3M™ Fire Barrier Sealant IC 15WB+
Product Data Sheet
FIRE BARRIER
UP
TO
3
HOUR
Fire Protection
SOUND BARRIER
SMOKE SEAL
L
RATED
Meets Optional
L Requirements
1. Product Description
3M™ Fire Barrier Sealant IC 15WB+ is a cost-effective, one-part,
gun-grade, latex-based, intumescent firestop sealant that dries to form a monolithic firestop seal that also acts
as a barrier to airborne sound transmission. 3M™ Fire Barrier Sealant IC 15WB+ firestops through penetrations
passing through fire-rated floor, floor/ceiling or wall assemblies, as well as other fire-rated interior building
partitions and assemblies (e.g. static construction joints or blank openings). In addition, the unique intumescent
property of this material allows 3M™ Fire Barrier Sealant IC 15WB+ to expand and help maintain a firestop
penetration seal for up to 3 hours as penetrants are exposed to fire. 3M™ Fire Barrier Sealant IC 15WB+
bonds to most construction substrates, including: gypsum wallboard, concrete, metals, wood, plastic (including
CPVC) and cable jacketing. No mixing is required.
THROUGH-PENETRATION FIRESTOP SYSTEMS
Product Features
Cost-effective firestop sealant
available in tube, pail or sausage.
Product Color: Yellow.
• Firestop
accordance with ASTM E 814
(UL 1479), ASTM E 1966
(UL 2079) & CAN/ULC-S115
•
CPVC compatible
•
Expanded fire protection systems
•
Helps minimize sound transfer*
Complies with the intent of LEED® NC-EQ Credit 4.1 for Low-Emitting Materials: Adhesives and Sealants,
contains <250 g/L VOC contents (less H2O and exempt solvents per SCAQMD Rule 1168).
*Minimizes noise transfer—STC-Rating of 54 when tested in STC 54-rated wall assembly.
tested up to 3 hours in
•
Sag-resistant
•
Halogen-free
•
Excellent adhesion
•
Re-enterable/repairable
•
Excellent caulk rate
•
Paintable
•
Water clean up
FILL, VOID OR CAVITY
54
STC
In STC 54-rated
wall assembly
FILL, VOID, OR CAVITY
FOR USE IN JOINT SYSTEMS,
AND PERIMETER CONTAINMENT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
MATERIALS
90G9
90G9
FIRESTOP SYSTEMS
SEE INTERTEK DIRECTORY
2. Applications
3M™ Fire Barrier Sealant IC 15WB+ is a general-purpose intumescent firestop ideal for sealing single or multiple
through penetrations in fire-rated construction. 3M™ Fire Barrier Sealant IC 15WB+ is typically used in mechanical, electrical and plumbing applications
to firestop openings created by the following penetrations in fire-rated floors, floor/ceilings or walls: metallic pipe, plastic pipe, conduit, power and
communication cable, cable trays, busways, combos, insulated pipe and HVAC duct penetrations. 3M™ Fire Barrier Sealant IC 15WB+ is also used to
firestop blank openings and static construction joints.
3. Specifications
3M™ Fire Barrier Sealant IC 15WB+
shall be a one component, ready-to-use, gun-grade, latex-based, intumescent
firestop sealant capable of expanding a minimum of 3 times at 1000°F. The
material shall be thixotropic and be applicable to overhead, vertical and
horizontal firestops. The sealant shall be listed by independent test agencies
such as UL, ULC, Intertek or FM. 3M™ Fire Barrier Sealant IC 15WB+ shall
be tested to and pass the criteria of ASTM E 814 (UL 1479) Standard Test
Method for Fire Tests of Penetration Firestop Systems, ASTM E 1966 (UL
2079) Standard Test Method for Fire Resistive Joint Systems and CAN/
ULC-S115 Standard Method of Fire Tests of Firestop Systems. 3M
™
Fire
Barrier Sealant IC 15WB+ meets the requirements of the IBC, IRC, NBCC,
Typically Specified MasterFormat (2004)
Section 07 84 00 – Firestopping
Related Sections
Section 07 27 00 – Air Barriers
Section 07 84 16 – Annular Space Protection
Section 07 84 43 – Fire-Resistant Joint Sealants
Section 07 86 00 – Smoke Seals
Section 07 87 00 – Smoke Containment Barriers
Section 07 92 13 – Elastomeric Joint Sealants
Section 07 92 19 – Acoustical Joint Sealants
Section 21 00 00 – Fire Suppression
Section 22 00 00 – Plumbing
Section 23 00 00 – Heating, Ventilating, and Air Conditioning (HVAC)
Section 26 00 00 – Electrical
IFC, IPC, IMC, NFPA 5000, NEC (NFPA 70) and NFPA 101.
For technical support relating to 3M Fire Protection Products and Systems, call: 1-800-328-1687
For more information on 3M Fire Protection Products, visit: www.3m.com/firestop
4. Performance & Typical Physical Properties
Color: Yellow
Application Temperature Range: 40° to 122°F (4° to 50°C)
(ASTM C 1299)
Service Temperature Range: -20° to 180°F (-28° to 82°C)
STC Acoustic Barrier: 54 when tested in STC 54 rated
(ASTM E 90 and ASTM E 413) wall assembly
Surface Burning (ASTM E 84): Flame Spread 5, Smoke Development 50
Unit Volume: 10.1 fl. oz tube (298.7 ml, 18.2 in.3), 20 fl. oz. sausage (591.5 ml, 36.1 in.3), 27 fl. oz tube (798.5 ml, 48.7 in.3), 4.5 gal. pail (17.03 L, 1039.5 in.3)
Hardness (ASTM D 2240 Shore A): 70
Tensile Strength: 85 psi (0.59 MPa)
Volume Shrinkage (ASTM C 1241): 28%
VOC Less H2O and Exempt Solvents:
Dry: Under typical conditions of 75°F (23°C) and 50% R.H., sealant
becomes tack-free in about ten minutes and dry-to-touch in 30 to 60
minutes. Full dry depends upon ambient conditions and volume of sealant.
Typical dry rate is approximately 1/8 inch (3 mm) per day.
<2 g/L
5. Packaging, Storage, Shelf Life
Packaging Product packaged in cartridge or pail is enclosed in HDPE plastic containers, sausage is packaged in aluminum foil wrap.
Storage 3M™ Fire Barrier Sealant IC 15WB+ should be stored indoors in dry conditions between 40°F and 90°F (4°C and 32°C)
in the original unopened package. Avoid repeated freeze / thaw exposures of the 3M™ Fire Barrier Sealant
IC 15WB+ prior to installation.
Shelf Life 3M™ Fire Barrier Sealant IC 15WB+ shelf life is 12 months in original unopened containers from date of packaging
when stored above 68°F (2°C).
Lot numbering (e.g. 8183AS): First digit = Last digit of year manufactured, Second to fourth digit = Julian Date, Letters = Random to
distinguish between lot numbers
6. Installation Techniques
Consult a 3M Authorized Fire Protection Products Distributor / Dealer or Sales Representative
for applicable UL, cUL, ULC, Intertek, FM or other third-party drawings and system details.
Preparatory Work The surface of the opening and any penetrating items should be cleaned to allow for the proper adhesion of the 3M™
Fire Barrier Sealant IC 15WB+. Ensure that the surface of the substrates are not wet and are frost free. Sealant can be
installed with a standard caulking gun, pneumatic pumping equipment or it can be easily applied with a putty knife or trowel.
Installation Details Install the applicable depth of backing material, if required, as detailed within the applicable UL, cUL, ULC, Intertek, FM
or other third-party listed system. Cut the end of the 3M™ Fire Barrier Sealant IC 15WB+ tube spout to achieve the desired
bead width when applying. Install the applicable depth of 3M™ Fire Barrier Sealant IC 15WB+ into the opening flush with
the surface of the substrate, or as detailed within the applicable listed system, at the depth for the assembly and rating that
is required. Tool within 5 minutes. Clean all tools immediately after use with water.
Limitations Do not apply 3M™ Fire Barrier Sealant IC 15WB+ when surrounding temperature is than less 40°F (4°C) and in
conditions where seals may be exposed to rain or water spray within 18 hours of application. Do not apply 3M™ Fire Barrier
Sealant IC 15WB+ to building materials that bleed oil, plasticizers or solvent (e.g. impregnated wood, oil-based sealants,
or green or partially vulcanized rubber). Do not apply 3M™ Fire Barrier Sealant IC 15WB+ to wet or frost-coated
surfaces or to areas that are continuously damp or immersed in water.
7. Maintenance
No maintenance is expected to be required when installed in accordance with the applicable UL, cUL, ULC, Intertek,
FM or other third-party listed system. Once installed, if any section of the 3M™ Fire Barrier Sealant IC 15WB+ is damaged, the following procedure will
apply: remove and reinstall the damaged section in accordance with the applicable listed system, with a minimum 1/2 in. (12.7 mm) overlap onto the
adjacent material.
8. Availability
3M™ Fire Barrier Sealant IC 15WB+ is available from 3M Authorized Fire Protection Products Distributors
and Dealers. 3M™ Fire Barrier Sealant IC 15WB+ is available in 10.1 fl. oz. cartridges (3M ID 98-0400-5509-1, 12/case), 20.0 fl. oz. sausages (3M ID
98-0400-5512-5, 10/case), and 4.5 gallon pails (3M ID 98-0400-5510-9, 1/case). For additional technical and purchasing information regarding this
and other 3M Fire Protection Products, please call: 1-800-328-1687 or visit www.3m.com/firestop.
9. Safe Handling Information
Important Notice to User:
Technical Information: The technical information, recommendations and other statements contained in this document are based upon tests or
experience that 3M believes are reliable, but the accuracy or completeness of such information is not guaranteed.
Product Use: Many factors beyond 3M’s control and uniquely within user’s knowledge and control can affect the use and performance of
a 3M product in a particular application. Given the variety of factors that can affect the use and performance of a 3M product, user is solely
responsible for evaluating the 3M product and determining whether it is fit for a particular purpose and suitable for user’s method of application.
Warranty and Limited Remedy: 3M warrants that each 3M Fire Protection Product will be free from defects in material and manufacture for
90 days from the date of purchase from 3M’s authorized distributor. 3M MAKES NO OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING
ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If a 3M product does not conform to this
Building and Commercial
Services Division
3M Center, Building 223-2N-21
St. Paul, MN 55144-1000 USA
1-800-328-1687
www.3M.com/firestop
warranty, the sole and exclusive remedy is, at 3M’s option, replacement of the 3M product or refund of the purchase price.
Limitation of Liability: Except where prohibited by law, 3M will not be liable for any loss or damage arising from the 3M product, whether
direct, indirect, special, incidental or consequential, regardless of the legal theory asserted.
Please Recycle. Printed in USA.
© 3M 2012. All rights reserved.
98-0400-5077-9 REV B
Consult country-of-use Material Safety Data Sheet (MSDS) prior to handling and disposal.
3M is a trademark of 3M. Used under license in Canada. All
other trademarks are the property of their respective owners.