plenums to ensure the airstream is free from debris or other blockage.
Condensate Hood Baffle Installation, Fig. 19 and 20
1. Grasp the baffle with drain holes facing down and lift into the hood. For short hoods with only one baffle, it may be necessary to turn the baffle slightly diagonally to fit it past the drain channel.
2. After the baffle clears the drain channel of the hood, turn the baffle so it is lined up with the upper hanger in the hood.
3. Hook the upper channel of the baffle over the upper hanger of the hood and set the lower edge of the baffle into the condensate gutter. Repeat until all baffles are installed in the hood.
4. Center the baffle from side to side in the hood.
Fig. 19 - CORRECT
UPPER
HANGER
UPPER HANGER
CONDENSATE GUTTER
Fig. 20 - INCORRECT
UPPER
HANGER
UPPER HANGER
CONDENSATE
UPPER HANGER
GUTTER
Air Diffusers
The air diffusers, located at the bottom of the back supply will need to be cleaned as often as the application dictates. Inspect periodically to determine the cleaning schedule.
1. To clean the air diffusers, unfasten the screws. Remove the air diffusers from the back supply unit and wash in the sink or dishwasher.
2. Refasten with the stainless steel screws.
Grease Grabber™ Filter Installation
NOTE
Never install the second stage filter in the front filter channel. The second stage filter must be installed behind a UL Classified Grease-X-Tractor™ primary filter.
1. Slide the top edge of the second stage filter into the top rear filter channel; Fig. 21.
Fig. 21
Kitchen Hoods • Type I and Type II 29
Page 30
2. Lifting the lower edge of the filter past the grease trough, continue to push the top of the filter into the channel.
3. When the filter is even with the bottom rear
Fig. 22
filter channel, set the filter into the channel; Fig. 22.
4. Slide the filter to one end of the hood and repeat until all the filters are installed. Make sure the filters are placed tightly together with no
Fig. 23
visible gaps.
5. Install the Grease-X-Tractor™ primary filters in the same manner using the front filter channel. (Fig. 23)
Grease Grabber™ Filter Cleaning
Step 1 Remove the front row of Grease-X-Tractor™
filters shown in 1A. Begin by removing the middle filter(s) first (1B), then slide the outer filters toward the hood center and continue removing the filters.
1A 1B
Grease-X-Tractor™ filters, first row of filters
1C
Grease Grabber™ filters, second row of filters
Step 2 Remove the Grease Grabber™ filters, starting
in the middle of the hood: (2A) grab the handles on either side and lift the filter up, (2B) pull the bottom of the filter toward yourself, (2C) lower the filter out of the hood.
Repeat this process for each filter. The filters
that are on the ends will have to be slid toward the middle and then lifted out.
2A
Slide filter up
2C
Pull filter down
2B
Pull bottom of filter towards yourself
Step 3 Frequent Maintenance
NOTE
Required washing frequency is dependent on type of cooking and quantity of food cooked.
- Remove filters from hood and place each filter in a whirlpool sink or dishwasher.
- If using a whirlpool sink, cycle for 10 minutes. Use standard dish wash soap. (3A)
- If using a dishwasher, cycle it three times to ensure all grease is removed. (3B)
- If using standard sink, cover with hot water and degreaser and soak for two hours. Rinse after soaking.
3A 3B
Whirlpool sink method Dishwasher method
NOTE
For hoods with large quantities of filters, it is acceptable to wash three to four filters each day, cycling all of the filters in three days.
NOTE
The beads will discolor. Standard cooking will turn the beads yellow in color. Open flame cooking will cause the beads to blacken. Neither affects the performance of the filters.
Periodic Inspection
- Inspect filter fasteners. Verify they are not loose or missing.
- Each filter may be soaked in hot soapy water for two hours once a month prior to washing if grease build­up is found.
- Test for grease build-up by running water through the filter. If water runs freely and no air gaps are in the beaded pack, the filter is in working condition.
- Inspect the filters by holding it up to a light. Light shining through more than six holes in a group indicates filter damage.
- For filter replacement, call 1-800-355-5354
Step 4 Replace Grease Grabber™ filters in hood. Do
Step 2 in reverse order (2C, then 2B, then 2A).
Step 5 Replace the front Grease-X-Tractor filters. Do
Step 1 in reverse. Be sure to install filters in the ends of the hood first, then install the filters in the middle of the hood (1B, then 1A).
CAUTION
To prevent damage to filter media, do not wash second stage filters in detergents that contain hydroxides such as sodium hydroxide or potassium hydroxide.
Kitchen Hoods • Type I and Type II30
Page 31
Filter Washing Frequency Guide
NOTE
Standard cooking will turn the beads yellow in color. Open flame cooking will cause the beads to blacken. Neither affects the performance of the beads.
Preference
1
Best
2
Washing Equipment
Type Temp.
Commercial
Grade Dish
Washer
180º F
Minimum
Low Temp.
Dish Washer
140º F
Chemical
Sanitizer
Cooking
Equipment
Chemical
Griddle
Fryer Weekly 2 cycles Twice a week, 1 cycle
Charbroiler Daily 2 cycles Daily, 2 cycles
Dish Washer
Detergent
Wok Daily 2 cycles Daily, 2 cycles
Griddle
Fryer Weekly 3 cycles Twice a week, 2 cycles
Charbroiler Daily 4 cycles Daily, 2 cycles
Dish Washer
Detergent
Wok Daily 4 cycles Daily, 2 cycles
CAUTION
To prevent damage to filter media, do not wash second stage filters in detergents that contain hydroxides such as sodium hydroxide or potassium hydroxide.
Grease Grabber™ Filter
Frequency
Required
Time or
Cycles
Every 3 days 2 cycles Every 3 days, 2 cycles
Every 3 days 3 cycles Every 3 days, 2 cycles
Baffle Filter or
Grease-X-Tractor™
Wash Frequency
3
4
5
6
Worst
Power Wash
Sink (Whirlpool)
with Heater
Power Wash
Sink (Whirlpool)
without Heater
Pot Sink
with Heater
Rinse with
sprayer after
soaking.
Pot Sink
no Heater
Rinse with
sprayer after
soaking.
180º F
Minimum
140º F
180º F
140º F
Griddle
Fryer Weekly 10 minutes Twice a week, 5 minutes
Charbroiler Daily 15 minutes Daily, 5 minutes
Pot & Pan Detergent
Every 3 days 10 minutes Every 3 days, 5 minutes
Wok Daily 15 minutes Daily, 5 minutes
Griddle
Fryer Weekly 15 minutes Twice a week, 5 minutes
Charbroiler Daily 25 minutes Daily, 10 minutes
Pot & Pan Detergent
Every 3 days 15 minutes Daily, 5 minutes
Wok Daily 25 minutes Daily, 10 minutes
Daily
Griddle
Pot & Pan
Fryer Every 2 days 1 hour
Charbroiler Daily 2 hours
Detergent
and/or
Degreaser
Wok Daily 2 hours
Every 2 days 1 hour
Soak 10 minutes, then scrub with
scour pad and bottle brush.
Daily
Soak 5 minutes, then scrub with
scour pad and bottle brush.
Daily
Soak 10 minutes, then scrub with
scour pad and bottle brush.
2 hours
Griddle
Daily
Commercial
Fryer Every 2 days
Grade Kitchen
Degreaser
Change hot water
every 30 minutes
2 hours
Change hot water
every 30 minutes
Soak 10 minutes then scrub with
Daily
scour pad and bottle brush.
Charbroiler Not Recommended
Wok Not Recommended
Kitchen Hoods • Type I and Type II 31
Page 32
Troubleshooting
Problem: Exhaust fan is not operating or is not operating at design levels.
Is the fan receiving power? Replace fuses, reset circuit breakers, check disconnect.
Is the belt loose or broken? Replace or tighten belt.
Is the fan rotating in correct direction? Have the electrician correctly wire the fan.
Is the make-up air operating?
Does the airflow need to be increased? Adjust or replace pulleys to increase fan RPM, install a larger motor.
Does the fan vibrate?
Problem: Hood is full of smoke. There is smoke coming out of the edges of the hood.
Is the fan operating at design levels? See exhaust fan troubleshooting section.
Is the fan correctly sized?
Are the filters in good condition? Clean filters, replace damaged filters, properly position filters.
Is there sufficient make-up air?
(Kitchen should be in a slight negative but not excessive. Check to see if there is a strong draft through an open door).
Does the current cooking equipment match the original design?
Are there multiple hoods on one fan?
Are there closed dampers in the duct? Open dampers.
Is the ductwork complex or too small? Change to a higher static fan, modify the ductwork.
Is the ductwork obstructed? Clear obstruction.
Is this a short circuit hood? Turn off or reduce the amount of air supplied to short circuit.
Problems with make-up air may interfere with the exhaust fan. Check the manufacturer’s installation manual.
Clean the fan wheel/blade, replace fan wheel if damaged, check for loose bolts, check for broken or damaged components, check for rags and other foreign objects.
Refer to test and balance report, design specifications and fan curves; have an electrician check the motor amperage; try removing the filter temporarily to see if capture improves. (Make sure to replace filter to prevent risk of fire!); switch to different filters with lower static pressure.
Check make-up air unit, increase make-up air, make-up air should be evenly distributed throughout the kitchen.
Adjust or replace fan to match the cooking equipment load.
One hood may be over exhausting and the other hood not drawing enough. Restrict second hood to help problem hood.
Problem: Smoke blows away before reaching the bottom of the hood.
Are there cooling fans directed at the hood or cooking equipment?
Are there ceiling diffusers directing air at the hood?
Are there open windows or doors? Close windows and doors.
Are there cross drafts or other drafts in the kitchen?
Is the hood near a main walkway?
Are there pass-thru windows near the hood?
Is this an air curtain hood? Turn off or reduce the amount of make-up air.
Is the make-up air part of the hood or an attached plenum?
Turn off or redirect fans.
Move diffusers to more neutral area or replace with a diffuser that directs air away from the hood.
Find source of the draft and eliminate, add side skirts to hood (test with cardboard; use stainless for permanent side skirts); increase the amount of overhang on the spillage side; add a 6 in. (152.4 mm) lip around the base of the hood (test with cardboard; use stainless for permanent side skirts); make-up air should be spread out evenly through the kitchen.
Add side skirts to hood (test with cardboard first); increase the amount of overhang on spillage side.
Adjust amount and locations of make-up air to eliminate drafts through the pass­thru windows.
Try turning off or reducing the amount of make-up air; block off portions of the supply to direct air away from the problem area (test with cardboard).
Kitchen Hoods • Type I and Type II32
Page 33
Troubleshooting
Problem: Pilot lights are being blown out or cooking equipment is being cooled by make-up air.
Try turning off or reducing the amount of make-up air; block off portions of the
Are there drafts from make-up air?
Problem: Cold air can be felt by the cook at the hood.
Is this a short circuit hood? Turn off or reduce the amount of air supplied to short circuit.
Is this an air curtain hood? Turn off or reduce the amount of air supplied to the air curtain; heat the supply air.
Is the make-up air part of the hood or an attached plenum?
Problem: The kitchen gets hot.
Is the hood capturing?
Is this an air curtain hood? Turn off or reduce the amount of air supplied to the air curtain.
Is the make-up air part of the hood or an attached plenum?
Problem: Cooking odors in the dining area.
Is the hood capturing?
Is there a draft through doors between the kitchen and dining area?
supply to direct air away from the problem area (test with cardboard first); remove any obstructions in front of supply that directs air toward cooking equipment.
Try turning off or reducing the amount of make-up air; heat the supply air.
Hood is not drawing enough air, see sections on fan performance and hood capture.
Try turning off or reducing the amount of make-up air; cool the supply air.
Hood is not drawing enough air, see sections above on fan performance and hood capture.
Decrease make-up air in the kitchen; increase exhaust air through hood.
Problem: Grease is running off the hood.
Is there grease on top of the hood? Exhaust duct is not correctly welded.
Is the caulk missing or damaged? Clean problem area and recaulk.
Is the grease cup inserted properly? Put grease cup back in place.
Problem: Hood is noisy.
Is the fan running in the correct direction? See exhaust fan troubleshooting section.
Are the filters in place? Replace missing filters.
Is the hood over exhausting? Slow down fan (see exhaust fan troubleshooting section)
Before calling your manufacturer’s representative to report a problem, have the following information available:
1. Review / summary of troubleshooting section in installation operation manual.
2. Hood model and serial number.
3. Current cooking equipment line-up.
4. Size of hood (length, width and height).
5. Island or wall configuration.
6. Multiple hoods on one fan.
7. Nature of spillage (one end; all around the edges).
9. Height hood is mounted above finished floor.
10. How make-up air is brought into the kitchen (hood, ceiling diffusers, separate plenum).
11. Is exhaust system controlled by a variable volume system?
12. Is the fan noisy?
13. Photos or videos of the issue/problem may be helpful.
8. Does the smoke make it to the hood?
Kitchen Hoods • Type I and Type II 33
Page 34
Replacement Parts
FILTERS
Part
Number
457626 16 x 16 Aluminum Baffle Filter
457628 16 x 20 Aluminum Baffle Filter
457632 20 x 16 Aluminum Baffle Filter
457634 20 x 20 Aluminum Baffle Filter
457627 16 x 16 Stainless Steel Baffle Filter
457629 16 x 20 Stainless Steel Baffle Filter
457633 20 x 16 Stainless Steel Baffle Filter
457635 20 x 20 Stainless Steel Baffle Filter
851656 16 x 16 High Velocity Cartridge Filter
851657 16 x 20 High Velocity Cartridge Filter
851659 20 x 16 High Velocity Cartridge Filter
851660 20 x 20 High Velocity Cartridge Filter
851703 16 x 16 Grease-X-Tractor™ Aluminum Filter
851704 16 x 20 Grease-X-Tractor™ Aluminum Filter
851706 20 x 16 Grease-X-Tractor™ Aluminum Filter
851707 20 x 20 Grease-X-Tractor™ Aluminum Filter
851709 16 x 16 Grease-X-Tractor™ SS Filter
851710 16 x 20 Grease-X-Tractor™ SS Filter
851712 20 x 16 Grease-X-Tractor™ SS Filter
851713 20 x 20 Grease-X-Tractor™ SS Filter
458763 16 x 16 Flame Gard® 1 Baffle Filter
458764 16 x 20 Flame Gard® 1 Baffle Filter
454878 20 x 16 Flame Gard® 1 Baffle Filter
454879 20 x 20 Flame Gard® 1 Baffle Filter
852879 20 x 16 Grease Grabber™ Second Stage Filter
852878 20 x 20 Grease Grabber™ Second Stage Filter
852881 16 x 16 Grease Grabber™ Second Stage Filter
852880 16 x 20 Grease Grabber™ Second Stage Filter
Filter Description (Height x Width)
SWITCHES
Part
Number
850551 Light Switch Only
851776 Fan Switch Only
851777 Light Switch & Fan Switch ( 2 switches)
851778 Fan Switch & Heat Switch (2 switches)
851779 Exhaust, Fan & Supply Switch (2 switches)
851780 Light, Fan & Heat Switch (3 switches)
851781 Light, Exhaust, Supply Separate Switch (3 switches)
851782 Exhaust, Supply, Heat Separate Switch (3 switches)
851783 Light, Exhaust, Supply, Heat Separate Switch (4 switches)
851784 Fan Switch & Temper (3 position) (2 switches)
851510 Light, Fans, & Temper (3 position) (3 switches)
851511 Exhaust, Supply, & Temper (3 position) (3 switches)
851512 Light, Exhaust, Supply, & Temper (3 position) (4 switches)
851618 Automatic Fire Damper Test Switch
Description
MISCELLANEOUS
Part
Number
451131 Grease Cup
453498 Glass Globe for hood lights (clear)
851744 Grease Extractor Filter Removal Tool
851834 Baffle Filter Removal Tool
851747 High Velocity Cartridge Filter Removal Tool
Description
REGISTERS
Part
Number
452700 24 x 8 Aluminum Single Deflection H-OB
452701 36 x 8 Aluminum Single Deflection H-OB
452702 36 x 8 Aluminum Single Deflection H-OB
452703 44 x 8 Aluminum Single Deflection H-OB
453796 24 x 12 Aluminum Single Deflection H-OB
453797 36 x 12 Aluminum Single Deflection H-OB
453798 38 x 12 Aluminum Single Deflection H-OB
453799 44 x 12 Aluminum Single Deflection H-OB
452729 24 x 8 Aluminum 38° Fixed Blade RA-OB
452730 30 x 8 Aluminum 38° Fixed Blade RA-OB
452731 36 x 8 Aluminum 38° Fixed Blade RA-OB
452732 38 x 8 Aluminum 38° Fixed Blade RA-OB
452733 44 x 8 Aluminum 38° Fixed Blade RA-OB
Kitchen Hoods • Type I and Type II34
Description
Page 35
Maintenance Log
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Kitchen Hoods • Type I and Type II 35
Page 36
Our Commitment
Our Commitment
As a result of our commitment to continuous improvement, Accurex reserves the right to change specifications without notice.
Product warranties can be found online at accurex.com, either on the specific product page or in the Warranty section of the website at Accurex.com/Resources/Warranty.
P.O. Box 410 Schofield, WI 54476 Phone: 800.333.1400 • Fax: 715.241.6191 Parts: 800.355.5354 • accurex.com
36
470399 • Kitchen Hoods, Rev. 13, May 2017 © 2017 Accurex, LLC36
Loading...