Zibro S2041, S2053, S2035 user manual

S2035 - S2041 - S2053
4
SERVICE MANUAL
2
SPECIFICATION
INDOOR OUTDOOR
TAN-A28EWI TAG-A28EWI
Moisture Removal
Power source
Airflow Method
Air circulation (at High)
Input
Electrical Data
Piping Connection Port (Flare piping)
Pipe Size (Flare piping)
Drain hose
Power Cord
Dimensions
Net Weight
Running Current Starting Current
Inner diameter Length Length Number of core-wire Height Width Depth
BTU/hCooling Capacity BTU/hHeating Capacity
L/h
phase
V
Hz
OUTLET
INTAKE
3
m/min
W
A
A inch inch inch inch
mm
m– m–
mm mm mm
kg
10,000(2,700-12,000) 13,200(2,400-18,000)
1.6 Single
230
50
SIDE VIEW
Cooling ; Heating ;
Cooling ; Heating ;
Cooling ; Heating ;
; Half Union 1/4''
L L
; Half Union 3/8''
G G
L (liquid side) ; 1/4'' G (gas side) ; 3/8''
core-wire/ 1 mm
9.0
11.0 660
765
2.9
3.4
3.4 ; 2-way valve 1/4'' ; 3-way valve 3/8''
L (liquid side) ; 1/4'' G (gas side) ; 3/8''
14
0.6
1.4
2
295 799 210
9.1
TOP VIEW
– –
550 780 278
35
– 1 –
SPECIFICATION
INDOOR OUTDOOR
TAN-A28EWI TAG-A28EWI
Type
Air Circulation
Heat Exchanger
Refrigerant Control Device Refrigerant (R410A ) Thermostat
Timer
Air Filter
Parts Provided
Motor Type Rated Output
W
g (oz)
Cross-flow Fan Propeller Fan
DC brushless(8-pole) DC brushless (8-pole)
30 40
Plate fin configuration,forced draft
21.2FPI 18.1 FPI
– –
Electronic Control
Real time dual ON/OFF 7-hour OFF
Mold-proof
1 Mounting plate 2 Remote controller 3 Battery (2 pcs.) 4 Remote controller holder 5 Screw cap (2 pcs.) 6 Drain elbow 7 Gum Bushing (2 pcs.) 8 Vibration proof rubber (4 pcs.)
Expansion Valve
1,100(38.8)
Specifications are subject to change without notice.
– 2 –
SPECIFICATION
INDOOR OUTDOOR
TAN-A32EWI TAG-A32EWI
Moisture Removal
Power source
Airflow Method
Air circulation (at High)
Input
Electrical Data
Piping Connection Port (Flare piping)
Pipe Size (Flare piping)
Drain hose
Power Cord
Dimensions
Net Weight
Running Current Starting Current
Inner diameter Length Length Number of core-wire Height Width Depth
BTU/hCooling Capacity BTU/hHeating Capacity
L/h
phase
V
Hz
OUTLET
INTAKE
3
m/min
W
A
A inch inch inch inch
mm
m– m–
mm mm mm
kg
12,500(2,700-14,100) 17,100(2,400-20,700)
1.7 Single
230
50
SIDE VIEW
Cooling ; Heating ;
Cooling ; Heating ;
Cooling ; Heating ;
; Half Union 1/4''
L L
; Half Union 3/8''
G G
L (liquid side) ; 1/4'' G (gas side) ; 3/8''
core-wire/ 1 mm
9.5
12.5
885 1,130
3.9
5.0
5.0
; 2-way valve 1/4''
; 3-way valve 3/8'' L (liquid side) ; 1/4'' G (gas side) ; 3/8''
14
0.6
1.4
2
295 799 210
9.1
TOP VIEW
– –
550 780 278
35
– 3 –
SPECIFICATION
INDOOR OUTDOOR
TAN-A32EWI TAG-A32EWI
Type
Air Circulation
Heat Exchanger
Refrigerant Control Device Refrigerant (R410A ) Thermostat
Timer
Air Filter
Parts Provided
Motor Type Rated Output
W
g (oz)
Cross-flow Fan Propeller Fan
DC brushless(8-pole) DC brushless (8-pole)
30 40
Plate fin configuration,forced draft
21.2FPI 18.1 FPI
– –
Electronic Control
Real time dual ON/OFF 7-hour OFF
Mold-proof
1 Mounting plate 2 Remote controller 3 Battery (2 pcs.) 4 Remote controller holder 5 Screw cap (2 pcs.) 6 Drain elbow 7 Gum Bushing (2 pcs.) 8 Vibration proof rubber (4 pcs.)
Expansion Valve
1,100(38.8)
Specifications are subject to change without notice.
– 4 –
SPECIFICATION
INDOOR OUTDOOR
TAN-A53EWI TAG-A53EWI
Moisture Removal
Power source
Airflow Method
Air circulation (at High)
Input
Electrical Data
Piping Connection Port (Flare piping)
Pipe Size (Flare piping)
Drain hose
Power Cord
Dimensions
Net Weight
Running Current
Starting Current
Inner diameter Length Length Number of core-wire Height Width Depth
BTU/hCooling Capacity BTU/hHeating Capacity
L/h
phase
V
Hz
OUTLET
INTAKE
3
m/min
W
A
A inch inch inch inch
mm
m– m–
mm mm mm
kg
17,700(1,700-18,800) 23,800(1,700-33,400)
2.8 Single
230
50
SIDE VIEW
Cooling ; Heating ;
Cooling ; Heating ;
Cooling ; Heating ;
; Half Union 1/4''
L L
; Half Union 3/8''
G G
L (liquid side) ; 1/4'' G (gas side) ; 3/8''
core-wire/ 2 mm
14.0
15.0
1,845 1,800
8.1
7.9
8.1
; 2-way valve 1/4''
; 3-way valve 3/8'' L (liquid side) ; 1/4'' G (gas side) ; 3/8''
14
0.6
2.3
2
295 799 210
9.5
TOP VIEW
– –
550 780 278
35
– 5 –
SPECIFICATION
INDOOR OUTDOOR
TAN-A53EWI TAG-A53EWI
Type
Air Circulation
Heat Exchanger
Refrigerant Control Device Refrigerant (R410A ) Thermostat
Timer
Air Filter
Parts Provided
Motor Type Rated Output
W
g (oz)
Cross-flow Fan Propeller Fan
DC brushless(8-pole) DC brushless (8-pole)
30 40
Plate fin configuration,forced draft
21.2FPI 18.1 FPI
– –
Electronic Control
Real time dual ON/OFF 7-hour OFF
Mold-proof
1 Mounting plate 2 Remote controller 3 Battery (2 pcs.) 4 Remote controller holder 5 Screw cap (2 pcs.) 6 Drain elbow 7 Photo-Catalytic Anti-Odor filter (2 pcs.) 8 Static,Catechin filter (2 pcs.) 9 Gum Bushing (2 pcs.)
Expansion Valve
1,100(38.8)
Specifications are subject to change without notice.
– 6 –
FUNCTIONS
REMOTE-CONTROL TRANSMITTER
ON/OFF Operation mode selection
COOL DRY HEAT AUTOMATIC
INDOOR UNIT
Sensing the room temperature
Room temperature sensor (thermistor)
Time delay safety control
Restarting is inhibited for approximately 3 minutes.
Indoor fan speed control
High, Med, Low
Air flow selection
AUTOMATIC HIGH MEDIUM LOW
Room temperature setting
16°C 30°C
Timer operation selection
CONTINUOUS operation OFF ON Sleep
Timer / time setting
Operation stops at the set time
(OFF timer)
Operation starts at the set time
(ON timer)
0.57.0hours(Sleep timer)
Operation indication lamps (LED)
(GREEN).......Light up in operation
(YELLOW) .... Timer in operation
(GREEN).......Outdoor unit operate
Dry operation mode
AUTOMATIC
Room temperature control
Maintains the room temperature in accordance with the setting temperature.
Deice (defrost) control
Deicing operation automatically starts when the heating efficiency is declined by the ice formed in the outdoor unit. After deicing operation, heating operation automatically starts with “Hot start function.”
Air flow direction control
Auto angle selection Auto swing mode Manual mode
– 7 –
Hot-start control (heating)
The indoor fan stops until the evaporator piping temperature will be reached.
Anti-freezing control for the evaporator
Compressor will be stopped when the evapolator’s piping temperature is below
2 for one minute. Compressor will be restarted when the evaporator’s piping temperature is above 2.
Airflow direction control
Automatic airflow direction control The louver automatically swings up and
down (cooling, dry)...horizontal and 35° downward. The louver is set at 70° downward during heating operation.
FUNCTIONS
OUTDOOR UNIT
Inverter control
Inverter control reduce the ON/OF times of compressor,so can keep the room
temperature changeless during operation.
Auto recovery function
If there is any power failure during operation, operation status before power
failure is memorized. 34 minutes after power recovery, the unit restarts automatically with previous operation status memorized. (34 minutes is protective time for compressor.)
Attention
Because of Auto recovery function, if shutting off the power supply during operation, the unit may restart irrespective your intention when turning on the power supply next time. If the unit is not to be used for a long time, shut off the power supply after terminating all operation with remote controller.
Electricity consumption
Inverter control can operate with less electricity consumption than normal air conditioner.
Deice(Defrost) control
(for outdoor unit panel) Deice operation automatically starts
when the outdoor temperature is lower than 2 and the ice is formed on the
bottom of outdoor unit.
– 8 –
SERVICE FUNCTION EXPLANATION
EMERGENCY AND TEST OPERATION
Emergency Operation
Use this operation only when the remote controller is out of order or lost.
When the emergency operation switch is pressed, beep starts once, which
means the start of this operation.
In this operation, the system automatically selects the operation modes, cooling
(or heating when available) according to the room temperature, as follows.
Beep
Temperature
ABOVE 23
BELOW 23
It is not possible to operate in dry mode.
Operation
mode
COOLING
HEATING
Designated
temperature
26
23
Timer mode Air flow
CONTINUOUS
CONTINUOUS
AUTOMATIC
AUTOMATIC
Test Operation
Test operation switch is same as emergency one.
Use this operation only for testing the performance of the machine in
the condition where the room temperature is less than 16°C.
Continue to press the test operation switch for more than 5 seconds.
After you hear twice beep, release your finger from the switch : the cooling operation starts with the air flow speed “HI.”
If the test operation switch is pressed more than 10 seconds, it doesn’t
work.
After 30 minutes, test operation ends automatically.
Twice beep
HOW TO RELEASE EMERGENCY AND TEST OPERA TION
• In case of releasing during those operations, you can either push emergency operation switch once more or
apply operation using remote control.
 You will hear a beep sound and emergency/ test operation is released. • If you release the operation by remote control, operation will continue as setting of the remote control
automatically.
INTERFERENCE PREVENTION OF SIGNALS FROM THE REMOTE CONTROLLER
When two indoor units used in the same room, interference of the signals may happen. To avoid this, alternative signal model B can be selected by the following. (Ex-factory setting is mode A)
J1
• Remote controller side : Have “J1” on the PC board short-circuited by soldering. • Indoor unit side : Cut “R13” on the PC board.
Soldering
J1
– 9 –
OPERATION DETAILS
TIMER OPERATION
ON Timer operation
Press the ON/OFF switch. Right after replacing new batteries, set the present time in advance.
Set the “ON T ime” : Press the “TIME ADJ” button twice.
Adjust the time with the “ , ” button.
Press the “TIME ADJ” button twice.The setting of “ON Time” is completed and the present time appears on the LCD.
Set the “ON Timer” : Press the Timer fixing button “ON”.
OFF Timer operation
Press the ON/OFF switch. Right after replacing new batteries, set the present time in advance.
Set the “OFF T ime” : Press the “TIME ADJ” button 3 times.
Adjust the time with the “ , ” button.
Press the “TIME ADJ” button once.The setting of “OFF Time” is completed and the present time appears on the LCD.
Set the “OFF Timer” : Press the Timer fixing button “OFF”.
Sleep Timer operation
Press the “SLEEP” button during the operation.
Set the operating period by pressing the “SLEEP” button until the period designated appears on the LCD.
Timer Cancellation
ON/OFF Timer : Press the Timer fixing button “ON”(On Timer) and/or “OFF”(Off Timer) once again.
Sleep Timer : Press the “SLEEP” button until the operating period on the LCD disappears.
AIRFLOW DIRECTION CONTROL
Vertical adjustment
When ON/OFF switch is pressed, the vertical louver will move to the adequate positions for each operation automatically.
Swing of air flow
If air flow direction switch is pressed once, the vertical louver will move within the range of figures.
Fixing the flow direction
If air flow direction switch is pressed again, the vertical louver will be fixed and that position is memorized. From the next operation the louver will be set at previous position automatically.
Notes :
In Swing Mode, the louver automatically moves up and down within the certain range, as the illustration below .
There is two different ranges of louver swinging; one is of cooling & dry mode operation and the other is of
heating operation.
Standard Position
Approx.10 degrees (Cooling/Dry)  Approx.70 degrees (Heating) 
Level
Swing of Air Flow
Level
Approx.10 degrees
Approx.40 degrees
Cooling
Dry
Heating
– 10 –
Approx.45 degrees
Approx.70 degrees
AIRFLOW DIRECTION CONTROL
OPERATION DETAILS
Horizontal Adjustment
Swing of Air Flow
The horizontal louver will keep moving steadly right and left if the horizontal louver button is pressed once.
Fixing the Flow Direction
The horizontal louver will come to a halt if the horizontal louver button is pressed once again.
NOTICE :
Dew drops may appear at the outlet under high humidity(e.g.during rainy season) if the system is operated
with the horizontal louver faced to the extreme right or left.
Use the wireless remote control unit without fail to change the angle of the horizontal louver. The horizontal
louver may move out of the normal range if forced by hands.
TAN/TAG-A53EWI
TIME DELAY SAFETY CONTROL FUNCTION - FOR PROTECTION OF COMPRESSOR
Compressor will not restart, in any operation modes, for 3 minutes after its stop.
Compressor does not stop during the first 6 minutes of its operation even if the room temperature reaches to
the designated temperature, except changing setting temperature.
COOLING MODE OPERATION
The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for 6 minutes and the room temperature becomes 1℃ lower than it was set.
The compressor will re-start when room temperature becomes 0 higher than it was set.
The operational frequency will be set every 1 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the set temperature on one end and the deviation factor at the time of previous setting on another.
Room temperature
Designated temperature
0˚C
-1˚C
MAX
2
Frequency of compressor
MAX 2
0
Hz
TAN/TAG-A28EWI, TAN/TAG-A32EWI TAN/TAG-A53EWI
MIN3
– 11 –
1
40
120
MIN3
2
90Hz
100Hz
3 24Hz 10Hz
OPERATION DETAILS
TAN/TAG-A28EWI, TAN/TAG-A32EWI
DRY MODE OPERATION
• Compressor stops when the room temperature fall to 0.3°C lower than the designated temperature continuously for 2 minutes.
• Compressor restarts when room temperature rises to the designated temperature.
• The operating frequency of the compressor is determined according to the room temperature (see the diagram below).
Indoor fan
Designated temperature
+6.0
+5.3
+4.7
+4.0
+3.3 +2.7
+1.7 +1.0
+0.0
-0.7
Designated
Fan blow
Super
low
Stop
Room temperature
2min.
Super
low
Designated Fan blow
Operating  frequency of  compressor
Indoor fan
98Hz 90Hz
70
66
62
58
5252
4848
Selected
speed
Super
low
OFF
(3min.)
Super
low
Selected speed
– 12 –
OPERATION DETAILS
TAN/TAG-A53EWI
DRY MODE OPERATION
During dry mode operation, both motors (TAN,TAG) run proportionally according to the temperatures (indoor,
outdoor).
The compressor runs continuously while unit is operating. (see the diagram below)
MAX
30Hz
Operating  frequency of  compressor
MAX
30Hz
MIN15Hz
– 13 –