Item Function Settings and options Default
settings
6 Key lock 0 - All keys are locked except the power supply key.
7 (1) Week option selection 0 – heating cycle time period in the 1-2-3-4-5 and 6-7 1 week – heating cycle time period in
7 (2) Communication protocol Store option 0.
8 Clock 12/24h 12h - mode 12-hour AM/PM 24h - mode 24-hour 24h
9 Backlight time Select time 3-99 seconds 10
10 Intelligent start-up 00 – programming the heating time
11 Return to factory settings
1 - All keys are locked
the 1-2-3-4-5-6 and 7 week.
Option 1 does not refer to the software including the controller’s functionality.
01- heating control in advance – it starts 30 minutes in advance to the pre-set time periods.
for settings in points rst 1 to rst 9.
Press
Press again to return to the default settings.
If sensors are in the AI mode (temperature sensor and floor sensor), it is possible to check the floor temperature by pressing the and
buttons for 3 seconds.
Controler’s lock
Press the buttons for 5 seconds to lock / unlock the keys.
Caution
The symbol means selective collecting of electrical and electronic equipment.
It is forbidden to put the used equipment together with other waste.
MATEC – ELECTRIC HEATING SYSTEMS
0
1
0
0
TEMPERATURE CONTROLER RTD-02
ZAMEL Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
tel. +48 32 449 15 00, +48 32 210 46 65, fax +48 (32) 210 80 04
www.zamel.com, e-mail: marketing@zamel.pl
TECHNICAL DATADESCRIPTION
RTD-02 is a 7-day programmable Control-
ler designed to control temperature in electric
fl oor heating systems. It is operated by means
of touch buttons placed under the screen.
The Controller is mounted on a wall in a ¢60 x 60 mm
deepened junction box.
FEATURES
• 3,2” LCD display
• Operation by means of touch buttons
• Anti-freezing function
• Floor overheating protection
• Key lock function
• Programmable temperature controller
cooperates with the inner floor sensor or
with both sensors simultaneously floor
sensor operates as the (floor temperature
limiter)
Temperature range during transport: -5 ÷+55°C
Temperature measurement accuracy: 1°C
Resolutions of temperature indications: 0,5°C
Cross-section of connecting cables: 0,5÷2,5 mm
Application environment with pollution degree 2 intended for domestic use of normal air circulation
Input (supply) terminals: N (3), L (4)
Power supply voltage: 95~240VAC
Nominal frequency: 50/60Hz
Nominal current consumption:
Battery backup: no
NTC sensor terminals: (5), (6)
Temperature sensor: NTC 10k for 25°C, 2,5m
Room temperature range: +5 ÷ +35°C
Floor temperature range: +5 ÷ +35°C
Operating temperature range: 5 ÷ +45°C
Hysteresis: 1-2-3-4-5°C (default 1°C)
Output terminals: (1), (2)
Output type: voltage contact 1NO-16 A/250 V AC
Number of terminal clamps: 6
Humidity: 5-90%, non-condensing
Mounting: deepen junction box ¢ 60mm x 60mm
Casing material: PC+ABS
Casing protection degree: IP20
Protection class: II
Overvoltage category: II
Dimensions: 86 x 86 x 13,3/39 mm (H x W x D)
Reference standards: EN 60950-2: 2006+A11:2009+A1:2010+A12:2011+
MANUAL INSTRUCTION
RTD-02
< 0,55W (STANDBY switched off relay and backlight)
2
Weight: 165g
A2:2013 EN 61000-6-3:2007+A1: 2011+AC:2012
EN 61000-6-1:2007
EN61000-3-2:2006+A1: 2009+A2:2009
EN 61000-3-3:2013
PN-EN 61000-4-3
PN-EN 61000-4-11
PN-EN 61000-4-6
WARRANTY CARD
There is a 24 month guarantee on the product
Salesman stamp and signature, date of sale
1. ZAMEL Sp. z o.o. assures a 24 month guarantee for the product.
2. The manufacturer’s guarantee does not cover any of the following actions:
a) mechanical damage during transport, loading / unloading or under other circumstances,
b) damage caused by incorrect product mounting or misuse,
c) damage caused by unauthorised modifi cations made by the PURCHASER or any third parties to the product or any other devices
required for the product functioning,
d) damage caused by Act of God or any other incidents independent of the manufacturer – ZAMEL Sp z o.o.
3. The PURCHASER shall lay any claims in writing in the place of purchase or to ZAMEL Sp. z o.o.
4. ZAMEL Sp. z o.o. is liable for processing any claim according to current Polish legislation.
5. ZAMEL Sp. z o.o. shall process the claim at its own discretion: product repair, replacement or money return.
6. The manufacturer’s guarantee is valid in the Republic of Poland.
7. The PURCHASER’s statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or otherwise
are not affected by this warranty.
VER. 004_21.03.2016 VER. 004_21.03.2016
CONTROLLER DESCRIPTIONS
Key lock symbol
Inner sensor temperature control
Inner sensor temperature control
Temperature setting
Floor sensor temperature control
Heating switched on
Automatic mode operation
acc. to the programme
Manual mode operation manual
Operating mode change:
manual / automatic
Day of the week Temperature
Parameter adjustment
Controller switching on
/ switching off
Clock adjustment /
Programme adjustment
Period
Morning / Afternoon
Time

OPERATIONAL SAFETY
CONTROLLER’S MOUNTING PLACE
START-UP continued
• The device is designed for a single-phase installation and must be installed in
accordance with standards valid in a particular country.
• The device should be connected according to the details included in this manual
instruction.
• Installation, connection and control should be carried out by a qualified electrician
staff, who acts in accordance with the service manual and the device functions.
• In case of casing dismantling, the guarantee is lost and an electric shock may
occur.
• Before installation, dismantling, cleaning or maintenance make sure the connection cables are not under voltage.
• The flathead screwdriver 2,5 mm should be used to install the device.
• Proper transport, storage, use of the device and particularly mounting of the Controller and the temperature sensor influence its correct functioning.
• It is forbidden to install the device in the following cases: if any device part is
missing or the device is damaged or deformed.
• In case of improper functioning of the device contact the manufacturer.
• Do not cover the controller and do not hang any items e.g. a towel on it.
• Do not douse the controller with water or any liquids.
• Do not interrupt power supply of the temperature controller. Power supply failure
causes the screen backlight and heating control are switched off. However, controllers’ settings remain unchanged.
• Children and people with sensory, psychological and intellectual impairments are
not allowed to control the device.
• Keep away the controller from shock and mechanical damages.
CONTROLLER MOUNTING
CONNECTION DIAGRAM
item 1-2 – loading
item 3 N – neutral
item 4 L – phase wire
item 5-6 – floor sensor
The controller is designed to be applied in the environment with pollu-
tion degree 2, it means it is intended for domestic use with normal
air circulation.
• The controller should be mounted in a heated room - mounting in a
¢60 x 60 mm junction box, at a height of 120 cm from the heated
surface.
• The controller must be mounted in a place not exposed to direct
sunlight and in well ventilated places.
Temperature and humidity in the installation place should not exceed
values given in technical parameters 0<T<45°C, humidity RH 5- 90%
non-condensing.
Controller
Sunlight
Heating mat
Exemplary RTD-02 installation
a) Press to set the time of the first period of days 1 to 5. A) Press to set the temperature of the first period of days 1 to 5.
b) Press
c) Press
d) Press
e) Press
f) Press
Use
g-G) Repeat the same procedure for days 6-7 (Saturday and Sunday).
The below table includes default settings of periods and temperature for days 1-2-3-4-5 and 6-7:
Proceed in a similar manner with the setting procedure for days 1-2-3-4-5-6 and 7 Sunday, but after a previous cycle change from 1-2-3-4-5-6 and 7 into 1-2-
3-4-5-6 and 7. The process of change is described in the ”Function and option setting” point – parameter in point 11 item 7.1 and 7.2.
to set the time of the second period of days 1 to 5. B) Press to set the temperature of the second period of days 1 to 5.
to set the time of the third period of days 1 to 5. C) Press to set the temperature of the third period of days 1 to 5.
to set the time of the fourth period of days 1 to 5. D) Press to set the temperature of the fourth period of days 1 to 5.
to set the time of the fifth period of days 1 to 5. E) Press to set the temperature of the fifth period of days 1 to 5.
to set the time of the sixth period of days 1 to 5. F) Press to set the temperature of the sixth period of days 1 to 5.
to change the values.
Days of the week 5 days Saturday and Sunday
Time interval
Heating
Start
time
6:00 wake up 20 °C 6:00 wake up 20 °C
8:00 work 15 °C 8:00 work 15 °C
11:30
afternoon
rest
13:30 work 15 °C 13:30 work 15 °C
17:00
end of work
22:00
rest
Temperature
15 °C
22 °C
15 °C
Start
time
11:30
afternoon
rest
17:00
end of work
22:00
rest
Temperature
15 °C
22 °C
15 °C
1. Disconnect power supply by the phase fuse, the circuit-breaker or the
switch-disconnector combined to the proper circuit.
2. Check if there is no voltage on the connection cables by means of a special
measuring equipment.
3. Insert the controller’s power supply cable, the floor sensor cable and the heating element power supply cable into the ¢ 60x60 junction box through a hole.
4. Mount the RTD-02 controller in a room according to the below indications:
a/ Carefully unfasten the front of the controller 4 from its rear part 2 by moving
the rear part vertically downward.
b/ connect the installation elements in the junction box according to the controller’s wiring diagram. The primary insulation for the electrical wiring connected to the controller should be fastened together to length of 4 mm.
c/ By means of 2 screws 3, screw the rear part of the controller 2 in the junction
box.
d/ Attach the front controller’s part 4 to the rear one by fitting the controller’s
front part holes with the hooks of the rear part, and slightly move downwards.
e/ Make sure the front part has been well mounted and it does not fall down.
5. Switch on the power supply from the mains.
6. Check if the controller operates properly and its mounting.
START-UP
After the temperature controller has been mounted and powered, press
button under the screen to activate the device.
the
Next, adjust parameters.
Controller settings
Press the
Temperature setting
Push the
Time (hour, minutes and day of the week) setting
Push the
Push the
Change values by means of
Programme settings
Press the
(manual) controller’s operation mode
In case of the automatic mode press the
controller’s operation programme.
Editing means entering the duration and temperature time for 6 time pe-
riods in the system of 1-2-3-4-5 days or 6-7 day.
periods for 1-2-3-4-5 days and 6-7 day.
button to switch on / switch off the temperature controller.
buttons to rise / lower the temperature.
button to change the minutes, hour and day of the week.
button again to move the selection to the nearest position.
buttons.
button to choose the automatic (weekly) handly
.
button for 5 seconds to edit the
for entering 6 time
Function and option
First, press the
and choose appropriate settings according to options included in the table. The functions are confi rmed just after power supply has been applied. Carry out
changes by means of
Item Function Settings and options Default
1 Thermal compensation (calibration) -9 ÷ +9 °C (for the inner sensor) 0
2 controller’s dead zone -
3 Type of sensor
4 Protection against low temperature
5 Protection against high temperature
button to switch off the power supply of the regulator and next press simultaneously the and buttons for 5 seconds. Then press
.
Hysteresis (temperature difference
between the output relay switching
on and switching off temperature).
(anti freeze temperature)
(fl oor overheating temperature)
1÷5 °C 1
In – room temperature control by means of the inner sensor
(built-in a controller),
Ou – room temperature control by means of the external sensor (fl oor sensor),
AL – Inner and external sensor. The Controller’s inner sensor controls the temperature.
The external sensor has the overheating control function.
Caution – while choosing an appropriate option, pay attention the correct sensor is connected. Otherwise an error (Err) appears on the display.
5 ÷ 10 °C. Use
adjusted one, the heating system starts to operate.
25 ÷ 70 °C. Use
against heating.
If the detected temperature is higher than the adjusted one, the Controller disconnects the
heating system.
button to rise the value. If the detected temperature is lower than the
buttons to lower / rise the temperature protection values
settings
In
5
45