Selection Guide
Tmax
MCCBs
T1 1P T1 T2 T3 Ts3
Type Tmax T1 1p Tmax T1 Tmax T2 Tmax T3 Tmax Ts3 Tmax Ts3
Frame size [A] 100 100 100 225 150 225
Number of poles [Nr] 1 3-4 3-4 3-4 2-3-4 2-3-4
Rated voltage AC (50-60Hz) [V] 347 600Y/347 480 600Y/347 600 480
DC [V] 500 500 600 500
Interrupting ratings B N S H N S N H L N H L
240V AC [kA rms]
277V AC [kA rms]
347V AC [kA rms]
480V AC [kA rms]
600Y/347V AC [kA rms] 10 10 10
600V AC [kA rms] 14 14 25
250V DC (2 poles in series) [kA rms] 25 25 35
500V DC (3 poles in series) [kA rms] 25 25 35
500V DC (2 poles in series) [kA rms] 35 50 65 20 35 50
600V DC (3 poles in series) [kA rms] 20 35 50
Trip units TMF
TMD/TMA
ELT
MA
Electronic
Dimensions H [in/mm] 5.12/130 5.12/130 5.12/130 5.9/150 6.7/170 6.7/170
W 3p [in/mm] 1/25.4 3/76 3.54/90 4.13/105 4.13/105 4.13/105
D [in/mm] 2.76/70 2.76/70 2.76/70 2.76/70 4.07/103.5 4.07/103.5
Mechanical life [No. operations] 25000 25000 25000 25000 25000 25000
16
Circuit breakers for power distribution
T1 – Ts3
50 2
18 1
14 1
22 2
■ ■ ■ ■ ■ ■
65 150 50 65 65 100 150 65 100 150
35 65 25 35 25 50
■
■ ■ ■ ■
■
85 5
25 50 65
1 In15A = 10kA@277VAC 10kA@347VAC
2 In15A = 35kA@240VAC 14kA@480Y/277 VAC
3 T5 600 with electronic trip units only and in three pole version
4 2p breakers: available only in N interrupting rating
5 In from 15A up to 30A=65kA@480V AC
16.2 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Selection Guide
Circuit breakers for power distribution
T4 – T8
T4 T5 T6 T7 T8
Tmax
MCCBs
Type Tmax T4 Tmax T5 Tmax T6 Tmax T7/T7M
Frame size [A] 250
Number of poles [Nr]
Rated voltage AC (50-60Hz) [V] 600 600 600 600
DC [V] 600 600 600
Interrupting ratings N S H L V N S H L V N S H L S H L V
240V AC [kA rms] 65 100 150 200 200 65 100 150 200 200 65 100 200 200 65 100 150 125
277V AC [kA rms]
347V AC [kA rms]
480V AC [kA rms] 25 35 65 100 150 25 35 65 100 150 35 50 65 100 50 65 100 125
600Y/347V AC [kA rms]
600V AC [kA rms] 18 25 35 65 100 18 25 35 65 100 20 25 35 42 25 50 65 100
250V DC (2 poles in series) [kA rms]
500V DC (3 poles in series) [kA rms]
500V DC (2 poles in series) [kA rms] 25 35 50 65 100 25 35 50 65 100 35 35 50 65
600V DC (3 poles in series) [kA rms] 16 25 35 50 65 16 25 35 50 65 20 20 35 50
Trip units TMF
TMD/TMA
ELT
MA
Electronic
Dimensions H [in/mm] 8.07/205 8.07/205 10.55/268 10.55/268 15 / 382
W 3p [in/mm] 4.13/105 5.51/140 8.26/210 8.26/210 16.8 / 427
D [in/mm] 4.07/103.5 4.07/103.5 4.07/103.5
Mechanical life [No. operations] 20,000 20,000 20,000 10,000 15,000
2-3-4 4 2-3-4 4
■
■ ■ ■
■ ■ ■ ■
400-600 3
800 1000-1200
3-4 3-4
6.06/154 (toggle)
7/178 (motor)
Insulated case
T8
1600, 2000,
2500 & 3000
3
600
11.2 / 282
16
1 In15A = 10kA@277 VAC 10kA@347 VAC
2 In15A = 35kA@240 VAC 14kA@480Y/277 VAC
3 T5 600 with electronic trip units only and in three pole version-
4 2p T4N250 and T5N400 available only in N interrupting capacity.
5 In from 15A up to 30A=65kA@480 VAC
6 Applies to MCS only.
Low Voltage Products & Systems 16.3