ABB SU200M, SU200MR, S200UDC Technical specifications

Technical specifications
SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5
Technical specifications
SU200M SU200MR S200UDC
Specifications
UL file number
Trip curves
Rated current
Rated voltage
Short circuit interrupt rating
Calibration temperature
Mounting position
Protection degree
Mounting
Terminal screw tightening
torque Cable size
Ambient temperature
Shock resistance (IEC60068-
2-27) Service life, mechanical
UL 489, C 22.2 No. 5, IEC 60947-2
E 212323, UL current limiting E 212323, UL current limiting E212323
1, 2, 3, 4 1, 2, 3, 4 1, 2
C, K, Z K Z, K
Up to 63 A Up to 63 A Up to 63 A 277/Y480 VAC up to 40 A (Z and C trip curves) 277/Y480 VAC (up to 35 A) 60/125 VDC (1/2-pole) 277/Y480 VAC up to 35 A (K trip curve) 240 VAC up to 63 A 240 VAC up to 63 A (all trip curves) 48/96 VDC up to 63 A (1/2-pole, all trip curves) 10 kA 10 kA 14 kA
40 ºC 40 ºC 25 ºC
Any Any Any
IP 20 IP 20 IP 20 with accessory
35 mm DIN rail 35 mm DIN rail 35 mm DIN rail
25 in. lbs (2.8 Nm) 25 in. lbs (2.8 Nm) 25 in. lbs (2.8 Nm)
AWG 4-16 AWG 4-16 AWG 4-16
-25 ºC...+55
25 g - 2 shocks - 13 ms 25 g - 2 shocks - 13 ms 25 g - 2 shocks - 13 ms
20,000 operations 20,000 operations 20,000 operations
º
C/-13 ºF...+131 ºF -25 ºC...+55 ºC/-13 ºF...+131 ºF -25 ºC...+55 ºC/-13 ºF...+131 ºF
UL 489, C 22.2 No. 5, IEC 60947-2 UL 489, VDE 0660
Auxiliary contact S2C-H6RU and S2C-S6RU
Rated current
Rated voltage AC/DC
Contact
Connection capacity mm
Tightening torque
Shock resistance acc. to DIN IEC 68-2-6
Mechanical service life
2
10
24
1 pole double throw
18-14 AWG (0.75...2.5 mm2)
11 in. lbs (1.2 Nm)
5 g, 20 frequency cycles 5...150...5 Hz at 24 VAC/DC, 5 mA auto-reclosing < 10 ms
10,000 operations
Shunt trip
S2C-A1U
Rated voltage AC V 12...60 110...415
DC V 12...60 110...250
Maximum release duration ms <10 <10 Minimum release voltage AC V 7 55
DC V 10 80
Consumption on release AC VA 40...200 55...210
DC VA 40...200 55...110
Coil resistance Terminals AWG/mm Tightening torque in. lbs./Nm 18/2 18/2
V
2
3.7 225
18...6/0.75-16 18...6/.075-16
S2C-A2U
14 Miniature Circuit Breakers | US Catalog
Technical specifications
SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5
Internal resistance and power loss per pole
Internal resistance per pole in mV, power loss per pole in W.
SU200M
C, K characteristics Z characteristics
Rated current Internal resistance per pole Power loss Internal resistance per pole Power loss I
n
A mΩ W mΩ W
0.2 42500 1.7 - -
0.3 18889 1.7 - -
0.5 5600 1.4 9000 2.3
0.75 2489 1.4 - ­1 1400 1.4 2200 2.2
1.6 703 1.8 1000 2.6 2 450 1.8 650 2.6 3 178 1.6 250 2.3 4 113 1.8 140 2.2 5 50 1.3 100 2.5 6 56 2.0 70 2.5 8 23 1.5 28 1.8 10 21 2.1 21 2.1 13 14 2.3 17 2.9 15 11 2.4 13 2.9 16 9.8 2.5 10 2.6 20 6.3 2.5 6.5 2.6 25 5.1 3.2 5.1 3.2 30 3.9 3.5 3.9 3.5 32 3.6 3.7 3.6 3.7 35 3.3 4.1 3.3 4.1 40 2.8 4.5 2.8 4.5 50 1.8 4.5 1.8 4.5 60 1.4 4.9 1.4 4.9 63 1.4 5.4 1.4 5.4
Internal resistances are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values.
R
i
P
v
R
i
P
v
SU200MR
Rated current Internal resistance per pole
A mΩ W
0.2 25300 1.01
0.3 13700 1.23
0.5 4740 1.19
0.75 2067 1.16 1 1270 1.27
1.5 610 1.56 2 442 1.77 3 140 1.26 4 109 1.75 5 50 1.26 6 54 1.94 8 22 1.41 10 18.2 1.82 13 14.8 2.50 15 8.1 1.83 16 11.1 2.83 20 8.5 3.40 25 5.5 3.43 30 3.8 3.39 32 4.6 4.70 35 3.9 4.76 40 2.8 4.40 50 1.7 4.25 60 1.7 6.18 63 1.9 7.56
1)
Internal resistances and power loss are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values.
1)
Power loss per pole
1)
US Catalog | Miniature Circuit Breakers 15