Accurex Grease Trapper ESP Operator’s Manual

Document 482584
Grease Trapper ESP™
Kitchen Exhaust Pollution Control System
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Grease Trapper ESP™
The Grease Trapper ESP™ is a pre-engineered electrostatic precipitator type pollution control unit with integral exhaust fan (available without exhaust fan as an option). The unit is designed to remove grease and smoke particles as well as odor from the kitchen exhaust airstream. This installation manual covers procedures for receiving, installing, and maintaining the unit.
For additional instructions and maintenance information on the integral exhaust fan, when applicable, refer to the fan nameplate to determine model type and visit accurex.com to download the corresponding manual.
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
To reduce the risk of fire, electric shock, and injury be sure to follow the cautions below:
• Before servicing, make sure the unit is properly grounded.
• When servicing the fan, motor may be hot enough to cause pain or injury. Allow motor to cool before servicing.
• Do not operate this unit in an explosive atmosphere.
• Keep all flammable materials (such as gasoline) away from the unit.
• Do not use flammable cleaner on or near the unit.
• The unit should be inspected frequently and the unit and cells should be manually cleaned at proper intervals to prevent a fire.
• Operating temperatures of the airstream should not exceed 130°F.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
2. The rotation of the fan wheel is critical. It must be free to rotate without striking or rubbing any stationary objects.
3. Fan motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan rpm. Adjustments to fan speed significantly affects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the wires to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to a duct while the fan is running.
8. The precipitator contains safety electrical interlock switches at all maintenance access doors. Do not attempt to defeat these interlocks.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System 1
Receiving
Upon receiving the product, check to make sure all items are accounted for by referencing items shown on the packing list. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The carrier will make a notation on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. A Carrier Inspection Report should be filled out by the carrier upon arrival and filed with the Traffic Department. If damaged upon arrival, file claim with carrier. Any physical damage to the unit after acceptance is not the responsibility of manufacturer.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the packing list. Remove all other shipping/ packing materials including fan tie down straps.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
INDOOR
The ideal environment for the storage of units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should be evenly maintained between 30°F (-1°C) and 110°F (43°C) (wide temperature swings may cause condensation and “sweating” of metal parts). All accessories (including the main control panel and the keypad/touchscreen user interface) must be stored indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts, allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection.
OUTDOOR
Units designed for outdoor applications may be stored outdoors, if absolutely necessary. Roads or aisles for portable cranes and hauling equipment are needed.
The unit should be placed on a level surface to prevent water from leaking into it. The unit should be elevated on an adequate number of wooden blocks so that it is above water and snow levels and has enough blocking to prevent it from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
NOTE
The main electrical panel, if stored, shall be stored indoors only in a dry environment protected from the elements.
Inspection & Maintenance during Storage
While in storage, inspect equipment once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. Every three months, the fan motor should be energized. If paint deterioration begins, consideration should be given to touch-up or repainting. Fans with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint­free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40® or the equivalent.
®
506 (Ashland Inc.) or the equivalent.
Removing from Storage
As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the equipment goes into operation. Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base, and accessories for tightness.
2. Rotate the fan wheel(s), where applicable, by hand and assure no parts are rubbing.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System2
Table of Contents
Grease Trapper ESP System Function . . . . . . .3
System Components
Unit Body . . . . . . . . . . . . . . . . . . . . . . .4
ESP Cells . . . . . . . . . . . . . . . . . . . . . . .4
Impingement Filters / Mist Eliminator / Filters /
Carbon Trays . . . . . . . . . . . . . . . . . . . . .4
Component Quantities . . . . . . . . . . . . . . . .4
Remote Mounted Detergent Dispenser. . . . . . . .4
Remote Mounted System Control Panel . . . . . . .5
Fire Cabinet . . . . . . . . . . . . . . . . . . . . . .5
PCU Field Assembly
Unit Modules . . . . . . . . . . . . . . . . . . . . .5
Terminal Enclosure . . . . . . . . . . . . . . . . . .6
Attaching Fan . . . . . . . . . . . . . . . . . . . . .6
Installation
Rigging and Placing Equipment . . . . . . . . . . .7
Ductwork Connections . . . . . . . . . . . . . . . .7
Cells and Carbon Trays . . . . . . . . . . . . . . . .7
Plumbing Connections
Detergent Dispenser . . . . . . . . . . . . . . . . .8
Wash Manifolds . . . . . . . . . . . . . . . . . . . .9
Electrical . . . . . . . . . . . . . . . . . . . . . . .9
Fire System
Ansul® . . . . . . . . . . . . . . . . . . . . . . . 10
Initial System Start-Up . . . . . . . . . . . . . . . 11
Sequence of Operation
Normal . . . . . . . . . . . . . . . . . . . . . . . 11
Wash . . . . . . . . . . . . . . . . . . . . . . . . 12
Controller Setup and Tutorial . . . . . . . . . 13-14
A.
B. Input/Output . . . . . . . . . . . . . . . . . 15
C.
D. Manufacturer . . . . . . . . . . . . . . . . 21
Keypad Navigation . . . . . . . . . . . . . . . . . 22
Touch Screen Navigation . . . . . . . . . . . 23-26
Variable Frequency Drive Information . . . . 27-28
BMS Points List . . . . . . . . . . . . . . . . . . . 29
Maintenance . . . . . . . . . . . . . . . . . . 30-31
Unit Layout . . . . . . . . . . . . . . . . . . . . . 31
Field Wiring Diagrams . . . . . . . . . . . . . 32-33
Wash Water Plumbing Schematic
Drain Line Plumbing . . . . . . . . . . . . . . . . 34
Detergent Dispenser Assembly . . . . . . . . . . . 34
Troubleshooting . . . . . . . . . . . . . . . . . . 35
Maintenance Log . . . . . . . . . . . . . .Backcover
Our Commitment . . . . . . . . . . . . . .Backcover
Clock. . . . . . . . . . . . . . . . . . . . . 15
Service. . . . . . . . . . . . . . . . . . 16-21
Grease Trapper ESP System Function
Grease Trapper ESP is an electrostatic precipitator pollution control unit (PCU), with an additional carbon filtration module designed for two specific functions:
• Remove smoke/grease particles from kitchen exhaust
• Remove odor from kitchen exhaust
NOTE
• Grease Trapper ESP must be connected to a listed exhaust hood assembly and must be installed in accordance with local building codes, NFPA 96 and NEC.
• The unit must be installed with a minimum 12 inch clearance to combustible materials on top of unit and six inches on the sides and bottom.
A mechanical impingement pre-filter removes large airborne particles from the incoming airstream prior to reaching the ionizer cell. The permanent electrostatic collector section removes grease and smoke particles from the airstream using a high voltage ionizer cell(s). The ionizer imparts a positive charge on the grease and smoke particles as they pass. These particles are then repelled by positively charged plates and collected on negatively charged plates. Upon completion of each cooking day, a wash sequence is initiated for the self­cleaning function of the electrostatic cell via the remote mounted control panel. The mesh mist eliminator filter prevents wash water from entering the carbon filtration section(s) of the unit.
NOTE
Do not use this unit for applications with high concentrations of water vapor, or other matter, that is highly conductive if condensed in the airstream. Heavy water vapor can causing continuous electrical shorting within the ESP cells, which does not allow the unit to collect cooking particulate and perform asdesigned.
There are two configuration options for the Grease Trapper ESP PCU’s. The standard unit will have two ESP modules and one carbon filtration section for use with light, medium and heavy duty cooking. For solid fuel applications which will contain a greater quantity of grease, smoke and odors, the solid fuel unit should be selected. The solid fuel unit will contain three ESP modules and two carbon filtration modules.
NOTE
This unit should NOT be installed in applications where incoming airstream at the inlet of the unit is capable of exceeding 130°F.
NOTE
Grease Trapper ESP is designed to remove sub­micron, airborne particulate generated from cooking processes. This system is NOT INTENDED to eliminate regular hood and ductwork cleaning and service. Improper care and maintenance of this system and associated hoods and ductwork may present a fire hazard.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System 3
System Components
NOTE
The installation criteria for each of the system components shown below should be considered when selecting a site for install. For further detail on installing the components, refer to the INSTALLATION section on page 7.
Unit Body
The unit body is shipped on a mounting rails ready for installation. If the unit was ordered with an exhaust fan, typically the fan will also be mounted on the same set of rails as part of the PCU assembly. Unless specified and built for outdoor use, the PCU must be mounted indoors and be protected from weather. The unit should be easily accessible for service personnel. (1) One-inch water supply line and (1) two-inch waste water drain line is required at the unit for the system’s wash function.
Power packs (power supply boxes) are attached to hinged cell access doors of the cabinet assembly which are wired to the terminal enclosure (disconnect box) mounted to the rail below. High voltage feed-through pins safely transfer voltage from power supply to the cells located inside the unit. Power supplies are self­protecting against overloads (which can be caused by contaminant build up that leads to short circuits in ionizer and collector sections) and are self regulating from AC input voltage variations from 108 - 264 VAC.
Impingement Filters / Mist Eliminator Filters / Carbon Trays
Impingement filters and mist eliminator filters will ship installed in the unit. Carbon trays will ship in a separate container. Filter quantities for each stage are based on unit size.
Each carbon filter is a 20 x 20 x 2 inch, 12 lbs, and contains coconut shell carbon, standard. Max designed velocity across each filter is 90 ft/min.
Component Quantities
STANDARD UNIT
Housing
Size
15 121 6
30 2 4 2 12
45 3 6 3 18
60 4 8 4 24
90 6 12 6 36
Impingement
Filter
ESP Cell
Mist Eliminator
Filter
SOLID FUEL UNIT
15 1 3 1 12
30 2 6 2 24
45 3 9 3 36
60 4 12 4 48
90 6 18 6 72
2" Deep
Carbon
Trays
ESP Cells
ESP cells will ship in separate crate to protect them during shipping. Cell quantities for each stage are based on unit size.
Cells have an ionizer section and collector section. Ionizer section includes spiked ionizer plates that are charged with 12,000 VDC. Collector section includes alternating plates between ground (0 VDC) and 6,000VDC potential. Cells are fed voltage through high voltage feed-through pins that are insulated from the unit housing. These pins contact brass plungers located on the side of the cell near the bottom. If a module has multiple cells, power is passed from cell to cell through these brass plungers coming into contact with the pins on nextcell.
The total current to both the ionizer section and collector section is below 6 mA.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System4
Collector Section
Stamped Airflow Direction Indicator
Collector Brass Plunger
Ionizer Brass Plunger
Airflow
Ionizer Section
Left Hand Access Unit Cell
Collector Section
Airflow
Ionizer
Ionizer Section
Brass Plunger
Right Hand Access Unit Cell
Stamped Airflow Direction Indicator
Collector Brass Plunger
Remote Mounted Detergent Dispenser
A 30 gallon remote mounted detergent dispenser equipped with 1/2 hp pump is included as part of the electrostatic collector self-wash system. Solenoid valves, pressure gauge, ball valve, ystrainer, and backflow preventer are to be provided by others. The detergent dispenser must be mounted indoors on a solid, level foundation, as close to the cabinet assembly as possible, and in a freeze protected location accessible to maintenance personnel. The 1/2 inch line from the detergent dispenser must be connected to the water supply line prior to the precipitator. Refer to the PLUMBING section for details on plumbing connections.
System Components - continued
Remote Mounted System Control Panel
The 115 VAC system control panel fed from a 30A building breaker allows the user to interface with the unit and controls operation, as well as monitors wash and other functions. Field wiring connects the system control panel to the terminal enclosures on the unit, and works in conjunction with the unit’s power supplies and high voltage ESP cells. The system control panel is designed to be mounted indoors (NEMA-1) in an area easily accessible to daily operational staff. Allow adequate room from the face of the panels for door swing clearance and servicing.
Fire Cabinet
The fire cabinet should be mounted as close to the Pollution Control Unit as possible, typically within 5 feet. Unless the fire cabinet was provided with an outdoor cabinet and heater, the cabinet should be mounted indoors and must be kept above freezing.
3. After rails and modules have been moved to desired location, the modules and rails can be reassembled.
Control boxes, access doors, filters, and ESP cells must be removed before welding modules together
Each module is attached to the rails with (4) 5/16-inch fasteners
1/8
Liquid Tight
PCU Field Assembly - if applicable
If unit is shipped in sections, each section will need to be welded in the field.
Unit Modules
1. Remove (4) 5/16 inch mechanical fasteners that attach each module to the rails.
2. Remove 5/16 inch mechanical fasteners that attach each module to the next adjacent module. PCU housing size can be found in the model number on tag on side of unit.
Housing
Size
15 3
30, 45 4
60, 90 6
Each module is attached to the adjacent module with 5/16-inch fasteners
Number of
Mechanical
Fasteners
4. It is recommended to reattach the fasteners from step 2 to properly align the modules with each other, but fasteners are not required when the modules are welded together from the outside.
INTERIOR OF MODULES
5/16 inch X 1 inch SS bolt
PN# 417205
SS washer with neoprene gasket
Liquid Tight
PN# 417246
1/8
EXTERIOR OF MODULES
5/16 inch SS hex nut PN# 415576
SS washer with neoprene gasket PN# 417246
5. Make sure all control boxes, access doors, filters and cells are removed from the modules before welding modules together.
6. Fully weld modules together on all four sides on the outside of the unit. Welds must be liquid tight.
NOTE
Doors will have to be opened and/or removed to access fasteners inside of modules. A 1/2 inch socket is required to remove door bolts.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System 5
Terminal Enclosure
1/2 inch silicone gasket
1. The bottom of each terminal enclosure mount needs to be attached to the rail with (2) 5/16 inch fasteners (provided by factory).
2. The top of each terminal enclosure mount needs to be welded to the side of the modules.
NOTE
Be sure terminal enclosures do not block module drains or doors.
3. Refer to wiring diagram provided with the unit control panel for more information. Limit switches (mounted on each module) need to be wired to terminal enclosures.
4. Plugs on power pack enclosure (ESP modules only) need to be plugged into the terminal enclosures.
Limit switch
Power pack enclosure
1/8 2-3.5
Weld top of terminal enclosure mount to modules
Attaching Fan
The ESP fan is shipped bolted to unit body and rails. If the unit was requested to be disassembled in the field, the unit body-to-fan connection has not been sealed.
1. To disassemble in the field, remove mechanical fasteners that attach the companion flange and fan to the unit body.
2. Remove mechanical fasteners that attach the fan to the isolators on the rails.
After fan and unit body have been moved to desired
location, the fan can be sealed and reattached to the unit body and rails.
3. To seal the fan to unit body connection, apply fire rated caulk (3M Fire Barrier Sealant CP25WP+ or equivalent) to fan inlet flange. Make sure to apply caulk
1/2 inch silicone gasket
around each bolt hole. Caulk to be located outside of silicon gasket
Seam on gasket to be
located on side of unit
mounted during step 4.
4. Attach 1/2 inch silicone gasket around fan inlet flange. Silicone gasket to be located inside of caulk applied in step 3 (seam of gasket to be located on the side of unit).
Transition collar
Companion flange
5. To reassemble locate fan on isolators on rails.
6. Reattach fasteners for companion flange removed in step 1.
7. Reattach fasteners attaching fan to isolators removed in step 2.
Liberally apply fire caulk to outside portion of companion flange and around each individual bolt hole
Fire rated caulk
Fan
Fasteners attaching fan to ESP transition are evenly spaced around fan inlet
Connect bottom of terminal mounting bracket to rails with (2) 5/16 inch fasteners each
(provided by others)
Terminal enclosure mount
Terminal enclosure
Fasteners attach the fan to the isolators on each corner of the fan
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System6
Installation
4 inches
Rigging and Placing Equipment
1. The unit is furnished with lifting lugs at the four corners. For corner weights, reference the unit’s submittal drawings.
2. Use a crane and a set of spreader bars hooked to all four factory lifting lugs to lift the unit.
3. Field weight will vary depending upon final selections such as fan type, accessories, etc. Approximate weights are shown in the table.
4. The unit can be positioned on a base or roof deck suitable for this purpose.
5. The unit must be anchored to its base/roof deck.
6. Alternatively, the unit may be suspended from an adequate overhead structure, using suitable undercarriage or hanging rods (by others). If suspended a cradle or support structure must be provided by others to support unit from bottom. All hanger brackets/lifting lugs must be used to ensure proper support. The unit must also be hung level to ensure proper operation.
7. A service clearance of 36 inches must be provided on the access door side of the unit.
8. A minimum 12inch clearance must be maintained between the top and 6 inches on each side and bottom of this unit and any combustible material.
Approximate Weight
Housing
Housing
STANDARD UNIT
Size
15 1410 641 30 1710 777 45 2120 964 60 2765 1257 90 3315 1507
Size
15 1860 845 30 2295 1043 45 2860 1300 60 3660 1664 90 4390 1995
36 inches
lbs kg
SOLID FUEL UNIT
lbs kg
Ductwork Connections
Ductwork must conform to IMC and SMACNA guidelines. All factory-built grease duct needs to be constructed
in accordance with ANSI/UL 1978 and should be manufactured and installed in accordance with their listing.
All field-built grease ductwork must be constructed in the following manner per NFPA 96, unless otherwise specified by the local authority having jurisdiction (AHJ):
Materials - Ducts shall be constructed of and supported by carbon steel not less than 1.37 mm (0.054 in.) (No. 16 MSG) in thickness or stainless steel not less than
1.09mm (0.043 in.) (No. 18 MSG) in thickness. Installation - All seams, joints, penetrations, and duct-
to-hood collar connections shall have a liquid-tight external weld.
Units intended for indoor mounting have an outlet mounting flange provided on the outlet of the fan. Outlet ductwork from the exhaust fan is required to be per the above mentioned methods unless otherwise specified by the local authority having jurisdiction (AHJ).
NOTE
Ductwork should be properly insulated to prevent formation of condensation through temperature change. Condensation that occurs in ductwork will short circuit ionizing-collecting cells.
Cells and Carbon Trays
Open ESP cell and carbon tray access doors using 1/2inch socket wrench to remove all bolts.
Insert cells into the ESP module(s) in the unit, making sure the brass plungers are on the bottom facing towards you and the airflow arrow stamped on each cell is pointing towards the fan. ESP cells should be pushed in by the one next in the row. For example, the second cell pushes the first cell, third cell pushes the second, etc. The last cell installed should be no more than 4 inches (±1/8inch) from the edge of the cell to the edge of the frame.
Insert carbon trays into the carbon module(s) in the unit. Make sure trays are inserted where gasketing material is orientated on the left and right hand side, NOT the top and bottom, so there is a seal against the filter next to them.
After all cells and filters are properly installed, refasten unit doors. Torque the bolts to 60-70 in-lbs. Bolts should be started by hand prior to using an impact driver or socket.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System 7
Plumbing Connections
NOTE
All water piping exposed to freezing temperatures must be trace heated and insulated to prevent damage to the unit.
Once all system components are installed, plumbing connections for the system can be made. It is recommended that plumbing connections be done prior to making electrical connections.
From the building, a 1-inch (refer to drawings) hot water line is required for connecting the wash system. Recommended water temperature is 140-180°F at 40 psi pressure. Make sure water pressure does not exceed 50 psi. Refer to the chart for information on water and detergent quantity requirements. Install the quarter turn ball valve (by others) at the incoming water source to allow the water to be turned off for servicing. Next, install the strainer (by others), backflow preventer (by others), pressure gauge (by others), and 24 VAC solenoid valve (by others) respectively. Locate these items along the incoming water line in a location convenient for inspection/servicing.
Approximate Water and Detergent Used per Wash Cycle (gallons)*
Housing
Size
15 70 1 105 2
30 140 1 210 2
45 210 2 315 4
60 220 2 330 4
90 330 2 495 4
Water usage numbers shown above are assuming factory default wash cycle times. Actual water and detergent required may be different based on the cooking load, appliance type, and cooking frequency/time. *Assuming 40 psi water pressure
STANDARD UNIT SOLID FUEL UNIT
Water Detergent Water Detergent
Detergent Dispenser
The detergent dispenser supplies detergent to the wash system during the WASH mode.
1/2-inch Hot Water Fill Line (Recommended To Make It Easier For Detergent Dillution)
Y-strainer
With Sediment Trap
Detergent
Flow Switch
Detergent Tank
Detergent Pump
1/2-inch Detergent Injection Line (Connect To 1-inch Water Line)
When the unit is washing and the wash sequence is calling for detergent, a pump housed underneath the detergent tank pumps the detergent into the hot water line. A Y-strainer is responsible for removing debris and sediment from reaching the pump. A flow switch determines if detergent is flowing when detergent is being injected (if the flow switch doesn't close within a time period upon detergent pump running, this will trigger a low detergent fault). A detergent flow valve is responsible for diverting some detergent back into the tank. Turning the flow valve knob clockwise (closing the valve) will force more detergent into the hot water line and to the unit during a wash. Turning the flow valve knob counter-clockwise (opening the valve) will force more detergent back into the tank during a wash. A series of colored rings on the flow control valve indicate how opened/closed the valve currently is. This can be adjusted as needed based on the detergent required for the wash cycle, but should start with setting the valve so that the red ring is visible, (see Flow Valve image) which should equate to roughly
0.6GPM. Adjustments to the flow control setting should be done in small increments over a period of several wash cycles.
Flow Valve
This flow valve may be locked into place by a black hex head set screw located on the bottom of the flow valve, just below the adjustable knob. Loosen the set screw before making an adjustment using a 2-mm Allenwrench.
From the pump located on the base of the detergent dispenser, connect a 1/2-inch piping connection for the detergent supply to the 1-inch water supply line. A quarter turn ball valve (by others) can be installed on this line if necessary for servicing. The connection of the 1/2-inch detergent supply line to the 1-inch water supply line should be made within 10 feet of the cabinetassembly.
NOTE
Upon the system detecting no detergent flow for the detergent alarm delay time, the system will go into a low detergent alarm and the detergent pump will be immediately shut off. The low detergent fault can be manually reset (see page 14 for details), or it will automatically reset if detergent flow is detected upon the next wash cycle when detergent injection is takingplace.
Pump should be located as close to unit as possible, on same floor. Maximum distance recommended from detergent pump to unit is 10 feet.
Detergent Flow Valve
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System8
Plumbing Connections - continued
Electrical
Wash Manifolds
The unit is supplied with 1-inch wash headers located at the top of each ESP module. Connect the hot water supply line to the wash headers at the top of the ESP module. Bring a 2-inch waste water drain piping connection with P trap to the drain pipe on the side of the ESP module. The trap drain line water column for the drain should be sized for the total system resistance plus 1 in. wg.
For more information, refer to the plumbing schematic located on page 34.
The Grease Trapper ESP PCU will be supplied with a detergent tank and pump and connection headers on each module. All other plumbing components and piping will be provided by others. Follow all applicable plumbing codes and best practices when installing system.
Required Plumbing Components
(Provided by Others)
Quantity Item Description
3 Ball Valve 1 Y Strainer 2 Backflow Preventer or Check Valve 1 Pressure Gauge 4 24 VAC Solenoid Valves - Standard Unit 5 24 VAC Solenoid Valves - Solid Fuel Unit
Once all system components are installed, electrical connections for the system can be made. It is recommended that plumbing connections be done prior to making electrical connections.
CAUTION
RISK OF ELECTRIC SHOCK. All wiring to be done by qualified personnel only.
NOTE
All wiring must be done according to the equipment data plate information, NEC (National Electrical Code NFPA 70), and local codes.
NOTE
All wiring must be permanently installed in conduit. Under no circumstances should extension cords be used to connect the source of electrical supply to the equipment.
NOTE
An earth ground must be provided to the unit assembly housing and main control panel. If shipped loose for remote mounting, terminal enclosures must be provided with earth ground. The detergent pump motor and solenoid valve must also be appropriately grounded.
The Grease Trapper ESP PCU will require additional field wiring for proper installation. The main control panel will be shipped loose and is designed to be mounted indoors. A typical field wiring diagram is shown on page
32. Refer to the unit specific wiring diagram located on the inside of the door of the system control panel for unit specific wiring that is required.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System 9
Fire System
The Pollution Control Unit (PCU) is furnished with factory pre-piped fire suppression nozzles. Field connection, tanks, controls, fusible link detectors, and commissioning is provided and installed, based on specifications at time of order. The Authority Having Jurisdiction (AHJ) may require additional protection.
The fire system must be installed and operational to maintain the UL Listing of the unit. Refer to the drawings below for information on field piping the fire system to the unit. The release and tanks should be mounted no more than 5feet away from the PCU unit.
ANSUL
To duct nozzles
(duct nozzles by Distributor)
RELEASE
TANK TANK TANK
FIRE SYSTEM DISTRIBUTOR / FIRE SYSTEM INSTALLER:
There are two quik-seals on each module. Connection to only one of the quik-seals on each module is required. Multiple quik-seals are provided for situations where there are obstructions to the connection point.
TYPICAL DRAWING
• Do not install fire piping in front of doors on module. Must have 36 inches of clearance.
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System10
Initial System Start-Up
1. Verify unit is installed properly and all field water
and electrical connections have been made.
2. Check that all ESP cells have been installed
properly. There is a directional arrow that indicates the direction of the proper airflow. If cells are not installed in the proper direction, the unit will not operate correctly.
3. Close and properly fasten the doors on the unit to
ensure the door limit switches are closed.
4. Turn on electrical power to control cabinet and
exhaust fan.
5. Turn on fan disconnect.
6. Turn on the disconnect switch on the PCU terminal
enclosures to energize the power packs.
7. Press the fan button on the user interface to start
the fan. The green indicator lights on the terminal enclosure(s) should illuminate indicating the power supply is powering cells. Some electrical arcing (audible snapping and cracking) is normal at initial power up as leftover debris in the duct and unit may occasionally get caught inside the cells. When the ionizer section on an ESP cell is arcing, the green indicator light on the terminal box will shut off, and the red indicator light will illuminate temporarily. When the collector section of an ESP cell is arcing, the green indicator light on the terminal box will shut off, and both the red and green indicator lights will remain off temporarily. Arcing should subside after a short period of time. If arcing continues, reference page 35 for troubleshooting assistance.
POWER SUPPLY OFF/FAULT
POWER SUPPLY ON
!
DANGER
High Voltage
Housing Size
15, 30, 45
DO NOT REMOVE THIS PANEL
Unless electrical switch is in the OFF position.
Failure to do so will damage switch.
ON
OFF
POWER SUPPLY OFF/FAULT
POWER SUPPLY ON
POWER SUPPLY OFF/FAULT
POWER SUPPLY ON
!
DANGER
High Voltage
Housing Size
60, 90
DO NOT REMOVE THIS PANEL
Unless electrical switch is in the OFF position.
Failure to do so will damage switch.
ON
OFF
RED indicates an ionizer fault within a cell
GREEN indicates normal operation
NO LIGHTS indicates power supply is off OR collector fault within a cell
8. The indicating lights on the terminal enclosure(s) will indicate status of the power supplies. Terminal enclosure indicator lights will remain off unless fan is running.
9. Check for alarms on the system controller. Correct any alarms that may be displayed (See page 14 fordetails).
10. System should now be ready for operation.
NOTE
As a safety precaution, the system will only operate in the NORMAL mode when the access doors of the unit are completely closed and the terminal box disconnect switch is in the ON position.
If the plunger of the safety switch on all of the doors is not fully depressed, the red FAULT light on the main controller (PLC) will illuminate and the unit will not start. Do not attempt to operate the unit with the access doors open or bypass the safety.
Sequence of Operation
The operation of the Grease Trapper ESP system falls into two main categories:
1. NORMAL: System collects smoke and grease
particulate from the airstream.
The unit can be started by pressing the fan button on the user interface or by closing the remote run contact (terminals RE-1A and RE-1B). The remote run command is a contact that can be wired to the kitchen control panel, timeclock, or any other contact closure desired to call for the system to run.
NOTE
BOTH the keypad fan button needs to be disengaged AND the remote run contact needs to be open in order for the fan to shut off. A call for the fan to run will not allow for a wash to start, which will prevent the cells from being cleaned.
During normal operation, as the grease enters the unit, it will pass through an impingement filter that is designed to remove the large grease particles. After passing through the impingement filter, it will enter the ESP module(s) which will remove the grease particles and smoke from the airstream through a process of electrostatic precipitation. Upon leaving the ESP modules, the air then passes through a mist eliminator filter which stops water from entering the carbon filters during the wash down process and also helps protect the carbon filter section from grease build-up. The air then enters the carbon filtration section which removes the odors from the airstream.
Normal Mode
• Exhaust Fan - Running
• Terminal Enclosure Indicator Lights - Green
• Main Solenoid Valve - Closed
• Detergent Pump - Off
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System 11
Loading...
+ 25 hidden pages