Zamel ASM-02 User guide

STAIRCASE LIGHTING TIMER ASM-02 INSTRUCTION MANUAL
Zakład Mechaniki i Elektroniki
ZAMEL sp.j.
J.W. Dzida, K. Łodzińska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamelcet.com, e-mail: marketing@zamel.pl
DESCRIPTION
The staircase lighting time delay switch ASM-02 is used to control lighting devices on staircases and corridors. After releasing the system it switches on the lighting for the preset time by the user. After that it switches off automatically. The operating time can be adjusted from 2 s to 10 min by means of the potentio­meter placed on the front panel of the device. The device is equipped with an anti-blocking function. The staircase li­ghting time delay switch ASM-02 can be used as standard time delay relay.
● Staircase lighting control,
● operating time adjustment from 2 sec
to 10 min,
● power supply indicator – red LED,
● cooperation with monostable push-
buttons equipped with illumination
lamps,
anti blocking function,
● cooperation with 4-wire installation,
● voltage relay output - one NO contact
max 16 A capacity,
● monomodular casing,
● TH 35 DIN rail installation.
TECHNICAL PARAMETERS
ASM-02
Input (supply) terminals: L, N
Input rated voltage: 230 V~
Input voltage tolerance: from -15 to +10 %
Nominal frequency: 50 / 60 Hz
Rated power consumption: 35 mA
Release terminals: IN, IN, IN
Release control current: 300 µA
Time adjustment range: from 2 sec to 10 min (rotational potentiometer)
Time accuracy adjustment: ±10 %
Time repeatability adjustment: ±5 %
Power/relay supply indicator: red LED
Output relay parameters: 1NO - 16 A / 250 V AC1 4000 VA
Number of terminal clamps: 8
Section of connecting cables: from 0,2 to 2,50 mm
Ambient temperature range: from -20 to +45
Operating position: free
Mounting: TH35 rail (PN-EN 60715)
Protection degree: IP20 (PN-EN 60529)
Protective class: II
Overvoltage category: II
Pollution degree: 2
Rated impulse withstand voltage: 1 kV (PN-EN 61000-4-5)
Dimensions (height / width / depth): monomodular (17,5 mm) 90x17,5x66 mm
Weight: 76 g
Reference standards: PN-EN 60669-1; PN-EN 60669-2-1
PN-EN 61000-4-2,3,4,5,6,11
2
o
C
The device is designed for one-phase instal­lation and must be in­stalled in accordance
CAUTION
with standards valid in a particular country.
The device should be connected according to the details inc­luded in this operating manual. Installa­tion, connection and control should be carried out by a qualied electrician staff, who act in accordance with the service manual and the device functions. Disas­sembling of the device is equal with a loss of guarantee and can cause electric shock. Before installation make sure the connection cables are not under voltage. The cruciform head screwdriver 3,5 mm should be used to instal the device. Im­proper transport, storage, and use of the device inuence its wrong functioning. It is not advisable to instal the device in the following cases: if any device part is missing or the device is damaged or de­formed. In case of improper functioning of the device contact the producer.
APPEARANCE
Input supply terminal (L)
Power/relay supply indicator
Time adjustment
Output (load) relay
terminals (11,11,14)
Input supply terminal (N)
Release terminals
(IN,IN,IN)
VER. 001_16.02.2009
MOUNTING, FUNCTIONING
CONNECTING
INNER DIAGRAM
1. Disconnect the power supply from the
mains by the phase fuse, the circuit­breaker or the switch-disconnector that are joined to the proper circuit,
2. Check if there is no voltage on con-
nection cables by means of a spe­cial measure equipment,
3. Install ASM-02 device in the switch-
board on TH 35 DIN rail,
4. Connect the cables with the terminals
according to installing diagram,
5. Switch on the power supply from the
mains,
6. Adjust the demanded switch on time
by means of a potentiometer.
After proper mounting and installa­tion the device is ready to work. Rele­asing the system with the monostable pushbutton causes the lighting to switch on for the preset time. After the preset time is over the lighting is automatically switched off till its another release. The staircase lighting time delay switch co­operates with 4-wire system. The stair­case lighting time delay switch ASM-02 has the anti blocking system. It means the light is switched off after the adju­sted time in cases the pushbutton is blocked.
DIMENSIONS
EXAMPLE OF INSTALLATION
NL
IN IN IN
t
TIME COURSE
t t
RELAY CAPACITY
2000 W
500 W
11 11
14
t
t
1000 W
750 W
PRODUCT FAMILY
The staircase lighting time delay switch ASM-02 belongs to staircase lighting time delay switches ASx family.
Version 24 V AC/DC
for ASM-02 available
Device version:
01 – three - or four-conductor
wiring 02 – anti-lock system 10 – dimmer function
Type of casing:
M – monomodular N – surface mounting H – hermetical P – for junction box mounting
Device symbol
GUARANTEE CARD
There is 24 months guarantee on the product
Salesman stamp and signature, date of sale
Typical application:
The staircase lighting time delay switch ASM-02 operating the staircase ligh­ting works in 4-wire installation. Monostable pushbutton (equipped with illumination) can be connected parallely.
1. ZAMEL provides a two-year warranty for its products.
2. The ZAMEL warranty does not cover: a) mechanical defects resulting from transport, loading / unloading or other circumstances, b) defects resulting from incorrect installation or operation of ZAMEL products, c) defects resulting from any changes made by CUSTOMERS or third parties, to products sold or equipment necessary
for the correct operation of products sold,
d) defects resulting from force majeure or other aleatory events for which ZAMEL is not liable.
3. All complaints in relation to the warranty must be provided by the CUSTOMER in writing to the retailer after discovering a defect.
4. ZAMEL will review complaints in accordance with existing regulations.
5. The way a complaint is settled, e.g. replacement of the product, repair or refund, is left to the discretion of ZAMEL.
VER. 001_16.02.2009
Loading...