TECHNICAL PARAMETERSDESCRIPTION
The staircase lighting time delay switch ASM-01 is used to control ligh­ting devices on staircases and corridors. After releasing the system it switches on the lighting for the preset time by the user. After that it switches off automa­tically. The operating time can be adju­sted from 10 s to 10 min by means of the potentiometer placed on the front panel of the device. The staircase lighting time delay switch ASM-01 can be used as standard time delay relay.
Staircase lighting control,
operating time adjustment from 10
sec to 10 min,
power supply indicator – red LED
diode,
cooperation with monostable
pushbuttons equipped with illumina-
tion lamps,
cooperation with 3-wire or 4-wire
installation,
voltage relay output max 16 A
capacity,
monomodular casing.
Input (supply) terminals: L, N
Input rated voltage: 230 V~
Input voltage tolerance: from -15 to +10%
Nominal frequency: 50 / 60 Hz
Rated power consumption: 48 mA
Supply/release terminals: IN / IN (connected inside the device)
Power/relay supply indicator: red LED
Time adjustment range: from 10 sec to 10 min
Time accuracy adjustment: ±10 %
Time repeatability adjustment: ±5 %
Time adjustment: fluent rotational potentiometer
Output relay parameters: 1NO - 16A/250 V AC1 4000 VA
Number of terminal clamps: 4
Section of connecting cables: from 0,2 to 2,50 mm
Ambient temperature range: from -20 to +45
Operating position: free
Protection degree: IP20 (PN-EN 60529)
Protective class: II
Overvoltage category: II
Pollution degree: 2
Rated impulse withstand voltage: 1 kV (PN-EN 61000-4-5)
Dimensions (height / width / depth): monomodular(17,5mm) 90x17,5x66mm
Reference standards: PN-EN 60669-1; PN-EN 60669-2-1
ASM-01
2
o
C
Mounting: TH35 rail (PN-EN 60715)
Weight: 0,073 kg
PN-EN 61000-4-2,3,4,5,6,11
The device is designed for one-phase installation and must be installed in accordance with stan­dards valid in a particular
CAUTION
country. The device sho-
uld be connected accor­ding to the details included in this opera­ting manual. Installation, connection and control should be carried out by a quali­ed electrician staff, who act in accordan­ce with the service manual and the device functions. Disassembling of the device is equal with a loss of guarantee and can cause electric shock. Before installation make sure the connection cables are not under voltage. The cruciform head screw­driver 3,5 mm should be used to instal the device. Improper transport, storage, and use of the device inuence its wrong func­tioning. It is not advisable to instal the de­vice in the following cases: if any device part is missing or the device is damaged or deformed. In case of improper functio­ning of the device contact the producer.
The symbol stands for selective collection of electrical and electronic devices. Placing used devices with other waste is not allowed
APPEARANCE
Input (supply) terminal (L) Input (supply) terminal (N)
Power/relay supply
indicator
Time adjustment
Supply/release terminals
(IN, IN)
VER. 002_02.10.2009
MOUNTING
CONNECTING
1. Disconnect the power supply from the
mains by the phase fuse, the circuit­breaker or the switch-disconnector that are joined to the proper circuit.
2. Check if there is no voltage on con-
nection cables by means of a spe­cial measure equipment.
3. Install ASM-01 device in the switch-
board on TH 35 DIN rail.
4. Connect the cables with the terminals
according to installing diagram.
5. Switch on the power supply from the
mains.
6. Adjust the demanded switch on time
by means of a potentiometer.
3 wire system 4 wire system
FUNCTIONING EXAMPLE OF INSTALLATION
After proper mounting and installa­tion the device is ready to work. Rele­asing the system with the monostable pushbutton causes the lighting to switch on for the preset time. After the preset time is over the lighting is automatically switched off till its another release. The staircase lighting time delay switch co­operates with 3-wire or 4-wire system. While mounting the device pay attention the release and load systems are pro­perly connected, otherwise the device can be irreparably damaged. Because of no anti-blocking system the light is constantly switched on in cases the pu­shbutton is blocked.
Typical application:
The staircase lighting time delay switch ASM-01 operating the staircase ligh­ting works in 3-wire installation. Monostable pushbutton (equipped with illumination) can be connected parallely.
DIMENSIONS
RELAY CAPACITY
2000 W
500 W
1000 W
750 W
GUARANTEE CARD
There is 24 months guarantee on the product
Salesman stamp and signature, date of sale
INNER DIAGRAM
LN
PRODUCT FAMILY
The staircase lighting time delay switch ASM-01 belongs to staircase lighting time
IN IN
t
TIME COURSE
t t
1. ZAMEL provides a two-year warranty for its products.
2. The ZAMEL warranty does not cover: a) mechanical defects resulting from transport, loading / unloading or other circumstances, b) defects resulting from incorrect installation or operation of ZAMEL products, c) defects resulting from any changes made by CUSTOMERS or third parties, to products sold or equipment necessary
for the correct operation of products sold,
d) defects resulting from force majeure or other aleatory events for which ZAMEL is not liable.
3. All complaints in relation to the warranty must be provided by the CUSTOMER in writing to the retailer after discovering a defect.
4. ZAMEL will review complaints in accordance with existing regulations.
5. The way a complaint is settled, e.g. replacement of the product, repair or refund, is left to the discretion of ZAMEL.
t
delay switches ASx family.
t
t
Voltage version: 24V - 24 V AC/DC available for
ASM-02
U - 12÷240 V AC/DC available for
ASH-01, ASM-01, ASN-01
Device version: 01 - 3- or 4-wire installation 02 - anti-blocking function 03 - anti-blocking function and ON/
AUTO/OFF mode switch
10 - uent lighting brightening and
dimming