Side mounted instantaneous contact blocks11––CAL19-111SFN010820R101120.040
Side mounted instantaneous contact blocks
11––CAL19-11B1SFN010820R331120.040
mounting outside other block
qty
Weight
(1 pce)
kg
Terminal shrouds
Type Order codePkg
For connection with compression lugsLT140-30L1SFN124203R10002
qty
Weight
(1 pce)
kg
0.070
1SFC101070D0201
Page 2
Overload relays
for AF116 ... AF146 3-pole contactors
Description
Ordering details Electronic overload relays
EF146
TF140DU
Setting rangeShort-circuit
protective device
Akg
54...150315 A, Fuse type gGE10, E20, E30 EF1461SAX351001R11010.890
Ordering details Thermal overload relays
Setting rangeShort-circuit
protective device
Akg
66...90125 A, Fuse type gG10 ATF140DU-901SAZ431201R10010.880
80...110160 A, Fuse type gG10 ATF140DU-1101SAZ431201R10020.820
100...135200 A, Fuse type gG10 ATF140DU-1351SAZ431201R10030.820
110...142200 A, Fuse type gG10 ATF140DU-1421SAZ431201R10040.820
Trip classType Order codeWeight
Trip classType Order codeWeight
(1 pce)
(1 pce)
ABB | 3
1SFC101070D0201
Page 3
AF116 … AF146 3-pole contactors
Technical data
Main pole - Utilization characteristics according to IEC
Contactor types AC / DC operated AF116AF140AF146
Standards
Rated operational voltage Ue max.
Rated frequency (without derating)
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
Ue max. ≤ 690 V, 50/60 Hz
With conductor cross-sectional area70 mm²70 mm²95 mm²
AC-3 Utilization category
For air temperature close to contactorθ ≤ 55 °C
Ie / Max. rated operational current AC-3
M
θ ≤ 40 °C 160 A200 A225 A
θ ≤ 60 °C
θ ≤ 70 °C
220-230-240 V
380-400 V
3
3-phase motors
Rated operational power AC-3
M
3
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
Ue ≤ 500 V AC - gG type fuse200 A315 A315 A
Max. electrical switching frequency
Connection capacity (min. ... max.)
Main conductors (poles)
Stranded1 or 2 x 10 ... 95 mm²
Flexible1 or 2 x 10 ... 70 mm²
Main pole - Utilization characteristics according to UL / CSA
Contactor types AC / DC operated AF116AF140AF146
Standards
Max.operational voltage
UL / CSA General use rating
600 VAC
With conductor cross-sectional area
UL / CSA maximum 3-phase motor rating
Full load current
Horse power rating
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
Fuse rating
Fuse type, 600 V
Connecion capacity acc to UL/CSA
220-208 V AC 88 A114 A114 A
220-240 V AC 104 A130 A130 A
440-480 V AC 96 A124 A124 A
550-600 V AC 99 A125 A125 A
220-208 V AC 30 hp40 hp40 hp
220-240 V AC 40 hp50 hp50 hp
440-480 V AC 75 hp100 hp100 hp
550-600 V AC 100 hp125 hp125 hp
1 or 2 x AWG 6 ...3/0
IEC 60947-4-1 and EN 60947-4-1
690 V690 V1000 V
50 / 60 Hz