Resistance and power loss per pole
Type Setting range Resistance per pole Power loss per pole
lower value
A
MS132-0.16 0.10 0.16 66.00 0.7 1.7
MS132-0.25 0.16 0.25 25.50 0.7 1.7
MS132-0.4 0.25 0.40 10.38 0.7 1.7
MS132-0.63 0.40 0.63 4.36 0.7 1.7
MS132-1.0 0.63 1.00 1.605 0.7 1.7
MS132-1.6 1.00 1.60 0.648 0.7 1.7
MS132-2.5 1.60 2.50 0.272 0.7 1.7
MS132-4.0 2.50 4.00 0.106 0.7 1.7
MS132-6.3 4.00 6.30 0.046 0.7 1.7
MS132-10 6.30 10.0 0.024 0.9 2.4
MS132-12 8.00 12.0 0.016 1.0 2.3
MS132-16 10.0 16.0 0.011 1.1 2.8
MS132-20 16.0 20.0 0.0057 1.5 2.3
MS132-25 20.0 25.0 0.0045 1.8 2.8
MS132-32 25.0 32.0 0.0030 1.9 3.1
upper value
A
Ω
at lower value
W
at upper value
W
2CDC131021D0201 - 3

Technical data IEC/EN
Data at TA = 40 °C and at rated values, if nothing else indicated
Main circuit
1L1-3L2-5L3
2T1-4T2-6T3
Rated operational voltage U
e
Setting range - thermal overload protection see table “Order data” on page 1
Rated operational current I
Rated operational current DC-5 I
e
e
3 conducting paths in series up to 250 V
Rated instantaneous short-circuit current setting I
Rated service short-circuit breaking capacity I
Rated ultimate short-circuit breaking capacity I
Rated service short-circuit breaking capacity d.c. I
i
cs
cu
cs
3 conducting paths in series up to 250 V
Trip class see table “Order data” on page 1
Rated frequency d.c., 50/60 Hz
Number of poles 3
Resistance per pole see table “Resistance and power loss per pole”
Power loss per pole
690 V a.c.
250 V d.c.
see table below
see “Rated operational current Ie”
see table below
see table “Short-circuit breaking capacity and
back-up fuses” on page 6
10 kA
on page 3
Isolation data
Rated impulse withstand voltage U
Rated insulation voltage U
i
imp
6 kV
690 V
Pollution degree 3
Electrical connection
MS132 ≤ 10 A MS132-12, -16 MS132-20, -25, -32
Connecting capacity solid 1/2 x 1 ... 4 mm² 1/2 x 2.5 ... 6 mm²
stranded 1/2 x 1 ... 4 mm² 1/2 x 2.5 ... 6 mm²
flexible with ferrule 1/2 x 0.75 ... 2.5 mm² 1/2 x 1 ... 6 mm²
flexible with ferrule insulated 1/2 x 0.75 ... 2.5 mm² 1/2 x 1 ... 6 mm²
flexible without ferrule 1/2 x 0.75 ... 2.5 mm² 1/2 x 2.5 ... 6 mm²
Stripping length 9 mm 10 mm 10 mm
Tightening torque 0.8 ... 1.2 Nm 1.5 Nm 2 Nm
Connection screw M3.5
(Pozidrive 2)
M4
(Pozidrive 2)
M4
(Pozidrive 2)
Type Rated instantaneous
short-circuit current setting l
A A
MS132-0.16
1.56 0.16
MS132-0.25 2.44 0.25
MS132-0.4
3.90 0.40
MS132-0.63 6.14 0.63
MS132-1.0 11.50 1.00
MS132-1.6 18.40 1.60
MS132-2.5 28.75 2.50
MS132-4.0 50.00 4.00
MS132-6.3 78.75 6.30
MS132-10 150 10.0
MS132-12 180 12.0
MS132-16 240 16.0
MS132-20 300 20.0
MS132-25 375 25.0
MS132-32 480 32.0
Rated operational current l
i
e
4 - 2CDC131021D0201

General data
Mechanical durability 10
Electrical durability 5 x 10
5
4
Duty time 100 %
Dimensions (W x H x D) see drawing “Dimensions” on page 3
Weight see table “Order data” on page 1
Mounting DIN-rail (EN 60715)
Mounting position position 1-6 (optional for single mounting)
Group Mounting on request
Minimum distance to other units same type horizontal 0 mm
vertical 150 mm
Minimum distance to electrical conductive board horizontal, up to 400 V 0 mm
horizontal, up to 690 V > 1.5 mm
vertical 75 mm
Degree of protection enclosure / terminals IP20
Utilization category A
Altitude up to 2000 m
Maximum operating frequency 170 cycles/h
Electromagnetic compatibility
Electromagnetic compatibility not applicable
Environmental data
Ambient air temperature
Operation
open - compensated without derating
open
-25 ... +60 °C
-25 ... +70 °C
Storage -50 ... +80 °C
Temperature compensation continuous
Vibration (sinusoidal) acc. to IEC/EN 60068-2-6 (Fc) 5g / 3 ... 150 Hz
Shock (half-sine) acc. to IEC/EN 60068-2-27 (Ea) 25g / 11 ms
Standards / directives
Product standard IEC/EN 60947–2
IEC/EN 60947-4-1
IEC/EN 60947-1
UL 508, CSA 22.2 No. 14
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2002/95/EC
2CDC131021D0201 - 5

Short-circuit breaking capacity and back-up fuses
lCSRated service short-circuit breaking capacity
lCURated ultimate short-circuit breaking capacity
o
No back-up fuse required, because short-circuit proof up to 100 kA
Type 230 V AC 400 V AC 440 V AC 500 V AC 690 V AC
ICS
kA
MS132-0.16
MS132-0.25
MS132-0.4
MS132-0.63
MS132-1.0
MS132-1.6
MS132-2.5
MS132-4.0
MS132-6.3
MS132-10
MS132-12
MS132-16
MS132-20
MS132-25
MS132-32
I
kA
gG
CU
A
I
kA
I
CS
kA
gG
CU
A
I
kA
I
CS
kA
gG
CU
A
I
kA
I
CS
kA
gG
CU
A
I
kA
I
CS
CU
kA
100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
100 100 ° 100 100 ° 20 20
100 100 ° 100 100 ° 20 20
100 100 ° 100 100 ° 20 20
100 100 ° 100 100 ° 20 20
100 100 ° 100 100 ° 20 20
100 100 ° 100 100 ° 20 20
50 50 100 50 50 100 20 20
25 50 125 25 50 125 20 20
on request
on request
on request
on request
on request
on request
on request
on request
20 20
20 20
20 20
20 20
20 20
20 20
10 10
10 10
on request
on request
on request
on request
on request
on request
on request
on request
3 3
3 3
3 3
3 3
3 3
3 3
3 3
3 3
gG
A
on request
on request
on request
on request
on request
on request
on request
on request
6 - 2CDC131021D0201

Technical data UL/CSA
Main circuit
Maximum operational voltage 600 V
Manual Motor Controller ratings
Motor ratings Horse power see table below
Full load amps (FLA) see table below
Locked rotor amps (LRA) see table below
see table “UL 508 — Manual Motor Controller” on page 8
Electrical connection
Connecting capacity stranded 1/2 x AWG 16 ... 12 1/2 x AWG 12 ... 8
flexible without ferrule 1/2 x AWG 16 ... 12 1/2 x AWG 12 ... 8
Stripping length 9 mm 10 mm 10 mm
Tightening torque 10 ... 12 lb-in 14 lb-in 18 lb-In
Connection screw M3.5
MS132 ≤ 10 A MS132-12, -16 MS132-20, -25, -32
(Pozidrive 2)
M4
(Pozidrive 2)
M4
(Pozidrive 2)
Motor rating, single phase
hp Horse power
FLA Full load amps
LRA Locked rotor amps
Type 220 ... 240 V AC 440 ... 480 V AC
hp FLA LRA hp FLA LRA
MS132-0.16 - 0.16 0.96 - 0.16 0.96
MS132-0.25 - 0.25 1.5 - 0.25 1.5
MS132-0.4 - 0.4 2.4 - 0.4 2.4
MS132-0.63 - 0.63 3.78 - 0.63 3.78
MS132-1.0 - 1 6 - 1 6
MS132-1.6 1/10 1.6 9.6 - 1.6 9.6
MS132-2.5 1/6 2.5 15 1/2 2.5 15
MS132-4.0 1/3 4 24 1/2 4 24
MS132-6.3 1/2 6.3 37.8 1 6.3 37.8
MS132-10 1-1/2 10 60 3 8.5 46
MS132-12 2 12 72 3 8.5 64
MS132-16 2 12 72 5 14 81
MS132-20 3 17 92 5 14 81
MS132-25 3 17 127 7-1/2 21 116
MS132-32 5 28 162 10 26 145
2CDC131021D0201 - 7

Motor rating, three phase
hp Horse power
FLA Full load amps
LRA Locked rotor amps
Type 110 ... 120 V AC 220 ... 240 V AC 440 ... 480 V AC 500 ... 600 V AC
hp FLA LRA hp FLA LRA hp FLA LRA hp FLA LRA
MS132-0.16 - 0.16 0.96 - 0.16 0.96 - 0.16 0.96 - 0.16 0.96
MS132-0.25 - 0.25 1.5 - 0.25 1.5 - 0.25 1.5 - 0.25 1.5
MS132-0.4 - 0.4 2.4 - 0.4 2.4 - 0.4 2.4 - 0.4 2.4
MS132-0.63 - 0.63 3.78 - 0.63 3.78 - 0.63 3.78 - 0.63 3.78
MS132-1.0 - 1 6 - 1 6 - 1 6 1/2 1 6
MS132-1.6 - 1.6 9.6 - 1.6 9.6 3/4 1.6 9.6 3/4 1.6 9.6
MS132-2.5 - 2.5 15 1/2 2.5 15 1 2.5 15 1-1/2 2.5 15
MS132-4.0 - 4 24 1 4 24 2 4 24 3 3.9 26
MS132-6.3 1/2 6.3 37.8 1-1/2 6.3 37.8 3 4.8 32 5 6.1 37
MS132-10 3/4 10 60 3 9.6 64 5 7.6 46 7-1/2 9 51
MS132-12 1-1/2 12 72 3 9.6 64 7-1/2 11 64 1 0 11 65
MS132-16 2 16 84 5 15.2 92 10 14 81 10 11 65
MS132-20 3 19.2 128 5 15.2 92 10 14 81 15 17 93
MS132-25 3 19.2 128 7-1/2 22 127 15 21 116 20 22 116
MS132-32 5 30.4 184 10 28 162 20 27 145 25 27 146
Manual Motor Controller for Motor Disconnect
Type Circuit Breaker or
Maximum short-circuit current rating
Class R fuse per UL/
NEC 480 V / 600 V
480 V 600 V
kA kA
MS132-0.16 with minimum
MS132-0.25 30 18
MS132-0.4 30 18
MS132-0.63 30 18
interrupting rating
of 35,000 rms
symmetrical amperes
30 18
MS132-1.0 30 18
MS132-1.6 30 18
MS132-2.5 30 18
MS132-4.0 30 18
MS132-6.3 30 18
MS132-10 30 18
MS132-12 30 18
MS132-16 30 18
MS132-20 30 18
MS132-25 30 18
MS132-32 30 18
8 - 2CDC131021D0201

Manual Motor Controller for Group Installation
Type Circuit Breaker or
MS132-0.16 with minimum
MS132-0.25 35 35
MS132-0.4 35 35
MS132-0.63 35 35
MS132-1.0 35 35
MS132-1.6 35 35
MS132-2.5 35 35
MS132-4.0 35 35
MS132-6.3 35 35
MS132-10 35 35
MS132-12 35 35
MS132-16 35 35
MS132-20 35 35
MS132-25 35 35
MS132-32 35 35
Class R fuse per UL/
NEC 480 V / 600 V
interrupting rating of
35,000 rms symmetrical
amperes
Maximum short-circuit current rating
480 V 600 V
kA kA
35 35
Manual Motor Controller for Group Installation in combination with current limitor S803W-SCLxxx-SR
Type Maximum short-circuit current rating
480 V 600 V
kA kA
MS132-0.16 65 65
MS132-0.25 65 65
MS132-0.4 65 65
MS132-0.63 65 65
MS132-1.0 65 65
MS132-1.6 65 65
MS132-2.5 65 65
MS132-4.0 65 65
MS132-6.3 65 65
MS132-10 65 65
MS132-12 65 65
MS132-16 65 65
MS132-20 65 65
MS132-25 65 65
MS132-32 65 65
2CDC131021D0201 - 9

Self-Protected Combination Motor Controller (Type E) and Combination Motor Controller (Type F)
Type UL 508 Self-Protected
Combination Motor
Controller (Type E)
in combination with
feeder block S1-M3-xx
Maximum short-circuit
current rating
480Y / 277 V 480Y / 277 V 480 V 600 V
kA kA kA kA
MS132-0.16 30 30 AF26...AF38 30 65
MS132-0.25 30 30 AF26...AF38 30 30
MS132-0.4 30 30 AF26...AF38 30 30
MS132-0.63 30 30 AF26...AF38 30 30
MS132-1.0 30 30 AF26...AF38 30 30
MS132-1.6 30 30 AF26...AF38 30 30
MS132-2.5 30 30 AF26...AF38 30 30
MS132-4.0 30 30 AF26...AF38 30 30
MS132-6.3 30 30 AF26...AF38 30 30
MS132-10 30 30 AF26...AF38 30 30
MS132-12 30 - - 30 30
MS132-16 30 - - 30 30
MS132-20 30 - - 30 30
MS132-25 30 - - 30 30
MS132-32 30 - - 30 30
UL 508 Combination Motor Controller (Type F) UL 508 Manual Motor Controller for
Maximum short-circuit
current rating
Minimum contactor
size
Tap Conductor Protection
Maximum short-circuit current rating
Self-Protected Combination Motor Controller (Type E) and Combination Motor Controller (Type F)
in combination with current limitor S803W-SCLxxx-SR
Type UL 508 Self-Protected Combination
Motor Controller (Type E) in
combination with current limitor
S803W-SCLxxx-SR
Maximum short-circuit current rating Maximum short-circuit current rating Minimum contactor size
480Y / 277 V 480Y / 277 V
kA kA
MS132-0.16 65 65 AF26...AF38
MS132-0.25 65 65 AF26...AF38
MS132-0.4 65 65 AF26...AF38
MS132-0.63 65 65 AF26...AF38
MS132-1.0 65 65 AF26...AF38
MS132-1.6 65 65 AF26...AF38
MS132-2.5 65 65 AF26...AF38
MS132-4.0 65 65 AF26...AF38
MS132-6.3 65 65 AF26...AF38
MS132-10 65 65 AF26...AF38
MS132-12 65 - -
MS132-16 65 - -
MS132-20 65 - -
MS132-25 65 - -
MS132-32 65 - -
UL 508 Combination Motor Controller (Type F) in combination with current
limitor S803W-SCLxxx-SR
10 - 2CDC131021D0201