ABB PBA2 Instruction For Installation And Maintenance

Bushing Potential Device,Type PBA2
PTAE-APD903 IZUA 7711-210
Instructions for Installation and Maintenance
All possible contingencies which may arise during installation, operation, or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding his particular installation, operation or maintenance of his equipment, the local ABB Inc representative should be contacted.
2
ABB
Description
Application
The condenser bushing potential device is a means for securing small amounts of 60 hertz power at 115 volts and 66.4 volts from high voltage lines through the medium of the condenser bushing. For 115kV and higher voltages this device is the most economical means of securing such small amounts of power.
These devices provide a 115 and 66.4 volt output which is substantially proportional to the system line-to-ground voltage and in phase with it. This output is commonly used to energize synchroscopes, voltmeters, and voltage responsive relays. The device accuracy is not adequate for use with metering instruments where revenue is involved.
Construction
The potential device is built in an outdoor, weatherproof, steel housing arranged for mounting on the side of an oil circuit breaker or transformer in the vicinity of one of the condenser bushings. A special cable assembly of
weatherproof construction, and with a grounded external shield, connects the potential device to one of the metallic layers of the condenser bushing.
The device network (see Fig. 6) consists of a main transformer having adjustable reactance, an auxiliary transformer of adjustable ratio, a tapped capacitor to correct burden power factor, a protective spark gap, and a dead-front adjusting panel.
A grounding switch permits de-energizing the device, and a heater (to be energized from an external voltage source) prevents internal sweating of the housing.
Standardized mounting dimensions permit the interchangeability with most standard ABB or Westinghouse units sold since the middle of 1934. The standard device is electrically usable for most bushings having capacitance taps per IEEE C57.19.01-2000 Type A: Normally Grounded having the tap on the second metallic layer above ground potential includes substan tured since the middle of 1935 and having a voltage rating of 115kV or higher. Cable lengths (see Fig. 2) are also standard for circuit breakers, but special lengths are general for trans­formers. End fittings of cables are common for all.
tially all Westinghouse bushings manufac-
. This
Figure 1: Outline and Mounting
ABB
3
PBA CABLE DRAW NUT
"
Figure 2: Cable Lead-in Assembly
Rating
Each device has output voltages of 115 and 66.4 for the main burden (terminals S1, S2, S3) and an auxiliary winding provides the same voltages (terminals Z1, Z2, Z3) for use when broken-delta connections are required.
The burden ratings of the standard devices, when used with standard bushings in each case, are shown in Table 1.
Table 1
System System Max. Watts* Device Voltage Voltage Total Style**
Line-To-Line Line-To-Ground Burden ***
115 kV 66.4 kV 25 3D69822G01 138 kV 79.7 kV 35 3D69822G01 161 kV 93.0 kV 45 3D69822G02
230 kV 133 kV 80 .....................
287 kV 166 kV 100 .....................
330-345 kV 191-199 kV 150 .....................
* In no case shall the burden on the auxiliary winding (Z1, Z2, Z3) exceed 75 watts.
** Styles do not include lead-in cable, see Table 2. *** These designs are for ABB or Westinghouse bushings. Bushings by other vendors require special PBA configuration.
PBA CONNECTION
HOUSING
"
Since the device rating is a function both of the system voltage and of the particular bushing capacitance values, it is obvious that special bushings, or standard bushings used at non-standard voltages may have burden ratings which are at variance with the foregoing tabulation. In this connection it is to be noted that the auxiliary capacitance built into each device varies according to the device ap
plication. See page 10 “Calculation of Approximate
Adjustment.”
Performance
The Type PBA2 Potential Device is a Class”“A” device as defined by AIEE Standard # 31 and NEMA Standards SG4-1968. The regulation characteristics with respect to varying line voltage and varying burden meet the limits established by these standards.
Since this type of device is basically a series-tuned device it is sensitive to the system frequency. For small frequency deviations there is practically no ratio effect, but there is a slight phase shift. For example, a deviation of one hertz in 60 will produce a phase shift up to 2 degrees, depending on the particular bushing device and system voltage. The greatest phase shift is experienced when the potential device is loaded to its rating, and when the normal system voltage is low relative to the bushing rating.
Table 2. Cables with Type A Connectors
Cable Length* Style#
96" 3D69768G01 120" 3D69768G02 144" 3D69768G03 168" 3D69768G04 192" 3D69768G05 216" 3D69768G06 240" 3D69768G07
*Cable lengths other than those listed can be ordered if necessary
4
When high-speed directional relays are energized from this device, it is recommended that the basic burden be power factor corrected to 100%, or slightly leading, and that the device be loaded to its rating in watts (as shown on the nameplate), by adding parallel resistance if necessary. The purpose of this is to reduce to a minimum the possibility of incorrect relay operation, which might result from device output transients following a system short circuit extremely close to a device.
ABB
Erection
The potential device may be lifted from its crate or pallet and handled by means of the two lifting lugs on the side of its roof to mount it on the circuit breaker or the transformer.
Depending on the particular breaker or transformer bracket provided for the lower edge of the potential device, proceed as follows (see Fig. 1):*
a. If the lower device support on the transformer or breaker
carries two tapped holes then bolt the J bracket, which is shipped loose with the potential device, to this pad using the two countersunk head bolts provided. There is a notch in the center of the rear lower flange of the device, which will fit into the hook provided by this J bracket. Rest the weight of the potential device into this bracket and place the two bolts into the two slots of the upper device support, and secure these in place.
b. If the transformer or breaker carries a lower device
support consisting of a bent steel bar, and with two notches cut into its edge instead of two tapped holes, then the J bracket may be scrapped and the potential device rested directly on the notched bar. The upper end is bolted into place with the two bolts.
c. In either case, the paint shall be scraped away from the
upper pad where it is bolted against the corresponding pad on the breaker or transformer in order to assure a good ground connection at this point.
d. The primary connection is made by installing the high
voltage cable assembly of Fig. 2. This is done with the bushing grounded. The cable is installed by t
he mounting flange cover from the side of the po device housing and removing the cover from the tap receptacle on the bushing flange. The tap receptacle on the bushings of recent manufacture may be found filled with approximately one pint of transformer oil, which will drain out when the cover is removed. Discharge the bushing tap layer by touching the socket contact with a grounded wire.
removing
tential
1. If the bushing is ABB O plus C or other type that permits addition of transformer oil to the test tap with the tap cover in place, you may choose to fill the PBA connector housing with transformer oil. In this case, do not add the petrolatum to the PBA connector housing.
2. Otherwise, pack the inside of the PBA connector hous
ing with the petrolatum provided, taking care to leave no air pockets.
e. Push the bushing connector into the tap, then thread the
PBA connector housing into the threaded portion of the bushings tap. Tighten by hand, approximately 1/4 turn after the gasket is in contact with both the tap and the connector housing. Lubricate the gasket with a thin application of transformer oil or petrolatum whichever is being used.
f. Turn the PBA cable draw nut clockwise, until tight.
g. If you have chosen to fill the PBA connector housing with
transformer oil, do so now. Please see the bushing's application literature for filling instructions and oil expansions space requirements.
h. Place the porcelain end of the cable assembly into the
hole in the side of the potential device housing. Bolt the two flanges in place using the hardware provided. The composition flange at the cable end is also the gasket. Draw up the bolts progressively around the cable so that there is not excessive pressure at any point. Tighten up the bolts only sufficient to create a slight bulge all around the edge of the composition.
i. Connect the internal jumper connection in line with
diagram of Fig. 6 by opening the partially dropping the front panel assem
It is suggested that when a device is installed and con
PBA'S door and
bly.
nected that its voltage adjustment be set to a minimum (and the ground switch opened) until such time as the normal bur­den is connected and the device adjusted.
* If the device is to be mounted on equipment that is not manufactured by ABB, the mounting arrangement may be slightly different than described here.
ABB
5
Loading...
+ 11 hidden pages