ABB Softstarters Installation Manual

Page 1
1SFC132057M0201
Softstarters Type PSE18...PSE370
Installation and commissioning manual
Page 2
This manual belongs to:
__________________________________________
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
2
Page 3
Installation and Commissioning Manual
ABB Softstarters PSE18...PSE370
1 General
This is the Installation and Commissioning Manual for Softstarters Type PSE18…PSE370.
Document number: 1SFC132057M0201
Revision: G
Issue date: 2018-11-20
Data subject to change without notice.
We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particu­lar reproduction and dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is kindly asked to notify us as soon as possible.
The data contained in this manual is intended solely for the product descrip­tion and is not to be deemed to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards.
As a result, there may be some differences between the softstarter and the infor­mation in this manual.
Author’s address:
ABB AB Control Products SE-721 61 Västerås, Sweden
Telephone: +46 (0) 21 32 07 00
www.new.abb.com/lowvoltage/products/softstarters www.abb.com/drives
© Copyright 2018. All rights reserved. Specifi cation subject to changes without notice.
Page 4
2 Safety
This chapter describes warning and information signs used in this manual, which the user should pay attention to. The softstarter shall be installed by authorized personnel only. This manual is a part of the PSE Softstarter and should always be accessible to personnel working with this product. The manual shall always be read through before performing any installation or commissioning tasks.
2.1 Use of signs warning and information
Warning!
Warning symbol indicates the presence of hazardous voltage which could result in personal injury.
Warning!
General warning symbol indicates the presence of a hazard which could result in personal injury and damage to equipment or property.
Information
Information sign alerts the reader to pertinent facts and conditions.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
4
Page 5
Chapter
1 Introduction ............................................ 7
2 Quickstart ............................................... 11
3 Description ............................................. 15
4 Mounting ................................................ 27
5 Connection ............................................. 31
6 Human-Machine Interface (HMI) .............. 45
7 Functions and confi guration .................... 55
8 Fieldbus communication ......................... 79
9 Maintenance ........................................... 81
10 Troubleshooting ...................................... 83
11 Wiring diagrams ...................................... 95
12 Index ...................................................... 99
Customer feedback report ............................... 102
Page 6
Notes
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
6
Page 7
Chapter 1 Introduction
Documentation for PSE18...PSE370 softstarter .......................................... 8
Installation and Commissioning Manual ...................................................... 8
Intended audience ................................................................................. 9
General ............................................................................................. 9
Requirements .................................................................................... 9
Revision notes and other documents ..................................................... 9
Acronyms and abbreviations .................................................................. 9
Explanation of concepts ......................................................................... 10
Cyber Security Legal Disclaimer .................................................................. 10
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 7 Chapter 1
Page 8
Chapter 1 Introduction
1.1 Documentation for PSE18...PSE370 softstarter
For the Softstarter Type PSE18...PSE370, the following manuals are available:
1SFC132059M9901 (User manual short form, printed) 1SFC132057M0201 (English version, PDF-fi le)
1.2 Installation and Commissioning Manual
This manual contains instructions on how to install, commission and maintain the softstarter. The manual covers procedures for mechanical and electrical installa­tion, and installation of communication devices. It also covers energizing, setting, and confi guration and verifying settings.
For brief information see Softstarters Type PSE18...PSE370 User Manual short form, containing the same languages as the Installation and Commissioning Manual. Softstarters Type PSE18...PSE370 User Manual short form has docu­ment ID 1SFC132059M9901.
For quickest possible start, read Chapter 2 Quickstart or go to the short form manual (1SFC132059M9901).
A complete compilation of ABB’s softstarters can be found in Main catalogue Softstarters, document ID 1SFC132012C0201.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M02018 Chapter 1
Page 9
1.2.1 Intended audience
1.2.1.1 General
The installation and commissioning manual is intended for the installation, com­missioning, and maintenance personnel responsible for getting the softstarter into normal service and out of service.
1.2.1.2 Requirements
The installation personnel must have a basic knowledge in handling electric equip­ment. The commissioning and maintenance personnel must be well experienced in using this kind of equipment.
1.2.2 Revision notes and other documents
For latest information on revisions and other documents related to the PSE Softs­tarters, please check
www.new.abb.com/low-voltage/products/softstarters www.abb.com/drives
1.2.3 Acronyms and abbreviations
The acronyms and abbreviations described in table 1.1 are used in this manual.
Table 1.1
Acronym/ abbre­viation
BP By-pass
DOL Direct-on-line
EOL Electronic overload protection for the Motor
FB Fieldbus
FBP FieldBusPlug
HMI Human-Machine Interface
I
e
IT Information Technology
LCD Liquid Crystal Display
LED Light Emitting Diode
PCB Printed Circuit Board
PLC Programmable Logic Controller
PTC Positive Temperature Coeffi cient
RTU Remote Terminal Unit
SC Short Circuit
SCR Silicon Controlled Rectifi er ( thyristor)
TOR Top of Ramp ( full voltage/ Full-On)
U
c
U
e
U
s
Description
Rated operational current
Rated control circuit voltage *
Rated operational voltage *
Rated control supply voltage *
*) For defi nition see IEC 60947-1 edition 5.0
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 9 Chapter 1
Page 10
1.2.4 Explanation of concepts
The setting of current Ie is the setting for the rated operational current (main cur­rent) of the motor.
Ue = Rated operational voltage on the motor’s operational current (three phase
main voltage feeding the motor). Us = Rated control supply voltage, feeding the electronics in the softstarter. Uc = Rated control voltage, used for controlling the softstarter.
1.3 Cyber Security Legal Disclaimer
This product is designed to be connected to and to communicate information and data via a communication interface. It is Customer’s sole responsibility to provide and continuously ensure a secure connection between the product and Customer network or any other network (as the case may be). Customer shall establish and maintain any appropriate measures (such as but not limited to the installation of rewalls, application of authentication measures, encryption of data, installation of anti-virus programs, etc) to protect the product, the network, its system and the interface against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information.
ABB Ltd and its affi liates are not liable for damages and/or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and/ or theft of data or information.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020110 Chapter 1
Page 11
Chapter 2 Quickstart
Quickstart ................................................................................................... 12
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 11 Chapter 2
Page 12
Ready Run
A
Protection
B
Fault
Chapter 2 Quickstart
This chapter is a short guide on how to connect, confi gure and start the softstarter in the easiest way.
This product has been carefully manufactured and tested but there is a risk that damage can occur from abnormal handling during transportation. Therefore, the procedure below should be followed during initial installation:
Warning!
Mounting, electrical connection and settings of the softstarter shall be made in accordance with existing laws and regulations and be performed by authorized personnel.
Exit
Select
Reset
C DE
Figure 2.1:
LED status indicators.
A
B
LCD display with backlight.
Exit key for cancelling parameter edits and
C
moving up one menu level.
Select/Reset key for changing and storing
D
parameter values, moving down one menu level, and to reset tripping events.
E
Navigation keys for navigating the menu and changing parameter values. Flashing numbers or text shown in the display indicates that the menu/value can be changed or scrolled.
1SFC132235F0001
Warning!
Connecting Softstarters PSE18...PSE370 Inside Delta will cause dam­age to the equipment, and there is a risk of death or serious injury.
PSE
1SFC132265F0001
In Line Inside Delta
PSE
1SFC132263F0001
Warning!
Before connecting the PSE18...PSE170 to operational voltage(Ue) for the fi rst time, the supply voltage(Us) must be connected and turned on to ensure the bypass relay is switched to open position. This is necessary to avoid unintentional starting of the equipment during the connection.
1. Be aware of the ambient temperature. Derating is required above 40 °C (104 °F). See chapter 3.6.
2. Mount the softstarter according to Chapter 4 Mounting.
L1 L2 L3 N
LN
Start Stop
KM1
1L1 3L2 5L3
2T1 4T2 6T3
U
V
12 1489
W
89
Start Stop
Run
TOR Fault
NC NO
67
543
11
11
1210 13
M
3
Figure 2.2: Example connection of PSE Softstarter
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020112 Chapter 2
Warning!
Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before starting work on this equipment.
3. Connect the terminals 1 L1, 3 L2 and 5 L3 to the operational voltage on the power supply line side.
4. Connect the terminals 2T1, 4T2 and 6T3 to the motor.
Warning!
Capacitors for power factor compensation are not allowed between the softstarter and the motor, since this can cause current peaks which can damage the thyristors in the softstarter. If such capaci­tors are to be used, they should be connected on the line side of the softstarter.
1SFC132237F0001
Page 13
5. Connect control supply voltage to terminals 1 and 2 (100-250 V 50/60 Hz).
Exit
Select
Reset
B
Exit
Exit
Select
Reset
C
Select
Reset
D
6. Connect the functional earth to terminal 14, with an earthing point close to the softstarter.
The earthing is not a protective earth, it is a functional earth. The earthing cable should be as short as possible. Maximum length 0.5 m. The earthing cable should be connected to the mounting plate, which should also be earthed.
7. Connect the start, stop and other control circuits including the analog out to the terminals, 8, 9, 10, 11, 12, 13 if needed. This section is using an internal 24 V DC. Do not feed with any external voltage.
Select
Reset
A
Exit
Select
Reset
Warning!
Do not connect an external voltage to the control terminals 8, 9, 10, 11, 12, 13 and 14. Failure to observe the above may damage the softs­tarter and the warranty may no longer be valid.
8. Connect terminals 3, 4, 5, 6 and 7 when using the signal output relays. These are potential free contacts for maximum 250 V AC, 1,5 A AC-15. Make sure you are using the same voltage level within this terminal section.
1SFC132268F0001
Figure 2.3:
Confi guration of the parameter Rated Current.
A
If disabled, press any key to activate the light in the display. Enter the application setting by pressing the Select key a second time.
B
Press select again to enable editing of the Ie parameter. This is indicated by a fl ashing value.
Increase or decrease the value by pressing the
C
Up or Down keys repeatedly. Holding the key down will speed up the change. Press the Exit key to abort change.
D
When the rated current of the motor is reached, press the Select key again to save.
If needed, continue to set other parameters according to the application following the same procedure.
Press the Exit key to return to the top level.
Warning!
The same external voltage (maximum 24 V DC or maximum 250 V AC) must be connected to the output relay terminals 3, 4, 5, 6 and 7. Failure to observe the above may damage the softstarter and the war­ranty may no longer be valid.
9. Switch ON the control supply voltage Us, terminals 1 and 2.
10. Continue to confi gure parameter Ie as described in fi gure 2.3. Complete information about confi guration is available in Chapter 6 Human-Machine Interface (HMI) and Chapter 7 Functions and confi guration.
11. Switch ON the operational voltage Ue. The green “Ready” LED will turn solid.
12. Give start command to the softstarter.
Warning!
Depending on the two phase control, a connected motor terminal always carries live hazardous voltage. Do not touch terminals when voltage is applied. Output terminals will have live voltage even when the device is OFF. This can cause death or serious injury.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 13 Chapter 2
Page 14
This page is intentionally left blank.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020114 Chapter 2
Page 15
Chapter 3 Description
Overview .................................................................................................... 16
Markings and connections .......................................................................... 17
Type designation ......................................................................................... 18
Documentation ........................................................................................... 18
Environmental infl uence .............................................................................. 18
Specifi cations ............................................................................................. 18
Technical data ............................................................................................ 19
General .................................................................................................. 19
Weights .................................................................................................. 19
PSE Softstarter types ............................................................................. 20
IEC information ...................................................................................... 21
information .............................................................................. 21
Dimensions ............................................................................................ 22
Drilling plan ............................................................................................ 24
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 15 Chapter 3
Page 16
Chapter 3 Description
This chapter describes the PSE Softstarter in general, specifi cations as well as available accessories and spare parts.
L1
L2 L3
M
Figure 3.1: Integrated By-pass. Controlled phases 1 and 3 (L1 and L3).
3.1 Overview
The PSE Softstarter is a microprocessor-based softstarter designed with the latest technology for soft starting and soft stopping of three-phase squirrel cage motors. The softstarter has several advanced features as standard.
• Integrated by-pass in phases L1 and L3, see fi gure 3.1.
Thyristors are used on phases L1 and L3 for controlling the motor voltage.
1SFC132253F0001
Select between voltage ramp or torque control during start and stop.
• Motor protection, as well as underload and locked rotor protection.
The keypad on the front is designed to be as user-friendly as possible, with a clear display showing icons.
The PSE Softstarter can be controlled in two ways:
Hardwire inputs control
Fieldbus communication interface
Only one type of control method can be enabled simultaneously. Default selection is hardwire inputs control.
The integrated fans for cooling are operated only during ramping ( start/stop) and when the temperature of the heat sink is high. The temperature is monitored by a thermistor mounted on the heat sink.
Phase L2 is directly connected to the motor, see fi gure 3.1.
Figure 3.2: Torque control is offered as standard with the PSE softstarter.
Check that you have the correct product in regards to operational voltage, control supply voltage and rated motor data. See chapter 3.3 Type designation.
The PSE18...PSE370 Softstarters operates over wide voltage ranges.
Rated operational voltage 208 - 600 V AC
Rated control supply voltage 100 - 250 V AC
Warning!
The product should only be used within the specifi ed ratings. Be aware of the ambient temperature and altitude above sea level. Derating is required above 40 °C (104 °F) and above 1000 m (3281 ft).
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020116 Chapter 3
Page 17
3.2 Markings and connections
Line side connection
Supply voltage U
Green
Green
Yellow Red
Order code
Technical data according to IEC 947-4-2
s
81 2 3 4 5 6 7 9 10 11 12 13 14
Terminal marking of control circuits
PSE 18-600-70
Display
Keypad
Fieldbus connection
Technical data according to UL 508 and CSA-C22.2 No. 14-05
Figure 3.3: Markings and connections
1SFC132238F0001
Motor side connection
External Keypad connection
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 17 Chapter 3
Page 18
PSE18 - 600 - 70 - 1
A
B
C
D E
3.3 Type designation
Type designation to be found on the softstarters front. See fi gure 3.4.
A
Softstarter type: PSE
B
Current rating: 18 = 18 A
C
Operational voltage: 600 = 208 - 600 V 50/60 Hz
Control supply voltage: 70 = 100 - 250 V 50/60 Hz
D
Figure 3.4: Type designation
Design code (PSE210...PSE370 only)
3.4 Documentation
Documentation such as brochures, catalogs, certifi cates, and drawings included can be found at:
www.new.abb.com/lowvoltage/products/softstarters.
3.5 Environmental infl uence
The product is designed to minimize the environmental effects during manufactur­ing and use of the product. Most of the materials used, are of recycle type, and shall be handled and recycled according to existing laws.
Further information regarding used material and recycling of the product can be found at:
www.new.abb.com/low-voltage/products/softstarters
www.abb.com/drives
3.6 Specifi cations
Table 3.1
Degree of protection ( Operational circuit)
Operating position Vertical at ±
Ambient temperature Storage. -40 oC to + 70 oC (-40 oF to 158 oF)
Altitude 1000 m (3281 ft.) above sea level without derating.
Pollution degree 3
Relative humidity 5-95% (non-condensing)
Standards IEC 60947-1
Standards
IP 00
o
30
o
Operation: -25 derating.
o
C to + 60 oC (104 oF to 140 oF) with derating 0.6
+ 40
o
C (0.6% / 1,8 oF).
% /1
1000-4000 m (3281 - 13123 ft.) above sea level with derating
0.67 % per 100 m above 1000 m
IEC 60947-4-2 EN 60947-1 EN 60947-4-2
UL 508, CSA C22.2 No 14-10
C to + 40 oC (-13 oF to 104 oF) without
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020118 Chapter 3
Page 19
3.7 Technical data
3.7.1 General
Table 3.2
General data
Rated insulation voltage, U
Rated operational voltage, U
Rated control supply voltage, U
Voltage tolerance +10% to -15%
Frequency tolerance
Rated impulse withstand voltage 6 kV operational circuit
Number of controlled phases 2
Inputs Start, stop, reset
Analog out 4-20 mA
Cooling system Fan
Rated form Form 1
Rated duty Uninterrupted
EMC
Recommended fuse Supply circuit
Communication protocols, Internal Modbus RTU
i
e
600 V
208-600 V 50 / 60 Hz
100 - 250 V 50 / 60 Hz
s
±
5%
/ 4 kV control supply circuit
IEC 60947-4-2 Class A Lloyd’s Register (2002)
6A Delayed MCB use characteristics
DeviceNet with fi eldbus plug/Profi bus DP with fi eldbus plug/ Modbus RTU with eldbus plug
1
1
This product has been designed for environment A. Use of this product in environmentB
may cause unwanted electromagnetic disturbances in which case the user may be required to take adequate mitigation measures.
3.7.2 Weights
Table 3.3
Type Weight in kg Weight in lbs
PSE18...PSE60 2.4 5.3
PSE72...PSE105 2.5 5.5
PSE142...PSE170 4.2 9.2
PSE210 9.5 20.9
PSE250...PSE370 10.9 24.0
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 19 Chapter 3
Page 20
3.7.3 PSE Softstarter types
Table 3.4
t + 40 oC (104 oF)
IEC
220-
240 V Softstarter type
PSE18 18 4 7.5 11 18 5 5 10 15
PSE25 25 5.5 11 15 25 7.5 7.5 15 20
PSE30 30 7.5 15 18.5 28 7.5 10 20 25
PSE37 37 9 18.5 22 34 10 10 25 30
PSE45 45 11 22 30 42 10 15 30 40
Ie (A)
P (kW)
380­400 V
P (kW)
500 V
P (kW) FLA (A)
208 V
P (HP)
220­240 V
P (HP)
440­480 V
P (HP)
550­600 V
P (HP)
PSE60 60 15 30 37 60 20 20 40 50
PSE72 72 18.5 37 45 68 20 25 50 60
PSE85 85 22 45 55 80 25 30 60 75
PSE105 106 30 55 75 104 30 40 75 100
PSE142 143 40 75 90 130 40 50 100 125
PSE170 171 45 90 110 169 60 60 125 150
PSE210 210 59 110 132 192 60 75 150 200
PSE250 250 75 132 180 248 75 100 200 250
PSE300 300 90 160 200 302 100 100 250 300
PSE370 370 110 200 250 361 125 150 300 350
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020120 Chapter 3
Page 21
3.7.4 IEC information
For more information see: https://applications.it.abb.com/SOC/Motor
3.7.5 information
For more information see: https://applications.it.abb.com/SOC/Motor
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 21 Chapter 3
Page 22
3.7.6 Dimensions
Dimensions PSE18...PSE105
6 mm (0.24 in)
6,5 mm (0.26 in)
230 mm (9.06 in)
80 mm (3.14 in)
PSE 18-600-70
245 mm (9.65 in)
188 mm (7.40 in) 28 mm (1.12 in)
30 mm (1.18 in)
185,5 mm (7.30 in)
90 mm (3.54 in) 3 mm (0.12 in)
13 mm (0.51 in)
90 mm (3.54 in)
3 mm (0.12 in)
7 mm (0.28 in)
278 mm (10.94 in)
Dimensions PSE142...PSE170
6,5 mm (0.26 in)
37 mm (1.46 in)
PSE142-600-70
221 mm (8.70 in)
295 mm (11.61 in)
5 mm (0.20 in)
219,5 mm (8.64 in)
3 mm (0.12 in)
35 mm (1.38 in)
113,5 mm (4.47 in)
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020122 Chapter 3
130 mm (5.12 in)
109,5 mm (4.31 in)
1SFC132260F0001
17,5 mm (0.69 in)
Page 23
163.5 mm (6.44 in)
6.5 mm (0.26 in)
8.2 mm (0.32 in)
Dimensions PSE210...PSE370
39 mm (1.54 in)
418 mm (16.46 in)
43.75 mm (1.72 in)
379 mm (14.92 in)
43.75 mm (1.72 in)
435 mm (17.13 in)
236.5 mm (9.31 in)
125.5 mm (4.94 in) 5 mm (0.20 in)
190 mm (7.48 in)
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 23 Chapter 3
Page 24
3.7.7 Drilling plan
Drilling plan PSE18...PSE105
80 mm (3.14 in)
230 mm (9.06 in)
M6 (1/4 in)
1SFC132271F0001
Drilling plan PSE142...PSE170
113,5 mm (4.47 in)
278 mm (10.94 in)
M6 (1/4 in)
70
0-
60
2-
14
SE
P
1SFC132272F0001
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020124 Chapter 3
Page 25
Drilling plan PSE210...PSE370
418 mm (16.46 in)
163,5 mm
M6 (1/4 in)
(6.44 in)
1SFC132273F0001
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 25 Chapter 3
Page 26
This page is intentionally left blank.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020126 Chapter 3
Page 27
Chapter 4 Mounting
Receiving, unpacking and checking ............................................................ 28
Intermediate storage .............................................................................. 28
Mounting .................................................................................................... 28
Handling when mounting ....................................................................... 28
Requirements ......................................................................................... 29
Minimum enclosure size ......................................................................... 29
Minimum distance to wall and front ........................................................ 30
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 27 Chapter 4
Page 28
Figure 4.1: Unpacking PSE18...PSE170
Chapter 4 Mounting
This chapter describes instructions on how to receive the softstarter and how to mount it in a proper way.
4.1 Receiving, unpacking and checking
Check that the package is turned with the correct side up, fi gures 4.1 and
Check for transport damages.
Remove the transport casing.
Visually inspect the softstarter.
Check that the order code corresponds with the delivery documents.
1SFC132239F0001
Check that all items are included, according to the delivery note.
Check the softstarter as well as the package. If you fi nd any damages, please
4.1.1 Intermediate storage
Until the softstarter is mounted it should be stored in its package.
4.2.
contact the transport company or the supplier immediately.
Figure 4.2: Unpacking PSE210...PSE370
4.2 Mounting
4.2.1 Handling when mounting
The softstarter is available in three physical sizes. All models of PSE can be taken out of the packages and be mounted without lifting equipment. See chapter 3.7.2 for weights.
Warning!
Never lift the softstarter by the connection bars, since it may cause damage to the product.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020128 Chapter 4
Page 29
H
4.2.2 Requirements
See Chapter 3 Description for environmental requirements.
The PSE Softstarters exist in three different physical sizes which are designed to be mounted with M6 (1/4 in.) bolts as well as bolts of equivalent dimension and strength. Measures and drilling plans will be found in chapters 3.7.6 Dimensions and 3.7.7 Drilling plan.
4.2.3 Minimum enclosure size
In applications where the softstarter is installed in an enclosure, the following minimum enclosure sizes are recommended. Dimensions according to the sketch in fi gure 4.3.
Table 4.1
IEC
PSE18...PSE105 508 610 305 PSE142...PSE170 762 914 305 PSE210...PSE370 610 762 305
Table 4.2
PSE18...PSE105 20 24 12 1 PSE142...PSE170 30 36 12 2 PSE210...PSE370 30 30 12 2
W (mm) H (mm) D (mm)
W (in) H (in) D (in) min number
of latches
D
W
Figure 4.3: Dimensions minimum enclosure size
Dimensions and drilling plan see Chapter 3 Description.
1SFC132269F0001
Warning!
Using a too small enclosure and/or failure to follow the instructions in other ways may result in overheating of the PSE Softstarter and operational dis­turbances.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 29 Chapter 4
Page 30
Figure 4.4: Airways
4.2.4 Minimum distance to wall and front
Check that a suffi cient fl ow of air for cooling purposes can circulate from the bot- tom to the top of the softstarter, and has a free passage away. Figure 4.3.
Warning!
Risk of damage to property. Ensure that no liquids, dust or conductive parts enter the softstarter.
1SFC132240F0001
Make sure that the distances to the surrounding walls are suffi cient, and that the mounting angle is within specifi cations shown in fi gure 4.5. Follow the minimum distance to front and wall, as described in fi gure 4.4 and the table below.
A
PSE 18-600-70
C
1SFC132243F000
Table 4.3
The values in table 4.3 are minimum distances.
A
(mm
[inch])
PSE18...PSE105 100
[3.937]
PSE142...PSE170 100
[3.937]
PSE210...PSE370 100
[3.937]
30
O
PSE 18-600-70
PSE 18-600-70
30
O
PSE 18-60
0-70
B
(mm
[inch])
10
[0.394]
10
[0.394]
10
[0.394]
30
O
C
(mm
[inch])
20
[0.787]
20
[0.787]
20
[0.787]
30
O
A
BB
Figure 4.5: Minimum distances to wall and front
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020130 Chapter 4
1SFC132280F0001
1SFC132242F0001
Figure 4.6: Maximum mounting angle
Page 31
Chapter 5 Connection
General ....................................................................................................... 32
Electrical connection ................................................................................... 32
Considerations when controlling two of three phases ............................. 32
Before connecting softstarters PSE18...PSE170 .................................... 33
Connection of the operational power circuit ........................................... 34
Control supply and control circuit ........................................................... 35
Control supply voltage, terminals 1 and 2 .......................................... 35
Functional earth, terminal 14 .............................................................. 36
Start and Stop, terminals 8 and 9 in circuit with terminals 11 or 12. .. 37
Reset event, terminal 10 .................................................................... 38
Analog output, terminals 13 and 14 ................................................... 39
Status output relays, terminals 3, 4, 5, 6, and 7 ................................. 40
Connection of communication devices (optional) ........................................ 41
External keypad ..................................................................................... 41
Technical data for External Keypad .................................................... 41
Transfer of parameters ....................................................................... 42
Transfer of parameters from softstarter to external keypad ............ 42
Transfer of parameters from external keypad to softstarter ............ 42
Cyber Security Deployment Guideline ......................................................... 43
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 31 Chapter 5
Page 32
Chapter 5 Connection
This chapter describes the electrical connections as well as connections for com­munication devices that have to be made before you can use the softstarter.
5.1 General
Warning!
Mounting and electrical connection of the softstarter shall be made in ac­cordance with existing laws and regulations and be performed by autho­rized personnel.
Warning!
Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before starting work on this equipment.
L1 L2 L3 N
LN
Start Stop
KM1
1L1 3L2 5L3
2T1 4T2 6T3
U
V
12 1489
W
89
Start Stop
Run
TOR Fault
NC NO
67
543
11
11
1210 13
M
3
Figure 5.1: Connection of PSE Softstarter and con­nection in series with a line contactor.
For basic connection, see Chapter 2 Quickstart.
For circuit diagrams for connection of the softstarter, see Chapter 11 Wiring diagrams.
5.2 Electrical connection
5.2.1 Considerations when controlling two of three phases
Even when stopped, there will be a voltage on the motor on phase 2. This will not start the motor and the motor will not be heated up (compare with inside delta connection). For more information about two phase control see Chapter 3 Description.
Semiconductors do not replace air isolation and the recommended solution is to use a line contactor to break the current. See fi gure 5.1.
Warning!
1SFC132237F0001
Depending on the two phase control a connected motor terminal always carries live voltage. Touching terminals and other live parts can result in death or serious injury.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020132 Chapter 5
Page 33
Since Softstarters PSE18…PSE370 has control in two phases, the connection must be done In Line only, in accordance with the circuit diagrams in fi gure 5.2 and in Chapter 11.
PSE
1SFC132265F0001
Figure 5.2: ABB PSE Softstarter must be con­nected In Line only.
PSE
Warning!
1SFC132263F0001
Softstarters PSE18...PSE370 must not be connected Inside Delta since this will cause damage to the equipment and there is a risk of death or serious injury. Figure 5.2.
5.2.2 Before connecting softstarters PSE18...PSE170
Warning!
Before connecting the PSE18...PSE170 to operational voltage(Ue) for the rst time, the supply voltage(Us) must be connected and turned on to ensure the bypass relay is switched to open position. This is necessary to avoid unintentional starting of the equipment during the connection.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 33 Chapter 5
Page 34
5.2.3 Connection of the operational power circuit
The softstarter is recommended to be connected with a line contactor as de­scribed in fi gure 5.1. Additional circuit diagrams will be found in Chapter 11 Wiring diagrams.
Softstarters PSE18...PSE105 are provided with built-in cable clamps. The cables must be stripped before connection, and the length of the exposed wire should be 20 mm or 0.8 in. Connect according to fi gures 5.3 and 5.5.
For Softstarters PSE142...PSE370 the cables must have lugs and be connected to the terminal bars, according to fi gure 5.4 and 5.5.
Connect the line side to terminals 1 L1, 3 L2, 5 L3.
Connect the motor to terminals 2T1, 4T2, 6T3.
The terminals marking are printed on the front of the softstarter.
5L3
3L2
1L1
2T1 4T2 6T3
Figure 5.3: PSE18...PSE105 connection of the connection module line side and motor side terminals
PSE18...PSE105
1L1
3L2 5L3
2T1 4T2 6T3
PSE142...PSE170
1L1
3L2 5L3
2T1 4T2 6T3
PSE210...PSE370
1L1
3L2 5L3
2T1 4T2 6T3
M8
11/6-16 UNF-2S
275 lb.in
3/4-16 UNF-2A
375 lb.in
Using connection module
AWG12 .. 6
2,5 .. 10 mm 2x2,5 .. 2x10 mm
AWG6 .. 2/0
10 .. 70 mm 2x10 .. 2x70 mm
Cu 75°C only
Using connection module
ATK185: AWG4 to 300kcmil Cu 75°C only
Using connection module
ATK300: AWG4 to 400kcmil ATK300/2: AWG4 to 500kcmil or 2xAWG4 to 2x500kcmil Cu 75°C only
Figure 5.5: Tightening torques and dimensions for terminal bars and lugs
5L3
3L2
1L1
Figure 5.4: PSE142...PSE370 connection of the line side and motor side terminals
Using connection bars
2
6 Nm - 53 lb.in
}
2
2
8 Nm - 71 lb.in
2
}
M6
9 Nm - 80 lb.in
M8
18 Nm - 160 lb.in
M10
28 Nm - 240 lb.in
(If connection module is removed)
max 22 mm (0.866 in)
Using connection bars
max 24 mm (0.945 in)
Using connection bars
max 30 mm (1.181 in)
2T1 4T2 6T3
max 20 mm (0.787 in)
max 5 mm (0.197 in)
max 22 mm (0.866 in)
max 8 mm (0.315 in)
max 30 mm (1.181 in)
max 10 mm (0.394 in)
1SFC13275F0001
Warning!
Capacitors for power factor compensation are not allowed between the softstarter and the motor, since this can cause current peaks which can burn the thyristors in the softstarter. If such capacitors are to be used, they should be connected on the line side of the softstarter.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020134 Chapter 5
Page 35
5.2.4 Control supply and control circuit
Wires in industrial control applications are divided into three groups: main power supply, control supply and control.
5.2.4.1 Control supply voltage, terminals 1 and 2
Connect neutral and live to terminal 1 and 2, as shown in fi gures 5.6 and 5.7.
Check that you have the correct control supply voltage Us.
L
N
Figure 5.6: Terminals for control supply voltage
12 34567
891011
12 13 14
M3
0,5 Nm - 4,3 lb.in
Figure 5.7: Tightening torques and wire area
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 35 Chapter 5
4 x 0,8 mm (0.157 x 0.031 in)
2
0,2 .. 4 mm 2x0,2 .. 1,5 mm
2
0,2 .. 4 mm 2x0,2 .. 1,5 mm
, AWG 24 ... 10
2
, 2 x AWG 24 ... 16
, AWG 24 ... 10
2
, 2 x AWG 24 ... 16
Page 36
5.2.4.2 Functional earth, terminal 14
Connect the cable to an earthing point close to the softstarter. The cable should be as short as possible. A suitable earthing point would be next to the softstarter on the mounting plate, as shown in fi gures 5.8 and 5.9. The mounting plate should also be earthed.
This is not a protective earth, it is a functional earth. The earthing cable should be as short as possible. Maximum length 0.5 m.
Do not use functional ground in IT-networks, commonly found in for instance marine applications.
1
2
3
4
5
6
7
8
9
10
11
Figure 5.8: Terminal for functional earth
12 34567
12
13
14
891011
12 13 14
M3
0,5 Nm - 4,3 lb.in
3,5 x 0,6 mm (0.138 x 0.24 in)
AWG 24 ... 12
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
2
2
2
2
Figure 5.9: Tightening torques and wire area
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020136 Chapter 5
Page 37
5.2.4.3 Start and Stop, terminals 8 and 9 in circuit with terminals 11 or 12.
The PSE Softstarter has a built-in holding circuit and does not require sustained signals on start input. Use internal control supply voltage from terminals 11 or 12.
Connection of start and stop terminals using conventional circuit with push but­tons, see fi gures 5.10 and 5.12.
A conventional circuit with auxiliary relay is also possible, see fi gure 5.11 and 5.12.
Warning!
Do not connect an external voltage to any of the control terminals 8, 9, 10, 11, 12 and 13. Failure to observe the above may damage the softstarter and the warranty may no longer be valid.
Start
Stop
812 3 4567 91011121314
PSE 18-600-70
L
Stop
Start
N
812 34567 91011121314
PSE 18-600-70
Figure 5.10: Terminals for start and stop, conventional circuit with push button
12 34567
891011
12 13
14
0,5 Nm - 4,3 lb.in
Figure 5.12: Tightening torques and wire area
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 37 Chapter 5
M3
Figure 5.11: Terminals for start and stop, conventional circuit with auxiliary relay
3,5 x 0,6 mm (0.138 x 0.024 in)
AWG 24 ... 12
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
2
2
2
2
Page 38
5.2.4.4 Reset event, terminal 10
The reset control terminal 10 is in circuit with terminals 11 or 12 used for remote reset of trip events. See fi gures 5.13 and 5.14.
Warning!
Do not connect an external voltage to any of the control terminals 8, 9, 10, 11, 12 and 13. Failure to observe the above may damage the softstarter and the warranty may no longer be valid.
Figure 5.13: Terminal for reset event
12 34567
891011
12 13
Reset
812 34567 91011121314
PSE 18-600-70
14
M3
0,5 Nm - 4,3 lb.in
3,5 x 0,6 mm (0.138 x 0.024 in)
AWG 24 ... 12
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
2
2
2
2
Figure 5.14: Tightening torques and wire area
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020138 Chapter 5
Page 39
5.2.4.5 Analog output, terminals 13 and 14
Analog output can be used for the connection of analog instruments.
If the analog output is used, the cables shall be connected to terminals 13 (+) and 14 (-). See fi gures 5.15 and 5.16.
Analog out signal can vary in the range 4 - 20 mA, corresponding to 0 - 120 per­cent of set value for parameter Ie. 100 percent corresponds to 17.3 mA.
Warning!
Do not connect an external voltage to any of the control terminals 8, 9, 10, 11, 12 and 13. Failure to observe the above may damage the softstarter and the warranty may no longer be valid.
812 34567 91011121314
PSE 18-600-70
Figure 5.15: Terminals for analog output
12 34567
891011
12 13
14
M3
0,5 Nm - 4,3 lb.in
Figure 5.16: Tightening torques and wire area
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 39 Chapter 5
3,5 x 0,6 mm (0.138 x 0.024 in)
AWG 24 ... 12
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
2
2
2
2
Page 40
5.2.4.6 Status output relays, terminals 3, 4, 5, 6, and 7
By connection to terminals 3, 4, 5, 6, and 7, RUN, TOR and EVENT are available for a contactor, a PLC or a status indicator, which can use these signals as an input.
The COM connection on terminal 3 is a shared neutral connection for terminals 4, 5, 6, and 7.
Run signal is given from terminal 4 during start ramp, running, and stop ramp if used. It can be used to control the line contactor.
Top of Ramp ( TOR) signal is given from terminal 5 when full voltage to the motor is applied.
The event relay is available as normal closed outlet on terminal 6 and normal open outlet on terminal 7. It is indicating a present fault or protection. The event signal can be used as input for a status indicating lamp or a LED.
For connection see fi gures 5.17 and 5.18.
Warning!
The same external voltage (24 V DC or 110-250 V AC) must be connected to the output relay terminals 3, 4, 5, 6 and 7. Failure to observe the above may damage the softstarter and the warranty may no longer be valid.
12 34567
AC
812 3 4567 91011121314
PSE 18-600-70
Figure 5.17: Terminals for status output signals
4 x 0,8 mm
M3
891011
12 13 14
0,5 Nm - 4,3 lb.in
(0.157 x 0.031 in)
AWG 24 ... 12
0,2 .. 4 mm
2x0,2 .. 1,5 mm
0,2 .. 4 mm
2x0,2 .. 1,5 mm
2
2
2
2
Figure 5.18: Tightening torques and wire area
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020140 Chapter 5
Page 41
Figure 5.19: External keypad
5.3 Connection of communication devices (optional)
5.3.1 External keypad
An external keypad for door mounting can be connected to the softstarter. A 3-meter cable including both the communication and the power supply to the keypad makes the connection. The cable shall be connected to the external key­pad connection at the bottom of the softstarter. See Figures 5.19 and 5.20.
The external keypad can also be used for transferring parameters from one softs­tarter to another. The parameters transferring through the external keypad should not be performed between two different versions of fi rmware. Note that IP66 cannot be achieved when the keypad is not mounted.
When the external keypad is used, both keypads will work in parallel, but the softstarter built-in keypad always has the highest priority if the keys on both units are pressed simultaneously.
5.3.1.1 Technical data for External Keypad
General data
Display LCD type
Status indicating LEDs Ready: Green
Run: Green Proction: Yellow Fault: Red
o
Ambient temperature Storage: -40
o
CF).
Operation: -25 +140 oF).
Standards IEC/EN 60947-4-2
UL508 CSA C22.2 No 14
Environmental ratings IP66
UL Type 1, 4X Indoor, 12
C to +70 oC (-40 oF to 158
o
C to +60 oC (-13 oF to
Figure 5.20: Connection of external keypad
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 41 Chapter 5
Page 42
5.3.1.2 Transfer of parameters
To transfer (copy) parameters from one PSE Softstarter to another, connect the External keypad to the chosen softstarter and follow the sequence below. For more information about navigating, see Chapter 6 in this manual. The Transfer Parameter menu is hidden and only possible to reach when the external keypad is connected to the softstarter. Start in Settings Level with cursor on Ie icon. Press Arrow Up to enter Transfer Parameter menu, and the text tP will be displayed on the LCD.
PSE 18-600-70
Figure 5.21: Transfer of parameters from softstarter to external keypad
PSE 18-600-70
Figure 5.22: Transfer of parameters from external keypad to softstarter
5.3.1.2.1 Transfer of parameters from softstarter to external keypad
Transfer of parameters from softstarter to external keypad is possible in all states,
1SFC132292F0001
except during ramping. During ramping it is not possible to enter the TP menu.
When you are in the Transfer Parameter menu confi rm and continue by pressing Select. A text toSS will now be present on the LCD display. Scroll to FrSS and confi rm selection by pressing Select key, and the text FrSS will now be fl ashing. Continue and transfer by pressing Select. If the transfer was successful, the text donE will be displayed on the LCD, otherwise a fault code will be displayed. Press Exit or select to return to Transfer Parameter menu. Press then exit for returning to a higher menu level.
5.3.1.2.2 Transfer of parameters from external keypad to softstarter
Transfer of parameters from external keypad to softstarter is possible only in standby state. During ramping, it is not possible to enter the TP menu. If transfer of parameters is done during TOR, a fault code will be displayed.
When you are in the Transfer Parameter menu confi rm and continue by pressing Select. A text toSS will now be present on the LCD display. Confi rm selection of toSS by pressing Select key and the text toSS will now be fl ashing. Continue by pressing select. If valid parameters will be accepted, a value for parameter Rated Motor Current Ie will be displayed, otherwise a fault code will be displayed. Scroll and select a setting for Ie, see chapter 7.5.1. Confi rm selection and save by pressing Select. If transfer is performed, the text donE will be displayed, otherwise
1SFC132293F0001
a fault code will be displayed. Press Exit or Select to return to Transfer Parameter menu. Press Exit for returning to a higher menu level.
A list showing all parameters which will be transferred is available in chapter 7.3 List of available parameters.
The parameters Rated Current of the motor and PSE will not be transferred.
Display Description
Transfer Parameter
Transfer of parameters from external keypad to softstarter
Transfer of parameters from softstarter to external keypad
Confi rmation of successful transfer
How to operate the External keypad, see Chapter 6 Human-Machine Interface (HMI).
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020142 Chapter 5
Page 43
5.4 Cyber Security Deployment Guideline
Cybersecurity has become of key importance for ABB customers and ABB alike. There are several reason for that, one of them is the modern control systems that can be distributed and interconnected, which means an increased attack surface compared to legacy and isolated systems. The PSE softstarter can be connected to different industial control networks either using the built-in Modbus RTU or by using additional fi eldbus plugs.
Important: The intention with the product is not to connect it to Internet.
To protect the reliability, integrity and availability of the softstarter against unauthorized access or attack the following countermeasures should be taken:
Restrict physical access to softstarter and industrial control network to authorized people only. The recommendation is to install the softstarter in a locked cabinet.
PSE softstarters should only be connected to private networks. It’s the customers responsibility to establish additional security measures if softstarter is to be connected to unknown or public networks. Example of such security measures are fi rewall, smart switches and VPN.
Backup/Restore - To minimize the downtime in case of malfunctioning softstarter for some reason, the recommendation is to backup the softstarter parameters using SoftstarterCare - Service Engineer Tool. The parameters can then be restored using SoftstarterCare. Instruction on how to backup and restore parameters are part of SoftstarterCare product documentation.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 43 Chapter 5
Page 44
This page is intentionally left blank.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020144 Chapter 5
Page 45
Chapter 6 Human-Machine Interface (HMI)
Overview .................................................................................................... 46
Application ............................................................................................. 46
Design ................................................................................................... 46
LED status indicators ......................................................................... 47
LCD display and keypad .................................................................... 48
Locking/unlocking the keypad ................................................................ 49
Reset of all settings ................................................................................ 49
Reset of tripping events ......................................................................... 49
Menu structure ....................................................................................... 50
Information Level ............................................................................... 50
Settings Level and settings menu ...................................................... 50
Navigating the menu ................................................................................... 52
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 45 Chapter 6
Page 46
Chapter 6 Human-Machine Interface
This chapter describes how the Human-Machine Interface ( keypad, LED status indicators and LCD display) works.
Ready Run
Exit
A
Protection
B
Select
Reset
C DE
Figure 6.1:
A
LED status indicators.
B
LCD display with backlight.
C
Exit key for cancelling parameter edits and exiting one menu level.
D
Select/Reset key for changing and storing parameter values, entering one menu level, and to reset tripping events.
E
Navigation keys for navigating the menu and changing parameter values. Flashing numbers or text shown in the display indicates that the menu/value can be changed or scrolled.
Fault
6.1 Overview
6.1.1 Application
The Human-Machine Interface is used for several purposes such as setting up the PSE Softstarter parameters, including protection functions and fi eldbus communi- cation. The HMI is also providing status information by LED status indicators and the LCD display.
The PSE Softstarter monitors and displays different values. When switching on the supply voltage the LCD will fi rst display the Information Level, which is showing motor current, input voltage on the line side, power factor, and voltage to the mo­tor.
The Information Level also displays information on whether the keypad is locked or unlocked.
1SFC132235F0001
6.1.2 Design
The appearance of the HMI is showed in fi gure 6.1.
The HMI consists of:
LED status indicators
LCD display with backlight
Selection and navigation keys
On start-up all LCD segments and LEDs will be briefl y illuminated.
The LCD backlight will automatically turn off after some time of inactivity. Turn it on by pressing any key.
When switching on the supply voltage the LCD will fi rst illuminate all available seg- ments, LEDs and the backlight. Thereafter the Information Level is displayed. See gure 7.1.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020146 Chapter 6
Page 47
6.1.2.1 LED status indicators
The LED status indicators work as in table 6.1:
Table 6.1
LED Color Description
Ready Green • Off: when control supply voltage Us is off or uncon-
nected.
• Flashing light when control supply voltage Us is On and operational voltage Ue is Off.
• Steady light when control supply voltage Us is On, and operational voltage Ue is On.
Run Green • Off when the motor not is running.
• Flashing light when softstarter is controlling opera-
tional voltage Ue during start or stop ramp.
• Steady light when full operational voltage Ue is on at Top of Ramp.
Protection Yellow • Off: when the softstarter has not tripped on any
protection
• Steady light on protection when reset is not pos­sible.
• Flashing light on protection when reset is possible.
Fault Red • Off: when the softstarter has not tripped on any
fault
• Steady light on fault when reset is not possible.
• Flashing light on fault when reset is possible.
When fault or protection LED is activated, the LCD display will show the actual fault or protection as an event code. See table 10.1.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 47 Chapter 6
Page 48
A
6.1.2.2 LCD display and keypad
The keypad is based on the same user concept as common on mobile phones.
Ready Run
Protection
Fault
See fi gure 6.1.
The LCD display contains three rows. The top row has 8 parameter icons. The middle row has a lock symbol, 4 digits and units. The bottom row has 4 param­eter icons.
On the middle row various information is presented.
A cursor A indicates which parameter value is possible to change at each posi­tion, as shown in fi gure 6.2.
Exit
Select
Reset
Figure 6.2: Cursor indicating parameter accessible for confi guration
The Exit key for cancelling parameter edits and for exiting one menu level.
The Select/Reset key normally has more than one function, such as selecting, changing, storing, and manual reset of tripping events, depending on present view.
The navigation keys are used for navigating in the menu and changing parameter values. Flashing numbers or text shown in the display indicates that the parameter value can be changed or scrolled.
If key is held down, scrolling will be faster. When selecting from a list, the scrolling is done in a closed loop.
You will fi nd a description of all settings in Chapter 7 Functions and confi guration and confi guration.
The menu structure of the keypad is illustrated in fi gure 6.7.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020148 Chapter 6
Page 49
Ready Run
Protection
Fault
6.1.3 Locking/ unlocking the keypad
1. Press the Exit key to exit to the Information Level.
2. The keypad is unlocked if the middle row is not indicating the lock icon to the right.
3. Press both Navigation keys 4 seconds to lock the keypad, and protect all parameter settings from unintentional change from the keypad. See fi gure 6.3.
4. The keypad is locked if the a padlock is present on the middle row.
5. Press both Navigation keys 2 seconds to unlock the keypad, and allow changes of the parameter settings.
Exit
Select
Reset
Figure 6.3: Locking/unlocking the keypad
Ready Run
Protection
Fault
6.1.4 Reset of all settings
How to reset all the changed parameters back to user default settings is de­scribed in chapter 7.7.1.
6.1.5 Reset of tripping events
The Select/Reset key can be used to reset tripping events via the keypad, see gure 6.4. For details about resetting of tripping events, see chapter 7.6.
Exit
Select
Reset
Figure 6.4: Reset of tripping events
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 49 Chapter 6
Page 50
6.1.6 Menu structure
The structure of the menu is described in fi gure 6.8. All different parameters and levels of the menu, and how they can be reached by scrolling, are also described.
Figure 6.5: Information Level
Exit
Select
Reset
Figure 6.6: Enter Settings Level pressing the Select key.
6.1.6.1 Information Level
By pressing a key the backlight will be switched on, and the Information Level will be displayed. The Information Level contains general operational information described in chapter 7.1.
Use navigation keys to present all selections. The selections are presented one by one on the middle row. See fi gure 6.5 and menu structure in fi gure 6.8.
6.1.6.2 Settings Level and settings menu
The Settings Level is reached from the Information Level by pressing the Select key. See fi gure 6.6. and menu structure in fi gure 6.8.
The settings menu is used to set up the PSE Softstarter with parameters for the current application.
Available settings are presented one by one on the top and bottom of the display. Use navigation keys to move the cursor to present all selections. In fi gure 6.7 the cursor is currently marking the parameter Rated Current Ie, which by pressing Select key a second time will be accessible for tuning.
Figure 6.7: Settings Level
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020150 Chapter 6
Page 51
Exit
Select
AInformation Level
%
Cos
V
Lock/Unlock Settings Level
Reset all parameter settings to user default values
PSE
Settings level
Ie (Rated current of motor)
Start Ramp time
Stop Ramp time
Initial/End Voltage
Current Limit
Torque Control during start ramp
Individual
1...30 s
OFF, 1...30 s
30...70 %
1.5...7 x I
OFF
On
e
Setting of time must be performed in Start Ramp time
OFF
Torque Control during stop ramp
On
U e
t
Kick Start
Set Initial Voltage
U e
t
Electronic Motor Overload Protection
Set Initial Voltage
OFF
30...100
OFF
Setting of time must be performed in Stop Ramp time
HAnd
10A/10/20/30
Auto
OFF
Underload Protection
0.2...1 x I
e
HAnd
Auto
OFF
Locked Rotor Protection
0.5...7 x I
e
HAnd
Auto
dPoF
Fbp
OFF 0...255
Int 0.5–60
dPon
9.6, 19.2, 38.4,
57.6, 76.8
8E1, 8o1, 8n1, 8n2
dPoF
dPon
FieldBus Control
Figure 6.8: Menu structure PSE Softstarter
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 51 Chapter 6
ON 0...255
dPoF
Fbp
dPon
Int 0.5–60
HAnd
trlP
Auto
LocC
9.6, 19.2, 38.4,
57.6, 76.8
8E1, 8o1, 8n1, 8n2
dPoF
dPon
HAnd
trlP
Auto
LocC
Page 52
Exit
Select
Reset
6.2 Navigating the menu
The menu is navigated by the keypad. The Navigation keys are used to scroll up or down. The Select key is used to select a setting and save. The Exit key is used to cancel without selecting or saving a setting, and to go to a higher level of the menu, as illustrated in fi gure 6.9.
1. Turn on the backlight by pressing any key.
1SFC132291F0001
Figure 6.9: Press Exit key to cancel and to go to a higher level of the menu.
2. On the Information level use the Navigation keys for scrolling the different operational information.
3. Press the Select key to Enter the Settings level. See
A
in fi gure 6.10. A cur-
sor is marking the accessible parameter, in this case Rated Current Ie.
4. Press Select key again to enable editing of the parameter Rated Current. See
B
in fi gure 6.10. A fl ashing value on the middle row indicates that the param-
eter is available for scrolling and for selection.
5. Increase or decrease the value by pressing Navigation key repeatedly. Hold-
C
ing the key down will speed up the scrolling. See
in fi gure 6.10.
6. When the rated current of the motor is reached, press the Select key again to
D
save. See
in fi gure 6.10.
7. It is possible to select and adjust the other parameters by following the same procedure.
8. At any point, press Exit to cancel a setting, and return to the information level.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020152 Chapter 6
Page 53
Exit
Select
Reset
B
Exit
Select
Reset
C
Exit
Select
Reset
D
Exit
Select
Reset
Exit
Select
Reset
A
Exit
Select
Reset
1SFC132268F0001
Figure 6.10: Navigating the menu
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 53 Chapter 6
Page 54
This page is intentionally left blank.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020154 Chapter 6
Page 55
Chapter 7 Functions and confi guration
Softstarter operational data ........................................................................ 56
Parameter settings ..................................................................................... 56
List of available parameters ........................................................................ 57
Basic settings principal ............................................................................... 59
Functions ................................................................................................... 60
Rated Current Ie of motor ...................................................................... 60
Start Ramp Time .................................................................................... 60
Stop Ramp Time .................................................................................... 61
Initial/End Voltage ................................................................................... 62
Current Limit .......................................................................................... 63
Torque Control during start ramp ............................................................ 64
Torque Control during stop ramp ............................................................ 65
Kick Start ............................................................................................... 66
Electronic Motor Overload Protection E.O.L. .......................................... 67
Underload Protection ............................................................................. 68
Locked Rotor Protection ........................................................................ 69
FieldBus Control (optional hardware required)......................................... 70
Fieldbus Address ............................................................................... 71
Download Parameter ......................................................................... 71
Fieldbus interface type ....................................................................... 72
Internal Modbus RTU timeout time .................................................... 72
Internal Modbus RTU baud rate ......................................................... 73
Internal Modbus RTU frame format .................................................... 73
Bypass open fault trip time ................................................................ 74
Delay before starting motor ............................................................... 74
Torque tune resistive losses ............................................................... 75
Torque controller gain ........................................................................ 75
Analog out scaling value .................................................................... 75
Fieldbus Operation When Fault .......................................................... 76
Type of Operation for Reset of Fieldbus Fault ..................................... 77
Reset of tripping events .............................................................................. 77
Special functions ........................................................................................ 78
Reset all parameter settings to user default values ................................. 78
PSE parameter ...................................................................................... 79
Representation of signals in time domain .................................................... 80
Application settings .................................................................................... 81
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 55 Chapter 7
Page 56
Chapter 7 Functions and confi guration
How to navigate the menu, see Chapter 6 Human-Machine Interface (HMI), espe­cially chapter 6.2 Navigating the menu.
7.1 Softstarter operational data
The information level is the top level of the user menu. Information about output current, line voltage, power factor, and voltage to the motor is displayed.
1
2
Exit
Select
Reset
4
1SFC132295F0001
Figure 7.1: Information Level, displayed information
On the information level the softstarter displays current values for:
1
Motor current (A)
2
Power factor / Cos
3
Voltage to the motor (%)
4
Input voltage on the line side (V)

The motor current is calculated as the maximum RMS value of the three phases. Using the motor current displayed on Information level as input for setting of Cur­rent Limit, may result in too low Current Limit. This may cause a longer starting time and unnecessary heating of the motor.
7.2 Parameter settings
Settings can be done in four different ways:
• Keypad
• Fieldbus communication (option)
• External keypad (option)
• SoftstarterCare
With the keypad or external keypad, settings can be done as individual parameter setting of all essential parameters.
When the fi eldbus communication (option) is enabled, most parameters can also be modifi ed from this interface.
User default parameter set is stored in the unit for a possible reset to default val­ues. See chapter 7.7.1 about resetting parameters to user default values.
Warning!
The motor may start unexpectedly if there is a start signal present, when do­ing any of the actions listed below.
Switching from one type of control to another ( fi eldbus control / hard- wire control).
Resetting events.
Using automatic event reset.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020156 Chapter 7
Page 57
7.3 List of available parameters
1
A list of the available parameters for PSE18...PSE370 is visible in table 7.1.
Table 7.1
Description Display
symbol
Rated Current of motor I
Start Ramp time
Stop Ramp time
Initial/End Voltage
Current limit
e
Setting range Default
value
Individual See tables in chapter 3.7.3 PSE Softstarter types. Setting range is 30-100 percent of I
OFF, 1...30 s OFF W W T
1.5...7 x
e
1...30 s 10 s W W T
30...70 % 40 % W W T
Individual W W
I
e
7.0 x I
Access
from
HMI
Fieldbus
WW T
e
Parameter
transfer with
External Keypad
Actual setting
Torque Control during start ramp OFF/On OFF W W T
Torque Control during stop ramp
Kick Start
Electronic Motor Overload Protection ( EOL)
Tripping Class (EOL)
Type of operation (EOL)
OFF/On On W W T
OFF, 30...100 % OFF W W T
OFF, 10 A, 10,
20, 30
HAnd/Auto
10 W W T
HAnd X X T
T
R = Readable
W = Writeable
T = Will be transferred ( uploaded/ downloaded)
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 57 Chapter 7
Page 58
6
1
1
2
3
4
5
6
7
Description Display
7
symbol
Setting range Default
value
Access
from
HMI
Parameter
Fieldbus
Underload Protection T
Actual setting
transfer with
External Keypad
Level
Type of operation
OFF, 0.2...1 x I
HAnd, Auto
Locked Rotor Protection
Level OFF, 0.5...7 x I Type of operation
Fieldbus Control
Fieldbus address
Fieldbus interface
Download Parameter
Fieldbus Operation When Fault
Type of Operation
HAnd, Auto
OFF, On
1SFC13235F0001
0...255
FbP, Int FbP W R T
dPon/dPoF
trIP/LocC
HAnd/Auto
Int only
OFF W W T
e
HAnd W W T
OFF W W T
e
HAnd W W T
OFF W R T
255
WR T
dPon W R T
LocC W R T
HAnd W R T
T
Timeout
Baudrate
Modbus frame format
R = Readable
W = Writeable
T = Will be transferred ( uploaded/downloaded)
1
HAnd = Manual reset of the protection or fault. Auto = Automatic reset of the protection or fault.
2
OFF = Fieldbus is not allowed to control the motor. On = Fieldbus is allowed to control the motor.
3
255 = Address of the FieldBusPlug will be used. dPon = Download of parameters from PLC enabled.
4
dPoF = Download of parameters from PLC blocked.
0.5...60 s 0.5 W R T
9.6, 19.2, 38.4,
19.2 W R T
57.6, 76.8 kBaud 8o1, 8E1, 8n2,
8E1 W R T
8n1
5
Accessible only if On is previously selected. trIP = Trip on fault. LocC = Local control on fault - hardwire control is possible Accessible only if trIP is previously selected. HAnd = Manual reset of the protection or fault. Auto = Automatic reset of the protection or fault. Databits(8), Parity (Even, odd, no), Stopbits (1, 2).
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020158 Chapter 7
Page 59
g
e
r
p
ge
7.4 Basic settings principal
The Settings level (menu) consists of predefi ned parameters for the selected application which should be used if an easy and quick set­up is required.
At any point, press Exit to cancel a setting and return to the informa­tion level.
1. Illuminate the display by pressing any of the keys.
2. From Information Level, enter Settings Level by pressing Select key. See fi gure 7.2.
Exit
Exit
Exit
Rated curr
ttin Setting Rated current
Exit
Select
Reset
Select
Reset
Select
Reset
Select
Reset
ramp
Stop ramp
Exit
d volta
Exit
Initial / end voltage
ent limit
Current limit
Exit
Select
Reset
Select
Reset
Select
Reset
3. Enter the setting for the Rated Current Ie by pressing Select key.
4. Set Ie using the navigation keys. Since the motor must be con­nected In Line, use the motor current on the rating plate.
5. Press Exit to Cancel, or Select to save.
6. Continue to the Start Ramp time setting, or press Exit key to return to the Information Level.
7. Go to the Start Ramp time setting using the lower navigation key.
8. Press Select and adjust the time using the navigation keys.
9. Press Select to save and continue, or press Exit to cancel and return to the Information Level.
10. Go to Stop Ramp time setting using the lower navigation key.
11. Press Select. Choose OFF or adjust the time using the naviga­tion keys.
12. Press Select to Save and continue to the next parameter, or Exit to Cancel and return to the Information level.
13. Go to the setting Initial/End Voltage using the lower navigation key.
14. Press Select, and adjust the value using navigation keys.
15. Press Exit to Cancel, or Select to save and continue.
16. Go to Current Limit by pressing the lower navigation key.
17. Press Select, and set the Current Limit factor On or OFF using the navigation keys.
18. Press Exit to Cancel or Select to save and continue.
Exit
Select
Reset
19. Press upper lower navigation key to continue to EOL class.
20. Press Select, and scroll with the navigation keys to choose the required Tripping Class, or OFF.
21. Press Exit to Cancel or Select to save and continue.
22. Press Select to set User or Auto.
t ram
Start ramp
Exit
Select
Reset
1SFC132250F0001
23. Scroll using the navigation keys.
24. Press Select to save and continue.
25. Press Exit to return to the information level.
Figure 7.2: Basic confi guration of frequently used parameters
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 59 Chapter 7
Page 60
7.5 Functions
This chapter describes all settings and functions possible in the PSE Softstarter, as well as the easiest way of fi nding them. Respective default values, setting ranges and parameter strings shown in the display are also stated.
7.5.1 Rated Current Ie of motor
This parameter allows for confi guring of the current that the softstarter will be exposed to. Since the motor must be connected In Line, set the rated motor cur­rent, which can be found on the motor rating plate.
Figure 7.3: Rated Current parameter displayed
Figure 7.4: Start Ramp Time parameter displayed
Display Default value Setting range Description
Individual (depending on size)
Individual (depending on size) See tables in chapter 3.7.3 PSE Softstarter types. Setting range is 30­100 percent of I
e
Rated motor current I
e
Warning!
Connecting Softstarters PSE18...PSE370 Inside Delta will cause damage to the equipment, and there is a risk of death or serious injury.
7.5.2 Start Ramp Time
The Start Ramp Time parameter allows for tuning of the time for the start ramp to reach full voltage (Top of Ramp, TOR).
U
rpm
Figure 7.5: The function of Start Ramp Time
This parameter is controlling both voltage controlled and torque controlled start ramps.
When a start signal is given the PSE Softstarter performs a start ramp by control­ling the output voltage to the motor so that the voltage is increased linearly from the initial voltage level to full voltage. Since the torque depends on both the volt­age and the current, the torque curve does not always follow the voltage curve. This has the effect that the torque curve will not increase linearly. If parameter Torque Control Start is set to OFF, a voltage ramp will be performed during the start ramp. The voltage and RPM of the motor will follow the graph in fi gure 7.5. If a torque curve with linear increase is preferred, choose Torque Control during start ramp described in chapter 7.5.6.
Display Default value Setting range Description
10 s 0–30 s Setting time for volt-
age controlled, and torque controlled, start ramps
The time set in Start Ramp Time is also the setting for the time in Torque Control Start, if this parameter is enabled.
1SFC132160F0001
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020160 Chapter 7
Page 61
Figure 7.6: Stop Ramp Time parameter displayed
U
7.5.3 Stop Ramp Time
The Stop Ramp Time parameter allows for tuning of the time for the stop ramp to reach the End Voltage from Top of Ramp ( TOR).
When a stop signal is given the PSE Softstarter performs a stop ramp by control­ling the output voltage to the motor so that the voltage is decreased linearly from full voltage to the end voltage level. Since the torque depends on both the voltage and the current, the torque curve does not always follow the voltage curve. This has the effect that the torque curve will not decrease linearly. If parameter Torque Control during stop is set to OFF, will a voltage ramp be performed during the stop ramp. The voltage and RPM of the motor will follow the graph in fi gure 7.7. If a torque curve with linear decrease is preferred, set Torque Control during stop to On. See chapter 7.5.7.
This parameter shall be set to OFF for applications with a big fl ywheel mass involved.
rpm
Figure 7.7: The function of Stop Ramp Time
Display Default value Setting range Description
OFF OFF, 1–30 s Setting time for voltage
controlled and torque controlled, stop ramps
The time set in Stop Ramp Time is also the setting for the time in Torque Control Stop, if this parameter is enabled.
1SFC132162F0001
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 61 Chapter 7
Page 62
7.5.4 Initial/End Voltage
This parameter makes it possible to set the initial voltage level where the start ramp begins. The value for end voltage where the stop ramp ends, will automati­cally be 10 percent lower than the initial voltage.
During start ramp will then the voltage increase from the initial voltage level, to full voltage.
During stop ramp will the voltage decrease from full voltage to the end voltage level and then cut the power to the motor. Figure 7.9.
Figure 7.8: Initial/End voltage parameter displayed
TOR
Figure 7.9: The function of Initial/End Voltage
If the initial voltage is set too low, it will cause longer starting time and un­necessary heating of the motor. The motor might not reach full speed ( TOR).
Display Default
value
40 % 30–70 % Initial and end voltage for start
Setting range initial voltage
Description
ramp and stop ramp
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020162 Chapter 7
Page 63
7.5.5 Current Limit
It is possible to limit the starting current by using this function. The limit can not be exceeded during start and stop ramp. When the Current Limit is reached, the output voltage stays stable until the current level falls below the limit, then the ramping continues.
The relation between Current Limit, the current I to the motor and the output volt­age is described in fi gure 7.13.
Figure 7.12: Current Limit parameter displayed
U
100%
30%
t1
I
5
t2
The starting current must be high enough to make it possible for the mo­tor to reach the rated speed. The lowest possible current depends on the performance of the motor and the characteristics of the load. If the Current Limit is set too low, it will cause longer starting time and unnecessary heat­ing of the motor.
Display Default
value
7 x I
e
Setting
Description
range
1.5...7 x IeLevel of Current Limit in relation to output voltage.
Current limmit
2
Figure 7.13: The relation between the Current Limit , the cur­rent I to the motor, and the output voltage U
1SFC132100F0001
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 63 Chapter 7
Page 64
7.5.6 Torque Control during start ramp
It is possible to use the torque control during the start by activating this parameter. Torque control results in a more linear accelerating of the speed in a majority of applications.
When using the torque control the output voltage to the motor is controlled so that the motor torque will follow a predefi ned optimal curve from the initial voltage level to full voltage during start.
This has the benefi t that the mechanical starting behavior of the equipment driven by the motor will be much softer compared to the use of voltage ramp. During the torque controlled start the motors voltage and RPM will follow the graph in fi gure
7.15.
Figure 7.14: Torque Control during start ramp parameter displayed
U
RPM
During start ramp, the output voltage to the motor is controlled so that the torque will follow a predefi ned optimal curve from the initial voltage level to full, voltage during start. This has the benefi t that the mechanical starting behavior of the equipment driven by the motor will be much softer compared to the use of voltage ramp. During the torque controlled start the voltage U and RPM of the motor will appear as the graphs in fi gure 7.15.
Display Default
value
OFF On/OFF Torque Control during start
Setting range
Description
The time for the Torque Control during start ramp is set in the parameter Start Ramp time.
Figure 7.15: The function of Torque Control during start
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020164 Chapter 7
1SFC132161F0001
Page 65
7.5.7 Torque Control during stop ramp
When activating this parameter (On) makes it possible to control the motor torque during stop. Using torque control will result in a more suitable decelerating of the speed mainly requested when stopping pumps.
When using torque control the output voltage to the motor is controlled so that the motor torque will follow a predefi ned optimal curve for best possible stop. This has the benefi t that the mechanical stopping behavior of the equipment driven by the motor will be much softer compared to using voltage ramp. This can be espe­cially useful in pump applications where a sudden stop can cause water hammer­ing and pressure surges. During the torque controlled stop the motors voltage and RPM will follow the graphs in fi gure 7.17.
Figure 7.16: Torque Control during stop ramp parameter displayed
U
RPM
Display Default
value
On On/OFF Torque Control during stop ramp
The time for the Torque Control during stop ramp is set in the parameter Stop Ramp time.
Setting range
Description
Figure 7.17: The function of Torque Control during stop ramp
1SFC132163F0001
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 65 Chapter 7
Page 66
7.5.8 Kick Start
This parameter makes it possible to tune the kick start voltage level which is ap­plied for a short time duration, before a normal start ramp is performed. Kick Start provides enough torque during start, but still ensuring a soft start.
It can be set on any of the predefi ned voltage levels. For each voltage level there is a fi xed time duration relation (t), which is increasing with the different kick voltage levels. This function can be useful for applications with high initial friction or having a need of extra power in the fi rst part of the start, as jammed pumps or conveyor belts. See table 7.2 and graph in fi gure 7.19.
Table 7.2 Kick Start settings
Figure 7.18: Kick Start parameter displayed
U
e
t
Kick start setting Kick start voltage
Ue (percent)
30 30 0.30
35 35 0.35
40 40 0.40
45 45 0.45
50 50 0.50
55 55 0.55
60 60 0.60
65 65 0.65
70 70 0.70
75 75 0.75
80 80 0.80
85 85 0.85
90 90 0.90
95 95 0.95
100 100 1.00
Kick start time
t (s)
Set Initial Voltage
Operational time
Normal ramp
Ramp with Kick Start
Figure 7.19: The function of Kick Start
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020166 Chapter 7
Note that the Current Limit function is not working during Kick Start.
Display Default
Setting range Description
value
U
e
t
Set Initial Voltage
OFF OFF, 30...100 % Level of Kick Start
Page 67
7.5.9 Electronic Motor Overload Protection E.O.L.
This parameter makes it possible to set the required class of motor overload pro­tection. Four different classes are available. See fi gure 7.21.
• Class 10A
• Class 10
• Class 20
• Class 30
There is an option for type of reset after tripping. Hand or automatic is available. Hand is default value for reset of Electronic Motor Overload Protection after trip­ping.
Reset of this protection is not possible before measuring a lower temperature, which must be reached by the motor.
Figure 7.20: Electronic Motor Overload Protection EOL parameter displayed
1000
100
A
10
B C
D
1
1
23456
Figure 7.21: Tripping curves for the Electronic Mo­tor Overload Protection (E.O.L.)
Display Default
value
10 OFF, 10A,
Setting range
10, 20, 30
Description
Tripping class for Electronic Motor Overload Protection (E.O.L)
HAnd HAnd/Auto Type of operation for reset of
Electronic Overload Protection
1
(E.O.L)
1. HAnd = Manual reset: When tripping will stop the motor, a manual reset is required before re start can be done.
Auto = Automatic reset: When tripping will stop the motor, an automatic reset is performed before the unit is ready for restart.
1SFC132102F0001
A Class 30 B Class 20 C Class 10 D Class 10A
Figure 7.22: Type of operation for reset of Electronic Motor Overload Protection fault parameter displayed
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 67 Chapter 7
Page 68
7.5.10 Underload Protection
When active the Underload Protection trip if the current ( Ie) will fall to a lower level than the set value for 30 seconds or more.
This protection could be used to avoid for example a pump running dry, detect a broken belt or similar.
There is an option for type of reset after tripping, hand or automatic. HAnd is default value for reset of Locked Rotor Protection after tripping.
Figure 7.23: Underload Protection param­eter displayed
Figure 7.24: Type of operation for reset of Un­derload Protection fault parameter displayed
Display Default
value
OFF OFF, 0.2...1
HAnd HAnd/Auto Type of operation for reset of
1. HAnd = Manual reset: When tripping will stop the motor, a manual reset is required before re start can be done.
Auto = Automatic reset: When tripping will stop the motor, an automatic reset is performed before the unit is ready for restart.
Setting range
x I
e
Description
Level of Underload Protection
Underload Protection
1
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020168 Chapter 7
Page 69
7.5.11 Locked Rotor Protection
This protection will when activated trip if the motor current exceeds the set level when the motor is running at full voltage. The Locked Rotor Protection parameter will be activated when the motor has been running at full voltage (Top of Ramp) for 30 seconds. The reaction time for tripping is 1 second.
Figure 7.25: Locked Rotor Protection param­eter displayed
Figure 7.26: Type of operation for reset of Locked Rotor Protection fault parameter displayed
Display Default
value
OFF OFF, 0.5 - 7
HAnd HAnd/Auto Type of operation for reset of
1. HAnd = Manual reset: When tripping will stop the motor, a manual reset is required before re start can be done.
Auto = Automatic reset: When tripping will stop the motor, an automatic reset is performed before the unit is ready for restart.
Setting range
x I
e
Description
Level of protection for locked rotor
Locked Rotor Protection
1
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 69 Chapter 7
Page 70
Figure 7.27 Fieldbus Control parameter displayed
7.5.12 FieldBus Control (optional hardware required)
This parameter is used for confi guration of the fi eldbus communication. Con- necting the PSE Softstarter to the FieldBusPlug automatically enables fi eldbus communication. To enable control of the softstarter using fi eldbus, this parameter must be set to On. If FieldBus Control is set to OFF, fi eldbus can only be used for monitoring softstarter data.
If this parameter is set to On, the softstarter might trip on fi eldbus fault if no fi eld- bus communication is available. If the intention is to run without fi eldbus control, this parameter should be set to OFF.
Warning!
The motor may start unexpectedly if there is a start signal present when do­ing any of the actions listed below.
Switching from one type of control to another (fi eldbus control / hard- wire control). Remember that when parameter Fieldbus Fault Reaction is set to LocC, this switch can happen automatically.
Resetting of events.
If using automatic event reset.
Fieldbus Control parameters and settings
Display Default
value
OFF OFF/On Control of the softstarter with
Setting range Description
eldbus.
255 0...255 Fieldbus Address 1
Fbp Fbp/Int Fieldbus interface type
0.5 0.5...60 Internal Modbus 5 timeout rate
19.2 9.6, 19.2, 38.4,
Internal Modbus 5 baud rate
57.6, 76.8
8E1 8E1, 8o1, 8n1,
Internal Modbus 5 frame format
8n2
dPon dPoF/dPon Possible to block parameter down-
load from PLC 2.
LocC LocC/trIP Operation When Fault
HAnd HAnd/Auto
4
Type of operation for reset of Field­bus Fault
3
2
1. 255 =Address of FieldBus Control will be used.
2. Accessible only if Fieldbus Control previously is set to On.
3. Accessible only if trIP is previously selected.
4. HAnd = Manual reset: When tripping will stop the motor, a manual reset is required before restart can be done. Auto = Automatic reset: When tripping will stop the motor, an automatic reset is performed before the unit is ready for restart.
5. Accessible only if Fieldbus interface type is previously set to Int.
More information about Fieldbus communication and optional accessories is avail­able in Chapter 8 Fieldbus communication.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020170 Chapter 7
Page 71
Figure 7.28: Fieldbus Address parameter displayed
7.5.12.1 Fieldbus Address
The parameter Fieldbus Address allows setting of address for the fi eldbus com- munication.
The setting range for the fi eldbus address is 0...255. If the address is set to 255, the address stored in internal memory of the fi eldbus plug will be used. See docu- mentation for the fi eldbus plug for more details on address setting.
It is possible to read and set this parameter via the keypad when Fieldbus Control is set to On or OFF.
Changing this parameter will automatically reset the fi eldbus interface and the new address will be active. If PLC was communicating with the old address, the PLC needs to be re-confi gured.
Figure 7.29: Download Parameter displayed
Display Default
value
255 0...255 Fieldbus Address
Setting range
Description
7.5.12.2 Download Parameter
This parameter allows for blocking parameter download from the fi eldbus. Note that download of parameters works differently for different fi eldbus protocols. See documentation for the protocol used.
It is possible to read and set this parameter via the keypad when Fieldbus Control is set to On or OFF.
Display Default
value
dPon dPoF/dPon Download Parameter enabled.
Setting range
Description
Download Parameter blocked.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 71 Chapter 7
Page 72
7.5.12.3 Fieldbus interface type
This parameter allows the confi guration of the Fieldbus interface type which can be either the fi eldbus plug or the internal Modbus RTU.
Figure 7.30: Fieldbus interface type parameter displayed
Figure 7.30: Internal Modbus RTU timeout time parameter displayed
Display Default
value
Fbp Fbp/Int Fieldbus interface type
Setting range
Description
7.5.12.4 Internal Modbus RTU timeout time
This parameter sets the max allowed time of no communication between the Modbus master and PSE before there will be a trip on fi eldbus fault. It works in such a way that in PSE, there is a counter that is always incrementing and every time the Modbus master writes a digital/analogue value or if the slave sends a digital/analogue value, the counter is reset. If the counter reaches the value cor­responding to the Modbus timeout time, this means there have been no commu­nication and there will be a trip on fi eldbus fault.
This parameter is only accessible if the fi eldbus interface type was previously set to internal Modbus RTU.
Display Default
value
0.5 0.5–60 Internal Modbus RTU timeout time
Setting range
Description
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020172 Chapter 7
Page 73
7.5.12.5 Internal Modbus RTU baud rate
This parameter is used to confi gure the baud rate (in kBaud) of the internal Mod- bus RTU.
This parameter is only accessible if the fi eldbus interface type was previously set to internal Modbus RTU.
Figure 7.30: Internal Modbus RTU baud rate parameter displayed
Figure 7.30: Internal Modbus RTU frame for­mat parameter displayed
Display Default
value
19.2 9.6, 19.2,
Setting range
38.4, 57.6,
76.8
Description
Internal Modbus RTU baud rate
7.5.12.6 Internal Modbus RTU frame format
This parameter is used to confi gure the frame format of the internal Modbus RTU. The number of data bits will always be eight but the parity and number of stop bits can be selected.
8E1 - 8 data bits, even parity, 1 stop bit 8o1 - 8 data bits, odd parity, 1 stop bit 8n1 - 8 data bits, no parity, 1 stop bit 8n2 - 8 data bits, no parity, 2 stop bits
This parameter is only accessible if the fi eldbus interface type was previously set to internal Modbus RTU.
Display Default
value
8E1 8E1, 8o1,
Setting range
8n1, 8n2
Description
Internal Modbus RTU frame format
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 73 Chapter 7
Page 74
7.5.12.7 Bypass open fault trip time
This parameter is used to set the trip time which is the time that the bypass open fault condition has to be true before a trip is generated. Bypass open occurs when the bypass relay/contactor is open when it should be closed.
This parameter can only be confi gured using the Softstarter Care PC tool.
Display Default
value
60 s 0–300 s Bypass open fault trip time
Setting range
Description
7.5.12.8 Delay before starting motor
Sometimes a line contactor is connected upstream or downstream of the softs­tarter to achive full disconnection.This parameter allows time for the line contactor to close before the softstarter starts detecting if it has correct 3 phase supply.
After the start command is given, the softstarter waits for the time set with this parameter before starting to detect if there is correct 3 phase supply. Some contactors may need extra time to close and then this parameter can be useful to avoid timing problemsthat can lead to unnecessary trips on for example phase loss fault.
This parameter can only be confi gured using the Softstarter Care PC tool.
Display Default
value
0 s 0–5 s Delay before starting motor
Setting range
Description
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020174 Chapter 7
Page 75
7.5.12.9 Torque tune resistive losses
This parameter sets the adjustment of the estimated resistive losses which is used in the torque ramp functions. It seldom needs to be changed but if a large speed drop occurs in the beginning of the torque stop ramp, increase this value.
This parameter can only be confi gured using the Softstarter Care PC tool.
Display Default
value
100 % 30–100 % Torque tune resistive losses
Setting range
Description
7.5.12.10 Torque controller gain
This parameter sets the gain of the proportional part of the PI controller which is used in the torque ramp functions. If a large speed drop occurs in the beginning of the torque stop ramp, normally the “Torque tune resistive losses” parameter should be increased, but increasing this value can also help in this case.
This parameter can only be confi gured using the Softstarter Care PC tool.
Display Default
value
0.24 0.01–10 Torque controller gain
Setting range
Description
7.5.12.11 Analog out scaling value
The PSE softstarter has an analog output (4-20 mA) to represent the value of the motor current in RMS. 4 mA corresponds to 0 A and this parameter sets what 20mA should correspond to. Default is that 20 mA corresponds to a motor cur­rent that is 1.2 x motor rated current (Ie).
This parameter can only be confi gured using the Softstarter Care PC tool.
Default value
1.2xI
e
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 75 Chapter 7
Setting range
0.7–2.0xI
Description
Analog out scaling
e
Page 76
7.5.12.12 Fieldbus Operation When Fault
This parameter is accessible only if Fieldbus Control is previously set to On.
In case of fi eldbus malfunction, for instance due to power loss or a broken cable, this parameter allows for different (operations in case of a fault) reactions to the fault.
Setting Fieldbus fault reaction to trIP will make the softstarter trip on a fi eldbus fault. Selecting trIP makes reset of the fault necessary, in case of a tripping event.
Figure 7.30: Fieldbus Operation When Fault parameter displayed
When LocC is selected, the control of the softstarter will automatically switch from eldbus control to local control. The switch to local control will make hard-wire control possible. When the Fieldbus starts working again the control is automati­cally switched back to the Fieldbus. There is a 10 second delay before controlling the motor is possible.
Display Default
value
LocC LocC,/trIP Operation When Fault
1. trIP = Trip on fi eldbus fault.
LocC = Automatically move to local control on fi eldbus fault.
Setting range
Description
1
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020176 Chapter 7
Page 77
7.5.12.13 Type of Operation for Reset of Fieldbus Fault
Select what operation shall be asserted if a fi eldbus communication fault occurs. Manual or automatic options are available. HAnd is the default value for reset of Fieldbus Fault:
If HAnd is selected - The motor will stop and manual reset is required.
If Auto is selected - The motor will stop and automatic reset is performed.
Figure 7.31: Type of operation for reset of Fieldbus fault parameter displayed
Ready Run
Protection
Fault
This parameter is accessible only if trIP is previously selected for the parameter eldbus Operation When Fault.
Display Default
value
HAnd HAnd/Auto Type of operation for reset of Field-
1. HAnd = Manual reset: When tripping will stop the motor, a manual reset is required before re start can be done.
Auto = Automatic reset: When tripping will stop the motor, an automatic reset is performed before the unit is ready for restart.
Setting range
Description
bus Fault.
1
7.6 Reset of tripping events
Exit
Select
Reset
Figure 7.32: Reset of tripping events
In case of tripping event the PSE Softstarter can be reset via hardwire, keypad, external keypad, or Fieldbus.
If the setting HAnd is chosen as an action in case of an tripping event for a pa­rameter with this option, manual resetting of the softstarter is required.
If the setting Auto is chosen as an action in case of an tripping event for a param­eter with this option, resetting of the softstarter will be performed automatically.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 77 Chapter 7
Page 78
Ready Run
Protection
Fault
7.7 Special functions
7.7.1 Reset all parameter settings to user default values
Start from Information Level and press in sequence the keys Exit and Select for a few seconds, as described in fi gure 7.29. The text string “rES” will be displayed on the LCD as in fi gure 7.34.
Press Select to enter Reset All Settings, and the text string “rES” on the LCD starts fl ashing.
Press Exit key to cancel, or press Select to reset all settings.
Exit
Select
Reset
Figure 7.33: Entering menu Reset all settings to user default values
After reset it is necessary to press Exit for returning to Information Level.
Warning!
The motor may start unexpectedly if there is a start signal present when do­ing any of the actions listed below.
Switching from one type of control to another ( fi eldbus control / hard- wire control)
Resetting all parameters
Resetting events
If using automatic event reset
Figure 7.34: Reset All Settings to user default values parameter displayed
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020178 Chapter 7
Page 79
Ready Run
Exit
Protection
Select
Reset
7.7.2 PSE parameter
Fault
This parameter contains information about the type of PSE Softstarter which is available. The PSE parameter must be confi gured after replacing the PCB. This parameter must not be changed if the PCB has not been replaced. Read chap­ter 3.3 Type designation to get information about how to fi nd out the size of the softstarter.
Start from Information Level and press in sequence the keys Exit, Select and Ar­row Up for a few seconds, see fi gure 7.31. The text string “Id” will be displayed on the LCD as in fi gure 7.36.
Press Select to enter parameter PSE, and the text string “Id” the LCD starts fl ash- ing.
Press Exit to return to Information level or Scroll to confi gure according to the softstarters size. Press Select to confi rm.
Figure 7.35: Entering PSE parameter
Figure 7.36: PSE parameter displayed
Confi gure parameter PSE only if the printed circuit board has been replaced.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 79 Chapter 7
Page 80
1 2 3
1 2 3 4
7.8 Representation of signals in time domain
Timing diagram for the basic functions of the softstarter, with a representation of a
set of signals in the time domain is found in table 7.3.
Table 7.3: Timing diagram
Control supply voltage
Operational voltage on the line side
Control circuit - Start input
Control circuit - Stop input
Operational voltage on the motor side
Signal output relay - Run signal
Signal output relay - TOR signal
12 3456 7
12 34567
12 34567
4 567
1
5 67
1412111098
13
1412111098
13
1412111098
13
1412111098
13
1412111098
13
Signal output relay
- Tripping event NC signal
Signal output relay
- Tripping event NO signal
Status signal - Ready LED
Status signal - Run LED
Status signal - Fault LED
12 3456 7
12 34567
1412111098
13
1412111098
13
1SFC132254F0001
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020180 Chapter 7
Page 81
7.9 Application settings
In table 7.4 the recommended parameter settings for different applications are described.
Table 7.4: Application settings
Recommended basic setting
Centrifugal fan 10 s OFF 40 % 5.0 x I
Axial fan 10 s OFF 40 % 5.0 x I
Centrifugal pump
High pressure pump
Compressor 5 s OFF 40 % 4.5 x I
Grinder 10 s OFF 40 % 5.0 x I
Mixer 10 s OFF 40 % 5.0 x I
Bow thruster 10 s OFF 40 % 4.5 x I
Hydraulic pump 10 s OFF 40 % 4.5 x I
Crusher 10 s OFF 40 % 5.0 x I
Conveyor belt 10 s OFF 50 % 5.0 x I
Escalator 10 s OFF 40 % 4.5 x I
Lift/Elevator 10 s OFF 40 % 4.5 x I
Cutter 10 s OFF 40 % 5.0 x I
Band saw 10 s OFF 40 % 5.0 x I
Circular saw 10 s OFF 40 % 5.0 x I
Please note that the parameter values above are to be used as a guide only. Variations in load conditions may require additional tuning.
10 s 10 s 40 % 5.0 x I
10 s 10 s 50 % 5.5 x I
e
e
e
e
e
e
e
e
e
e
e
e
e
e
e
e
OFF OFF
OFF OFF
OFF On
OFF On
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
For Heavy Duty applications the Initial/End Voltage might need to be increased.
as well as the Current Limit
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 81 Chapter 7
Page 82
This page is intentionally left blank.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020182 Chapter 7
Page 83
Chapter 8 Fieldbus communication
Overview .................................................................................................... 80
Required accessories ............................................................................. 80
Instructions ............................................................................................ 80
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 83 Chapter 8
Page 84
Chapter 8 Fieldbus communication
8.1 Overview
The PSE Softstarter has an interface on the front for connecting the ABB Field­BusPlug used for fi eldbus communication. Through this interface it is possible to control the softstarter, retreive status information, as well as upload and download of parameters.
The interface between the softstarter and the FieldBusPlug is independent of the fi eldbus protocol used. Independent of softstarter size or delivery date it is possible to connect any of the available Fieldbus protocols later on, since this is defi ned in the FieldBusPlug itself. The built-in Modbus RTU communication is sup- ported (without any need of a fi eldbus plug). However the Modbus RTU adaptor is needed.
The following Fieldbus protocols are available:
Internal Modbus RTU
DeviceNet with fi eldbus plug
• Profi bus DP with fi eldbus plug
Modbus RTU with fi eldbus plug
PSE 18-600-70 PSE 18-600-70
Figure 8.1: Principle of a fi eldbus network with PSE Softstarters connected
More information about the installation of fi eldbus communication is available in chapter 7.5.12 FieldBus Control (optional hardware required).
8.1.1 Required accessories
To connect the PSE Softstarter to a fi eldbus system, the following accessories are required:
ABB FieldBusPlug Accessory FBPA
ABB FieldBusPlug for present fi eldbus protocol (check that the cable length is suffi cient).
Modbus RTU adaptor is needed for internal Modbus communication.
Connectors for bus connection.
End plug (some protocols).
Software for PLC set-up.
8.1.2 Instructions
To do the set-up of input and output telegrams, parameter settings, instructions, etc. are available at:
www.abb.com/drives
www.new.abb.com/low-voltage/products/softstarters
:
Internal Modbus RTU 1SFC132367M0201
• DeviceNet with fi eldbus plug 1SFC132066M0201
• Profi bus DP with fi eldbus plug 1SFC132067M0201
Modbus RTU with fi eldbus plug 1SFC132068M0201
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020184 Chapter 8
Page 85
Chapter 9 Maintenance
Regular maintenance .................................................................................. 82
Service and repair ....................................................................................... 82
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 85 Chapter 9
Page 86
Chapter 9 Maintenance
This chapter describes the maintenance required for the PSE Softstarter. This product needs very little maintenance, but some components should be checked regularly.
Warning!
Do not open the softstarter or touch any live parts when the operational voltage and control supply voltage are connected. Due to the two phase control, a connected motor terminal always carries live hazardous voltage. Do not touch terminals when voltage is applied. Output terminals will have live voltage even when the device is OFF. This can cause death or serious injury.
9.1 Regular maintenance
Check that all mounting bolts/screws are fastened. Tighten if necessary.
Check that all connections of main, control- and supply circuits are fastened.
Tighten the terminal screws and bolts on the connection bars, if necessary.
Check that the cooling airways are free from dirt and dust. If required, use pressurized air to clean.
• Check external fi lters. Clean, if necessary.
Check that the fan is working and rotating freely The blades shall rotate with­out any resistance. This can be checked at voltage free state.
Check the Real Time Clock and adjust if necessary.
In case of a fault, or if a fault can not be reset, see Chapter 10. Refer to the timing diagram for the basic functions of the softstarter.
9.2 Service and repair
In case the PSE Softstarter has to be repaired, a spare parts list and necessary instructions are available at:
www.abb.com/drives
Service and repair should be performed by authorized personnel only. Note that unauthorized repair may affect the warranty.
Warning
In the event of a short circuit on the load side of a softstarter the device could be completely destroyed and possibly cause danger to personnel. By using a correctly rated short circuit protection device, i.e. a fuse or a circuit breaker, the damage will be limited to one of the following two categories, defi ned IEC 60947-4-2 and EN 60947-4-2:
Type 1: The softstarter might be damaged and some or all parts might need to be replaced. The case or enclosure must not be damaged or become live during the short circuit. Type 2: The device should be operable after the event of a short circuit.
www.new.abb.com/low-voltage/products/softstarters
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020186 Chapter 9
Page 87
Chapter 10 Troubleshooting
General ....................................................................................................... 84
Overview of indications ............................................................................... 84
Tripping events ........................................................................................... 85
Start up problems and faults ....................................................................... 86
General problems and faults ....................................................................... 87
Fault indications .......................................................................................... 89
Protection indications ................................................................................. 92
Failure indications ....................................................................................... 93
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 87 Chapter 10
Page 88
Chapter 10 Troubleshooting
10.1 General
This chapter is a guide that can be used in case problems should arise with the PSE Softstarter or the application.
The PSE Softstarter normally indicates a fault with LED Fault status indicator, and the LCD displays type of fault. When a protection is activated, it will be indicated with the LED protection status indicator, and the LCD displays what type of protection is active. More information about LEDs and LCD display is available in chapters 6.1.2.1 and 6.1.2.2.
Faults not displayed on the PSE Softstarter Human Machine Interface can also be found in this chapter.
10.2 Overview of indications
This table shows in which state the different indications for protections, faults, and failures may show up.
Table 10.1 Overview of indications for protections, faults and failures
Motor control states
Event code
Electronic Motor Overload Protection P1 XXXXXXX
Underload Protection P2
tions
Protec-
Locked Rotor Protection P3
Software faults SF20 XXXXXXXX
Shunt fault
By-pass open
Internal
SF3x
SF4x
2
2
Softstarter thermal overload SF50 XXXXXX
Phase loss
EF1x
2
Bad Network quality EF20 X X X X
Faults
Current lost
EF3x
2
Fieldbus fault, timeout EF40 XXXXXXX
External
Fieldbus fault, parity error EF41 XXXXXXX
Stand by
At start command
At start ramp
At completed
start ramp
TOR
4
X
4
X
At stop command
At stop ramp
XX X
XX
XX
1
1
XX
XXXXXX
At completed stop
ramp
Low supply voltage EF50 XXXXXXX
High current
External keypad failures
ures
Fail-
1
Displayed as Current lost
x = phase number, 4 indicates multiple or unknown phase
2
3
y = failure number 1-8
4
Activated after 30 s.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020188 Chapter 10
EF6x
Fy
2
3
XX XXX X
XXXXXXX
Page 89
10.3 Tripping events
Depending on PSE Softstarter confi guration, different events may be signalled on the LCD. All event codes are found in table 10.2: Event list.
Table 10.2: Event list
Event
Event description Cause
code
SF20 Software fault Fault in software
SF3x
SF4x
Shunt fault
1
By-pass open
1
By-pass relay/contactor does not open or thyristor short circuit
By-pass relay or by-pass contactor does not close or opens
SF50 Softstarter thermal overload Thyristors overheated
EF1x
1
Phase loss fault
Power loss on operational current on one or several phases
EF20 Bad network quality Excessive disturbances in the operational supply network
Current lost fault Operational current on one or several phases lost
1
EF3x
EF40 Fieldbus fault Fault on Fieldbus communication, timeout
EF41 Fieldbus fault Fault on Fieldbus communication, parity
EF50 Low supply voltage Voltage too low or briefl y interrupted in control supply network for softstarter
EF6x
1
High current fault
Operational current higher than 8 x I
e
P1 Motor overload protection Load on motor higher than motor rating and corresponding selected EOL
Class. Current limit parameter is set on a too low value.
P2 Underload protection Load on motor too low
P3 Locked rotor protection Load on motor too high for a short time
SF = Softstarter fault EF = External fault P = Protection
1
x = phase number, 4 indicates multiple or unknown phase
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 89 Chapter 10
Page 90
10.4 Start up problems and faults
Status Possible cause Solution
LED’s not lighting and LCD is blank.
Ready Run Protection
Fault
Green Ready LED steady lighting or fl ash- ing, and LCD faint.
Control supply voltage Us is not con­nected.
1SFC132297F0001
LCD display backlight auto shut off. Touch any key on the keypad.
Connect according to a circuit dia­gram. See Chapter 5 Connection and Chapter 11 Wiring diagrams.
Ready Run Protection
Fault
1SFC132298F0001
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020190 Chapter 10
Page 91
10.5 General problems and faults
Status Possible cause Solution
Motor humming/starts without given start signal.
By-pass relay closed, due to abnormal handling. (PSE18...PSE170 only).
Switch off operational voltage and control supply voltage. Switch on volt­age in correct succession.
1. Control supply voltage on terminals
2. Wait 4 seconds, and then switching
• If same fault remains, contact your ABB Sales Offi ce.
By-pass contactor/relay stuck in closed position.
Check and replace relay or contactor.
If same fault remains, contact your ABB Sales Offi ce.
Shorted thyristor. Check and replace thyristor. Contact
your ABB Sales Offi ce.
The motor connection is not correct. (Must be connected In Line).
Check and correct the wiring. Con­nect the control supply voltage according to a circuit diagram. See Chapter 5 and Chapter 11. Connecting Inside Delta not allowed.
1 and 2. See chapter 5.2.4.
on operational voltage on terminals L1, L2 and L3. See chapter 5.2.3.
PSE
1SFC132263F0001
Bad motor sound during start and opera­tion.
The motor connection is not correct. (Must be connected In Line).
Check and correct the wiring. Con­nect the control supply voltage according to a circuit diagram. See Chapter 5 and Chapter 11. Connecting Inside Delta not allowed.
PSE
1SFC132263F0001
Incorrect ramp time for start. Try different ramp times (some adjust-
ments can be necessary for best result). See chapter 7.5.2.
Incorrect Initial/End Voltage. Try different settings for the parameter
Initial /End Voltage. See chapter 7.5.4, or contact your ABB Sales Offi ce.
Incorrect current limit. Try different settings for the parameter
Current Limit. See chapter 7.5.5, or contact your ABB Sales Offi ce.
The motor is too small. (current is out of measuring range).
Check that the softstarter corre­sponds to the motor size.
Bad motor sound during stop. Incorrect ramp time for stop. Try different ramp times for stop (some
adjustments can be necessary for best result). See chapter 7.5.3.
Incorrect Initial/End Voltage. Try different settings for the parameter
Initial /End Voltage. See chapter 7.5.4, or contact your ABB Sales Offi ce.
Motor does not start when giving start command using hardwire inputs.
Start and stop command given at the same time.
Control wiring not correct. Check connection for start and stop.
Start and stop command given at the same time.
Check that start and stop command is not given at the same time.
See chapter 5.2.4.3.
Check that start and stop command is not given at the same time.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 91 Chapter 10
Page 92
Status Possible cause Solution
Displayed current in LCD is not stable. The motor is too small.
(current is out of measuring range).
Motor does not start with fi eldbus Softstarter has tripped on fault or protec-
tion.
Check that the softstarter corre­sponds to the motor size.
Perform a reset on any active event. See chapter 6.1.5 Reset of tripping events.
Softstarter is in Local Mode. Check that the Auto Mode bit of the
binary output telegram setting is 1.
Check that the Local Mode digital input on the FieldBusPlug accessory is set to Remote.
Fieldbus Operation When Fault parameter is set to LocC.
If the parameter Fieldbus Operation When Fault is set to LocC, there will be a 10 second delay before it is pos­sible to re-start after communication is reestablished.
Digital or binary signals incorrect. PLC confi guration incorrect. Check PLC confi guration.
Loading of parameters with fi eldbus does not work properly.
Fieldbus settings Verify that parameters are matching
between the PLC and the softstarter eldbus documentation for the fi eld- bus protocol used.
• Verify that fi eldbus Download Param- eter is set to dPon.
Ensure that block-parameters are enabled.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020192 Chapter 10
Page 93
10.6 Fault indications
Status Possible cause Solution
Software fault
Red Fault LED steady lighting or fl ashing, and LCD event code SF20. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Fault in software. Disconnect and reconnect the control
supply voltage (Us) and make a re­start. See chapter 5.2.4.
If same fault remains, contact your ABB Sales Offi ce.
Ready Run Protection
Fault
Shunt fault
Red Fault LED steady lighting, and LCD event code SF3x
1
. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
By-pass open
Red Fault LED steady lighting, and LCD event code SF4x 1. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
PSE parameter fault. Check parameter PSE and select cor-
rect setting corresponding to the type of PSE Softstarter. See chapter 7.7.2.
1SFC132300F0001
By-pass relays closed after transport, (PSE18...PSE170 only).
Switch off operational voltage and control supply voltage. Switch on volt­age in correct succession.
1. Control supply voltage on terminals 1 and 2. See chapter 5.2.4.
2. Wait 4 seconds, and then switching on operational voltage on terminals L1, L2 and L3. See chapter 5.2.3.
The by-pass contactor’s/relays are not opening.
Check and replace relay. Contact your ABB Sales Offi ce for replacement kit.
Thyristors short circuit. Check and replace thyristor. Contact
your ABB Sales Offi ce for replacement
1SFC132317F0001
kit.
Power loss on control supply circuit. Check control supply voltage
By-pass relays/contactor’s open or by­pass relays/contactor’s do not close.
Check and replace by-pass relay/con­tactor. Contact your ABB Sales Offi ce for replacement kit.
Ready Run Protection
Fault
Softstarter thermal overload
Red Fault LED steady lighting, and LCD event code SF50. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
SF = Softstarter fault EF = External fault P = Protection
1SFC132302F0001
Thyristors overheated. If the fault remains after reset, the heat sink temperature is too high.
1SFC132303F0001
Check that the fans are working in a proper way. See chapter 9.1.
Check that the cooling airways are free from dirt and dust. See chapter
9.1.
Check that the ambient temperature is not too high. Derating is required above 40oC (104 oF). See chapter 3.6.
Check that the mounting angle is not more than 30 o. See chapter 4.2.4.
Check that PSE Softstarter not is too small for the number of starts and stops performed each hour.
1
x = phase number, 4 indicates multiple or unknown phase
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 93 Chapter 10
Page 94
Status Possible cause Solution
Phase loss fault
Red Fault LED steady lighting, and LCD
Fuse blown. Check and replace fuses in all three
phases. event code EF1x 1. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
Power loss on operational current on one or several phases.
The main contactor or circuit breaker is open.
Check and correct supplying opera­tional network.
Check and close contactor/breaker or any external switching device.
Main contactor opens too quickly at stop. Control main contactor with Run
signal relay on terminal 4. See chapter
5.2.4.6.
Add a time relay before contactor
1SFC132318F0001
opening.
If Stop Ramp not is needed, set Stop Ramp Time to 0.
Bad network quality
Red Fault LED steady lighting, and LCD
Excessive disturbances in the operational supplying network.
Check and correct supplying opera­tional network.
event code EF20. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
Current lost fault
Red Fault LED steady lighting, and LCD
1
event code EF3x
. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
Short power loss on all three phases in the operational network.
1SFC132311F0001
Operational current too low or lost on one
Check and correct supplying opera­tional network.
Check and correct supplying network
or several phases.
Phase loss on line side or motor side. Check and correct supplying network
See Phase loss EF14.
Thyristors not able to conduct Check and replace PCB/thyristor.
Contact your ABB Sales Offi ce for replacement kit.
1SFC132310F0001
The motor is too small. (current is out of measuring range).
Check that the softstarter corresponds to the motor size.
SF = Softstarter fault EF = External fault P = Protection
1
x = phase number, 4 indicates multiple or unknown phase
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020194 Chapter 10
Page 95
Status Possible cause Solution
Fieldbus fault
Red Fault LED steady lighting, and LCD event code EF40. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
Fieldbus fault
Red Fault LED steady lighting, and LCD event code EF41. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
Fault on fi eldbus connection or Field- BusPlug Accessory.
Check that the correct type of FieldBusPlug accessory is used. See Chapter 8 or contact your ABB Sales Offi ce.
Check that the connection of the FieldBusPlug is correct. See chapter
3.2.
Check the connection of the fi eldbus accessory.
Perform a reset on any active event. See chapter 6.1.5 Reset of tripping events.
Fieldbus communication is not working. Check that the correct type of
1SFC132313F0001
FieldBusPlug accessory is used. See Chapter 8 or contact your ABB Sales Offi ce.
Check that the connection of the FieldBusPlug is correct. See chapter
3.2.
Check the connection of the fi eldbus accessory.
• Check PLC confi guration.
Possible Fieldbus fault.
PLC is not running. Put PLC in run mode.
Check PLC confi guration.
Fieldbus Control is enabled on a non-fi eld- bus application.
• Set Fieldbus Control parameter to OFF.
Wrong parity confi guration Note that this fault is only related to the
built-in Modbus RTU communication
Check the Modbus frame format parameter
Check the parity confi guration in the Modbus master
1SFC132313F0001
Low supply voltage
Red Fault LED steady lighting, and LCD event code EF50. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
The control supply voltage is too low on terminals 1 and 2.
Short power loss on the control supply network.
1SFC132314F0001
SF = Softstarter fault EF = External fault P = Protection
1
x = phase number, 4 indicates multiple or unknown phase
Check and correct control supply voltage.
Check control supply network for short interruptions.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 95 Chapter 10
Page 96
High current fault
Operational current higher than 8 x Ie. Check if the motor is locked or running Red Fault LED steady lighting, and LCD event code EF6x
1
. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
1SFC132315F0001
SF = Softstarter fault EF = External fault P = Protection
1
x = phase number, 4 indicates multiple or unknown phase
stiff.
Check the bearings in the motor and connected equipment.
Check if the load on the motor is too heavy.
Check isolation on the motor wind­ings.
Replace the motor.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020196 Chapter 10
Page 97
10.7 Protection indications
Status Possible cause Solution
Motor Overload Protection ( EOL)
Red Fault LED steady lighting, and LCD event code P1. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections. Remark that time delay for reset can be long depending on temperature.
Ready Run Protection
Fault
Underload Protection
Red Fault LED steady lighting, and LCD event code P2. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
Load on motor higher than motor rating and corresponding selected EOL Class.
Too many starts and stops during a short time.
1SFC132320F0001
The motor has been exposed to an over­load condition because the current over a certain time is too high. (The load on the motor shaft is too high).
The motor current is below set level and time.
At start
Check and correct the reason for the overload.
• Increase Initial/End Voltage.
Check the motor rating plate for Ie.
• Increase Current Limit.
• Make Start Ramp Time shorter.
At start
Chose a motor with more power, and a softstarter rated for higher current.
Check and correct the reason for the overload.
Check that the ramp time for start not is too long.
Check that correct EOL Class is used.
Continuous run
Check the rating of the plate for Ie.
Check operational voltage.
Chose a motor with more power, and a softstarter rated for higher current.
Check and correct the reason for the overload.
Check that correct EOL Class is used.
Check and correct the reason for the underload.
Check that the setting Ie are accord­ing to the operation conditions. See chapter 7.5.1.
Check that the Underload Protection parameter is set according to opera­tional conditions. Se chapter 7.5.10.
Locked Rotor Protection
Red Fault LED steady lighting, and LCD event code P3. See chapter 6.1.2.1 about LED status indi­cators activation for faults and protections.
Ready Run Protection
Fault
1SFC132316F0001
The motor is running stiff for some reason. A damaged bearing or a stuck load could be possible causes.
Decrease in operational voltage can give a higher operational current.
1SFC132322F0001
Check the bearings of the motor and load.
• Check voltage.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 97 Chapter 10
Page 98
Status Possible cause Solution
Transfer of parameters failed
Only showing on external keypad. Can occur for transfer both from the PSE and to the PSE. Same failure for F1, F2, F3, F4 and F6.
10.8 Failure indications
Fault in software. Try again.
If the same failure remains, contact your local ABB Sales Offi ce.
Ready Run Protection
Fault
Transfer of parameters failed
Only showing on external keypad. Can occur for transfer to the PSE.
Ready Run Protection
Fault
External keypad fault
Showing on both HMI and external key­pad. Can occur for transfer parameters between two different fi rmware.
No parameters stored in the PSEEK. Load the parameters that you want to
transfer from selected PSE.
If the same failure remains, contact your local ABB Sales Offi ce.
Transfer parameters between two different versions of fi rmware.
Upgrade all softstarters to latest rmware version that are availably on ABB Library.
Ready Run Protection
Fault
All parameters was not transferred
Only showing on external keypad. Can occur for transfer both from the PSE and to the PSE.
Ready Run Protection
Fault
Fault in software. Try again.
If the same failure remains, contact your local ABB Sales Offi ce.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M020198 Chapter 10
Page 99
Transfer of parameters failed
Only showing on external keypad. Can occur for transfer to the PSE.
Not possible to transfer parameters to PSE when it is in TOR.
Return the PSE to idle state and try again
If the same failure remains, contact your local ABB Sales Offi ce.
Ready Run Protection
Fault
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 99 Chapter 10
Page 100
This page is intentionally left blank.
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201100 Chapter 10
Loading...