Zamel PCM-08 Instruction Manual

TIME RELAY
- MOTOR START (STAR/DELTA) PCM-08
ZAMEL Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04 www.zamel.com, e-mail: marketing@zamel.pl
plik: inst_ext_gb_pcm-08 | modykacja: 30.12.2016
MANUAL
APPEARANCE
FEATURES
TECHNICAL PARAMETERS
DESCRIPTION
● Three-phase delta-star motor control,
● current decrease during high power
motor start,
● device mode optical signalling (LED
red),
● supply voltage optical signalling (LED
green),
● trigger by applying supply voltage,
● starting time adjustment (STAR sys-
tem),
● interval time adjustment of STAR to DELTA switching,
● two independent relay outputs, dry
contact 2 x NO/NC of 10 A capacity,
● mounting in distribution boards (TH35
rail).
The PCM-08 time relay is used to
control the STAR-DELTA contactor switch. It is applied in three-phase mo­tor control systems. This control me­thod allows to reduce starting currents in case of motor units with a capacity of more than 4-5 kW and additionally it provides safety. The PCM-08 device has two independent relay outputs activated according to the settings of P1-P3 po­tentiometers. It is possible to adjust the starting time (in the STAR system) and time interval of star to delta switching.
Relay operation is triggered by applying
power supply voltage to the L, N supply terminals. The device is designed to be mounted in distribution boards (TH35 rail). The LEDs on the front panel in­dicate power supply (LED green), and device operating mode (LED red).
PCM-08
Power supply terminals: L, N
Nominal supply voltage: 230 V AC
Input voltage tolerance: -15 ÷ +10 %
Nominal frequency: 50 Hz
Nominal power consumption: 0,8 W
Supply voltage control indicator: LED green
Device mode indicator: LED red
Interval time adjustment of STAR to DELTA switching: discreet – 8 ÷ 250 ms
Starting time adjustment (STAR system):
1 ÷ 100 s with multiplier 1÷10
Output elements:
2 x relay
Output relay parameters:
NO/NC – 10 A / 250 VAC
Number of terminal clamps:
8
Cross-section of connecting cables: 0,2 ÷ 2,5 mm
2
Operating temperature range: -20 ÷ +50 °C
Operating position: free
Casing mounting: TH35 rail (1-MOD casing)
Casing protection degree: IP20
Protection level: II
Overvoltage category: II
Pollution degree: 2
Surge voltage: 1 kV (PN-EN 61000-4-5)
Dimensions: monomodular 90x17,5x66 mm
Weight: 0,08 kg
Reference standard: PN-EN 60669-1, PN-EN 60669-2-1,
PN-EN 61000-4-2,3,4,5,6,11
The symbol means selective collecting of electrical and electronical equipment. It is forbidden to put the used equipment together with other waste.
P1 potentiometer
Interval time adjustment of STAR to DELTA switching (strobe adjustment)
P3 potentiometer Starting time multiplier
in the star system 1÷10 (strobe adjustment)
P2 potentiometer
starting time value adjustment
(STAR system),
Device operating mode
optical signalling
Power supply optical signalling
Relay output terminals PK1 (14, 11, 12)
Relay output terminals PK2 (24, 21, 22)
Power supply terminals
CONNECTION
FUNCTIONIG
The PCM-08 device is equipped with two electromagnetic relays at its end, which control the correct contactors that switch the motor winding according to the adjusted time of start and interval (P - „star” contactor, P - „delta” contactor).
After power supply is switched on, the PK1 relay switches on the contactor responsible for switching the motor windings into STAR system for the adjusted time. After that time has elapsed, the relay switches off PK1 relay and the interval time, adjusted by P1 poten­tiometer, is measured. After the interval time has elapsed, the PK2 relay switches on. It is responsible for switching the motor windings into DELTA system. PK2 relay remains on until there is no power supply in L, N terminals.
Switching on PK1 relay – normally closed 11-14.
Switching on PK2 relay – normally closed 21-24.
Measuring delta start time is indicated by a ashing red LED with a frequency of 1 second. Whereas delta operation is optically signalled by a continuous LED light.
MOUNTING
1. Disconnect power supply by the phase
fuse, the circuit-breaker or the switch-
-disconnector combined to the proper
circuit.
2. Check if there is no voltage on con-
nection cables by means of a special measure equipment.
3. Mount the PCM-08 device on the
TH35 rail.
4. Connect the cables with the terminals
in accordance with the installing dia-
gram.
5. By means of P1 ÷ P3 potentiometers
adjust: a) starting time in the star system
t – potentiometer P2 (1 ÷ 100 s)
b) starting time multiplier – P3 poten-
tiometer (1 ÷ 10 with strobe ‘1’)
t
STARTING
= t x multiplier
(potentiometer P2) (potentiometer P3)
c) star to delta switching time (P1 po-
tentiometer)
6. Switch on the power supply from the
mains. After power supply voltage is applied to the L, N supply terminals, the P
and P output relays switch ac-
cording to the adjusted time.
CASING DIMENSIONS INNER DIAGRAM
NL
WARRANTY CARD
There is a 24-month guarantee on the product
Salesman stamp and signature, date of sale
1. ZAMEL Sp. z o.o. assures a 24-month guarantee for the product.
2. The manufacturer’s guarantee does not cover any of the following actions: a) mechanical damage during transport, loading / unloading or under other circumstances,
b) damage caused by incorrect product mounting or misuse,
c) damage caused by unauthorised modications made by the PURCHASER or any third parties to the product or any other
devices required for the product functioning, d) damage caused by Act of God or any other incidents independent of the manufacturer – ZAMEL Sp z o.o. e) supply sources (batteries) included in the device during selling (if they are included).
3. The PURCHASER shall lay any claims in writing in the place of purchase or to ZAMEL Sp. z o.o.
4. ZAMEL Sp. z o.o. is liable for processing any claim according to current Polish legislation.
5. ZAMEL Sp. z o.o. shall process the claim at its own discretion: product repair, replacement or money return.
6. The manufacturer’s guarantee is valid in the Republic of Poland.
7. The PURCHASER’s statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or otherwise are not affected by this warranty.
The device is designed for single-pha-
se installation and must be installed in
accordance with standards valid in a
particular country. Installation, connec-
tion an d contro l should be ca rried out by a qualied electrician staff, who act in accordance with the instruction manual and the device functions. In case of ca­sing dismantling, the guarantee is lost and an ele ctric shock may occ ur. Before installation make sure the connection cables are not under voltage. The cru­ciform head screwdriver 3,5 mm should be used to install the device. Improper transpor t, storage, and use of the de­vice inuence its wrong functioning. It is not advisable to install the device in the following cases: if any device part is missing or the device is damag ed or de -
formed. In case of improper functioning
of the device contact the producer.
CAUTION
L1 L2 L3 N
t
STARTING
t
OPERATION
t
BREAK
main contactor
motor (delta) switch
on contactor
motor (star) switch
on contactor
Loading...