Accurex Auto Scrubber Operator’s Manual

Document 481488
Auto Scrubber
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and all applicable local and national building and fire codes. Personnel should be aware of general safety precautions. SMACNA guidelines should be followed for hanging and supporting the hood. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near a unit. Lock and tag the disconnect switch or breaker to prevent accidental power up.
NOTE
Follow all local electrical, plumbing and safety codes, as well as the National Electrical Code (NEC) and the latest edition of the National Fire Protection Agency Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, (NFPA 96). Follow the Canadian Electrical Code (CEC) and ULC-S650 if installing this product in Canada.
Receiving
Upon receiving the product, check to ensure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier of any damage detected. The customer will make a notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which is countersigned by the delivering carrier. If damaged, immediately contact your Accurex Representative. Any physical damage to the unit after acceptance is not the responsibility of Accurex, LLC.
is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading. Filters are shipped on a separate skid in their original packaging. Do not remove factory packaging or install filters until just prior to commissioning. Remove all other shipping/packing materials.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or denting. Damaged finish may reduce ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage.
The ideal environment for storage of the hood and accessories is indoors, above grade in a clean, dry atmosphere that is sealed from the elements. While in storage, inspect equipment routinely. If any moisture, dirt or other accumulations are found on the hood or any of the parts, the source should be located and eliminated.
Removing from Storage
As equipment is removed from storage to be installed in their final location, it should be protected and maintained as outlined in the Handling section above.
Auto Scrubber 1
Table of Contents
Auto Scrubber Hood Function
General Safety Information . . . . . . . . . . . . . . 1
Receiving/Unpacking/Handling . . . . . . . . . . . 1
Storage/Removing from Storage . . . . . . . . . . 1
Auto Scrubber Hood Function . . . . . . . . . . . . . 2
System Components
Hood. . . . . . . . . . . . . . . . . . . . . . . . . 3
Auto Scrubber Control Panel . . . . . . . . . . . . 3
Backflow Preventer . . . . . . . . . . . . . . . . . 3
User Interface . . . . . . . . . . . . . . . . . . . . 3
Hood Weights . . . . . . . . . . . . . . . . . . . . . 3
Supply Plenum Weights and Dimensions . . . . . . . 4
Prior to Installation . . . . . . . . . . . . . . . . . . . 5
Unpacking . . . . . . . . . . . . . . . . . . . . . . . 5
Hood Installation Overview . . . . . . . . . . . . . 6-7
Filler Panel Installation . . . . . . . . . . . . . . . . . 7
Clearance Reduction Method . . . . . . . . . . . . 7-8
Top Clearance Reduction Options . . . . . . . . . 7
Back and Front Clearance Reduction Options . . . 8
End Clearance Reduction Method . . . . . . . . . 8
Installing Duct Collars
Exhaust Duct Collars . . . . . . . . . . . . . . . . 8
Supply Duct Collars to the Plenum . . . . . . . . . 8
Installing Back Supply Plenum . . . . . . . . . . . . 9
Ductwork
Exhaust/Supply . . . . . . . . . . . . . . . . . . . 9
Continuous Capture Plenum Hoods . . . . . . . . . . 9
Installing Front/Side External Supply Plenums . . . .10
Uni-Strut . . . . . . . . . . . . . . . . . . . . . . .10
Hanger Brackets and Threaded Rod . . . . . . . .10
Supply Duct Collar . . . . . . . . . . . . . . . . .10
Installing Backsplash / Side Splash Panels . . . . . .11
Installing End Skirts . . . . . . . . . . . . . . . . . .12
Plumbing
Connections . . . . . . . . . . . . . . . . . . . . .13
Detergent Tank Installation . . . . . . . . . . . . .13
Detergent Requirements . . . . . . . . . . . . . .13
Preventative Maintenance . . . . . . . . . . . . . .13
Typical Plumbing Connection Layout . . . . . . . .14
Electrical Connections
Wiring . . . . . . . . . . . . . . . . . . . . . .15-16
Typical Electrical Connection Layout . . . . . . . .17
Installing Ceiling Enclosure Panels . . . . . . . . . .18
Double Island Canopy Style Hoods . . . . . . . . . .18
Initial System Start-Up . . . . . . . . . . . . . . . . .19
System Operation
Fan Operation . . . . . . . . . . . . . . . . . . . .19
Hood Light Operation . . . . . . . . . . . . . . . .19
Wash Operation . . . . . . . . . . . . . . . . . . .20
Wash Sequence of Operation . . . . . . . . . . . 21-22
Airflow Testing Procedure . . . . . . . . . . . . . . .23
Additional Wiring Schematics
Ansul® and Amerex® Wiring Plan View . . . . . .24
Maintenance
Filters and Capture Tank . . . . . . . . . . . . . .25
Auto Scrubber Start-Up Checklist . . . . . . . . . . .26
Troubleshooting . . . . . . . . . . . . . . . . . . 27-29
Replacement Parts. . . . . . . . . . . . . . . . . . .30
Maintenance Log. . . . . . . . . . . . . . . . . . . .31
Our Commitment. . . . . . . . . . . . . . . Backcover
Accurex’s Auto Scrubber hoods are designed for three primary functions:
• Capture and contain the effluent produced by the cooking process.
• Remove grease and other contaminants from the airstream with either one or multiple stages of mechanical filters.
• Wash the filters and other surfaces within the exhaust plenum to remove contaminants.
NOTE
The wash sequence of the hood is not designed for fire suppression and will not engage in the event of afire.
NOTE
For information on the complete wash cycle, please refer to the Wash Sequence of Operation, pages 21 and 22.
Auto Scrubber2
System Components Hood Weights
Hood
The hood is shipped from the factory pre-piped and ready to install. All wash components within the hood are complete and ready for connection to hot water, sanitary sewer drain and the electrical sources. If the Auto Scrubber Control Panel is mounted on the hood, wiring from the control panel to the hood lights, valves and sensors is completed by Accurex. All field plumbing and wiring must conform to plumbing and electrical codes.
Auto Scrubber Control Panel (ASCP)
The control cabinet contains the water and electrical components, including the Programmable Logic Controller (PLC), that controls the wash sequencing and operations. The control cabinet also includes the detergent reservoir, detergent pump, and other water piping.
NOTE
Filters are shipped loose with the hood and installed in the field. To install the filters, perform the sequence of steps outlined on page 25 in reverse.
Backflow Preventer
A backflow preventer will be shipped loose with the ASCP and will need to be installed in-line with the hot water supply to the ASCP to prevent detergent from back-feeding into the building water supply. Plumbing instructions begin on page 13.
Hood Weights
Hood Width
inches (cm)
48
(121.92)
51
(129.54)
54
(137.16)
57
(144.78)
60
(152.40)
63
(160.02)
66
(167.64)
69
(175.26)
72
(182.88)
4 feet
lbs. (kg)
244
(110.7)
250
(113.4)
256
(116.1)
262
(118.8)
268
(121.6)
274
(124.3)
280
(127.0)
286
(129.7)
292
(132.4)
Length
8 feet
lbs. (kg)
398
(135.2)
404
(183.3)
410
(186.0)
416
(188.7)
422
(191.4)
428
(194.1)
434
(196.9)
440
(199.6)
446
(202.3)
12 feet
lbs. (kg)
553
(250.8)
559
(253.6)
565
(256.3)
571
(259.0)
577
(261.7)
583
(264.4)
594
(269.4)
600
(272.2)
606
(274.9)
CAUTION
To ensure proper structural support, all hanger brackets must be used for hanging the hood.
16 feet
lbs. (kg)
707
(320.7)
713
(323.4)
719
(326.1)
725
(328.9)
731
(331.6)
737
(334.3)
743
(337.0)
749
(339.7)
755
(342.5)
User Interface
The user interface will be either a keypad with LCD screen or touch screen. It can be mounted on the Auto Scrubber control cabinet, hood or shipped loose for remote mounting. It will provide a WASH button (WASH ON/OFF with touch screen), and a means of turning on/off hood fans and lights, if applicable. It also includes system alarm notifications to alert of any faults on the system, such as a low detergent alarm.
SYSTEM FAULT
MENU
NAV
Keypad Touch Screen
NOTE
For detailed information on the Auto Scrubber Control Panel (ASCP), please refer to the Accurex website, www.accurex.com
Auto Scrubber 3
Supply Plenum Weights and Dimensions
External Supply
Plenum Type
Air Curtain Supply (ASP)
Split Air Curtain Supply (Split ASP)
lbs/ft kg/m in. mm in. mm ft. m
Refer to Air Curtain
Supply Plenum
Weight Table
15.5 23.07 24 609.6 10 254.0 3 to 16 .91 to 4.88
Weight Width Height Length per section
Refer Air Curtain
Supply Plenum
Weight Table
10 to 24 254.0 to 609.6 10 254.0 3 to 16 .91 to 4.88
Back Supply (BSP) 35.0 52.09 6 152.4 Variable Variable 3 to 16 .91 to 4.88
Horizontal Supply (HSP) 14.0 20.83 12 304.8 18 457.2 3 to 16 .91 to 4.88
Variable Supply (VSP) 16.0 23.81 12 304.8 18 457.2 3 to 16 .91 to 4.88
Weight
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Air Curtain Supply Plenum Width (inches)
lbs/ft 8.3 8.6 8.9 9.2 9.5 9.8 10.1 10.4 10.7 11.1 11.3 11.6 11.9 12.2 12.5
kg/m 12.35 12.80 13.24 13.69 14.14 14.58 15.03 15.48 15.92 16.52 16.82 17.26 17.71 18.16 18.60
Auto Scrubber4
Prior to Installation
Unpacking
Prior to installation, check with the Authorities Having Jurisdiction (AHJ) on clearance requirements to structures surrounding the hood and other equipment. Verify there is enough space to safely lift the hood up into its operating position and enough clearance around the hood for components like fire system connections, hood lights, hood control components, plumbing connections, etc. Consider access for servicing the equipment and the different components when locating the hood.
The UL label located on the end panel on the inside of the hood will provide pertinent information regarding the hood installation. Information includes:
• Allowable cooking surface temperatures of the cooking equipment
• Front and side overhang requirements
• Minimum exhaust airflow requirements
• Hood lights load information and restrictions
• Filter information
• Fire damper fusible link replacement information, if applicable
Carefully remove the top of the crate and set aside all accessories in the crate such as backsplash panels, control packages, and boxes with loose parts. When removing the hood from the crate, place protective material on the floor next to the crate to avoid damaging the hood.
Lift the hood only by utilizing the hanger brackets. Make sure the hood weight is evenly distributed. Slowly lift the hood out of the crate and place on the protective material.
NOTE
If using straps, the straps should not interfere with plumbing on the top of the hood in an effort to prevent internal piping damage which could cause future leaks.
Top of Hood
Pallet
Protective Material
Auto Scrubber 5
Hood Installation Overview
It is recommended that the protective plastic sheeting remain on the hood until fully installed to better protect the product from scratching and marking. Once removed, use stainless steel polish, such as BlueAway or equivalent, to clean the hood and/or remove marks or discoloration. Be sure to wipe with the grain and not against it.
1. If the hood is provided with filler panels, shipped loose, install them now. See page 7, Filler Panel Installation. Filler panels may be integral to the hood, which requires no additional installation.
2. If the hood is equipped with Clearance Reduction Methods, refer to pages 7 and 8 for special considerations with hanging the hood.
3. If the hood is provided with hood/duct sensors or thermostats that were shipped loose, install them now. See the Installation and Operations guide provided with the control panel.
4. If the hood was provided with either exhaust collars or supply collars that have shipped loose, it is recommended that the exhaust and supply openings are cut and collars are attached now, prior to hanging the hood. See Installing Duct Collars on page 8.
5 If the hood is provided with a back supply plenum
(BSP) install it now. See page 9, Installing the Back Supply Plenum.
6. If possible, connect (weld) exhaust duct to the hood while on the floor, unless it prohibits the hood from being raised into place. For information on ductwork, see page 9, Ductwork.
7. At this point, drill holes in the building structural support system or utilize uni-strut to match up with the hanger bracket holes. Then slowly and evenly raise the hood into position and insert 1/2-inch (12.7mm) diameter threaded rod (provided by others) between the hanger brackets and structure.
The hood hanging height requirements are given on
the UL label. Typical canopy hood hanging height will be 80inches (198.12cm) off the finished floor.
NOTE
If the hood is supplied with ceiling enclosure panels, the height of the enclosures will typically be the distance from the ceiling to the top of the hood. Use this dimension to find the hood’s hanging height off of the floor.
For questions regarding the supporting structure and its integrity, either the contractor or structural engineer needs to be consulted.
NOTE
All hanger brackets MUST be used and the hood must be properly supported while lifting to prevent damage or distortion to the hood.
NOTE
Ensure the hood is hung evenly to prevent drainage problems. Provide adequate support so that the hood does not move in a manner that is unacceptable to the Authorities Having Jurisdiction (AHJ).
WARNING
When mounting the hood or any components against the hood, never puncture or drill into the canopy unless otherwise instructed in this manual. Doing so will void the hood listing and warranty.
8. If the hood was provided in sections with the continuous capture option, once each hood section is hung, install this option now. See page 9, Continuous Capture Plenum Hoods.
9. If the hood was provided with any front or side external supply plenums (other than the back supply plenum), install these now. See page 10, Installing Front/Side External Supply Plenums.
10. Install the remainder of both the exhaust and supply ductwork. For further guidelines see page 9, Ductwork.
11. If the hood is provided with any backsplash/ sidesplash panels, install them now. See page 11, Installing Backsplash Panels.
12. If the hood is provided with any end skirts, install them now. See page 12, Installing End Skirts.
13. This is a Type I hood and it requires a fire suppression system. Once the hood(s) and ductwork are fully installed, appliance(s) are in place and walls are complete, the fire system should be completed.
If the hood is provided with a full factory-
coordinated fire suppression system installation, the certified fire system installer should be contacted at this time to complete the final hookups, testing and system certification based upon manufacturer’s specification and local fire codes.
If the hood is equipped with pre-piping only, and/
or does not include fire suppression, it is the responsibility of a certified fire system installer to install, test and certify the system based upon manufacturer’s specification and local fire codes.
14. The Auto Scrubber Control Panel (ASCP), if shipped loose, will need to be installed at this time. Once mounted, plumbing and electrical wiring will need to be completed by the jobsite plumber and electrician. Typical site wiring responsibilities include wiring hood temperature sensors, hood lights, hood sequencing valves, fire suppression micro-switches, and fans (if applicable) to the control panel. Hood plumbing details are given on page 13-14, and hood electrical wiring details are provided on page 15-17.
Auto Scrubber6
Hood Installation Overview, continued
Clearance Reduction Methods
15. If the hood is provided with enclosure panels, install them now. See page 18, Installing Enclosure Panels.
16. Install the rest of the hood accessories provided. This may include grease filters or condensate hood baffles, grease cups, light bulbs (provided by others unless LED tube style), light globes, and trim strips.
Filler Panel Installation
1. Uncrate the hood and lay it on the floor with
protective material between the hood and the floor.
2. Bolt the filler panels together with 5/16 in. bolts
provided in the hardware package.
3. Position the filler panels to the hood back, and tack-
weld them into place.
HOOD
Clearance reduction methods have been evaluated and tested and are listed by UL (Underwriters Laboratory). The method of test was derived from the UL 710 test standard.
The hood may be installed with zero clearance to combustible materials if constructed in the following manner.
1. One inch (2.54 cm) thick layer of insulation of Owens Corning
®
Type 475, Johns Manville Type 475, IIG® MinWool-1200® Flexible Batt, or Knauf Insulation Type EI 475.
2. Insulation must be held securely in place. Pins that are welded or secured with an adhesive may be used.
3. A backsplash panel must be attached to the wall (insulated or uninsulated).
To comply with the UL Listing, the cooking appliances must be as follows:
• Maximum surface temperature is 700°F (371°C)
• Appliances are located at least 3 in. (7.62 cm) from the rear wall
• Appliances are at least 40 in. (101.6 cm) below the bottom front edge of the hood
The hood may be installed with 3 in. (7.62 cm) clearance to limited combustible materials per NFPA 96 if constructed in one of the following methods:
• 3 in. (7.62 cm) rear uninsulated stand-off
• 3 in. (7.62 cm) top enclosure panel system
• 3 in. (7.62 cm) end uninsulated stand-off
Top Clearance Reduction Options
One inch (2.54 cm) layer of insulation installed on top of the hood (optional) meets zero inch requirements for clearance to combustible surfaces as outlined under the clearance reductions methods.
HOOD
HOOD
TACK-WELDED TO HOOD BACK
5/16 IN. X 3/4 IN. BOLTS WITH WASHERS & NUTS
RIGHT FILLER PANEL
BOTTOM FILLER PANEL
4. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
Three inches (7.62cm) uninsulated airspace installed on top of hood (optional) meets NFPA 96 requirements for clearance to limited combustible surfaces.
Auto Scrubber 7
Back and Front Clearance Reduction Options
One inch (2.54 cm) layer of insulation in 3 in. (7.62cm) back stand-off meets zero inch requirements for clearance to combustible surfaces as outlined under the clearance reduction methods.
Three inches (7.62 cm) uninsulated back stand-off meets NFPA 96 requirements for clearance to limited combustible surfaces.
One inch (2.54 cm) layer of insulation factory-installed on the front of the hood (optional) meets zero inch requirements for clearance to combustible surfaces.
Installing Duct Collars
Exhaust Duct Collars
1. The exhaust duct connection needs to be located within 48 in. (121.92 cm) from the center of the hood length to the center of the duct connection and within shaded area as shown.
Top View of the Hood
8 in.
Hanger Bracket
Exhaust Plenum
Duct cut out area
8 in.
14 in.
3 in.
Hood Width
End Clearance Reduction Options
One inch (2.54 cm) layer of insulation factory-installed on the end of the hood (optional) meets zero inch requirements for clearance to combustible surfaces under the clearance reduction methods.
Three inches (7.62 cm) uninsulated airspace installed on end of hood (optional). Meets NFPA 96 requirements for clearance to limited combustible surfaces.
Hood Length
Front of hood
NOTE
An 8x8x4-inch enclosure and sequencing solenoid valves will be mounted on top of the Auto Scrubber hood near the right or left-hand side. Avoid interference with these items by keeping the exhaust collars 20 inches from the end of the hood where these components are mounted.
2. The exhaust duct connection is to be a continuous liquid-tight weld. Weld with a non-ferrous filler wire, such as silicon bronze or stainless steel filler wire. Protect all stainless steel areas from weld splatter.
Supply Duct Collars to the Plenum
Place the duct collar(s) over the opening, fastening with tack-welds at 1 to 2 in. (2.54 to 5.08 cm) intervals, or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm) intervals.
3 in.
Auto Scrubber8
Installing the Back Supply Plenum
BOLT OR WELD
HOOD TOP
HOOD END
SUPPORT ANGLES
CAULK
BOLT
U-CLIP
HOOD
ACORN NUT
2. RAIS AND
3. FAST
4. FAST
5. CAU
& CAP
1. REM
HOOD FRONT
HOOD FRONT
REMOVE SUPPORT ANGLES ON THE OPEN END PANEL
Ductwork
Install the Supply Duct Collar
1. Find the center of the back supply plenum.
2. If the back supply plenum is to have one opening, cut the opening such that it is centered at L /2 from the plenum end. (Fig.1)
3. If the back supply plenum is to have two openings, cut openings such that they are centered at L /4 from each end of the plenum. (Fig. 2)
4. Place the duct
L/4
collar(s) over the opening(s), fastening with screws or tack-welds every 4 to 6 in. (10.16 to
15.24cm). (Fig. 3)
Hang the Plenum
Fig. 2
5. Hang the back supply plenum from the ceiling.
The back supply plenum
needs to be mounted 31.25in. (79.375 cm) above the finished floor. This is measured from the lowest rear edge of the back supply plenum to the finished floor. (Fig. 4)
Hang using threaded rod
placed through the hanger brackets.
6. Fasten the back supply to the wall, going through the lower back supply wall.
L (MODULE LENGTH)
L/2
Fig. 1
L (MODULE LENGTH)
L/2
Fig. 3
L/2
L/4
Exhaust - As specified in NFPA 96, Ch. 7.5 (latest
edition), exhaust duct systems must be constructed in the following manner:
Materials: Ducts shall be constructed of and supported by carbon steel not less than 1.37 mm (0.054 in.) (No. 16 MSG) in thickness, or stainless steel not less than
1.09 mm (0.043 in.) (No. 18 MSG) in thickness. Installation: All seams, joints, penetrations, and duct to
hood collar connections shall have a liquid-tight external weld. If you have an automatic fire damper, please refer to that manual for installation instructions now.
Supply - Supply ductwork (where applicable) should
be connected to the hood in a manner approved by the local code authorities.
NOTE
For hoods with fire dampers in the exhaust and supply duct collars, an access panel for cleaning and inspection shall be provided in the duct. This panel shall be as close to the hood as possible but should not exceed 18 in. (45.72 cm).
For proper installation of duct collars when they are shipped unattached, see page 8.
Continuous Capture Plenum Hoods
1. Remove the support angles provided for support during shipping on the open end panels. Install and level both hoods.
FASTENERS HOLDING THE
BACKSUPPLY TO THE WALL
31.25 INCH CRITICAL
Fig. 4
DIMENSION
These fasteners are to help maintain the location of the back supply, and are not intended to hold the weight of the back supply unit.
The fasteners should not interfere with the removable air diffusers.
2. After leveling, secure the hoods together by tack­welding and/or bolting the angles that are located at the top of the hoods along its width (Fig. 5).
3. Next, fasten the hoods together at its inside plenum profile using u-clips and bolts (Fig.6). Caulk this joint with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
Fig. 5
Fig. 6
Auto Scrubber 9
Installing Front/Side External Supply Plenums
Using Uni-strut
THREADED ROD
SUPPLIED BY OTHERS
UNI-STRUT (U-CHANNEL)
SUPPLIED BY OTHERS
END VIEW
HOOD
The uni-strut (supplied by others) supporting the hood may be cantilevered over the end of the hood. Utilizing the external supply plenum’s hanger brackets, securely fasten to the uni-strut.
THREADED
THREADED
ROD
ROD
UNI-STRUT
UNI-STRUT
(U-CHANNEL)
(U-CHANNEL)
EXTERNAL
SUPPLY PLENUM
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by others) into hanger brackets on the external supply plenum top. Raise and hang the external supply plenum from adequate roof or ceiling supports.
NOTE
Ensure the external supply plenum is installed flush with the hood front and is plumb and level by adjusting the threaded rod(s). There should be no gap between the bottom of the external supply plenum and the hood after installation and adjustments are completed.
2. The external supply plenum should be resting lightly against the hood. The hood is only used to position the plenum; it is not intended to support the plenum. All hanger brackets on the external supply plenum must be used and the plenum must be properly supported while lifting to prevent damage or distortion. The external supply plenum must be level to operate properly.
NOTE
After hanging, secure the external supply plenum to the hood (or to another external supply plenum) using the supplied turnbuckle(s). Use caution tensioning the turnbuckle. Too much tension may cause the bottom of the external supply plenum to pull away from the hood or cause the face of the hood to become deformed.
Air Curtain Supply (ASP)
Horizontal Supply Plenum (HSP)
Variable Supply Plenum (VSP)
Mounted with uni-strut and threaded rod
When using uni-strut (supplied by others), it must be bolted to the hood and external supply plenum hanger brackets.
NOTE
The uni-strut needs to be the full length of the hood and the external supply plenum.
Using Hanger Brackets and Threaded Rod
Air Curtain
Supply Plenum (ASP)
Horizontal Supply Plenum (HSP)
Variable Supply Plenum (VSP)
TURNBUCKLE
TURNBUCKLE
HOOD HANGER
HOOD HANGER
BRACKET
BRACKET
EXTERNAL
EXTERNAL
SUPPLY PLENUM
SUPPLY PLENUM
HANGER BRACKET
HANGER BRACKET
HOOD
EXTERNAL
SUPPLY
PLENUM
3. It is recommended that caulk be applied at the mating seams and surfaces of the external supply plenum, the hood, and the wall. If the external supply plenum is next to a wall, you will need to caulk around the surface next to the wall. Caulk the joints with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
Installing the Supply Duct Collar to thePlenum
Place the duct collar(s) over the opening, fastening with tack-welds at 1 to 2 in. (2.54 to 5.08 cm) intervals, or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm) intervals.
Auto Scrubber10
Loading...
+ 22 hidden pages