ABB AF range contactors Application Information

Appli cation descr iption
AF range contactors / CP-C, -S, -E, -T range power supply units
Primary switch mode power supply units for supplying contactors with electronic coil
The following table shows which of our power supply units can safely switch-on and operate each size of ABB contactor with electronic coil.
Assignment of the devices under the following conditions:
The power supply units have been loaded with contactors only. There was no additional load. The contactors have been actuated in cold state or after thermally built-up hold power. The single-phase power supply units have been tested on the primary side with 115 and 230 V AC. The three-phase power supply units have been tested on the primary side with 400 V AC. The secondary voltage was in both cases 24 V DC.
Co-ordination parameters
Average pick-up current of the contactors Max. load operating point of the power supply units Ambient temperature range: 0...70 °C Switching frequency: 120/h Mounting position of the contactors: horizontal Wire length: 2 x 2.5 m Cross section: 1.5 mm²
Result / Co-ordination table
CP-T 24/5.0
CP-E 24/5.0
Max. load operating point of the power supply units (A)
CP-C 24/10.0
CP-S 24/10.0
CP-T 24/10.0
CP-E 24/10.0
CP-C 24/20.0
CP-S 24/20.0
CP-T 24/20.0
CP-E 24/20.0
CP-T 24/40.0
AF-45 AF-50 AF-63
AF-75
AF-95
AF-110
AF-145
AF-185
Type of contactor
Operating range of the coil
20...60
(V)
Average pick-up power of the
190 7,9
400 16,7
500 20,8
CP-S 24/5.0
CP-C 24/5.0
coil (W)
at 24V DC
7,3 7,3 6,4 6,0 12,3 12,3 13,5 13,0 22,5 22,5 25,0 25,0 45,0
Average pick-up current (A)
x(*1 x(*1 n.a n.a x x x x x x x x x
n.a n.a n.a n.a n.a n.a n.a n.a x x x x x
n.a n.a n.a n.a n.a n.a n.a n.a x x x x x
AF-210
AF-300
AF-400
AF-460
AF-580
AF-750
Note (*1
520 21,7
990 41,2
24...60
950 39,6
The pick-up current of the contactors exceeds the max. load operating point of the power supply units CP-
C 24/5.0 and CP-S 24/5.0 slightly (8%). Due to the sufficient acceleration of the mechanical parts inside
the contactor during the pick-up phase, the co-ordination of the units is nevertheless guaranteed.
n.a n.a n.a n.a n.a n.a n.a n.a x x x x x
n.a n.a n.a n.a n.a n.a n.a n.a n.a n.a n.a n.a x
n.a n.a n.a n.a n.a n.a n.a n.a n.a n.a n.a n.a x
Example of supply of the contactor AF-750
Fig. 1: Functioning supply with power supply unit CP-T 24/40.0
Fig. 2: Critical supply with power supply unit CP-T 24/20.0
Fig. 3: Non functioning supply with power supply unit CP-T 24/10.0
2 2 CDC113031D010 1
Loading...