TRANSFORMERS TRM-8, -12, -24, -358
Zakład Mechaniki i Elektroniki
ZAMEL sp.j.
J.W. Dzida, K. Łodzińska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamelcet.com, e-mail: marketing@zamel.pl
INSTRUCTION MANUAL
DESCRIPTION
Transformers are used to supply
electronic systems where it is required
to lower voltage value to the appropriate
level. The universal casing enables mounting on the TH-35 DIN rail or on the
surface. Available versions of secondary
voltage: 8 V AC, 12 V AC, 24 V AC and
3 V AC, 5 V AC, 8 V AC.
FEATURES
● Electronic systems supply
● used as bells and doorchimes trans-
formers,
● short circuits and overloads resi-
stant,
● inner thermal protection,
● threemodular casing,
● TH-35 DIN rail or surface mounting.
The device is designed
for single-phase installation and must be installed
in accordance with standards valid in a particular
CAUTION
the details included in this operating manual. Installation, connection and control should be carried out by a qualied
electrician staff, who act in accordance
with the service manual and the device
functions. Disassembling of the device is
equal with a loss of guarantee and can
cause electric shock. Before installation
make sure the connection cables are
not under voltage. The cruciform head
screwdriver 3,5 mm should be used to
instal the device. Improper transport,
storage, and use of the device inuence
its wrong functioning.
It is not advisable to instal the device in
the following cases: if any device part is
missing or the device is damaged or deformed. In case of improper functioning
of the device contact the producer.
country. The device should
be connected according to
The symbol means selective
collecting of electrical and electronical
equipment. It is forbidden to put
the used equipment together
with other waste
TECHNICAL DATA
Parameters for all transformers TRM-XXX
Rated primary voltage: 230 V AC
Rated frequency: 50 / 60 Hz
Rated power: 15 VA
Rated surrounding temperature: +40
Average increase coil temperature admissible: 80
Number of terminal clamps: 4 (6 for TRM-358)
Protective class: II
Thermal insulation class: B (120
Operating mode: continuous
Section of connecting cables: 0,2 ÷ 2,50 mm
Operating position: free
Mounting: TH35 rail (PN-EN 60715) or surface
Protection degree: IP20 (PN-EN 60529)
Overvoltage category: II
Pollution degree: P2
Rated impulse withstand voltage: 2,1 kV
Dimensions (height / width / depth): threemodular (53 mm) 90x53x66 mm
Weight: 0,474 kg
Reference standards: PN-EN 61558-1, PN-EN 61558-2-6
No-load state current: maks. 32 mA AC (U=230 V AC, f=50 Hz)
No-load state secondary voltage: 9,6 V AC
No-load state secondary voltage tolerance: ±5 %
Rated secondary current: 1,88 A AC
Rated secondary voltage: 8 V AC
Rated secondary voltage tolerance: ±5 %
TRM-12
No-load state current: maks. 32 mA AC (U=230 V AC, f=50 Hz)
No-load state secondary voltage: 14,4 V AC
No-load state secondary voltage tolerance: ±5 %
Rated secondary current: 1,25 A AC
Rated secondary voltage: 12 V AC
Rated secondary voltage tolerance: ±5 %
TRM-24
No-load state current: maks. 32 mA AC (U=230 V AC, f=50 Hz)
No-load state secondary voltage: 28,7 V AC
No-load state secondary voltage tolerance: ±5 %
Rated secondary current: 0,625 A AC
Rated secondary voltage: 24 V AC
Rated secondary voltage tolerance: ±5 %
TRM-358
No-load state current: maks. 36 mA AC (U=230 V AC, f=50 Hz)
No-load state secondary voltage: 3,9 V AC or 6,3 V AC or 9,8 V AC
No-load state secondary voltage tolerance: ±5 %
Rated secondary current: 5 A AC or 3 A AC or 1.88 A AC
Rated secondary voltage: 3 V AC or 5 V AC or 8 V AC
Rated secondary voltage tolerance: ±10 %
NOTE: Minimum distance to the other devices - 10 mm
TRM-8
o
C
o
C
o
C)
2
VER. 001_16.09.2009
MOUNTING
1. Disconnect the power supply from the
mains by the phase fuse, the circuitbreaker or the switch-disconnector
that are joined to the proper circuit,
2. Check if there is no voltage on con-
nection cables by means of a special measure equipment,
3. nstall TRM-XXX devices in the switch-
board on TH 35 DIN rail or on the surface,
4. Connect the cables with the termi-
nals,
5. Switch on the power supply from the
mains,
6. While surface mounting screw protec-
tion shield,
7. Switch on the voltage.
APPEARANCE
Protection shield
Input (supply) terminals
(230 V AC)
Protection shield
Input (supply) terminals
(230 V AC)
LEGENDA
Safety transformer resistant to
short-circuit (directly and indirectly).
Bell and doorchimes transformer
resistant to short circuits (conditionally and non-conditionally).
Inner thermal transformer protection against overload and short
circuits.
Construction made acc. to protection level II.
PRODUCT FAMILY
TRM-XXX
Device version:
8 - power 15 VA, voltage:
8 V AC
12 - power 15 VA, voltage:
12 V AC
24 - power 15 VA, voltage:
24 V AC
358 - power 15 VA, voltage:
3 V AC, 5 V AC, 8 V AC
Symbol
DIMENSIONS
Output (load) terminals
(8 V AC)
Output (load) terminals
(12 V AC)
Protection shield
Input (supply) terminals
(230 V AC)
Protection shield
Input (supply) terminals
(230 V AC)
Output (load) terminals
(24 V AC)
WARRANTY CARD
There is 24 months guarantee on the product
Salesman stamp and signature, date of sale
Common termianal (COM)
Output (load) terminal (3 V AC)
Output (load) terminal (5 V AC)
Output (load) terminal (8 V AC)
1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product.
2. The manufacturer’s guarantee does not cover any of the following actions:
a) mechanical damage during transport, loading / unloading or under other circumstances,
b) damage caused by incorrect product mounting or misuse,
c) damage caused by unauthorised modications made by the PURCHASER or any third parties to the product or any other devices
needed for the product functioning,
d) damage caused by Act of God or any other incidents independent of the manufacturer.
3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J.
4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation.
5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement or money return.
6. The manufacturer’s guarantee is valid in the Republic of Poland.
7. The PURCHASER’s statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or
otherwise are not affected by this warranty.
VER. 001_16.09.2009