ABB AF26, AF210, AFN00, AF30, AF260 General information

...
General information
Product overview
Description
AF09 – AF750 and AFN00 - AFN4
• Maximum UL/CSA horsepower ratings
• Available with non-reversing, reversing, two speed one winding and two
speed two winding
• Available in non-combination and combination
• Available in UL type 1,3R,12, 4, and 4X stainless steel enclosures
magnetic circuit breaker
• Compact space saving design
• Standard auxiliary contact configurations: AF09 – AF750 (AFN00-AFN4)
1 N.O. & 1 N.C.
• Double break contact design
• Lowest possible contact bounce
• Operates over an extended voltage range of 85% to 110% of rated control
voltage
Overload relay protection
Starters, sizes AF09 – AF300 (AFN00-AFN4), have Class 10 adjustable ther­mal bimetallic overload relay protection as standard.
Sizes AF400 – AF750, have selectable Class 10, 20, 30 adjustable electronic
overload relay protection as standard.
Optional electronic overload relay protection is available for all starter sizes.
Field modification kits
Offers a wide variety of pilot device kits for non-reversing, reversing, two speed one winding and two speed two winding starters.
Control circuit transformer kits are also available with the following voltages:
Control Voltage 200-208 230-240 460-480 575-600
120V AC @ 50/60 Hz A B C D
24V AC @ 50/60 Hz E F G H
The field kits are pre-wired, ready to operate, making installation easy and reliable
2 | IEC & NEMA Enclosed starters
General information
Features and benefits
7
56
1
8 3
Features and benefits
1. Durable protective finish (carbon steel enclosures)
- Industry exclusive electrophoretic dip coat prime
- Power coated surface for added protection
2. Flange trough collar opening
- Channels liquids and dust away from enclosure gasket and enclosure interior
3. Seamless foamed-in-place gasket
- Provide secure seal against contaminates
- Ensures a dust tight and water tight seal
4. Pre-drilled mounting plate
- Easy mounting for control circuit transformer kit
2
4
5. Rugged and compact 22 mm pilot devices
- Meets UL/NEMA Type 1, 3R. 4, 4X. 12, 13
6. Convenient hole plugs for pilot device control
- Allows for quick installation of pilot device kit
7. Disconnect handle accepts 3 -3/8” padlocks in off position for safe
maintenance
8. Quarter turn enclosure latches
- Allows for quick entry and proper sealing of enclosure
IEC & NEMA Enclosed starters | 3
Catalog number explanation
Non-combination starter
AF26 1 S N 1 - 2 H A
Contactor size
AF26 AF210 AFN00 AF30 AF260 AFN0 AF50 AF300 AFN1 AF63 AF400 AFN2 AF75 AF460 AFN3 AF110 AF580 AFN4 AF145 AF750 AF185
Starter type
1 - Non reversing 2 - Reversing 3 - 2 Speed, 1 winding 4 - 2 Speed, 2 winding
Single phase
S - Single phase (insert only for single phase)
Disconnect type
Blank - Non-combination (starter only)
N - Non-fusible disconnect
Enclosure type
2 - NEMA/UL Type 1, 3R, 4, 12 X - NEMA/UL Type 4X (Stainless steel)
Coil voltage CCT
Option 1
See factory installed modifications on pages 29 & 30
Overload selection
See overload relay selection on pages 34 - 37
Coil voltage selection
24 AC 100 - 250 AC 250 - 500 AC
1 2 3
Control Voltage 200-208 230-240 460-480 575-600
120V AC @ 50/60 Hz A B C D
24V AC @ 50/60 Hz E F G H
AC Volts, 40-60 Hz
CCT Selection
IEC & NEMA Enclosed starters | 5