ABB AF09Z, AF12Z, AF16Z, AF26Z, AF30Z Catalog Page

...
AF09Z ... AF38Z 2-stack 3-pole contactors
4 to 18.5 kW AC / DC operated - Low consumption
Description
AF09Z ... AF38Z contactors are mainly used for controlling 3-phase motors and power circuits up to 690VAC and 220VDC. These contactors are of the block type design with 3 main poles (1st stack):
chanically linked (side-marked symbol) and the N.C. auxiliary contacts are mirror contacts
– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage
range (e.g. 100...250VAC and DC), only 4 control voltage ranges covering 24...250V 50/60Hz and
1SBC101002V0014
AF09Z-30-22
1SBC101003V0014
AF26Z-30-11
1SBC101004V0014
AF26Z-30-22
12...250VDC
- can manage large control voltage variations, allow direct control by PLC-output ≥ 24VDC 500mA, reduced panel energy consumption, very distinct closing and opening,
- can withstand short voltage dips and voltage sags (SEMI F47-0706 conditions of use on request).
– built-in surge suppression – add-on auxiliary contact blocks for side mounting and a wide range of accessories.
Ordering details
IEC UL/CSA Rated control circuit Rated operational 3-phase General
power current motor use
θ ≤ 40 °C
rating rating
voltage Uc min. … Uc max.
400 V 480 V 600 V AC AC-3 AC-1
kW A hp A V 50/60 Hz V DC kg
4
25
5
25
- 12...20 2 2
24...60 20...60 2 2
48...130 48...130 2 2
5.5
7.5
11
28
30
45
7.5
10
15
100...250 100...250 2 2
28
- 12...20 2 2
24...60 20...60 2 2
48...130 48...130 2 2
100...250 100...250 2 2
30
- 12...20 2 2
24...60 20...60 2 2
48...130 48...130 2 2
100...250 100...250 2 2
45
- 12...20 1 1
24...60 20...60 1 1
48...130 48...130 1 1
100...250 100...250 1 1
15
50
20
50
- 12...20 1 1
24...60 20...60 1 1
48...130 48...130 1 1
100...250 100...250 1 1
18.5
50
25
50
- 12...20 1 1
24...60 20...60 1 1
48...130 48...130 1 1
100...250 100...250 1 1
(1) For other auxiliary contacts arrangements, please contact your ABB local sales organization. Note: Only AF..Z contactors with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the coil terminals: A1+ for the positive pole and A2- for the negative pole
Auxiliary contacts fitted
22
22
22
22
22
22
22
22
22
22
22
22
Main dimensions mm, inches
45 1.77"
110.5 4.35"
71 2.80"
5.5 0.22"
10 0.39"
Type
Order code Weight
(1)
AF09Z-30-22-20 1SBL136001R2022 AF09Z-30-22-21 1SBL136001R2122 AF09Z-30-22-22 1SBL136001R2222 AF09Z-30-22-23 1SBL136001R2322 AF12Z-30-22-20 1SBL156001R2022 AF12Z-30-22-21 1SBL156001R2122 AF12Z-30-22-22 1SBL156001R2222 AF12Z-30-22-23 1SBL156001R2322 AF16Z-30-22-20 1SBL176001R2022 AF16Z-30-22-21 1SBL176001R2122 AF16Z-30-22-22 1SBL176001R2222 AF16Z-30-22-23 1SBL176001R2322 AF26Z-30-11-20 1SBL236001R2011 AF26Z-30-22-20 1SBL236001R2022 AF26Z-30-11-21 1SBL236001R2111 AF26Z-30-22-21 1SBL236001R2122 AF26Z-30-11-22 1SBL236001R2211 AF26Z-30-22-22 1SBL236001R2222 AF26Z-30-11-23 1SBL236001R2311 AF26Z-30-22-23 1SBL236001R2322 AF30Z-30-11-20 1SBL276001R2011 AF30Z-30-22-20 1SBL276001R2022 AF30Z-30-11-21 1SBL276001R2111 AF30Z-30-22-21 1SBL276001R2122 AF30Z-30-11-22 1SBL276001R2211 AF30Z-30-22-22 1SBL276001R2222 AF30Z-30-11-23 1SBL276001R2311 AF30Z-30-22-23 1SBL276001R2322 AF38Z-30-11-20 1SBL296001R2011 AF38Z-30-22-20 1SBL296001R2022 AF38Z-30-11-21 1SBL296001R2111 AF38Z-30-22-21 1SBL296001R2122 AF38Z-30-11-22 1SBL296001R2211 AF38Z-30-22-22 1SBL296001R2222 AF38Z-30-11-23 1SBL296001R2311 AF38Z-30-22-23 1SBL296001R2322
AF..-30-22 119.5 4.70"
45 1.77"
AF..-30-11 111.5 4.39"
80 3.15"
5.5 0.22"
10 0.39"
Pkg (1 pce)
0.360
0.360
0.360
0.360
0.360
0.360
0.360
0.360
0.360
0.360
0.360
0.360
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
0.390
0.400
5
6 0.24"
80 3.15"
AF09Z, AF12Z, AF16Z
5.5 0.22"
EN/IEC 60715
35 mm
6 0.24"
80 3.15"
43 1.69"
AF26Z, AF30Z, AF38Z
5.5 0.22"
EN/IEC 60715
35 mm
43 1.69"
1SBC101374S0201 - Rev. B
ABB | 5/115