ABB B6 Contactors, K6 control relays Technical data

Miniature
Controls
4
IEC Technical data
B6 Contactors & K6 control relays Auxiliary contacts & magnetic coils
Endurance curves – B 6, BC 6, B 6S
10
8 6
5 4
4
3 2
1
0.8
0.6
0.5
0.4
0.3
Millions of operations
0.2
0.1
0.08
0.06
0.05
0.04
0.03
0.02
0.01
10
8 6
5 4
3 2
1
0.8
0.6
0.5
0.4
0.3
Millions of operations
0.2
0.1
0.08
0.06
0.05
0.04
0.03
0.02
0.01
Rated operating current[A]
Switch off current [A]
Endurance curves – K6, KC6, CA6, CAF6
10
5
2
1
Millions of operations
0.5
0.2
0.1
0.01 0.02 0.05 0.1 0.2 0.5 1 2 3 5 10 Switch off current (A)
AC3
B6 contactors & K6 control relays
Rated insulating voltage Vi 500 Permissible ambient temperature
Contactor without relay °C – 25 ... + 55 Contactor with relay °C – 25 ... + 50 Storage temperature °C – 40 ... + 80
Climatic resistance acc. to DIN 50 017 alternating climate proof acc. to UTE C 63-100 30 cycles, version 1
Mounting position optional Mechanical endurance 10 million operations Max. switching frequency AC 1 cyc./h 300
AC 2/AC 3 cyc./h 600 Rated operating voltage V
AC1
1013 0201. 2 3 4 5 6 8
15
Rated operating current I Rated operating power 55 °C 40 °C I
220/240 V 16 20 9 2.2 380/440 V 16 20 9/8 4.0
V AC 12 to 500
e
/AC 1, AC 3 AC 1/Ie A AC 2, AC 3
e
A P kW
e
500 V 12 12 5.5 3.0 Switching times B6 BC6 K6 KC6
Closing delay NO ms 20 to 26 20 to 26 Opening delay NO ms 16 to 20 4 to 6 16 to 20 4 to 6 Closing delay NC ms 16 to 20 4 to 6 16 to 20 4 to 6 Opening delay NC ms 14 to 18 14 to 18
Auxiliary Contacts and Magnetic Coils
Rated operating voltage Ve VDC 12 to 240 VAC 12 to 500
Conventional rated thermal current Ith A 6
Rated operating current Ie/ AC 15 at Ve 220/240 V A 4 380/440 V A 3 500 V A 2
Rated operating current Ie/DC 13 at Ve 24 V A 2.5 60 V A 1.2 110 V A 0.7 220/240 V A 0.4
Rated power of magnetic coils Basic contactors closing /holding
B6 / K6, VB6 AC VA 3.5 BC6 / KC 6, VBC6 DC W 3.5
Interface contactors BC6 / KC6-1.4 DC • 24 • V W 1.4 BC6 / KC6-2.4 DC 17 ... 32 V W 2.4
Mini contactor for connection to PLC's cold warm I mA P W I mA P W B6 S-1.7 DC + 24 + V W 77 1.75 60 1.35
B6 S-2.8 DC + 17 ... 32 +V W 125 2.80 94 2.10 Coil voltage range 0.8 ...1.1x V
c
1013 0201.5 2 3 4 5 6 8
AC4
15
AC 15
4.14 Low Voltage Products & Systems
1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • www.abb-control.com